The document proposes a new differential protection scheme for busbar protection that accounts for CT saturation effects. It presents simulation results showing the performance of the proposed scheme on a model of the Indian power transmission system in PSCAD/EMTDC software. The scheme compares the current values on incoming and outgoing lines to generate differential signals, avoiding maloperation from CT saturation during heavy through faults. Simulation results demonstrate the scheme's fast and stable operation for different internal faults, as well as its insensitivity to external faults and ability to operate during high resistance faults.
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online from Scribd
A New Differential Protection Scheme For Busbar Considering CT Saturation Effect
The document proposes a new differential protection scheme for busbar protection that accounts for CT saturation effects. It presents simulation results showing the performance of the proposed scheme on a model of the Indian power transmission system in PSCAD/EMTDC software. The scheme compares the current values on incoming and outgoing lines to generate differential signals, avoiding maloperation from CT saturation during heavy through faults. Simulation results demonstrate the scheme's fast and stable operation for different internal faults, as well as its insensitivity to external faults and ability to operate during high resistance faults.
The document proposes a new differential protection scheme for busbar protection that accounts for CT saturation effects. It presents simulation results showing the performance of the proposed scheme on a model of the Indian power transmission system in PSCAD/EMTDC software. The scheme compares the current values on incoming and outgoing lines to generate differential signals, avoiding maloperation from CT saturation during heavy through faults. Simulation results demonstrate the scheme's fast and stable operation for different internal faults, as well as its insensitivity to external faults and ability to operate during high resistance faults.
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online from Scribd
Download as pdf or txt
0 ratings0% found this document useful (0 votes)
33 views4 pages
A New Differential Protection Scheme For Busbar Considering CT Saturation Effect
The document proposes a new differential protection scheme for busbar protection that accounts for CT saturation effects. It presents simulation results showing the performance of the proposed scheme on a model of the Indian power transmission system in PSCAD/EMTDC software. The scheme compares the current values on incoming and outgoing lines to generate differential signals, avoiding maloperation from CT saturation during heavy through faults. Simulation results demonstrate the scheme's fast and stable operation for different internal faults, as well as its insensitivity to external faults and ability to operate during high resistance faults.
Copyright:
Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online from Scribd
Download as pdf or txt
You are on page 1of 4
1
A New Differential Protection Scheme for Busbar
Considering CT Saturation Effect
This work is funded by Gujarat Council on science and Technology, Government of Gujarat, India, under Project no. GUJCOST/MRP/201409/2009-10.
Nilesh Chothani, Lecturer Department of Electrical Engineering, ADIT, New Vidyanagar, Anand, Gujarat 388121, India. e-mail: chothani_nilesh@rediffmail.com
Bhavesh Bhalja, Senior Member IEEE Department of Electrical Engineering, ADIT, New Vidyanagar, Anand, Gujarat 388121, India. e-mail: brb77dee@iitr.ernet.in Abstract-- The protection of busbar demands high integrity and high speed relaying scheme. This paper presents a new differential relaying scheme for the protection of busbar. The proposed scheme depends on the difference of the value of incoming and outgoing line currents of the respective phase at a particular bus. The proposed scheme has been tested extensively using the PSCAD/EMTDC software package with fault data generated, by modeling the existing 230 kV Indian power transmission systems. The proposed scheme provides stability against external faults, more sensitivity towards high resistance faults and better reliability in discriminating in-zone and out of zone faults. Moreover, the proposed scheme avoids the effect of early & severe CT saturation during heavy through faults.
