3D Catalog HG11 31 en
3D Catalog HG11 31 en
3D Catalog HG11 31 en
R-HG11-226.eps
Contents
Contents
Page
Description
General Construction and mode of operation Operating mechanisms Ambient conditions and dielectric strength Product range overview
5
6 7 8 11 12
Equipment Selection
Ordering data and configuration example Selection of disconnectors Built-on components for disconnectors Selection of earthing switches Built-on components for earthing switches Accessories and spare parts
13
14 15 19 21 23 25
Technical Data
Electrical data, dimensions and weights of disconnectors Electrical data, dimensions and weights of earthing switches Technical data of built-on components Circuit diagrams
27
28 36 38 40
Annex
Inquiry form Configuration instructions Configuration aid
41
42 43 Foldout page
R-HG11-173.tif
Description
Contents
Contents
Page
Description
General Construction and mode of operation: Application Endurance Functions of the switching devices Short-circuit capability Operating mechanisms: Motor operating mechanism Auxiliary mechanism for motor operating mechanism
R-HG11-174.tif
5
6
7 7 7 7
8 8 9 9 10 10 10 10 11 11 12
Manual operating mechanisms Interlocks Interlocks for motor operating mechanisms Auxiliary switch Spherical joint mechanism Standards Ambient conditions Dielectric strength Product range overview
Disconnectors have to isolate downstream operational equipment i.e., de-energised equipment from the connected circuits. Thus they establish a visible isolating distance in air towards downstream operational equipment.
R-HG11-227.tif
The task of an earthing switch is to earth de-energised parts of the switchgear and in the case of multi-pole earthing switches to short-circuit them at the same time.
R-HG11-228.eps
Description
Construction and mode of operation
Application Disconnectors and earthing switches are suitable for indoor installations up to 36 kV. Due to their cast-resin ribbed insulators, the disconnectors and earthing switches can also be used with high air humidity and occasional condensation, e.g., in tropical areas. The devices are protected against corrosion. Steel parts are either galvanised and yellow-passivated, or electrostatically coated with epoxy-resin powder over a phosphate layer. The switching devices can be installed in any position with horizontal shaft. Designs for installation with the shaft in vertical position are also available. Endurance Normally, disconnectors and earthing switches are operated very rarely. Therefore they are not designed for a high number of operating cycles. The mechanical endurance and the contact endurance are: 5,000 operating cycles for the disconnector 1,000 operating cycles for the earthing switch. Functions of the switching devices 3DA/3DC disconnectors have the following functions: Opening or closing circuits when either negligibly small currents have to be switched off/on or when there is no significant voltage difference between the circuits to be disconnected or connected. Establishing an isolating distance between the terminals of each pole in the open position. The task of 3DD/3DE earthing switches is to earth deenergised parts of the switchgear and in the case of multi-pole earthing switches to short-circuit them at the same time. Short-circuit capability The short-circuit capability of closed disconnectors and earthing switches is tested according to VDE.Due to the loopless circuit, the disconnectors need not be interlocked against being opened by short-circuit forces. Earthing switches built on disconnectors or used as independent devices have to be interlocked in presence of peak withstand currents above 50 kA if the earthing switch is installed with the peak withstand current flowing through the earthing switch in direction 2 according to the drawing shown on the right. In this direction, strong opening forces are effective. Sufficient interlocking is guaranteed for motor operating mechanisms as well as for self-blocking manual operating mechanisms (e.g., spherical joint mechanism). For earthing switches built on a disconnector, the mechanical interlock between the disconnector and the earthing switch is a simple means to exclude the disadvantages of the energy direction with opening force effect.
R-HG11-227.tif
1 Energy directio n produces no or small opening forces; permissi ble withou t interlock up to the rated peak withstan d curr ent 2 Energy direct ion produce s stron g openin g forces ; permissi ble withou t interlock up to a peak value of 50 kA
Motor operating mechanism The motor operating mechanism provided for disconnectors and earthing switches type 3D mainly consists of a DC compound-wound motor, degree of protection IP00, which drives the eccentric shaft of a free-wheeling mechanism via a single-step spur gearing. The free-wheeling mechanism makes the crank (2) rotate counter-clockwise. The crank is linked with the drive lever through a short drive rod, and the drive lever is connected with the operating shaft (4). A 180 turn of the crank produces a switching angle of 90 at the operating shaft. In the end positions of the switching device, the drive motor is de-energised via built-in position switches. If an AC motor operating mechanism is required, a rectifier is installed additionally. The time from initiation of the command until reaching the end position or arrival of the feedback (total operating time) is 3 s as a maximum at the lowest value of the operating voltage. Auxiliary mechanism for motor operating mechanism If the auxiliary voltage fails, the motor operating mechanism can be emergency-operated. The auxiliary mechanisms provided for this purpose (for dimensions see page 39) are fixed-mounted in the switchgear panel and required for each motor operating mechanism. The simplest design consists of a straight shaft running horizontally from the eccentric shaft (pin for emergency operation) of the motor operating mechanism to the front of the switchgear panel. There it is guided in a bearing plate, and ends with an operating pin. The switching operation is performed by means of an auxiliary crank, which is only required once for the switchgear assembly. If the direct way to the panel front is not possible, the straight shaft can be equipped with a spherical joint at the motor operating mechanism. This built-on system enables deflecting the shaft by max. 10 to all directions. Another design is provided for motor operating mechanisms that are hard to access. This operating mechanism is designed with a flexible shaft, which is also operated with the auxiliary crank. For disconnectors and earthing switches in open switchgear panels, a complete auxiliary mechanism 3CX6 is recommended as crank.
Position of the motor operatin g mechanism Earthing switch 1 Mount ed on the opening side (EO) 2 Mounte d on the pivot point (EP) The motor operatin g mechanis m is built on as follows: 3 Disconn ector withou t earthin g switch (moto r operatin g mechanis m top-left) 4 Disconnecto r with earthin g switch on the pivot point 4a (moto r operatin g mechanis m for disconn ector bottom-right) 4b (moto r operatin g mechanis m for earthin g switch topleft with extended drive rod) 5 Disconn ector with earthin g switch on the opening side 5a (moto r operatin g mechanis m for disconn ector top-left) 5b (moto r operatin g mechanis m for earthin g switch top-right)
Motor operatin g mec hanis m 1 Motor operatin g mechanis m with cover 2 Crank 3 Drive rod 4 Operatin g shaft
R-HG11-229.eps
Description
Operating mechanisms
Manual operating mechanisms Instead of being operated by a motor, the operating shaft can also be actuated manually. Operation by means of a switching rod depends on the mounting position and the accessibility. Switching rods are made of glass-fibre reinforced polyester tube and can be used in switchgear with rated voltages above 1 kV. These switching rods are used to actuate the switching rod lever (available as an accessory) mounted on the operating shaft. Switching rod levers made of insulating material are always used where the necessary minimum distances are not reached. For fixing in the end positions, an elastic latch is always provided for switching rod actuation (see interlocks). Interlocks Latch For disconnectors and earthing switches a latch can be supplied, which latches tight in the end positions in an elastic way. Such a latch must be provided when these switching devices are operated manually with a switching rod. Mechanical interlocki ng Disconnectors with built-on earthing switch can be equipped with a mechanical interlock if the earthing switch is actuated by means of a switching rod. Power-operated switching devices must be interlocked with the means belonging to the operating mechanism, i.e., actuation must be prevented. For this purpose, the part without power operating mechanism requires an auxiliary switch. If neither the disconnector nor the earthing switch are power-operated, mechanical interlocking is possible in connection with an electromechanical lockout. The electromechanical lockout is then mounted on the disconnector. Electromechanical lockout Electromechanical lockout devices can be installed on all disconnectors and earthing switches without power operating mechanism. The lockout devices block the switching devices in the end positions when the solenoid is not excited. In the intermediate position (faulty position) the lockout is not effective. The magnet coils are suitable for continuous operation.
