SYSTEM
HONEYWELL EXCEL 5000 OPEN SYSTEM
SPECIFICATION DATA
FEATURES
Plug-and-play Panel Bus I/O modules for easy maintenance. LONW ORKS Bus I/O modules (FTT10-A, link power compatible) for easy integration into any system. Pluggable I/O modules: I/O module exchange without rewiring the power and bus connections. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase. Reuseability of existing applications (Excel 500, etc.) Fast wiring with state-of-the-art push-in terminals (screwtype terminals also available) and bridge connectors. Wide range of sensors supported (NTC20k, NTC10k, PT1000-1/-2, NI1000TK5000, PT3000, Balco500, 0/210 V, 0/420 mA). NOTE: The mixed I/O modules XF830A and XFU830A feature inputs suitable for signals from NTC20k sensors and 0/210 V, 0/420 mA, only! Binary input LEDs can be configured for status display (off/yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules XF830A and XFU830A feature only non-configurable binary input LEDs! Configurable safety position for outputs, in case of loss of communication with the Controller module. XCL8010A Controller Module with real-time clock. Max. wiring flexibility due to optional accessories like aux. terminals, manual disconnectors, and cross-connectors. Can be mounted in small installation housings. Flexible I/O module mix covering all your application requirements. Utmost flexibility to design and control your most complex applications through increased memory size. State-of-the-art control of critical applications thanks to short cycle times (30% faster than Excel 500). Fast firmware download (~90 sec) via serial connection. C-Bus to upgrade from and operate with existing Honeywell installations, thereby protecting your investment. Web access via optional OpenViewNet. Dedicated modem interface for remote operation. Human-Machine-Interface, Laptop connection.
GENERAL
The Excel 800 System (consisting of the XCL8010A Controller Module and connected Excel 800 Panel Bus and/or Excel 800 LONW ORKS Bus input/output modules) provides highly cost-effective freely programmable control for heating, ventilation, and air conditioning (HVAC) systems. It performs a wide range of energy management functions, including optimum start/stop, night purge, and max. load demand. The Excel 800 System provides excellent value during installation and long-term operation. Its modular design enables the system to be expanded to meet growing needs. The use of "plug & play" Excel 800 Panel Bus I/O modules yields huge installation and commissioning cost-savings due to new, patented technologies, while the Excel 800 LONW ORKS Bus I/O modules employ the LONW ORKS communication standard. The mixed Excel 800 Panel Bus I/O modules (XF830A and XFU830A) consist of a terminal socket with an integrated electronic module. The pluggable (i.e., non-mixed) Excel 800 Panel Bus (XF82x) or LONW ORKS Bus (XFL82x) I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. Such removable electronic modules can be hot-swapped without disrupting the power and bus connections. Software updates, configuration, and commissioning are done automatically for all Excel 800 Panel Bus I/O Modules. The open LONW ORKS standard enables easy integration of rd 3 -party controllers and devices, and communication with other CentraLine / Honeywell devices (e.g. Excel 10 and Excel 12 room controllers). Remote service can be done via a modem / ISDN terminal adapter in connection with a building supervisor. Direct Web is supported via Honeywell's OpenViewNet, which may be connected via C-Bus to the Excel 800.
U.S. Registered Trademark Copyright 2011 Honeywell Inc. All Rights Reserved
EN0B-0564GE51 R0711
SYSTEM OVERVIEW
EBI / SymmetrE BNA Ethernet LAN/WAN Internet Browser OVN = OpenViewNet
XLWeb
C-Bus
IO (XF8xx)
LON
LON IO (XFL8xx)
XFCxxx
XFCLxxx
XL10/12
General
The Excel 800 Controller Module (XCL8010A) can communicate with a variety of other devices (see Fig. 4), including any combination of up to sixteen Panel Bus I/O Modules and a large number of LONW ORKS devices (e.g. rd room controllers, LONW ORKS I/O modules, 3 -party devices). The Excel 800 Panel Bus I/O Modules communicate via the Panel Bus, while the Excel 800 LONW ORKS Bus I/O modules utilize the LONW ORKS communication standard and can thus also communicate with other LONW ORKS controllers. The pluggable I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connections: Simply unplug the old and insert the new module. Software updates, configuration, and commissioning are all done automatically by the Excel 800 Controller Module for all Panel Bus I/O Modules. The Excel 800 Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Excel 800 LONW ORKS I/O Modules are configured using CARE. Alternatively, LonMaker and LNS plug-ins can also be used for configuration.
