Province of Alberta

SAFETY CODES ACT

BUILDING CODE REGULATION

Alberta Regulation 117/2007


With amendments up to and including Alberta Regulation 227/2012

Office Consolidation
Published by Alberta Queens Printer Alberta Queens Printer 5th Floor, Park Plaza 10611 - 98 Avenue Edmonton, AB T5K 2P7 Phone: 780-427-4952 Fax: 780-452-0668 E-mail: qp@gov.ab.ca Shop on-line at www.qp.alberta.ca

Copyright and Permission Statement Alberta Queen's Printer holds copyright on behalf of the Government of Alberta in right of Her Majesty the Queen for all Government of Alberta legislation. Alberta Queen's Printer permits any person to reproduce Albertas statutes and regulations without seeking permission and without charge, provided due diligence is exercised to ensure the accuracy of the materials produced, and Crown copyright is acknowledged in the following format: Alberta Queen's Printer, 20__.* *The year of first publication of the legal materials is to be completed. Note All persons making use of this consolidation are reminded that it has no legislative sanction, that amendments have been embodied for convenience of reference only. The official Statutes and Regulations should be consulted for all purposes of interpreting and applying the law.

(Consolidated up to 227/2012) ALBERTA REGULATION 117/2007 Safety Codes Act BUILDING CODE REGULATION

Table of Contents
1 2 3 5 Code in force Disclaimer Repeal Coming into force Schedule Code in force

1 The Alberta Building Code 2006, as established by the Safety Codes Council and published by the National Research Council of Canada, is declared in force with respect to buildings, with the variations set out in the Schedule.
AR 117/2007 s1;49/2009

Disclaimer

2 The Code declared in force in this Regulation, and any codes and standards referred to in that Code, do not make or imply any assurance or guarantee by the Crown in right of Alberta with respect to the life expectancy, durability or operating performance of materials, appliances, systems and equipment referred to in that Code, codes or standards.
Repeal

3(1) The Building Code Regulation (AR 50/98) is repealed. (2) Notwithstanding subsection (1), the Building Code Regulation (AR 50/98) remains in force (a) for work for which a permit is issued by a safety codes officer or other person designated by an Administrator pursuant to section 44 of the Safety Codes Act prior to September 2, 2007, or (b) for work for which a permit application is submitted prior to March 2, 2008 to a safety codes officer or other person

Section 5

BUILDING CODE REGULATION

AR 117/2007

designated by an Administrator pursuant to section 44 of the Safety Codes Act who is satisfied that the preparation of the plans and specifications for the project commenced prior to September 2, 2007, until that work has been completed or the permit has expired or been revoked. 4 Repealed AR 227/2012 s1.
Coming into force

5 This Regulation comes into force on September 2, 2007. Schedule 1 Volume 1 is amended in Division A, Compliance, Objectives, Functional Statements and Attribution Tables,
(a) in Table 4.2.1.1. (i) by striking out item 3.2.3.1. and substituting the following:

3.2.3.1. Limiting Distance and Area of Unprotected Openings

(1) (5) (6) (8) (9) (10)

[F03OP3.1] [F03OP3.1] [F03OP3.1] [F03OP3.1] [F03OP3.1] [F03OP3.1]


(ii) by striking out items 3.2.3.6. and 3.2.3.7. and substituting the following:

3.2.3.6. Combustible Projections

(1) (3) (4) (5)

[F03OP3.1] [F03OP3.1] [F03-OP1.2] [F03-OS1.2] [F03OP3.1] [F03-OP1.2] [F03-OS1.2] [F03OP3.1] [F03-OP1.2] [F03-OS1.2] [F03,F02OP3.1] [F03,F02OP3.1]
2

3.2.3.7. Construction of Exposing Building Face

(1) (2)

Schedule

BUILDING CODE REGULATION

AR 117/2007

(3)

[F03, F02OP3.1]

(b) in Table 4.7.1.1 (i) by striking out items 9.10.14.4 and 9.10.14.5 and substituting the following:

9.10.14.4. Openings in Exposing Building Face (1) [F03OP3.1] (2) [F03OP3.1] (3) [F03OP3.1] (4) [F03OP3.1] (6) [F03OP3.1] (7) [F03OP3.1] 9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building Face (1) [F02,F03OP3.1] (2) [F02,F03OP3.1] (3) [F02,F03OP3.1] (4) [F03OP3.1] (5) [F03OP3.1] [F03-OP1.2] [F03-OS1.2] (6) [F03OP3.1] [F03-OP1.2] [F03-OS1.2] (7) [F03OP3.1] [F03-OP1.2] [F03-OS1.2]
(ii) by striking out items 9.10.15.4 and 9.10.15.5.and substituting the following:

9.10.15.4. Glazed Openings in Exposing Building Face (1) [F03-OP3.1] (3) [F03-OP3.1] (4) [F03-OP3.1] 9.10.15.5. Construction of Exposing Building Face of Houses (1) [F02,F03-OP3.1] (2) [F02,F03-OP3.1] (3) [F02,F03-OP3.1] (5) [F03-OP3.1] (7) [F02,F03-OP3.1] (8) [F03-OP3.1] [F03-OP1.2] [F03-OS1.2] (9) [F03-OP3.1] [F03-OP1.2] [F03-OS1.2] (10) [F03-OP3.1] [F03-OP1.2]
3

Schedule

BUILDING CODE REGULATION

AR 117/2007

[F03-OS1.2]

2 Volume 2 is amended in Division B, Acceptable Solutions,


(a) in Table 1.3.1.2. (i) in the line that refers to ASTM document D 2898-94 (2004), Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing, by adding 3.2.3.7.(3)(c)(iii) after 3.1.5.21.(1) under the column heading Code Reference; (ii) in the line that refers to CGSB document CAN/CGSB-93.2-M91, Prefinished Aluminum Siding, Soffits and Fascia, for Residential Use, by adding 3.2.3.6.(5)(b)(ii) after Table 5.10.1.1. under the column heading Code Reference; (iii) in the line that refers to CGSB document CAN/CGSB-93.4-92, Galvanized Steel and Aluminum-Zinc Alloy Coated Steel Siding, Soffits and Fascia, Prefinished, Residential by adding 3.2.3.6.(5)(b)(i) after Table 5.10.1.1. under the column heading Code Reference; (iv) in the line that refers to ULC document CAN/ULC S134-92 (R1998), Fire Test of Exterior Wall Assemblies, by striking out 3.1.5.5.(1) under the column heading Code Reference and substituting the following:

3.1.5.5.(1) 3.2.3.7.(2) 9.10.14.5.(2) 9.10.15.5.(2)(c) 9.10.15.5.(3)(c)


(b) in Sentence 3.1.5.5.(1) by striking out required to

and substituting with a maximum aggregate area of

conform to Sentence 3.2.3.7.(1) or Sentence 3.2.3.7.(4)

unprotected openings that is not more than 10% of the exposing building face as determined by Sentence 3.2.3.7.(1);

(c) in Sentence 3.1.7.2.(1) by striking out Sentence 3.2.3.1.(6) and substituting Sentence 3.2.3.1.(9);

Schedule

BUILDING CODE REGULATION

AR 117/2007

(d) by adding the following after the heading 3.2.3.1. Limiting Distance and Area of Unprotected Openings:

(See Appendix A.)


(e) by striking out Sentences 3.2.3.1.(5) to 3.2.3.1.(7) and substituting the following:

5) Individual unprotected openings in an exposing building face shall have a projected area that is not more than the value determined in accordance with Table 3.2.3.1.E., unless a) the building is sprinklered throughout, or b) the limiting distance is more than 2 m. Table 3.2.3.1.E Maximum Concentrated Area of Unprotected Openings Forming Part of Sentence 3.2.3.1.(5) Limiting Distance, m 0 1.2 1.5 2.0 Maximum Area of Individual Unprotected Openings, m 0 0.35 0.78 1.88

6) An individual unprotected opening described in Sentence (5) shall be separated by not less than 2 m horizontally and 2 m vertically from any other unprotected opening that is located on the same exposing building face and within the same fire compartment. (See Appendix A.) 7) For the purposes of Sentence (6), a) two adjacent spaces are permitted to be considered as separate fire compartments where there is a full height wall extending not less than 1.5 m from the interior face of the exterior wall, finished in accordance with Subsection 9.29.4. or 9.29.5., and b) two stacked spaces shall be considered to be a single room or space where the spaces are on the same storey.
5