Mechanica l interlock betwee n disconnec tor and built-on earthin g switc h Latch for disconnector fixed on the base frame 1 Latch 2 Insulatin g coupling 3 Operatin g shaft 4 Switching angle limiter
1
Switc hing rod lever made of metal 1 Switching rod lever 2 Operatin g shaft made of insulatin g material
1 Operatin g shaft 2 Upper blocking disc 3 Double actuation 4 Lower blocking disc 5 Earthing switch shaft
1 Magne t core 2 Cover 3 Magne t armature 4 Blocking lever 5 Operatin g shaft Built-on electromechanical lockout
Interlocks for motor operating mechanisms Via switc hgear interlocki ng system For operation in connection with a switchgear interlocking device 8TJ2, a poled relay is required to prevent maloperation. Interlocks on the disconnector can be omitted. For operation in connection with a switchgear interlocking device 8TK, no other auxiliary contactors are required. Via auxiliary contactor With an auxiliary contactor (with or without command execution) and pushbuttons, additional protective measures must be taken against impermissible switching operations. Via cha ngeover switch The simplest possibility of control is a changeover switch. However, adequate protective measures against impermissible switching operations must be taken here as well. Auxiliary switch Disconn ectors and earthing switches can be equipped with auxiliary switches with 2 NO + 2 NC or 6 NO + 6 NC contacts. If there is a motor operating mechanism available, the auxiliary switch is located on the side opposite of the motor. The rated current is 10 A.
Auxiliary switch for disconnecto r and built-on earthin g switch 1 Auxiliary switch of disconnector 2 Disconn ector shaft 3 Auxiliary switch of built-on earthin g switch with cover 4 Earthing switch shaft
Spherical joint mechanism Disconnectors can also be operated through a spherical joint mechanism. The rotary movement is transmitted from the front side of a switchgear panel to the switching device via levers and rods. Spherical joint mechanisms are also available for make-proof earthing switches. Standards The disconnectors and earthing switches conform to the following standards and recommendations:
DIN VDE 0670 Part 2 DIN VDE 0111 Part 1 IEC 129 IEC 62271-1 (former IEC 60694)
Spherical joint mec hanis m 3DX2 1 Operatin g shaft lever 2 Switching rod (threade d rod with spherical joints M12 on both sides) 3 Lever on the drive shaft 6 90 stop CLOSE-OPEN 7 Indicatio n label black for switch- disconn ector and disconnector red for earthin g switch and make-proo f earthin g switch
4 Drive shaft: steel shaft with 8 Operatin g lever for spherical joint 25 mm , or insulatin g shaft mechanis m 3DX2 with 30 mm 5 Latch (only for disconn ector and earthin g switch)
Description
Ambient conditions and dielectric strength
Ambient conditions The disconnectors and earthing switches are designed for the normal operating conditions defined in the standards. Condensation can occasionally occur under the ambient conditions shown opposite.
Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IE C 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration power-frequency withstand voltage specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to both rated withstand voltages. To select the devices, the following applies: U W U0 x Ka
U U0 Ka Rated withstan d voltage under reference atmos phere Rated withstan d voltage requested for the place of installation Altitude correction factor acco rding to the opposite diagram
Exa mple For a requeste d rated lightnin g impulse withstan d voltage of 75 kV at an altitude of 2500 m, an insula tion level of 90 kV under referenc e atmospher e is require d as a minimum: 90 kV W 75 kV x 1.2
!!
"
Description
Product range overview
12
24 36
Equipment Selection
Contents
Contents
Page
Equipment Selection
Ordering data and configuration example Selection of disconnectors for general switchgear construction: Voltage level 12 kV Voltage level 24 kV Voltage level 36 kV Selection of disconnectors for switchgear panels with a panel width of 650 mm Selection of disconnectors for switchgear panels with a panel width of 900 mm
R-HG11-230.eps
13
14
15 16 16
17
18
Built-on components for disconnectors: Disconnector with motor operating mechanism Disconnector with switching rod actuation Disconnector with electromechanical lockout Disconnector with built-on auxiliary switch Disconnector with mechanical interlock Special versions Selection of earthing switches for general switchgear construction Selection of earthing switches for switchgear panels with a panel width of 650 mm Selection of earthing switches for switchgear panels with a panel width of 900 mm Built-on components for earthing switches: Earthing switch with motor operating mechanism 23 Earthing switch with switching rod actuation 23 23 24 24 25 26 Earthing switch with electromechanical lockout Earthing switch with built-on auxiliary switch Special versions Accessories and spare parts Spherical joint mechanism 19 19 19 20 20 20
21
22
22
3DA disconnector
R-HG11-231.eps
Order number structure The disconnectors and earthing switches are described by a 9-digit order number. The positions 10 to 16, which are provided for the usual 16-digit order number, are not required. These 9 characters describe the primary data of the switching devices. Built-on components such as motors, interlocks, auxiliary switches, etc. are ordered by means of order codes.
Built-on co mponents and special versions ( ) For built-on components and special versions, -Z is added to the order number and a descriptive order code follows. If several built-on components and special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department in the Switchgear Factory Berlin.
2
1st positio n Primary data Superior group Switching devices Main group Disconn ector and earthing switch Subgroup Disconn ector and earthin g switch type series Basic equipment Design and ratings of the swit ching device Built-on components , specia l versions ( ) Initiated with -Z Group of 3 after the Order No. Format: a n n 2nd positio n
a: alphab etical
Position: 1 2 3 4 5
n: numerical
6 7 8 9 Order codes
Order No.:
D a
3rd positio n
Configuration example In order to simplify the selection of the correct order number for the requested type of switching device, you will find a configuration example on each page of the chapter Equipment Selection. For the selection of the built-on components, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (pages 20 and 24) a completely configured switching device results as an example.