EN0B-0564GE51 R0711
MIXED I/Os
XFLR822A
XFLR824A
XFL822A
XFL823A
XFL824A
XFR822A
XFR824A
XFR825A
XF821A
XF822A
XF823A
XF824A
XS821-22 XSU821-22
XS823 XSU823
XS824-25 XSU824-25
Fig. 2. Overview of Excel 800 Modules Table 1. Overview of Excel 800 Modules order number description Excel 800 Controller Module XCL8010A Panel Bus I/O Modules
XF821A XF822A XFR822A XF823A XF824A XFR824A XFR825A XF830A XFU830A Pluggable Panel Bus Analog Input Module (with 8 analog inputs) Pluggable Panel Bus Analog Output Module (with 8 analog outputs) Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides) Pluggable Panel Bus Binary Input Module (with 12 binary inputs) Pluggable Panel Bus Relay Output Module (with 6 relay outputs) Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides) Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides) Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with push-in terminals Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with screw terminals Pluggable LONW ORKS Bus Analog Input module (with 8 analog inputs) Pluggable LONW ORKS Bus Analog Output Module (with 8 analog outputs) Pluggable LONW ORKS Bus Analog Output Module (with 8 analog outputs and manual overrides) Pluggable LONW ORKS Bus Binary Input Module (with 12 binary inputs) Pluggable LONW ORKS Bus Relay Output Module (with 6 relay outputs) Pluggable LONW ORKS Bus Relay Output Module (with 6 relay outputs and manual overrides) Push-in terminal socket for pluggable AI/AO modules (incl. connector bridge, swivel label) Screw-type terminal socket for pluggable AI/AO modules (incl. connector bridge, swivel label) Push-in terminal socket for pluggable BI modules (incl. connector bridge, swivel label) Screw-type terminal socket for pluggable BI modules (incl. connector bridge, swivel label) Push-in terminal socket for pluggable relay/floating output modules (incl. connector bridge, cross connector, swivel label) Screw-type terminal socket for pluggable relay/floating output modules (incl. connector bridge, cross connector, swivel label)
Terminal Sockets (not needed for the mixed I/O modules XF830A and XFU830A)
EN0B-0564GE51 R0711
description
Manual Disconnector Module for AI/AO/BI Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. For pluggable I/O modules, only.
XS812RO
Manual Disconnector Module for Relay Output Modules (for manual disconnection of individual signals; useful during start-up). Plugged between Terminal Socket and Electronic Module. Not suitable for line voltage. For pluggable I/O modules, only.
XS814 XS830
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals. For pluggable I/O modules, only. Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only. Ten Auxiliary Terminal Blocks (for connection of 020 mA signals). Each terminal block supports up to 8 current inputs. For XF830A and XFU830A, only. 20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package. For pluggable I/O modules, only. 40 Cross-Connectors for connection of three relay commons (if voltage in relay block 1 is different from voltage in relay block 2). For pluggable I/O modules, only. 10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package / in the mixed I/O module package. 10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules, only. 10 Swivel Label Holders for Mixed I/O modules. One Swivel Label Holder is included in each mixed I/O module package. For mixed I/O modules, only.
XS831
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2
XS815
XS817
XS816
XAL10
XAL11
XW586
RJ45
XW882
Adapter cable for connection of XCL8010A Controller Module to XI582 Operator Interface (alternatively, XW586 + XW582 can be used). Download cable (alternatively, XW586 + XW585 can be used).
RJ45
XW885
NOTE: All Excel 800 I/O Modules (pluggable and mixed) are protected against short circuit, 24 Vac +20% and 30 Vdc.
