Excel 500XCL5010

SPECIFICATION DATA

CONTROL SYSTEM

FEATURES
Various state-of-the-art communication options: C-bus (between up to 30 Excel 500 controllers) or Open LONW ORKS bus communication; modem or ISDN terminal adapter at up to 38.4 Kbaud; wireless communication via GSM; dial-up through TCP/IP networks Unique features in open LONWORKS networks: NVBooster reduces the number of required NVs and thus also the number of required controllers; NV bindings can be restored after controller reset (and thus need not be redone after exchanging controllers); 512 NVs supported for LONW ORKS integration; autobinding of Honeywell I/O modules makes NV binding unnecessary, thus saving considerable engineering effort Typically, 190 physical inputs/outputs can be controlled via network variables in a LONW ORKS network 128 physical data points, 256 pseudo data points, and up to 16 Distributed I/O modules per Excel 500 controller (Cbus communication) DIN-rail mounting (e.g. in control cabinet) Applications programmable with Honeywell's CARE programming tool and downloadable into Flash EPROM Enhanced controller functions including: alarm, trend and global broadcast hysteresis, network-wide time synchronization, firmware downloading via modem and C-bus Internal power supply module Shared transformer (CPU and Distributed I/O modules connected to the same transformer) Optimum access to terminals NOTE: The XCL5010 has no internal display; thus, an XI582AH operator interface or PC-based Excel Online (formerly XI584) operator and service software is needed when interfacing. Table 1. Modules for the Excel 500 (XCL5010) System Modules
XCL5010 XFL521/B XFL522A/B XFL523/B XFL524A/B XFCxxxxxx

GENERAL
The Excel 500 is a freely programmable control and monitoring system designed specifically for building management. Using the latest Direct Digital Control (DDC) technology, the Excel 500's modular design is particularly well-suited for use in medium-sized buildings (e.g. schools, hotels, offices, shopping centers, and hospitals). With its LONW ORKS network interface, the Excel 500 is LONMARK compliant and offers a whole range of interoperability options. In addition to control applications for heating, ventilation, and air conditioning (HVAC), the Excel 500 also performs a wide range of energy management functions, including optimum start/stop, night purge, and maximum load demand. Up to four Building Supervisors can be connected via the system bus. A modem or ISDN terminal adapter can be connected directly to the XCL5010 for communication with a data transmission rate of up to 38.4 Kbaud via the public telephone network. The modular design enables the system to be expanded to meet growing needs. The data point user addresses and plain language descriptors are stored in the controller and are therefore available for viewing locally at an external interface without the need of a central PC. The Excel 500 is suitable for use in open LONW ORKS networks. Thus, in addition to its own I/O modules (see Table 1), an Excel 500 can operate on the same LONW ORKS bus as other Excel 500 controllers (each with its own I/O modules), Excel 10 and Excel 50 controllers, and other Honeywell and third-party LONW ORKS devices.
U.S. Registered Trademark Copyright 2002 Honeywell Inc. All Rights Reserved

Description
Computer module Excel 500 (supports Distributed and Smart I/O), incl. power supply and communication; UL916-approved Analog input module Analog output module Digital input module Digital output module Smart I/O modules

NOTE: See also Distributed I/O Specification Data (EN0B0090GE51) and Smart I/O Product Data (EN0B0311GE51) for more information.

EN0B-0203GE51 R0802 74-3666

EXCEL 500 CONTROL SYSTEM

DESCRIPTION
The Excel 500 System is part of Honeywell's EXCEL 5000 family of controllers. The Excel 500 is freely programmable and can be used as a stand-alone controller or as part of a network. The Excel 500 System provides energy management and control functions via LONW ORKS bus to Honeywell rd LonWorks I/O modules, 3 -party LonWorks I/O modules, rd or 3 -party LonWorks devices. NOTE: The XCL5010 CPU can use only external I/O modules. There is no possibility of connecting internal plug-in I/O modules. The Excel 500 can communicate with any LONW ORKS product. Up to 512 LONW ORKS network variables can be mapped to internal data points. There are three sources for Excel 500 program applications: 1. Standard HVAC technology applications can be assembled as needed using Honeywell's Windows-based CARE programming tool. 2. Excel 500 application programs can be freely programmed using CARE. The user program is then automatically generated based on the graphically designed schematic diagram, instrumentation, and control strategies. 3. A set of predefined applications (MODAL) is available in order to provide state-of-the-art applications without the need of programming.