On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your switching device.
3 D C 1
2 G
Equipment Selection
Selection of disconnectors for general switchgear construction
12 kV
50/6 0 Hz
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
1)
Ur kV 12
Up kV 75
Ud kV 28
Ir A 630
Ith kA 20
Idyn kA 50 3 mm 210 wi thou t EP EO wi thou t EP EO withou t EP EO wi thou t EP EO wi thou t EP EO wi thou t EP EO withou t EP EO wi thou t EP EO wi thou t EP EO wi thou t EP EO wi thou t EP EO withou t EP EO wi thou t EP EO 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 G G G L L L N N N S S S U U U C C C G G G J J J E E E J J J L L L J J J L L L
31.5
80
2)
210
See page 19
1250
31.5
80
3)
210
50
125
210
63
160
210
1600
31.5
80
3)
210
50
125
210
63
160
210
2500
31.5
80
210
50
125
210
63
160
210
3000
50
125
230
63
160
230
1) EP = with earthing switch moun ted on the pivot point; EO = with earthing switch moun ted on the opening side 2) Disconnec tors without earthing swit ches can also be used for 87 kA if the connectin g bars are suppo rted at a distanc e of 100 mm from the post insula tors of the disconnec tor 3) Can also be used for 87 kA Configuratio n example Disconnector , 3-pole Rated voltag e Ur = 12 kV Rated normal curren t Ir = 2500 A Rated short-tim e withstan d curr ent Ith = 50 kA Pole-centre distanc e 210 mm Earthing switch mounte d on the openin g side of the disconnecto r EO Example for Order No.: Order codes: 3 D C
1 3 D C 1
0 0
3 3
2 2
5 5
J J
Equipment Selection
Selection of disconnectors for general switchgear construction
24 kV
50/6 0 Hz
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
1)
Ur kV 24
Up kV 125
Ud kV 50
Ir A 630
Ith kA 20
275
1250
31.5
80
275
1600
31.5
80
275
2500
31.5
80
300
36 kV
50/60 Hz Ur kV 36 Up kV 170 Ud kV 70 Ir A 630 Ith kA 20 Idyn kA 50 3 mm 400 withou t EP EO withou t EP EO withou t EP EO withou t EP EO withou t EP EO 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 D D D D D D D D D D D D D D D C C C C C C A A A C C C C C C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 G G G N N N C C C E E E E E E
1250
31.5
80
400
1600
31.5
80
2500
31.5
80
400
3000
31.5
80
420
1) EP = with earthin g switch mount ed on the pivot point; EO = with earthin g switch mount ed on the opening side Configuratio n example Disconnector , 1-pole Rated voltag e Ur = 36 kV Rated normal curren t Ir = 1600 A Rated short-tim e withstan d curr ent Ith = 31.5 kA Earthing switch mounte d on the pivot point of the disconnecto r EP Example for Order No.: Order codes: 3 D A
1 3 D A 1
0 0
2 2
6 6
4 4
C C
See page 19
Equipment Selection
Selection of disconnectors for switchgear panels with a panel width of 650 mm
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
1)
Ur kV 12
Up kV 60
Ud kV 28
Ir A 630
Ith kA 20
31.5
80
2)
150
See page 19
1250
31.5
80
3)
150
D C 1
1) EP = with earthing switch moun ted on the pivot point; EO = with earthing switch moun ted on the opening side 2) Disconnec tors without earthing swit ches can also be used for 87 kA if the connectin g bars are suppo rted at a distanc e of 100 mm from the post insula tors of the disconnec tor 3) Can also be used for 87 kA
Configuratio n example Disconnector , 3-pole For switchg ear panels with a panel width of 650 mm Rated voltag e Ur = 12 kV Rated normal curren t Ir = 1250 A Rated short-tim e withstan d curr ent Ith = 31.5 kA Pole-centre distanc e 150 mm Without built-on earthin g switch Example for Order No.: Order codes:
D C
1 3 D C 1
0 0
4 4
1 1
3 N
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
1)
Ur kV 12
Up kV 75
Ud kV 28
Ir A 630
Ith kA 20
Idyn kA 50 3 mm 210 withou t EP EO withou t EP EO withou t EP EO withou t EP EO withou t EP EO withou t EP EO withou t EP EO withou t EP EO 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 D D D D D D D D D D D D D D D D D D D D D D D D C C C C C C C C C C C C C C C C C C C C C C C C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 7 8 9 7 8 9 7 8 9 7 8 9 7 8 9 7 8 9 7 8 9 7 8 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4 5 5 5 5 5 5 G G G L L L N N N S S S C C C G G G E E E J J J
31.5
80
2)
210
1250
31.5
80
3)
210
50
125
210
1600
31.5
80
3)
210
50
125
210
2500
31.5
80
3)
210
50
125
210
24 kV for switchgea
50/60 Hz Ur kV 24 Up kV 95
1250
31.5
80
210
1) EP = with earthin g switch mount ed on the pivot point; EO = with earthin g switch mount ed on the opening side 2) Disconn ectors withou t earthin g switch es can also be used for 87 kA if the conn ecting bars are supported at a distanc e of 100 mm from the post insulator s of the disconnector 3) Can also be used for 87 kA Configuratio n example Disconnector , 3-pole For switchg ear panels with a panel width of 900 mm Rated voltag e Ur = 12 kV Rated normal curren t Ir = 2500 A Rated short-tim e withstan d curr ent Ith = 50 kA Pole-centre distanc e 210 mm Earthing switch mounte d on the pivot point of the disconnecto r EP Example for Order No.: Order codes:
D C
1 3 D C 1
0 0
8 8
2 2
5 5
J J
See page 19
Equipment Selection
Built-on components for disconnectors
Position:
Order codes
Order No.:
Number of motor s
V DC V DC V DC V AC V DC V DC V DC V AC
50/60 Hz
50/60 Hz
Z Z Z Z Z Z Z Z
A A A A A A A A
0 0 0 1 2 2 2 3
3 4 6 6 3 4 6 6
2
Z Z B 3 B 3 1 2
Disconnecto r design
Number of latches
Disconn ector without built-on earthing switch Disconn ector with built-on earthin g switch 1) Switching rod and swit ching rod lever as accessories
Disconn ector with elect romech anical lockout (manua l operatio n only)
50/60 Hz 50/60 Hz
50/60 Hz 50/60 Hz
Z Z Z Z Z Z Z Z Z Z Z Z
C C C C C C C C C C C C
0 0 0 0 0 0 2 2 2 2 2 2
1 3 4 6 7 8 1 3 4 6 7 8
Configuratio n example Disconnector , 3-pole (Ur = 12 kV, Ir = 2500 A, Ith = 50 kA, pole-centr e distanc e 210 mm, earthin g switch mounte d on the pivot point of the disconnecto r EP) With one motor operatin g mechanis m each for disconn ector and earthin g switch 60 V DC Example for Order No.: Order codes:
D C 1 0 0 8 8 2 2 5 5 J Z Z A 2 3 J
3 D C 1 A 2 3
Equipment Selection
Built-on components for disconnectors and special versions
Position:
Order codes
Order No.:
2 NO + 2 NC 6 NO + 6 NC 2 NO + 2 NC 6 NO + 6 NC
Option
Arrang ement between disconn ector and earthing switch (only possible if disconn ector or earthing switch is operated with swit ching rod)
F 0
Special versions
Options Y 0 Other pole-cent re distanc e If disconnec tors are required with a larger pole-cent re distanc e than specified in the selection tables, these versions are available within the scope of the general polecentre distanc es (210, 275 and 400 mm). Specify distanc e in mm additionall y in clear text. Other leng th of operatin g shaft Disconnec tors for genera l swit chgea r construction (3DC101, 3DC102 and 3DC103) are available with extended or sho rtened operatin g shaft. Specify length in mm additionall y in clear text. Vertically arrang ed operatin g shaft Special version for installatio n of the swit ching device in vertical position . Y 0 Z Z Z Y 0 1 2 3
Configuratio n example Disconnector , 3-pole (Ur = 12 kV, Ir = 2500 A, Ith = 50 kA, pole-centr e distanc e 210 mm, earthin g switch mounte d on the pivot point of the disconnecto r EP) With one motor operatin g mechanis m each for disconn ector and earthin g switch 60 V DC Auxiliary switch 2 NO + 2 NC for disconn ector and earthin g switch
D C 1 0 8 2 5 J Z Z
A 2 E 2
3 2
Equipment Selection
Built-on components for disconnectors
3 D C 1 A 2 3 +
2 2
E 2
Equipment Selection
Selection of earthing switches for switchgear panels with a panel width of 650 mm and 900 mm
12 kV
50/6 0 Hz
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
Ur kV 12
Up kV 75
Ud kV 28
Ith kA 20 31.5 50 63
See page 23
24 kV
50/60 Hz Ur kV 24 Up kV 125 Ud kV 50 Ith kA 20 31.5 Idyn kA 50 80 1 3 1 3 mm 275 275 3 3 3 3 D D D D D E D E 1 1 1 1 0 0 0 0 1 1 1 1 4 4 4 4 0 0 0 0 J J N N
36 kV
50/60 Hz Ur kV 36 Up kV 170 Ud kV 70 Ith kA 20 31.5 Idyn kA 50 80 3 3 mm 400 400 3 3 D E 1 D E 1 0 0 1 1 6 6 0 0 J N
Configuratio n example Earthing switch, 1-pole Rated voltag e Ur = 24 kV Rated short-tim e withstan d curr ent Ith = 31.5 kA Example for Order No.: Order codes:
D D 1 0 0 1 1 4 4 0 N
3 D D 1
0 N
Equipment Selection
Selection of earthing switches for general switchgear construction
Position:
Order codes
Order No.:
Pole-centre distance
Number of poles
Rated voltage
Ur kV 12
Up kV 60
Ud kV 28
Ith kA 20 31.5
12 kV for switchgea
50/60 Hz Ur kV 12 Up kV 75
24 kV for switchgea
50/60 Hz Ur kV 24 Up kV 95
Configuratio n example Earthing switch, 3-pole Rated voltag e Ur = 24 kV Rated short-tim e withstan d curr ent Ith = 20 kA Pole-centre distanc e 210 mm Example for Order No.: Order codes:
D E
1 3 D E 1
0 0
7 7
3 3
0 0
J J
See page 23
Equipment Selection
Built-on components for earthing switches and special versions
Position:
Order codes
Order No.:
Earthing switch with latch for switchin g rod actuatio n (manua l operation ) 1)
Option With one latch 1) Switching rod lever and swit ching rod as accessories Z B 3 3
Configuratio n example Earthing switch, 3-pole Rated voltag e Ur = 24 kV Rated short-tim e withstan d curr ent Ith = 20 kA Pole-centre distanc e 210 mm With one latch for switchin g rod actuatio n With electromechanica l lockout, rated voltage 24 V DC Example for Order No.: Order codes:
D E
J Z Z Z B 3 C 1 3 1
3 D E 1 B 3 3 +
3 1
C 1
Equipment Selection
Built-on components for earthing switches
Position:
Order codes
Order No.:
Special versions
Options
Other pole-cent re distanc e If earthing swit ches are required with a larger pole-centre distance than specified in the selection tables, these versions are available within the scope of the general polecentre distanc es (210, 275 and 400 mm). Specify distanc e in mm additionall y in clear text. Other length of operatin g shaft Earthing switch es for general switchg ear constructio n (3DE101) are available with extended or sho rtened operatin g shaft. Specify length in mm additionall y in clear text. Vertically arrang ed operatin g shaft Special version for installatio n of the swit ching device in vertical position .
Z Z Z
Y 0 Y 0 Y 0
1 2 3
Configuratio n example Earthing switch, 3-pole Rated voltag e Ur = 24 kV Rated short-tim e withstan d curr ent Ith = 20 kA Pole-centre distanc e 210 mm With one latch for switchin g rod actuatio n With electromechanica l lockout, rated voltage 24 V DC With auxiliary switch 2 NO + 2 NC
D E
J Z Z Z
B 3 C 1 E 1
3 1 2
Equipment Selection
Built-on components for earthing switches and special versions
3 D E 1 B 3 3 +
3 1
J 2
C 1
E 1
Equipment Selection
Accessories and spare parts
Accessories and spare parts The order numbers are applicable to disconnectors and earthing switches of current manufacture. When built-on components or spare parts are being ordered for existing disconnectors and earthing switches, always quote the type designation, serial number and the year of manufacture of the switching device to be sure to get the correct delivery. Spare parts must only be replaced by instructed personnel.
Remarks For motor operatin g mechanis m 3DX11 (fixed-moun ted in the panel ) For straigh t shaft For articula ted shaft For flexible shaft 0A
Order No.
3DX4 101-0A 3DX4 101-0B 3DX4 1023DX4 102-0B 3DX4 102-0C 3DX4 100-
For fixed-moun ted auxiliary mechanism s For motor operatin g mechanis m 3DX11 (only required once per switchgear) With 45 swingin g angle 012 With 90 swingin g angle 013 Is required additionall y for auxiliary mechanism s 3CX6 To opera te the swit ching rod lever Up to 36 kV
3CX6 3CX6 3CX6 014 1025 mm 2000 mm 3000 mm Made of metal Made of insulatin g material PFS: 364035-005 PFS: 364035-035 PFS: 364035-037 3DX4 210 3DX4 220
Data on the rating plate Note: For any query regarding spare parts, subsequent deliveries, etc. the following four details are necessary: Type designation Serial No. Design code Year of manufacture
Designatio n
Remarks
Order No.