EN0B-0564GE51 R0711
Features: Features: Changeover relays 2 relays per Voltage: 19250 Vac, floating output 129 Vdc, P>50 mW Voltage: max. total current: 19250 Vac, Features: 12 A 129 Vdc, current per relay: P>50 mW 1 LED per input N.O.: 4(4) A ac. or max. total current: Color mode can 4(1) A dc, 12 A be set per input N.C.: 2(1) A ac or current per relay: to OFF/yellow 4(1) A dc N.O.: 4(4) A ac or or green/red Safety position 4(1) A dc, using CARE (remain, 0%, 100%) N.C.: 2(1) A ac or yellow LED per output 4(1) A dc 1 potentiometer per floating output Version with manual 2 LEDs per output: override (R): green: relay 1 1 switch per output closed, red: relay 2 auto feedback signal closed (mode + value) blinking in manual blinking in manual override position override position auto feedback signal (mode + value)
Also configurable as: binary outputs (0 V / 10 V) Features: 10-bit resolution (default) Safety position (remain, 0%, 50%, 100%)
EN0B-0564GE51 R0711
75 76 77 78
87654321
11 LON 1 12
1 8 C+ 9 C10
SHIELD
Fig. 3. XCL8010A Controller Module The XCL8010A Controller Module can communicate with a variety of other devices (see Fig. 4), including any combination of up to sixteen Panel Bus I/O Modules and/or LONW ORKS devices (e.g. room controllers). A total of 381 data-points (of all types, e.g. internal virtual data-points and hardware data-points) are permitted. Typically, HVAC applications require an equal number of internal virtual data-points and hardware data-points. The Excel 800 Controller Module and Panel Bus I/O Modules can be separated by up to 40 m.
HMI INTERFACE and LEDs
13 14
5 C+ 6 C7
SHIELD
2 3
* *WATCHDOG RELAY
4 NC
Electrical Specifications
Operating Voltage
24 Vac, 20%, 2130 Vdc The Excel 800 System (XCL8010 Controller Module and connected Excel 800 I/O Modules together with field devices) can be powered by one or more external transformers.
Memory
128 kB EPROM 512 kB RAM 2 MB Flash EPROM (firmware and application)
Watchdog
Honeywell
C-BUS
RESET BUTTON
PC/HMI
The watchdog output is active if the Excel 800 Controller Module is not operating properly.
POWER LED
LonWorks INTERFACE
87654321
8 7 65 4 3 2 1 !
Microprocessor
16-bit processor (TMP 91 CY22). 22 MHz
11
S1
all mid end 76k
S2
Panel LON
Modem
87654321
1 2 3
ALARM LED
12 13 14
Tx Rx
C-Bus in
C-Bus out
C-BUS TERMINALS C-BUS TERMINATION SWITCH I/O BUS SELECTION SWITCH MODEM INTERFACE and LEDs
In case of power failure, the super capacitor saves RAM content and real-time clock for 72 hours (environmentally friendly; no problems disposing of dead batteries).
EN0B-0564GE51 R0711
XL-ONLINE
The PC-based XL-Online is the local intelligent operating and service software. It performs all the operating functions of the XI582 as well as having the advantages of a PC. Not only can the XL-Online make major modifications such as changing setpoint values and time program switching points, it also offers all service and commissioning functions. XL-Online can be operated at five different access levels, three of which are password-protected. A printer can be connected to the parallel interface of the PC to log alarms and error messages. As with the XI582, the PC with the XLOnline operator and service software can be placed up to 15 meters from the computer module. Line drivers allow distances of up to 100 m (328 ft.).
Fig. 6. The XI582 Operator Interface The XI582 Operator Interface is the command and information center of the Excel 800 System. With it, data can be entered and displayed. Information such as current temperature values, control status, etc. can also be displayed. The menu-driven, 6-line, backlit LCD graphic display with 34 characters per line, together with eight clearly marked keys, makes the device easy to use. The XI582 is connected to the HMI Interface on the front of the Excel 800 Controller Module. The XI582 can be mounted up to 15 m (48 ft.) away from the Controller Module. This can be extended to 100 m (328 ft.) using line drivers.
Communication
Human-Machine Interface
The XCL8010A Controller Module is equipped with an HMI Interface (RJ45 socket serving as a serial port) for the connection of HMIs, e.g.: the XI582 Operator Interface or the XI882A Operator Interface, or a laptop (with XL-Online / CARE).
C-Bus Interface
Up to 30 C-bus devices (e.g. controllers, etc.) can communicate with one another and a PC central via the Cbus interface. The C-bus must be connected through the individual controllers (open ring topology).
Web Interface
The optional OpenViewNet (OVN, see also Fig. 1 on page 2) is an intelligent BMS (Building Management System) that interfaces Excel 800 Controller Modules on one end and provides TCP/IP interface on the other. The device is then IPenabled and accessible from anywhere in the world. The OpenViewNets processor and in-house memory hosts and runs both the operating system and the application that enables a user to monitor and supervise buildings remotely. Notification of alarms and events are provided so that actions can be taken accordingly. You can also generate reports, schedule them to run periodically, use customized graphics for monitoring, and trend important data off-line or online. The processing of data between the device and the clients is distributed to utilize the resources effectively and efficiently.