SPECIFICATIONS
Electrical
Operating voltage 24 Vac/dc, 20% Power consumption Max. 5 VA (max. 4 W) Memory buffer In case of power failure, the super gold capacitor saves RAM content and real-time clock for 72 hours (environmentally friendly; no problems disposing of dead batteries). Overvoltage protection All inputs and outputs are protected against 24 Vac and 40 Vdc overvoltage as well as short-circuiting. Terminal 2 of the screw terminal block is protected by a quick-acting 4-A fuse behind the terminal block.

Memory
64 KB EPROM (boot) 256 KB RAM 1 MB Flash EPROM (firmware and application) 4 K bit EEPROM

Communication
C-Bus The C-bus transmits data between the EXCEL 5000 Sysrd tem controllers, gateways to 3 -party systems, and building supervisors at 9.6 Kbaud up to 76.8 Kbaud. The max. C-bus network length is 1,200 m (3,900 ft.) or 15,700 ft. (4,800 m) using the XD509 repeater. A switch is provided for selectable termination. There is a max. of 30 controllers or devices per C-bus. See Excel 500/600 Installation Instructions (EN1R-1047GE51) for wiring details. LONWORKS Bus The Excel 500 uses an FTT-10A Free Topology Transceiver, transmitting data at 78 Kbaud using LonTalk protocol. Cable length from 1,050 to 7,200 ft. (320 to 2,200 m). See Excel 500/600 Installation Instructions (EN1R-1047GE51) for wiring details. External Interface / Modem A 9-pin Sub-D connector, RS232, is provided as a serial port to connect an external interface (e.g. the XI582AH operator interface or the PC-based XI584 operator and service software) or a modem or ISDN terminal adapter for dial-up access at a transmission rate of up to 38.4 Kbaud.
Comm_Prt

Environmental
Ambient temperature Operation: 32...122 F (0...50 C) Storage: -4...+158 F (-20...+70 C) Ambient humidity (operation and storage) 5 to 93% r.h. non-condensing

Mechanical
Housing dimensions (H x W x D) 5.90 x 7.79 x 3.82 in. (150 x 198 x 97 mm) Housing material Plastic, flame-retardant Mounting methods DIN-rail mounting (e.g. in control cabinet) Calculated lifetime of weakest components MTBF 13.7 years Protection class IP 30

COMMUNICATION MODULE

C-BUS CONNECTOR LON-BUS CONNECTOR

EXCEL 500XCL5010 HOUSING

SERIAL PORT FOR EXTERNAL MMI, MODEM, OR ISDN TERMINAL ADAPTER

EN0B-0203GE51 R0802

EXCEL 500 CONTROL SYSTEM

Communication Module XDL505


Housing Plug-in plastic module.

Assignment Terminal Block


1 2 3
4
Term_Ass

Communication Module LEDs and Ports


LON SERVICE BUTTON POWER, GRN LON SERVICE, RED C-BUS TxD, YEL C-BUS RxD, YEL RESERVED

24 Vac 24 Vac

24 Vac 24 Vac

5
6 7

LEDs

DO NOT USE!

8 9 10 11
12

C-BUS TERMINATION SWITCH 1 2 3 4 5 6

13 14

NOT USED

Terminal Block
Excel 500 (XCL5010) RESET BUTTON
Term_Blk

SCREW TERMINAL BLOCK (REMOVABLE)

REMOVABLE FUSE BELOW TERMINAL BLOCK

SHIELD C+ C-

COMMUNICATION MODULE (REMOVABLE)

00000124

A1 A2

LON BUS

C-BUS

EN0B-0203GE51 R0802

EXCEL 500 CONTROL SYSTEM

EXTERNAL I/O MODULES


See the Specification Data sheets for Distributed I/O (EN0B-0090GE51) and Smart I/O (EN0B-0311GE51).

OPERATOR INTERFACE XI582AH


The XI582AH operator interface is the command and information center of the Excel 500 system. With it, data can be entered and displayed. Information such as current temperature values, control status, etc. can also be displayed. The menu-driven, 6-line, backlit LCD graphic display with 34 characters per line, together with eight clearly marked keys, makes the device easy to use. The operator interface is connected to the serial port next to the communication module. The XI582AH can be mounted up to 48 ft. (15 m) away from the controller. This can be extended to 328 ft. (100 m) using line drivers. Fig. 1. The XI582AH Operator Interface

OPERATOR AND SERVICE SOFTWARE EXCEL ONLINE (FORMERLY XI584)


The PC-based Excel Online (formerly XI584) is the local intelligent operating and service software. It performs all the operating functions of the XI581AH/XI582AH as well as having the advantages of a PC. Not only can the Excel Online (formerly XI584) make major modifications such as changing setpoint values and time program switching points, it also offers all service and commissioning functions. The Excel Online (formerly XI584) can be operated at five different access levels, three of which are passwordprotected. A printer can be connected to the parallel interface of the Excel Online (formerly XI584) to log alarms and error messages. As with the XI582AH, the PC with the Excel Online (formerly XI584) operator and service software can be placed up to 15 meters from the computer module. Line drivers allow distances of up to 328 ft. (100 m).