Schedule

BUILDING CODE REGULATION

AR 117/2007

8) A limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where a) the time from receipt of notification of a fire by the fire department until the first fire department vehicle capable of beginning suppression activities arrives at the building is greater than 10 minutes in not less than 10% of all calls to the building, and b) any storey in the building is not sprinklered. (See Appendix A and A 3.2.3.1. in Appendix A.) 9) If the surface temperature on the unexposed surface of a wall assembly exceeds the temperature limit of a standard fire test as permitted by Article 3.1.7.2., an allowance shall be made for the radiation from the hot unexposed wall surface by adding an equivalent area of unprotected opening to the area of actual openings as follows:

A C = A + (A F FEO )
where AC = corrected area of unprotected openings including actual and equivalent openings, A = actual area of unprotected openings, AF = area of exterior surface of the exposing building face, exclusive of openings, on which the temperature limit of the standard test is exceeded, and FEO = an equivalent opening factor derived from the following expression:

FEO

(Tu + 273)4 = (Te + 273)4

Tu = average temperature in degrees Celsius of the unexposed wall surface at the time the required fire-resistance rating is reached under test conditions, Te = 892C for a fire-resistance rating not less than 45 min, 927C for a fire-resistance rating not
6

Schedule

BUILDING CODE REGULATION

AR 117/2007

less than 1 h, and 1 010C for a fire-resistance rating not less than 2 h. 10) Unless a closure used to protect an opening in an exposing building face has a protective performance equivalent to that required for the wall assembly in which it is located, an equivalent area of unprotected opening, determined in accordance with the procedures of Sentence (9) shall be added to the greater of a) the actual area of unprotected openings, or b) the corrected area of unprotected openings.
(f) by striking out Article 3.2.3.6. and substituting the following: 3.2.3.6. Combustible Projections

1) Except as provided in Sentence (2), combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within a) 1.2 m of a property line or the centre line of a public way, or b) 2.4 m of a combustible projection on another building on the same property. 2) Sentence (1) shall not apply to a) buildings containing 1 or 2 dwelling units, and b) detached garages or accessory buildings, where i) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite, ii) the detached garage or accessory building is located on the same property as that dwelling unit, and iii) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property. (See A-9.10.15.5.(6) in Appendix A.)

Schedule

BUILDING CODE REGULATION

AR 117/2007

3) Where the limiting distance is not more than 0.45 m, projecting roof soffits shall not be constructed above an exposing building face. 4) Where the limiting distance is more than 0.45 m, the face of roof soffits above an exposing building face are permitted to project to not less than 0.45 m from a property line. 5) Where roof soffits project closer than 1.2 m from a property line, they shall a) have no openings, and b) be protected by i) not less than 0.38 mm thick sheet steel conforming to CAN/CGSB-93.4, Galvanized Steel and Aluminum-Zinc Alloy Coated Steel Siding, Soffits and Fascia, Prefinished, Residential, ii) unvented aluminum conforming to CAN/CGSB-93.2-M, Prefinished Aluminum Siding, Soffits and Fascia for Residential Use, iii) not less than 12.7 mm thick gypsum board conforming to Sentence 9.29.5.1.(2), Subclauses 9.29.5.2.(1)(e) and (f), and Articles 9.29.5.3. to 9.29.5.10., iv) not less than 11 mm thick plywood conforming to Sentences 9.27.9.1.(1), 9.27.9.3.(1) and 9.27.9.4.(1), v) not less than 12.5 mm thick OSB or waferboard conforming to Sentences 9.27.11.1.(1) and 9.27.11.3.(1), or vi) not less than 11 mm thick lumber conforming to Sentence 9.27.6.1.(1).
(g) by striking out Article 3.2.3.7. and substituting the following: 3.2.3.7. Construction of Exposing Building Face

1) Except as provided in Sentences (2) and (3) and Articles 3.2.3.10. and 3.2.3.11., fire-resistance rating, construction and cladding for exposing building faces of buildings or fire compartments shall comply with Table 3.2.3.7.