EN0B-0564GE51 R0711
LONWORKS Interface
The LONW ORKS bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a polarity; that is, it is not important which of the two LONW ORKS bus terminals are connected to each wire of the twisted pair. The LONW ORKS bus can be wired in daisy chain, star, loop or any combination thereof as long as the max. wire length requirements are met. The recommended configuration is a daisy chain with two bus terminations. This layout allows for max. LONW ORKS bus length, and its simple structure presents the least number of possible problems, particularly when adding on to an existing bus.
Alarm Handling
The alarm handling facility offers system security. Alarm signals can, for example, alert the operator to scheduled maintenance work. All alarms that occur are stored in data files and reported immediately. If your system configuration allows, you can also list alarms on a printer or transmit alarms to higher-level devices via the local bus or a modem. There are two types of alarms, critical and non-critical. Critical alarms (e.g. system alarms caused by communication failures) have priority over non-critical alarms. To distinguish between alarm types, you can generate your own alarm messages or use pre-programmed system messages. The following events all generate alarm messages: exceeding limit values, overdue maintenance work, totalizer readings, digital data point changes of state.
Modem Interface
The XCL8010A Controller Module is equipped with a Modem Interface (RJ45 socket serving as a serial port) for the connection of a modem or an ISND terminal adapter.
PROGRAMMING
The Excel 800 System includes the CARE software package specially designed to meet the requirements of application engineers. The easy-to-use, menu-driven software features the following functions: data point description, time program, alarm handling, application program (DDC program), password protection, LONW ORKS configuration.
Password Protection
The Excel 800 System is also protected by passwords. This ensures that only authorized persons have access to system data. There are four operator levels, each protected by its own password. Operator level 1: Read only. The operator can display information about setpoints, switching points, and operating hours. Operator level 2: Read and make limited changes. The operator can display system information and modify certain pre-set values. Operator level 3: Read and make changes. System information can be displayed and modified. Operator level 4: Access level for tools (e.g. CARE, XLOnline).
Time Program
The time program can be used to enter the setpoint or status at any time for any data point. The following time programs are available: daily program, weekly program, annual program, TODAY function, special day list. Daily programs are used to create a weekly program. The annual program is created automatically by multiplying the weekly program and then incorporating daily programs. The TODAY function allows direct changes to the switching program. It allows you to allocate a setpoint or status to the selected data point for a defined period of time.
Trending
The Excel 800 System provides controller-based trending. This feature allows historical values to be stored in the Controller Module. Both time-based or value-hysteresisbased trending are possible.
EN0B-0564GE51 R0711
23
45
67
PRESS
S1
EF
S2
8 9A
S1
23 EF
45
67
S2
8 9A
Honeywell
LON
C-BUS
RESET
PC/HMI
1
87 654321 876543 21 !
Honeywell
1 2 3 4 5 6 7 8 9 10 11 12
S1
all mid end
S2
Panel LON
Modem
87654321
1 2 3 21 22 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12
V AUX
AI/AO GND
9 10 11 12 13 14 15 16 17 18 25 26
BI GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
Rx Tx
LON
C-Bus in
C-Bus out
Power/ Alarm
GND
01
01
01
23
45
67
23
45
67
PRESS
S1
EF
S2
8 9A
S1
EF
S2
8 9A
S1
23 EF
Honeywell
Honeywell
100
100
AUTO
AUTO
11 12 13
21 22 23
31 32 33
41 42 43
51 52 53
61 62 63
21
22
11
21 22 23
31 32 33
V AUX GND
AI/AO GND
9 10 11 12 13 14 15 16 17 18 25 26
12 13
14
24
34
44
54
64
25
14
24
34
General
Each Excel 800 I/O Module is equipped with: one green power LED one yellow service LED
Overvoltage Protection
All inputs and outputs are protected against 24 Vac and 40 Vdc overvoltage as well as against short-circuiting.
Service LED
Each I/O Module is equipped with a yellow service LED (status: yellow/OFF) for easy diagnosis of failures.
Microprocessor
Each I/O Module is equipped with its own microprocessor.