Index Terms--Busbar fault, differential protection, protective relay simulation, CT saturation detection. I. INTRODUCTION Igh speed bus protection is required not only to limit the damaging effects on equipment and system stability but also to maintain service to as much load as possible [1]. In practice, busbar is protected by various differential protection schemes such as biased percentage differential protection scheme, low impedance protection scheme and high impedance voltage scheme. Percentage differential relays create a restraining signal in addition to the differential signal and apply a percentage (biased) characteristic. The low- impedance approach does not require dedicated CTs. Further, this approach tolerates substantial CT saturation and provides high-speed tripping. High impedance voltage scheme is used in order to overcome the problem of spill current due to CT saturation in case of heavy through fault. However, this requires dedicated CTs (a significant cost associated) and cannot be easily applied to re-configurable buses. For better security, directional protection principle used to dynamically supervise the main current differential function. The main theme of this scheme is that if the power flow in one or more circuits is away from the bus, an external fault exists whereas for the power flow in all of the circuits into the bus, an internal bus fault exists [2]. The principal disadvantage of this scheme is that it requires greater maintenance and there is a probability of failure of the scheme due to large numbers of contacts connected in series with the trip circuit. Further, the operation of relays depends on bus voltage for polarization; they might not operate for a metallic short circuit that reduced the voltage practically to zero. The common practice in busbar protection is to use numerical busbar protection scheme which provides complete protection for all types of extra/ultra high voltage busbar configurations. The digital relays use innovative techniques such as CT saturation detection and processing algorithms which provides a unique combination of security, speed and sensitivity [3]. Many digital busbar relaying schemes have been developed by the designers and researchers using microprocessors, microcontrollers, digital signal processors, Artificial Neural Network (ANN), traveling waves, Wavelet Transform and employing various Artificial Intelligence techniques [4]-[7]. Protection of substation busbars is almost universally accomplished by differential relaying scheme. The conventional busbar differential relaying scheme may maloperate in case of CT saturation during an external fault [8]. Hence, in order to avoid maloperation of the conventional differential protection scheme due to CT saturation during heavy through fault, authors have proposed a new differential relaying scheme. Verification of the proposed scheme has been done on simulated data of an existing part of the Indian power system network using PSCAD /EMTDC software package. The proposed scheme is highly sensitive and provides fast protection in case of internal fault. Moreover, it remains stable in case of external fault. Furthermore, it avoids early and severe CT saturation problem during heavy external fault. The proposed scheme has shown satisfactory performance under various fault conditions, especially for high resistance fault. II. SIMULATION AND MODELING Fig. 1 shows single line diagram of a portion of Indian power system network consisting of four sources represented by Thevenins equivalent. These sources are connected to the bus under consideration through different lines Line-1, Line-2 Line-3 & Line-4 respectively. The system and line parameters are given in Appendix. A sampling frequency of 4 kHz for a system operating at a frequency of 50 Hz is used in this study. The components of power system such as generators, H IEEE CCECE 2011 - 000007 CCECE 2011 Niagara Falls, Canada 978-1-4244-9789-8/11/$26 2011 IEEE 2 generator transformers (GT) and transmission lines (TL) etc. are designed according to the collected data and specifications. The transmission line is represented using the Bergeron line model. The said developed model uses some of the main library components available in PSCAD. Also, own components have been developed by authors using programming in Fortran 77 compiler. The current signals measured from each line for all three phases are delivered to Current Transformers (CTs). The CT ratio has been decided on the basis of loading condition of the system (in this case respective change in load angle of the source). The difference between the current quantities of each incoming and outgoing lines at the bus of the respective phase has been given as an input to the relay. Test data for verifying the said scheme have been generated by modeling the complete system using the PSCAD/EMTDC software package [9]. The performance of the proposed scheme has been evaluated for different types of in-zone and out of zone faults. Relay responses for some special case such as high resistance fault was also investigated. Fig. 2 shows the tripping logic for differential relay connected at the bus. In this logic, the differential principle is accomplished by comparing the value of CT secondary currents of the respective phase of all four lines connected to the main bus. As shown in Fig. 2, the summing block generates three differential current signals namely I sa , I sb and I sc as per the direction and magnitude of fault current. Thereafter, these differential signals are given to the respective phase relay unit. If the values of I sa , I sb and I sc exceed the pick-up setting (0.5 pu which is decided on the basis of loading condition of system), the differential relay generates a spike, which will be made constant by Hysteresis-Buffer. Thereafter, the output of each phase relay is given to OR gate. Depending upon the output (logic 1) of the relay of the respective phase, OR gate generates a final tripping signal (BRK) which will be given to all the circuit breakers connected to the main bus.
Fig. 1 Busbar relaying scheme modeled in PSCAD software III. SIMULATION RESULTS The system shown in Fig. 1 was subjected to various types of fault. The performance of the proposed technique was evaluated for different types of internal and external faults. The effect of high resistance fault and CT saturation has been also investigated. The output of all branch currents, along with the differential current of CT secondaries and the status of circuit breakers are represented graphically in this paper.