Schedule

BUILDING CODE REGULATION

AR 117/2007

Table 3.2.3.7. Minimum Construction Requirements for Exposing Building Faces Forming Part of Sentence 3.2.3.7.(1)
Occupancy Classification of Building or Fire Compartment Maximum Area of Unprotected Openings Permitted, % of Exposing Building Face Area 0 - 10 > 10 - 25 Minimum Required Fire-Resistance Rating Type of Construction Required Type of Cladding Required

Group A, B, C, D, or Group F, Division 3

1h 1h

> 25 - 50 > 50 - < 100 0 - 10 > 10 - 25

45 min 45 min 2h 2h

Group E, or Group F, Division 1 or 2

> 25 - 50 > 50 - < 100

1h 1h

Noncombustible Combustible or Noncombustible Combustible or Noncombustible Combustible or Noncombustible Noncombustible Combustible or Noncombustible Combustible or Noncombustible Combustible or Noncombustible

Noncombustible Noncombustible(1) Noncombustible(2) Combustible or Noncombustible Noncombustible Noncombustible(1) Noncombustible(2) Combustible or Noncombustible

Notes to Table 3.2.3.7: (1) See Sentence (2). (2) See Sentence (3). 2) Except as provided in Sentence (3), cladding for buildings or fire compartments where the maximum aggregate area of unprotected openings is more than 10% of the exposing building face need not be noncombustible where the wall assembly satisfies the criteria of Sentences 3.1.5.5.(2) and (3) when subjected to testing in conformance with CAN/ULC S134, Fire Test of Exterior Wall Assemblies. 3) Cladding for buildings or fire compartments where the maximum aggregate area of unprotected openings is more than 25% but not more than 50% of the exposing building face need not be noncombustible where a) the limiting distance is not less than 5 m, b) the building or fire compartment is sprinklered throughout, c) the cladding
9

Schedule

BUILDING CODE REGULATION

AR 117/2007

i) conforms to Subsection 9.27.6., 9.27.7., 9.27.9., 9.27.10., or 9.27.11., ii) is installed with or without furring members, over gypsum sheathing not less than 12.7 mm thick conforming to Articles 9.23.16.2 and 9.23.16.3 or over masonry (see Articles 3.1.11.2. and 9.10.16.2. for additional requirements for fire stopping of concealed spaces in wall assemblies), and iii) after conditioning in conformance with ASTM D2898, Methods for Accelerated Weathering on Fire-Retardant-Treated Wood for Fire Testing, has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1.(1), or d) the cladding i) conforms to Subsection 9.27.13., ii) is installed with or without furring members, over gypsum sheathing not less than 12.7 mm thick conforming to Articles 9.23.16.2 and 9.23.16.3 or over masonry (see Articles 3.1.11.2. and 9.10.16.2. for additional requirements for fire stopping of concealed spaces in wall assemblies), iii) has a flame-spread rating not more than 25 when tested in accordance with Sentence 3.1.12.1.(2), and iv) does not exceed 2 mm in thickness exclusive of fasteners, joints and local reinforcements. 4) The construction requirements for the exposing building face stated in Sentence (1) shall be satisfied before increasing the unprotected opening area as permitted by Sentence 3.2.3.12.(1).
(h) in Article 3.2.3.8. (i) in Sentence (1) by striking out of Sentences 3.2.3.7.(2), (3), (5) and (6) and substituting for

buildings with a maximum aggregate area of unprotected openings more than 10% of the exposing building face as determined by Sentence 3.2.3.7.(1),;

10

Schedule

BUILDING CODE REGULATION

AR 117/2007

(ii) in Sentence (3) by striking out A-3.2.3.7.(7) in; (i) in Sentence 3.2.3.12.(1) by striking out Sentence 3.2.3.7.(9) and substituting Sentence 3.2.3.7.(4); (j) in Article 3.2.5.13. (i) by striking out Sentence (2) and substituting the following:

2) Except as required by Sentences (10) and (11), NFPA 13R, Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, is permitted to be used for the design, construction, installation and testing of an automatic sprinkler system installed in a building of residential occupancy throughout, not more than 4 storeys in building height, conforming to Articles 3.2.2.42. to 3.2.2.48.
(ii) by adding the following after Sentence (9):

10) Notwithstanding the requirements of Sentence (2) regarding the installation of automatic sprinkler systems, in buildings of combustible construction, sprinklers shall be required in a) porches and balconies, b) public corridors, c) stairs that are open and attached, d) attics and floor/ceiling spaces, e) penthouse equipment rooms, f) elevator machine rooms,

g) concealed spaces dedicated exclusively to and containing only dwelling unit ventilation equipment, h) crawl spaces, i) closets or storage rooms on exterior balconies, and j) other concealed spaces that are not used or intended for living purposes or storage and do not contain fuel-fired appliances.
11