BCD
BCD
BCD BCD
PRESS PRESS
PRESS PRESS
Honeywell
45
67
S2
8 9A
BCD
Honeywell
41 42 43
51 52 53
61 62 63
44
54
64
25
EN0B-0564GE51 R0711
Fig. 9. XF821A Panel Bus AI Module (shown with socket) and XFL821A LonWorks Bus AI Module (shown without socket) The pluggable Excel 800 Analog Input Modules, with 8 analog inputs, are available in the following versions: XF821A Panel Bus Analog Input Module XFL821A LONW ORKS Bus Analog Input Module They are installed with the XS821-22 or XSU821-22 Terminal Socket (incl. one connector bridge and one swivel label). Accessory disconnector module: XS812 (see also Table 2 on page 4).
Vaux Vaux 21 9 22 10
AI1 1 11
AI2 2 12
AI3 3 13
AI4 4 14
AI5 5 15
AI6 6 16
GND GND
21 22
Vaux GND
9 10 11 12 13 14 15 16 17 18
EN0B-0564GE51 R0711
BCD
71 72 73 74
S1
S2
01 2
345
67
75 76 77 78
8 9A
EF
AI7 7 17
AI8 8 18
25 26
AI / AO GND
25 26
10
XF822A
XFL822A
Fig. 11. XF822A Panel Bus AO Module and XFL822A LonWorks Bus AO Module (both shown without socket)
NC 21 9
NC 22 10
GND GND
21 22
Vaux GND
9 10 11 12 13 14 15 16 17 18
Fig. 12. XFR822A Panel Bus AO Module (shown with socket) and XFLR822A LonWorks Bus AO Module (shown without socket) The pluggable Excel 800 Analog Output Modules, with 8 analog ouputs, are available in the following versions: XF822A Panel Bus Analog Output Module (without manual overrides) XFR822A Panel Bus Analog Output Module (with manual overrides) XFL822A LONW ORKS Bus Analog Output Module (without manual overrides) XFLR822A LONW ORKS Bus Analog Output Module (with manual overrides) They are installed with the XS821-22 or XSU821-22 Terminal Socket (incl. one connector bridge and one swivel label). Accessory disconnector module: XS812 (see also Table 2 on page 4).
Features
011 Vdc, +/-1 mA Floating actuator (requires MCD3) Binary output (0 V / 10 V) red LED per output (brightness according to signal level) Optional versions with manual override potentiometers (Auto, 0100%; LED flashes in override mode) Feedback on manual override signal 8-bit resolution Configurable safety position for outputs in case of communication problems (remain, 0%, 50%, 100%)
11
BCD
71 72 73 74
S1
S2
01 2
345
67
75 76 77 78
8 9A
EF
25 26
AI / AO GND
25 26
EN0B-0564GE51 R0711
Fig. 14. XF823A Panel Bus BI Module (shown with XS823) and XFL823A LonWorks Bus BI Module (shown without socket) The pluggable Excel 800 Binary Input Modules, with 12 binary inputs, are available in the following versions: XF823A Panel Bus Binary Input Module XFL823A LONW ORKS Bus Binary Input Module They are installed with the XS823 or XSU823 Terminal Socket (incl. one connector bridge and one swivel label). Accessory disconnector module: XS812 (see also Table 2 on page 4).
BI1 1 13
BI2 2 14
BI3 3 15
BI4 4 16
BI5 5 17
BI6 6 18
BI7 7 19
BI8 8 20
GND GND GND GND GND GND GND GND GND GND GND GND
BI GND
13 14 15 16 17 18 19 20 21 22 23 24 25 26
EN0B-0564GE51 R0711
BCD
71 72 73 74
S1
S2
01 2
345
67
75 76 77 78
8 9A
EF
25 26
10 11 12
12
XF824A
XFL824A
RELAY1
Fig. 16. XF824A Panel Bus Relay Output Module and XFL824A LonWorks Bus Relay Output Module (both shown without socket)
NO 11 NC 12 COM 13 CON 14
11 12 13 14
21 22 33 24 34
31 32 33 44
Fig. 18. Excel 800 Relay Output Modules (schematic) Fig. 17. XFR824A Panel Bus Relay Output Module (shown with socket) and XFLR824A LonWorks Bus Relay Output Module (shown without socket) The pluggable Excel 800 Relay Output Modules, with 6 relay outputs, are available in the following versions: XF824A Panel Bus Relay Output Module (without manual overrides) XFR824A Panel Bus Relay Output Module (with manual overrides) XFL824A LONW ORKS Bus Relay Output Module (without manual overrides) XFLR824A LONW ORKS Bus Relay Output Module (with manual overrides) They are installed with the XS824-25 or XSU824-25 Terminal Socket (incl. one connector bridge, one cross connector, and one swivel label). Accessory disconnector module: XS812-RO (see also Table 2 on page 4).