Spherical joint mechanis m for disconnec tors (data of widths X and L in clear text) For disconnec tor 3DC 3DC 3DC 3DC 3DC 3DC 3DC Spherical joint mechanis m for make-proof earthing switch (data of widths X and L in clear text) For disconnec tor 3DC 3DC 3DC 3DC 3DC 3DC 3DC Accesso ries for spherical Operatin g lever for disconn ector joint mechanis m Operat ing lever for make-proof earthing switch Interlocking between disconnec tor and make-proof earthing Additive blocking solenoid with data of operatin g voltag e Bearing for shaft extensio n Setting lever for swit chgear Dowel pin for shaft extensio n
For recommende d panel width 600 750 mm 800 1000 mm 800 900 mm 900 1100 mm 800 900 mm 900 1000 mm
For recommende d panel width 600 750 mm 800 1000 mm 800 900 mm 900 1100 mm 800 900 mm 900 1000 mm
switch
3DX2013 X =... 3DX2014 X =... 3DX2013 X =... 3DX2014 X =... 3DX2013 X =... 3DX2014 X =... 3DX2014 X =... 3DX2081 3DX2082 3DX2072 3DX2071-Z 3DX2901 3DX2902 3DX2903
7 Indicatio n label black for switch-disconnecto r and disconnector red for earthin g switch and mak e-proof earthin g switch 8 Operat ing lever for spherical joint mechanis m 3DX2
Technical Data
Contents
Contents
Page
Technical Data
Electrical data, dimensions and weights of disconnectors: Voltage level 12 kV Voltage level 24 kV Voltage level 36 kV Electrical data, dimensions and weights of earthing switches: Voltage level 12 kV Voltage level 24 kV Voltage level 36 kV Technical data of built-on components:
R-HG11-233.eps
27
28 30 30
36 36 36
Data of motor operating mechanism 3DX11 Data of electromechanical lockout Breaking capacity of the auxiliary switches Circuit diagrams
38 38 38 40
Mechanical interlock
R-HG11-234.eps
Ir mm 3DC1 012-2G 3DC1 012-2L 3DC1 012-3N 3DC1 012-3S 3DC1 012-3U 3DC1 012-4C 3DC1 012-4G 3DC1 012-4J 3DC1 012-5E 3DC1 012-5J 3DC1 012-5L 3DC1 012-6J 3DC1 012-6L 3DC1 022-2G 3DC1 022-2L 3DC1 022-3N 3DC1 022-3S 3DC1 022-3U 3DC1 022-4C 3DC1 022-4G 3DC1 022-4J 3DC1 022-5E 3DC1 022-5J 3DC1 022-5L 3DC1 022-6J 3DC1 022-6L 3DC1 032-2G 3DC1 032-2L 3DC1 032-3N 3DC1 032-3S 3DC1 032-3U 3DC1 032-4C 3DC1 032-4G 3DC1 032-4J 3DC1 032-5E 3DC1 032-5J 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 210 210 210 210 210 210 210 210 210 210 210 230 230 210 210 210 210 210 210 210 210 210 210 210 230 230 210 210 210 210 210 210 210 210 210 210 A 630 630 1250 1250 1250 1600 1600 1600 2500 2500 2500 3000 3000 630 630 1250 1250 1250 1600 1600 1600 2500 2500 2500 3000 3000 630 630 1250 1250 1250 1600 1600 1600 2500 2500
Ith kA 20 31.5 31.5 50 63 31.5 50 63 31.5 50 63 50 63 20 31.5 31.5 50 63 31.5 50 63 31.5 50 63 50 63 20 31.5 31.5 50 63 31.5 50 63 31.5 50
Idyn kA 50 80 80 125 160 80 125 160 80 125 160 125 160 50 80 80 125 160 80 125 160 80 125 160 125 160 50 80 80 125 160 80 125 160 80 125
Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 3DY 1221 3DY 1221 3DY 1222 3DY 1222 3DY 1224 3DY 1222 3DY 1223 3DY 1224 3DY 1223 3DY 1223 3DY 1224 3DY 1223 3DY 1224 3DY 1221 3DY 1221 3DY 1222 3DY 1222 3DY 1224 3DY 1222 3DY 1223 3DY 1224 3DY 1223 3DY 1223 3DY 1224 3DY 1223 3DY 1224 3DY 1221 3DY 1221 3DY 1222 3DY 1222 3DY 1224 3DY 1222 3DY 1223 3DY 1224 3DY 1223 3DY 1223 N 5000 5000 1000 0 1600 0 2500 0 1000 0 1600 0 2500 0 1600 0 1600 0 2500 0 1600 0 2500 0 5000 5000 1000 0 1600 0 2500 0 1000 0 1600 0 2500 0 1600 0 1600 0 2500 0 1600 0 2500 0 5000 5000 1000 0 1600 0 2500 0 1000 0 1600 0 2500 0 1600 0 1600 0 kg 20.5 20.5 27.5 48 56 27.5 48 56 64 65 72 68 76 30 30 36.5 62 70 36.5 62 70 78 80 88 83 91 30 30 36.5 62 70 36.5 62 70 78 80 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 9530 0 007 9530 0 007 9530 0 007 9530 0 008 9530 0 008 9530 0 007 9530 0 008 9530 0 008 9530 0 009 9530 0 009 9530 0 009 9530 0 010 9530 0 010 9530 0 007 9530 0 007 9530 0 007 9530 0 008 9530 0 008 9530 0 007 9530 0 008 9530 0 008 9530 0 009 9530 0 009 9530 0 009 9530 0 010 9530 0 010 9530 0 007 9530 0 007 9530 0 007 9530 0 008 9530 0 008 9530 0 007 9530 0 008 9530 0 008 9530 0 009 9530 0 009 1 1 1 2 2 1 2 2 3 3 3 4 4 1e 1e 1e 2e 2e 1e 2e 2e 3e 3e 3e 4e 4e 1e 1e 1e 2e 2e 1e 2e 2e 3e 3e
50/60 Hz
12 kV
Pole-centre distance
Number of poles
Order No.