Fig. 2 Tripping logic of differential relay connected at bus A. Internal Fault Fig. 3 shows the behavior of the proposed scheme in terms of differential currents and breaker status for single-line to ground fault (a-g) which is applied at 0.06 second on the main bus (Fig. 1) with fault resistance R f = 0.01. It has been observed from Fig. 3 that the differential current exceeds the predetermine threshold value depending upon the types of faults. Accordingly, the respective relay generates a tripping signal which will be given to all the line circuit breakers connected to the main bus. It is to be noted from Fig. 3 that the differential relay operates successfully and clears a-g fault within 13ms. A wide variation of in-zone faults such as single- line to ground fault, double line fault, double line to ground fault and triple line fault have been investigated. However, due to space limitations, the results are not shown in the paper. Fig. 3 Relay response during L-g (a-g) internal fault on bus with R f = 0.01 B. External Fault Fig. 4 shows the response of the proposed differential scheme for a single line-to-ground external fault (a-g) on line-4 at 10 km from the main bus (Fig. 1) which is applied at 0.07 second with fault resistance R f = 0.01. It has been observed from IEEE CCECE 2011 - 000008 3 Fig. 4 that the differential current remains well below the predetermine threshold value and hence, the relay dost not operate. In this condition, no trip signal is generated by the relay. A wide variation of external faults such as single-line to ground fault, double line fault, double line to ground fault and triple line fault at different locations have been investigated. It is to be noted that for all types of external faults, the proposed differential scheme remains stable and hence, gives better stability.
Fig. 4 Relay response during external fault on line-4 with R f = 0.01 C. High Resistance Fault Many algorithms related to bus protection fail to detect fault with a considerable value of fault resistance. Although, high resistance fault reduces the magnitude of the fault current, the proposed scheme is capable to detect these faults. To analyze the said situation, a single line-to-ground fault with fault resistance of 75 has been simulated inside the zone of the main bus. Although, there is a delay in the action of crossing the threshold boundary of the relay, as shown in Fig. 5, the proposed differential relaying scheme operates within 18ms. The proposed scheme has been tested for different types of high resistance faults such as single line to ground fault and double line to ground faults up to R F =200 (not shown in the paper). In these situations, it has been observed by the authors that the operating time of relay was within 20ms after the inception of fault. D. Effect of CT Saturation The effect of CT saturation for any busbar protection scheme is of crucial importance particularly during heavy through fault. The protection scheme must remain stable during external fault and must not delay or prevent operation in case of an internal fault. The CT saturation is obtained by CT model block available in PSCAD/EMTDC. By changing the CT secondary burden resistance, different degrees of CT saturation can be obtained [10].
Fig. 5 Relay response during internal fault at F on phase A with R f = 75
The performance of the proposed scheme during CT saturation is carried out by simulating different faults on line-4 at 10 km from the main bus with varying fault resistances. When a heavy through fault occurs, the secondary current of CT is reduced sharply due to saturation of CT. Therefore, the time between two successive zero crossings of the secondary current becomes smaller than half a cycle. This phenomenon is used to detect the CT saturation by comparing the zero crossing interval of the secondary current of saturated CT to the zero crossing interval of the secondary current of unsaturated CT for half a cycle time interval. The zero crossing time of CT secondary during fault can be considered as 8 ms9 ms instead of 10 ms (half a cycle for a rated frequency of 50 Hz) because of noise and transient frequency penetration [11]. Fig. 6 shows simulated module of zero crossing detector developed by authors in PSCAD which uses zero detectors, monostable multivibrators and logical circuits.
Fig. 6 The simulated module of zero crossing detector IEEE CCECE 2011 - 000009 4
Fig. 7 Simulation results of unsaturated signal, saturated signal and the difference of zero crossing of two signals.