Features
Cross-Connecter 1 yellow LED per output Optional versions with manual override switches (Auto, 0, 1; LED flashes in override mode) Feedback on manual override signal Configurable safety position for outputs in case of communications problems (remain, OFF, ON) Permissible Load per Relay Output Module (Total) Max. load: 19250 Vac: 12 A 124 Vdc: 12 A resistive, 3 A inductive Permissible Load per Normally-Open Contact: Max. load: 19250 Vac: 4 A resistive or inductive 124 Vdc: 4 A resistive, 1 A inductive Min. load: P > 50 mW Permissible Load per Normally-Closed Contact: Max. load: 19250 Vac: 2 A resistive, 1 A inductive 124 Vdc: 2 A resistive, 1 A inductive Min. load: P > 50 mW
13
BCD
71 72 73 74
S1
S2
01 2
345
67
75 76 77 78
8 9A
EF
25
41 42 43 54 64
51 52 53
61 62 63
25
EN0B-0564GE51 R0711
Fig. 19. XFR825A Panel Bus Floating Output Module (shown with socket) The pluggable XFR825A Panel Bus Floating Output Module (with manual overrides), with 3 floating outputs, is installed with the XS824-25 or XSU824-25 Terminal Socket (incl. one connector bridge, one cross connector, and one swivel label). Accessory disconnector module: XS812-RO (see also Table 2 on page 4).
11 12 13 14
21 22 33 24 34
31 32 33 44
EN0B-0564GE51 R0711
BCD
71 72 73 74
S1
S2
01 2
345
67
75 76 77 78
8 9A
EF
25
41 42 43 54 64
51 52 53
61 62 63
25
14
Features
1 yellow LED per output Configurable safety position for outputs in case of communications problems (remain in last position, OFF, ON) Permissible Load per mixed Excel 800 Panel Bus I/O module (total) Max. load: 1929 Vac: 3 A 124 Vdc: 3 A resistive, 3 A inductive Permissible Load per Normally-Open Contact: Max. load: 1929 Vac: 0.5 A resistive or inductive 124 Vdc: 0.5 A resistive, 1 A inductive Min. load: P > 50 mW
Fig. 21. XF830A and XFU830A Mixed Panel Bus Modules The mixed Excel 800 Panel Bus I/O modules, with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs, are available in the following versions: XF830A mixed Excel 800 Panel Bus I/O module, with push-in terminals XFU830A mixed Excel 800 Panel Bus I/O module, with screw terminals Each features an integrated terminal socket and electronic module and comes complete with one connector bridge and one swivel label. The XF830A can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top and/or bottom. The XFU830A can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top, only.
71 72 73 74 COM a COM b 24V~ 24V~0
40
External 24V
01 2
34 5
Binary Inputs
Analog Inputs
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
DI
1 2 3 4 5 6 7 8 9 10 11 12
XF830A
12 BI / 8 AI / 8 AO / 6 RO 24V, 15VA, T50 0706AX0001-XFU830A 8
Made in Germany 0532
7 8 9 10 11 12 17 18 19 20
1 2 3 4 5 6 13 14 15 16
A1 A2 A3 A4 A5 A6 A7 A8 A9
1 3
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 B1 A2 B2 A3 B3 A4 B4 G1
Fig. 22. XF830A mixed Excel 800 Panel Bus I/O module, shown with 4 optional aux. terminal blocks (top view)
71 72 73 74 COM a COM b 24V~ 24V~0
40
External 24V
01 2
Binary Inputs
Analog Inputs
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
DI
1 2 3 4 5 6 7 8 9 10 11 12
XFU830A
12 BI / 8 AI / 8 AO / 6 RO 24V, 15VA, T50 0706AX0001-XFU830A 8
Made in Germany 0532
7 8 9 10 11 12 17 18 19 20
1 2 3 4 5 6 13 14 15 16
Fig. 23. XFU830A mixed Excel 800 Panel Bus I/O module, shown without optional aux. terminal blocks (top view)
BCD
EF
S2
BCD
EF
S2
75 76 77 78
34 5
67
8 9A
GND
Analog Outputs
AO5 AO6 25 26 21 22 AO1 AO2 AO7 27 23 AO3
24V Relays
IN4 38 32 NO4 IN5 39 33 NO5 IN6 40 34 NO6
Honeywell
G1 G2 41 42
1 2 3 4 5 6
DO
25 26 27 28 35 36 37 38 39 40
41 42
21 22 23 24 29 30 31 32 33 34
2 4
B1 B2 B3 B4 B5 B6 B7 B8 B9
A5 B5 A6 B6 A7 B7 A8 B8 G2
75 76 77 78
67
8 9A
GND
Analog Outputs
AO5 AO6 25 26 21 22 AO1 AO2 AO7 27 23 AO3
24V Relays
IN4 38 32 NO4 IN5 39 33 NO5 IN6 40 34 NO6
Honeywell
G1 G2 41 42
1 2 3 4 5 6
DO
25 26 27 28 35 36 37 38 39 40
41 42
21 22 23 24 29 30 31 32 33 34
15
EN0B-0564GE51 R0711
Mounting Methods
DIN-rail mounting (e.g. in control cabinet).