Schedule

BUILDING CODE REGULATION

AR 117/2007

11) A concealed space mentioned in Sentence (10) does not require sprinkler protection provided the concealed space meets one of the criteria described in Clause 8.14.1.2. of NFPA 13, Installation of Sprinkler Systems.
(j.1) in Sentence 7.2.1.2.(2) by striking out Subsection 7.2.3. and substituting Part 10 of the Alberta Private

Sewage Systems Standard of Practice, 2009;

(j.2) by striking out Articles 7.2.3.1. and 7.2.3.2.; (k) in Article 9.10.12.4. (i) in Sentence (3) by striking out Sentences (2) and (6) and substituting Sentence (2); (ii) by striking out Sentence (6); (l) by adding the following after Article 9.10.12.4.: 9.10.12.5. Protection of Balconies

(See Appendix A.) 1) This Article applies to buildings that a) contain more than 2 suites of residential occupancy, b) are not less than 2 storeys in building height, c) have dwelling units located in whole or in part above other dwelling units, and d) are not sprinklered throughout. 2) The protection required by Sentences (3) and (4) shall be provided by cladding that conforms to a) Subsection 9.27.8. or 9.27.12., b) Section 9.28., or c) one of the methods described in Clause 3.2.3.7.(3)(c) or (d). 3) Balcony walls shall be protected by one of the methods mentioned in Sentence (2) from the floor level of the balcony to the underside of the balcony or roof assembly above for a) the full width and depth of the balcony, and b) 1.2 m on either side of the balcony.
12

Schedule

BUILDING CODE REGULATION

AR 117/2007

4) Ceiling and roof assemblies above balconies mentioned in Sentence (3) shall be protected by one of the methods mentioned in Sentence (2).
(m) in Sentence 9.10.14.2.(2) by striking out Table 9.10.14.4. and substituting Table 9.10.14.4.A.. (n) by striking out Sentence 9.10.14.3.(1) and substituting the following: 9.10.14.3. Limiting Distance where Firefighting Facilities are Inadequate

1) Except for the purpose of applying Sentences 9.10.14.4.(2), (8) and (9), and Sentence 9.10.14.5.(8), a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where a) the time from receipt of notification of a fire by the fire department until the first fire department vehicle capable of beginning suppression activities arrives at the building is greater than 10 minutes in not less than 10% of all calls to the building, and b) any storey in the building is not sprinklered. (See A-3.2.3.1. and A-3.2.3.1.(8) in Appendix A.)
(o) in Article 9.10.14.4. (i) by striking out Sentence (1) and substituting the following:

1) Except as provided in Sentences (6) to (9), the maximum aggregate area of unprotected openings in an exposing building face shall a) conform to Table 9.10.14.4.A., b) conform to Subsection 3.2.3., or c) where the limiting distance is not less than 1.2 m, be equal to or less than i) the limiting distance squared, for residential occupancies, business and personal services occupancies and low-hazard industrial occupancies, and

13

Schedule

BUILDING CODE REGULATION

AR 117/2007

ii)

half the limiting distance squared, for mercantile occupancies and medium-hazard industrial occupancies.

14

Table 9.10.14.4.A. Maximum Aggregate Area of Unprotected Openings in Exterior Walls Forming Part of Sentence 9.10.14.4.(1)

Schedule

Occupancy Classification of Building 10.0 84 40 100 97 79 42 20 55 100 100 60 27 100 92 100 46 12.0 16.0 20.0 100 70

25.0 100

Maximum Total Area of Exposing Building Face, m 30 40 50 100 Over 100 30 40 50 100 Over 100 0 0 0 0 0 4 4 4 4 4 4 4 4 4 4 6 6 5 4 4 20 16 14 9 6 44 34 29 17 10 80 61 50 28 14 0 7 7 8 12 19 28

Maximum Aggregate Area of Unprotected Openings, % of Exposing Building Face Area Limiting Distance, m Less 1.2 1.5 2.0 4.0 6.0 8.0 than 1.2 0 7 9 12 39 88 100 0 7 8 11 32 69 100 0 7 8 10 28 57 100 0 7 8 9 18 34 56