In this module, zero detector measures the zero crossing interval of the secondary current of saturated CT. A standard estimated 50 Hz signal is given to another zero detector which measures the zero crossing interval of the secondary current of unsaturated CT (estimated signal) at every 10 ms. The computation is repeated for every half a cycle and the difference between the zero crossing interval of the estimated signal and the saturated CT secondary signal are calculated. Fig. 7 shows the simulation results for estimated signal (unsaturated signal), saturated CT secondary current and the difference of the zero crossing interval for phase-a during single line to ground external fault on line-4 at 0.04 second with R f = 0.01 . The middle section shows the closer view of signals shown in the first section (Fig. 7) for one cycle interval. If this difference exceeds a predetermined threshold value, a phase comparator circuit (not shown in the paper) is activated and the blocking command is given to the bus differential relay. With wide range of variations in fault conditions and transient frequency penetration, it has been found by the authors that the appropriate value of threshold is 1.5 ms. It is to be noted that the proposed scheme is able to detect heavy and low saturation of CT during external faults. IV. CONCLUSION A new differential relaying scheme for busbar protection is proposed in this paper. The proposed scheme was tested extensively by using data that was generated by modeling an existing 230 kV Indian power transmission system network using PSCAD/EMTDC software package. The proposed scheme has the ability to detect all types of in-zone faults and remains stable during out of zone faults. An average tripping time for most of the internal faults is within 20ms. The proposed zero crossing technique is able to detect severe CT saturation during all types of external faults with different system parameters to achieve better security. Further, the proposed scheme is highly sensitive in case of high resistance in-zone faults.
APPENDIX Source Data Positive-sequence impedance of sources G1, G2 = 585 0 Zero-sequence impedance of sources G1, G2= 1085 0 Positive-sequence impedance of sources G3, G4 = 1085 0 Zero-sequence impedance of sources G3, G4= 2085 0 Frequency = 50 Hz Load angle of G1, G2 and G4 = 0 0
Load angle of G3 = 20 0
Transmission-line Data Length: Line-1 and Line-2 = 50 km Line-3 = 100 km Line-4 = 80 km Voltage = 230 kV Positive-sequence impedance = 0.0297 + j0.332 /km Zero-sequence impedance = 0.162 + j1.24 /km Positive-sequence capacitance = 9.23 nF/km Zero-sequence capacitance = 6.72 nF/km V. REFERENCES
[1] N. G. Chothani, B.R. Bhalja and R.P.Maheshwari, A new digital differential relaying scheme for the protection of busbar, 4 th
International Conference on CERA-09,February 19-21, 2010.IIT Roorkee. [2] M. M. Eissa, A novel digital directional technique for bus-bars protection, IEEE Transactions on Power Delivery, Vol. 19, No. 4, pp. 1636-1641, October 2004. [3] P740 Numerical Busbar Protection, Technical Data Sheet, Publication No. P740/EN TD/G22, AREVA T&D, pp. 1-22. [4] T. S. Sidhu, L. Mital and M. S. Sachdev, A Comprehensive Analysis of an Artificial Neural-Network-Based Fault Direction Discriminator, IEEE Transactions on Power Delivery, Vol. 19, No. 3, pp. 1042-1048, July 2004. [5] Gang Wang, Heifeng Li and Xiaohua Li, A New Numerical Distributed Busbar Protection, In Proceedings of 8 th IEE International Conference on Developments in Power System Protection, Vol. 1, 5-8 April 2004, pp. 387-390. [6] M. M. Eissa, A novel wavelet approach to busbar protection during CT saturation and ratio-mismatch, Electric Power System Research, Vol. 72, 2004, pp. 41-48. [7] S. P. Valsan and K. S. Swarup, Computationally Efficient Wavelet-Transform Based Digital Directional Protection for Busbars, IEEE Transactions on Power Delivery, Vol. 22, No. 3, July 2007, pp. 1342-1350. [8] M. E. Mohammed, High speed differential busbar protection using wavelet packet transform, Proceeding IET Generation, Transmission & Distribution, Vol. 152, No. 6, November 2005, pp. 927-933. [9] PSCAD/EMTDC Manual, Getting Started, Manitoba HVDC Research Centre Inc., January 2001. [10] Annakkage, U.D. McLaren, P.G., Dirks, E., Jayasinghe, R.P., and Parker, A.D.: A current transformer model based on the Jiles Atherton theory of ferromagnetic hysteresis, IEEE Trans. On Power Delivery, Vol. 15 No. 1, 2000, pp. 57 61 [11] Hamed Dashti, Majid Sanaye Pasand , Senior Member, IEEE, and Mahdi Davarpanah, Fast and Reliable CT Saturation Detection Using a Combined Method, IEEE Transactions On Power Delivery, Vol. 24, No. 3, July 2009,Pp. 1037-1044. IEEE CCECE 2011 - 000010