Technical Data
Electrical data, dimensions and weights of disconnectors
Ir mm 3DC1 032-5L 3DC1 032-6J 3DC1 032-6L 3DC1 041-2G 3DC1 041-2L 3DC1 041-3N 3DC1 051-2G 3DC1 051-2L 3DC1 051-3N 3DC1 061-2G 3DC1 061-2L 3DC1 061-3N 3DC1 072-2G 3DC1 072-2L 3DC1 072-3N 3DC1 072-3S 3DC1 072-4C 3DC1 072-4G 3DC1 072-5E 3DC1 072-5J 3DC1 082-2G 3DC1 082-2L 3DC1 082-3N 3DC1 082-3S 3DC1 082-4C 3DC1 082-4G 3DC1 082-5E 3DC1 082-5J 3DC1 092-2G 3DC1 092-2L 3DC1 092-3N 3DC1 092-3S 3DC1 092-4C 3DC1 092-4G 3DC1 092-5E 3DC1 092-5J 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 210 230 230 150 150 150 150 150 150 150 150 150 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 210 A 2500 3000 3000 630 630 1250 630 630 1250 630 630 1250 630 630 1250 1250 1600 1600 2500 2500 630 630 1250 1250 1600 1600 2500 2500 630 630 1250 1250 1600 1600 2500 2500
Ith kA 63 50 63 20 31.5 31.5 20 31.5 31.5 20 31.5 31.5 20 31.5 31.5 50 31.5 50 31.5 50 20 31.5 31.5 50 31.5 50 31.5 50 20 31.5 31.5 50 31.5 50 31.5 50
Idyn kA 160 125 160 50 80 80 50 80 80 50 80 80 50 80 80 125 80 125 80 125 50 80 80 125 80 125 80 125 50 80 80 125 80 125 80 125
Up kV 75 75 75 60 60 60 60 60 60 60 60 60 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75
Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 3DY 1224 3DY 1223 3DY 1224 3DY 1221 3DY 1222 3DY 2023 3DY 1221 3DY 1222 3DY 2023 3DY 1221 3DY 1222 3DY 2023 3DY 1221 3DY 1221 3DY 1222 3DY 1223 3DY 1222 3DY 1223 3DY 1223 3DY 1223 3DY 1221 3DY 1221 3DY 1222 3DY 1223 3DY 1222 3DY 1223 3DY 1223 3DY 1223 3DY 1221 3DY 1221 3DY 1222 3DY 1223 3DY 1222 3DY 1223 3DY 1223 3DY 1223 N 2500 0 1600 0 2500 0 5000 5000 1000 0 5000 5000 1000 0 5000 5000 1000 0 5000 5000 1000 0 1600 0 1000 0 1600 0 1600 0 1600 0 5000 5000 1000 0 1600 0 1000 0 1600 0 1600 0 1600 0 5000 5000 1000 0 1600 0 1000 0 1600 0 1600 0 1600 0 kg 88 83 91 19 19 25.5 28 28 34.5 28 28 34.5 20 20 26.5 47 27 47 63 64 29 29 35.5 61 36 61 77 79 29 29 35.5 61 36 61 77 79 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 9530 0 009 9530 0 010 9530 0 010 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 003 9530 0 004 9530 0 004 9530 0 004 9530 0 005 9530 0 004 9530 0 005 9530 0 006 9530 0 006 9530 0 004 9530 0 004 9530 0 004 9530 0 005 9530 0 004 9530 0 005 9530 0 006 9530 0 006 9530 0 004 9530 0 004 9530 0 004 9530 0 005 9530 0 004 9530 0 005 9530 0 006 9530 0 006 3e 4e 4e 5 5 5 5e 5e 5e 5e 5e 5e 6 6 6 7 6 7 8 8 6e 6e 6e 7e 6e 7e 8e 8e 6e 6e 6e 7e 6e 7e 8e 8e
50/60 Hz
12 kV
Pole-centre distance
Number of poles
Order No.
Technical Data
Electrical data, dimensions and weights of disconnectors
Ir mm 3DA1 014-2G 3DA1 014-3N 3DA1 014-4C 3DA1 024-2G 3DA1 024-3N 3DA1 024-4C 3DA1 034-2G 3DA1 034-3N 3DA1 034-4C 3DC1 014-2G 3DC1 014-3N 3DC1 014-4C 3DC1 014-5E 3DC1 024-2G 3DC1 024-3N 3DC1 024-4C 3DC1 024-5E 3DC1 034-2G 3DC1 034-3N 3DC1 034-4C 3DC1 034-5E 3DC1 073-2G 3DC1 073-3N 3DC1 083-2G 3DC1 083-3N 3DC1 093-2G 3DC1 093-3N 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 275 275 275 300 275 275 275 300 275 275 275 300 210 210 210 210 210 210 A 630 1250 1600 630 1250 1600 630 1250 1600 630 1250 1600 2500 630 1250 1600 2500 630 1250 1600 2500 630 1250 630 1250 630 1250 Ir mm 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 400 400 400 420 400 400 400 420 400 400 400 420 A 1600 1600 1600 630 1250 2500 3000 630 1250 2500 3000 630 1250 2500 3000
Ith kA 20 31.5 31.5 20 31.5 31.5 20 31.5 31.5 20 31.5 31.5 31.5 20 31.5 31.5 31.5 20 31.5 31.5 31.5 20 31.5 20 31.5 20 31.5 Ith kA 31.5 31.5 31.5 20 31.5 31.5 31.5 20 31.5 31.5 31.5 20 31.5 31.5 31.5
Idyn kA 50 80 80 50 80 80 50 80 80 50 80 80 80 50 80 80 80 50 80 80 80 50 80 50 80 50 80 Idyn kA 80 80 80 50 80 80 80 50 80 80 80 50 80 80 80
Up kV 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 95 95 95 95 95 95 Up kV 170 170 170 170 170 170 170 170 170 170 170 170 170 170 170
Ud kV 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 Ud kV 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 3DY 1227 3DY 1227 3DY 1227 3DY 1227 3DY 1227 3DY 1228 3DY 1228 3DY 1227 3DY 1227 3DY 1228 3DY 1228 3DY 1227 3DY 1227 3DY 1228 3DY 1228 N 5000 5000 5000 5000 5000 1000 0 1000 0 5000 5000 1000 0 1000 0 5000 5000 1000 0 1000 0 kg 26 32 32 53.5 58 100 107 69.5 74 122 130 69.5 74 122 130 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 9530 0 029 9530 0 029 9530 0 029 9530 0 014 9530 0 014 9530 0 015 9530 0 016 9530 0 014 9530 0 014 9530 0 015 9530 0 016 9530 0 014 9530 0 014 9530 0 015 9530 0 016 13 13e 13e 14 14 15 16 14e 14e 15e 16e 14e 14e 15e 16e 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1224 3DY 1225 3DY 1225 3DY 1225 3DY 1224 3DY 1225 3DY 1225 3DY 1225 3DY 1224 3DY 1225 3DY 1225 3DY 1225 3DY 1225 3DY 1225 3DY 1225 3DY 1225 3DY 1225 3DY 1225 N 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 1000 0 5000 5000 5000 1000 0 5000 5000 5000 1000 0 5000 5000 5000 5000 5000 5000 kg 12.5 14 14 16.5 18.5 18.5 16.5 18.5 18.5 31.5 36 36 66 43.5 48.5 48.5 82 43.5 48.5 48.5 82 27.5 32 37.5 42.5 37.5 42.5 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 106 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 019 9530 0 012 9530 0 012 9530 0 012 9530 0 013 9530 0 012 9530 0 012 9530 0 012 9530 0 013 9530 0 012 9530 0 012 9530 0 012 9530 0 012 9530 0 011 9530 0 011 9530 0 011 9530 0 011 9530 0 011 9530 0 011 9 9 9 9e 9e 9e 9e 9e 9e 10 10 10 11 10e 10e 10e 11e 10e 10e 10e 11e 12 12 12e 12e 12e 12e
36 kV
50/60 Hz 3DA1 016-4C 3DA1 026-4C 3DA1 036-4C 3DC1 016-2G 3DC1 016-3N 3DC1 016-5E 3DC1 016-6E 3DC1 026-2G 3DC1 026-3N 3DC1 026-5E 3DC1 026-6E 3DC1 036-2G 3DC1 036-3N 3DC1 036-5E 3DC1 036-6E
30
50/60 Hz
24 kV
Pole-centre distance
Number of poles
Order No.