Applicable Literature
Mounting Instructions (EN1B-0359GE51); Installation Instructions (EN1B-0375GE51).
Power Consumption
Table 5. Power consumption of XCL8010A supply voltage devices powered 24 Vac 24 Vdc XCL8010A watchdog load (terminal 4) XF821A, XFL821A XF822A, XFR822A XFL822A, XFLR822A XF823A, XFL823A XF824A, XFR824A, XFR825A XFL824A, XFLR824A XF830A, XFU830A 190 mA < 500 mA 130 mA 150 mA 160 mA 180 mA 140 mA 140 mA 200 mA 140 mA < 500 mA 80 mA 90 mA 90 mA 130 mA 80 mA 90 mA 95 mA
Mechanical
Housing Dimensions (H x W x D)
The XCL8010A Controller Module has the dimensions: 110 X 144 X 93 mm (see also Fig. 24 on page 17). The pluggable Excel 800 I/O Modules (mounted on Terminal Sockets) all have the dimensions: 110 X 90 X 93 mm (see also Fig. 25 on page 17). The mixed Excel 800 I/O Modules have the dimensions: 216 X 110 X 93 mm (see also Fig. 26 on page 18).
Housing Material
Plastic, flame-retardant
EN0B-0564GE51 R0711
16
Dimensions
144
92.75
110
28 32
Fig. 24. XCL8010A Controller Module, dimensions (in mm)
89.5
94.1
TERMINAL SOCKET
LOCK
110
67.5
30.6 28
83
SCREW-TYPE TERMINALS
38
14
XS814 Aux. Terminal Package (optional)
SWIVEL LABEL HOLDER
51.5
Fig. 25. Pluggable Excel 800 I/O Modules (example shows Manual Overrides), incl. Terminal Socket, dimensions (in mm)
17
EN0B-0564GE51 R0711
45
45
216
71 72 73 74 COM a COM b 24V~ 24V~0
40
External 24V
3 45
92.5
24V for relay 1...5
J1 J2 J3 J4 J5
Binary Inputs
Analog Inputs
110
B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 7 8 9 10 11 12 17 18 19 20 1 2 3 4 5 6 13 14 15 16 B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4
G1 G2 41 42
DI
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6
DO
100 CLEARANCE
7 8 9 10 11 12 17 18 19 20
25 26 27 28 35 36 37 38 39 40
69
XF830A
1 2 3 4 5 6 13 14 15 16
41 42
21 22 23 24 29 30 31 32 33 34
28 15
SWIVEL LABEL HOLDER
38
SCREW-TYPE TERMINALS (XFU830A)
A1 A2 A3 A4 A5 A6 A7 A8 A9
A C
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B D
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
A1 B1 A2 B2 A3 B3 A4 B4 G1
A5 B5 A6 B6 A7 B7 A8 B8 G2
51.5
Fig. 26. Mixed Excel 800 I/O Modules (example shows XF830A with 4 auxiliary terminal packages), dimensions (in mm)
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Rolle, Z.A. La Pice 16, Switzerland by its Authorized Representative:
Automation and Control Solutions Honeywell GmbH Bblinger Strasse 17 71101 Schnaich / Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany EN0B-0564GE51 R0711