Fig. 2. Excel 500 (XCL5010) with XI584 and printer

PROGRAMMING
The Excel 500 system includes a comprehensive software package specially designed to meet the requirements of application engineers. The easy to use, menu-driven software features the following functions: data point description time program alarm handling application program (DDC program) password protection

XI584con

Time Program
The time program can be used to enter the setpoint or status at any time for any data point. The following time programs are available: daily program weekly program annual program TODAY function special day list Daily programs are used to create a weekly program. The annual program is created automatically by multiplying the weekly program and then incorporating daily programs. The TODAY function allows direct changes to the switching program. It allows you to allocate a setpoint or status to the selected data point for a defined period of time.

Data Point Description


Data points are the basis of the Excel 500 system. They contain system-specific information such as values, status, limit values, and default settings. The user has easy access to data points and the information that they contain. The user can recall and modify information in the data points. In the case of LONW ORKS applications, up to 512 NVs can be created.

EN0B-0203GE51 R0802

EXCEL 500 CONTROL SYSTEM

Alarm Handling
The alarm handling facility offers system security. Alarm signals can, for example, alert the operator to scheduled maintenance work. All alarms that occur are stored in data files and reported immediately. If your system configuration allows, you can also list alarms on a printer or transmit alarms to higher-level devices via the local bus or a modem. There are two types of alarms, critical and non-critical. Critical alarms (e.g. system alarms caused by a fault in the controller) have priority over non-critical alarms. To distinguish between alarm types, you can generate your own alarm messages or use pre-programmed system messages. The following events all generate alarm messages: exceeding limit values overdue maintenance work totalizer readings digital data point changes of state

ACCESSORIES
Table 2 lists the accessories which are available for the Excel 500 (XCL5010). Table 2. Accessories for the Excel 500 (XCL5010) Order code XD509 XI582AH XW582 XW585 Description C-bus repeater operator interface cable to XI582AH, 15 ft. (5 m) cable to XI584, 15 ft. (5 m) Pair of DIN-rail mounting clips XL50-ACC2 NOTE: One pair of DIN-rail mounting clips is included in each Excel 500 package

Application Program (DDC program)


You can use the Honeywell CARE (Computer Aided Regulation Engineering) programming tool to create application programs for your system. A particular advantage offered by CARE is the ability to create a fully functional control program without needing to be familiar with the programming language. A set of predefined applications (MODAL) is available in order to provide state-of-the-art applications without the need of programming.

Password Protection
The control system is also protected by passwords. This ensures that only authorized persons have access to system data. There are four operator levels, each protected by its own password. Operator level 1: Read only. The operator can display information about setpoints, switching points, and operating hours. Operator level 2: Read and make limited changes. The operator can display system information and modify certain pre-set values. Operator level 3: Read and make changes. System information can be displayed and modified. Operator level 4: Programming can be carried out.

Trending
The Excel 500 system provides controller-based trending. This feature allows historical values to be stored in the controller. Both time-based or value-hysteresis-based trending are possible.

EN0B-0203GE51 R0802

EXCEL 500 CONTROL SYSTEM

Dimensions
0000042b

7.79 in. (198 mm)

5.90 in. (150 mm)

PORT FOR SCREW TERMINAL BLOCK PORT FOR COMMUNICATION MODULE

FUSE

HARDWARE RESET

SERIAL -PORT

1.34 in. (34 mm)

COMMUNICATION MODULE 3.94 in. (100 mm) LON-BUS C-BUS PORT PORT 2.83 in. (72 mm) 3.82 in. (97 mm) 4.96 in. (126 mm)

DIN-RAIL MOUNTING CLIP

EN0B-0203GE51 R0802

3.34 in. (85 mm)

EXCEL 500 CONTROL SYSTEM

EN0B-0203GE51 R0802

EXCEL 500 CONTROL SYSTEM

Control Products Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524 USA EN0B-0203GE51 R0802 74-3666

Control Products Honeywell Limited-Honeywell Limitee 155 Gordon Baker Road North York, Ontario M2H 3N7 Canada

Control Products Honeywell AG Bblinger Strae 17 D-71101 Schnaich Germany http://europe.hbc.honeywell.com

Manufacturing location certified to

printed in Germany

Subject to change without notice