&
Dimension drawing 1
Order No. 3DC 10.22G 3DC 10.22L 3DC 10.23N 3DC 10.24C e 238 238 245 254 h 370 370 414 414 k 242 242 256 256 m 270 270 284 284 n 445 445 444 444 Dim. drawing 1/1e 1/1e 1/1e 1/1e
'
&
Dimension drawing 1e
Dimension drawing 2
Dimension drawing 2e
Dimension drawing 3
Dimension drawing 3e
Dimension drawing 4
Dimension drawing 4e
Dimension drawings (shown: 12 kV disconnectors with motor operating mechanism and auxiliary switch)
% %
&
Dimension drawing 5
Order No. 3DC 10.12G 3DC 10.12L 3DC 10.13N 3DC 10.22G 3DC 10.22L 3DC 10.23N 3DC 10.24C
%
'
&
Dimension drawing 5e
&
'
&
Dimension drawing 6
Dimension drawing 6e
Dimension drawing 7
Dimension drawing 7e
Dimension drawing 8
Dimension drawing 8e
32
Dimension drawings (shown: 24 kV disconnectors with motor operating mechanism and auxiliary switch)
% %
&
Dimension drawing 9
Order No. 3DA 10.42G 3DA 10.43N 3DA 10.44C 3DC 10.42G 3DC 10.43N 3DC 10.44C e 28 35 44 303 310 319 h 470 514 514 470 514 514 k 338 352 352 338 352 352 m 366 380 380 366 380 380 n 637 639 639 637 639 639 Dim. drawing 9/9e 9/9e 9/9e 10/10e 10/10e 10/10e
&
'
Dimension drawing 9e
3
&
&
Dimension drawing 10
'
Dimension drawing 11
Dimension drawings (shown: 24 kV/36 kV disconnectors with motor operating mechanism and auxiliary switch)
% %
'
&
Dimension drawing 12
Order No. 3DC 10.32G 3DC 10.33N e 238 245 h 470 514 k 338 352 m 366 380 n 637 639
&
3
Dimension drawing 13
%
&
Dimension drawing 14
Order No. 3DC 10.62G 3DC 10.63N e 431 438 h 570 614 k 452 466 m 480 494 n 842 852
&
'
Dimension drawings (shown: disconnectors with motor operating mechanism and auxiliary switch)
)
&
&
Dimension drawing 15
Order No. 3DC10.65E 3DC10.66E e 400 450 h 1550 1650 k 1038 1138 m 450 500 n 529 507
3
)
&
&
Dimension drawing 16
Technical Data
Electrical data, dimensions and weights of earthing switches
50/60 Hz
Ith mm 3DE1 012-0J 3DE1 012-0N 3DE1 012-0S 3DE1 012-0U 3DE1 041-0J 3DE1 041-0N 3DE1 072-0J 3DE1 072-0N 3DE1 072-0S 3 3 3 3 3 3 3 3 3 210 210 210 210 150 150 210 210 210 kA 20 31.5 60 63 20 31.5 20 31.5 50
Up kV 75 75 75 75 60 60 75 75 75
Ud kV 28 28 28 28 28 28 28 28 28 3FA1 110-7 3FA1 110-7 3FA1 111-8 3FA1 112-0 3FA1 110-7 3FA1 110-7 3FA1 110-7 3FA1 110-7 3FA1 111-8 N 5000 5000 1600 0 2500 0 5000 5000 5000 5000 1600 0 kg 13.5 13.5 32 38 11 11 12.5 12.5 31.5 552-5162 .9 552-5162 .9 552-5183 .9 552-5183 .9 552-5145 .9 552-5145 .9 552-5136 .9 552-5136 .9 552-521 0 .9 552-5247 552-5247 552-5248 552-5248 552-5244 552-5244 552-5245 552-5245 552-5246 .9 .9 .9 .9 .9 .9 .9 .9 .9 17 17 18 18 19 19 20 20 21
24 kV
50/60 Hz mm 1 1 3 3 3 3 275 275 210 210 3DD1 014-0J 3DD1 014-0N 3DE1 014-0J 3DE1 014-0N 3DE1 073-0J 3DE1 073-0N
Idyn kA 50 80 50 80 50 80
Ud kV 50 50 50 50 50 50 3FA1 170-7 3FA1 170-7 3FA1 170-7 3FA1 170-7 3FA1 170-7 3FA1 170-7 N 5000 5000 5000 5000 5000 5000 kg 7 7 20 20 19 19 552-5154 552-5154 552-5139 552-5139 552-5148 552-5148 .9 .9 .9 .9 .9 .9 552-5252 552-5252 552-5250 552-5250 552-5249 552-5249 .9 .9 .9 .9 .9 .9 22 22 23 23 24 24
36 kV
50/60 Hz mm 3 3 400 400 3DE1 016-0J 3DE1 016-0N
Ith kA 20 31.5
Idyn kA 50 80
Up kV 170 170
Ud kV 70 70 3FA1 230-7 3FA1 230-7 N 5000 5000 kg 31 31 552-5142 .9 552-5142 .9 552-5251 .9 552-5251 .9 25 25
12 kV
Detailed dimension drawing for earthing switch with manual operating mechanism (can be ordered)
Detailed dimension drawing for earthing switch with motor operating mechanism (can be ordered)
Pole-centre distance
Number of poles
Order No.
Dimension drawings (shown: earthing switches with motor operating mechanism and auxiliary switch)
Dimension drawing 17
Dimension drawing 18
Dimension drawing 19
Dimension drawing 20
3
Dimension drawing 21 Dimension drawing 22
Dimension drawing 23
Dimension drawing 24
Dimension drawing 25
Technical Data
Technical data of built-on components
Switching angle at max. torque Disconnec tor Degrees Earthing switch Degrees 78 78 77 78 78 77 79 79 77 79 79 64 74 74 74 74 81 78 81 78 78 75 85 83 83 83
Rated voltage
Earthing switch Nm
Three-pol e 1) disconnec tors with earthin g swit ches 3DC1 0.1-2G 60 80 76 3DC1 0.1-2L 60 80 76 3DC1 0.1-3N 90 80 81 3DC1 0.2-2G 60 80 76 3DC1 0.2-2L 60 80 76 3DC1 0.2-3N 90 80 81 3DC1 0.2-3S 130 140 79 3DC1 0.2-3U 130 140 79 3DC1 0.2-4C 90 80 81 3DC1 0.2-4G 130 140 79 3DC1 0.2-4J 130 140 79 3DC1 0.2-5E 95 95 66 3DC1 0.2-5J 150 140 80 3DC1 0.2-5L 150 140 80 3DC1 0.2-6J 150 140 80 3DC1 0.2-6L 3DC1 0.3-2G 3DC1 0.3-3N 3DC1 0.4-2G 3DC1 0.4-3N 3DC1 0.4-4C 3DC1 0.4-5E 3DC1 0.6-2G 3DC1 0.6-3N 3DC1 0.6-5E 3DC1 0.6-6E 150 80 100 80 100 100 105 110 120 140 140 140 100 100 100 100 100 120 120 160 160 160 80 79 83 79 83 83 80 82 86 83 83
V DC V DC V DC V AC, 50/60 Hz
2) 2)
2) 2)
Data of electromechanical
Rated voltag e
lockout
Power consum ption max imum W 15 15 15 15 VA 50 50 50
2) 2) 2) 2)
Operatin g voltag e Max. value V 27 66 121 242 110 121 253 Min. value V 21 51 97 193 85 97 193
Three-pol e 1) earthing swit ches 3DE1 041-0J 3DE1 041-0N 3DE1 0.2-0J 3DE1 0.2-0N 3DE1 0.2-0S 3DE1 012-0U 3DE1 073-0J 3DE1 073-0N 3DE1 014-0J 3DE1 014-0N 3DE1 016-0J 3DE1 016-0N
75 75 75 75 76 76 79 79 79 79 84 84
1) Single-pole devices require max. 50 % of the specified torques for actuation 2) For opening
3) =
L R
= 20 ms
38
&+
"
Flexible shaft
3DX4 102-0A shaft lengt h 1 m 3DX4 102-0B shaft lengt h 2.5 m 3DX4 102-0C shaft lengt h 5 m
Legend
a b c d e f l Front plate of switchgear panel Bearing plate Bearing block Eccentric shaft (17.133) of the motor operating mechanism 3DX11 Operating pin Insulating tube Shaft length 1m, to be shortened according to the panel depth
Technical Data
Circuit diagrams
Control examples for motor operating mechanism 3DX11 (for OPENposition of disconnector and earthing switch)
$, . . $ / $, . . $ /
# -
# -
# / / . $ / . 0 / $
/ . . 0 /
$,
$, 4# 5 * # -
2$1 .3 #
1(.0
3
# 2$1 .3 . $
Legend
H1A Luminous indicator OPEN H1E Luminous indicator C LOSED K1 Auxiliary contactor: 4 NO + 1 NC for control via auxiliary contactor with command execution; 2 NO for control via auxiliary contactor without command execution M1 S1 S1A S1E 2 Motor Changeover switch, 2-pole OPENpushbutton 2 NO + 1 NC CLO SE pushbutton NO + 1 NC S3, S4 X1 X3, X4 Position switches, 2 NO + 2 NC at the motor operating mechanism Connection terminals at the motor operating mechanism Connection terminals at the switchgear interlocking device 8TJ2
40
Contents
Page
Annex
Inquiry form Configuration instructions Configuration aid
41
42 43 Foldout page
R-HG11-181.tif
4
R-HG11-180.tif
Annex
Inquiry form
Inquiry concerning
Technical data
Rated voltag e Rated lightnin g impulse withstan d voltage Rated short- duratio n powerfrequency withstan d voltage Rated normal curren t 12 kV 60 kV 125 kV 28 kV 70 kV 630 A 2500 A 20 kA 50 kA 50 kA 125 kA 1-pole 24 kV 75 kV 170 kV 50 kV 36 kV 95 kV
Oth er values _ _ _ kV
_ _ _ kV
Please
_ _ _ kA
Your address
Company Dept.
Number of poles
Built-on components
Disconnecto r with earthin g switch Motor operatin g mechanis m for disconn ector/ earthin g switch Elect romechani cal lockout Earthing switch mounte d on pivot point Earthing switch mount ed on opening side 60 V DC 220 V DC 24 V DC 110 V DC 2 NO + 2 NC 2 NO + 2 NC 110 V DC 230 V AC, 50/60 Hz
60 V DC 220 V DC 6 NO + 6 NC
Auxiliary switch Auxiliary switch for built-on earthin g switch Mechanica l interlockin g Other pole-centr e distanc e Other lengt h of operatin g shaft
Yes _ _ _ mm _ _ _ mm Yes
No
No
_ _ _ Please fill in
D + +
+ + + + + + + + + + + +
+ 3 D
+ + + + + + + + + + + + + + +
Should you still need more options than the possible special equipment like pole-centre distances, other lengths of the operating shaft, vertical arrangement of the switching device, etc., please contact your responsible sales partner.
3 D
3 D
43
43
Published by and copyrigh t 2008: Siemen s AG Energy Sector Freyeslebenstrass e 1 9105 8 Erlangen , Germany Siemen s AG Energy Sector Power Distribution Division Medium Voltage Nonnendammalle e 104 1362 3 Berlin, Germany For more information , please contac t our Custome r Support Center. Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges dependin g on provider) E-mail: support.energ y@siemens.com Order No. E50001-K1511-A311-A2-7600 Printed in Germany Dispo 31601 KG 10.0 8 1.0 46 En 6101/1546 0 480001
Printed on element ary chlorine- free bleached paper. A ll rights reserved. If not stated otherwi se on the individual pages of this catalog , we reserve the right to include modific ation s, especially regar din g the sta ted values, dimension s and weights. Drawings are not binding. A ll produc t designations used are tradem arks or product name s of Siemen s AG or other supplie rs. If not stated otherwi se, all dimen sions in this catalog are given in mm . Subject to chang e wi thou t prior notice. The inform ation in this documen t cont ains gener al descri ption s of the technica l option s available, whi ch may not apply in all cases. The required techn ical option s should therefore be specified in the contr act.
R-HG11-235.eps
www.siemens.com/energy