BUILDING CODE REGULATION

15

Residential, business and personal services, and low-hazard industrial Mercantile and medium-hazar d industrial

AR 117/2007

Schedule

BUILDING CODE REGULATION

AR 117/2007

(ii) by striking out Sentences (3) to (8) and substituting the following:

3) Individual unprotected openings in an exposing building face shall have a projected area that is not more than the value determined in accordance with Table 9.10.14.4.B., unless (a) the building is sprinklered throughout, or (b) the limiting distance is more than 2 m. Table 9.10.14.4.B. Maximum Concentrated Area of Unprotected Openings Forming Part of Sentence 9.10.14.4.(3) Limiting Distance, m Less than 1.2 1.2 1.5 2.0 Maximum Area of Individual Unprotected Openings, m 0 0.35 0.78 1.88

4) An individual unprotected opening described in Sentence (3) shall be separated by not less than 2 m horizontally and 2 m vertically from any other unprotected opening that is located on the same exposing building face and within the same fire compartment. (See A-3.2.3.1.(6) in Appendix A.) 5) For the purposes of Sentence (4), a) two adjacent spaces are permitted to be considered as separate fire compartments where there is a full-height wall extending not less than 1.5 m from the interior face of the exterior wall, finished in accordance with Subsection 9.29.4. or 9.29.5., and b) two stacked spaces shall be considered to be a single room or space where the spaces are on the same storey. 6) The maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1), where the unprotected openings are glazed with
16

Schedule

BUILDING CODE REGULATION

AR 117/2007

a) wired glass in steel frames, as described in Article 9.10.13.5., or b) glass blocks, as described in Article 9.10.13.7. 7) Where the building is sprinklered, the maximum aggregate area of unprotected openings shall be not more than twice the area determined according to Sentence (1), provided all rooms, including closets and bathrooms, that are adjacent to the exposing building face and that have unprotected openings are sprinklered, notwithstanding any exemptions in the sprinkler standards referenced in Article 3.2.5.13. 8) The maximum aggregate area of unprotected openings in an exposing building face of a storage garage need not comply with Sentence (1), where a) all storeys are constructed as open-air storeys, and b) the storage garage has a limiting distance of not less than 3 m. 9) The maximum aggregate area of unprotected openings in an exposing building face of a storey that faces a street and is at the same level as the street need not comply with Sentence (1), where the limiting distance is not less than 9 m.
(p) by striking out Article 9.10.14.5. and substituting the following: 9.10.14.5. Construction of Exposing Building Face and Walls above Exposing Building Face

1) Except as permitted in Sentences (2) to (9), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Table 9.10.14.5. (See also Subsection 9.10.8.) (See Appendix A.)

17

Schedule

BUILDING CODE REGULATION

AR 117/2007

Table 9.10.14.5. Minimum Construction Requirements for Exposing Building Faces Forming Part of Sentence 9.10.14.5.(1)
Occupancy Classification of Building or Fire Compartment Maximum Area of Unprotected Openings Permitted, % of Exposing Building Face Area 0 - 10 > 10 - 25 Minimum Required Fire-Resistance Rating Type of Construction Required Type of Cladding Required

Residential, business and personal services, and low-hazard industrial

1h 1h

> 25 - 50 > 50 - < 100 0 - 10 > 10 - 25

45 min 45 min 2h 2h

Noncombustible Combustible or Noncombustible Combustible or Noncombustible Combustible or Noncombustible Noncombustible Combustible or Noncombustible Combustible or Noncombustible Combustible or Noncombustible

Noncombustible Noncombustible(1) Noncombustible(2) Combustible or Noncombustible Noncombustible Noncombustible(1) Noncombustible(2) Combustible or Noncombustible

Mercantile and medium-hazard industrial

> 25 - 50 > 50 - < 100

1h 1h

Notes to Table 9.10.14.5.: (1) See Sentence (2). (2) See Sentence (3). 2) Except as provided in Sentence (3), cladding on exposing building faces and any exterior wall above an exposing building face that enclose an attic or roof space for buildings or fire compartments where the maximum aggregate area of unprotected openings is more than 10% of the exposing building face need not be noncombustible where the wall assembly satisfies the criteria of Sentences 3.1.5.5.(2) and (3) when subjected to testing in conformance with CAN/ULC S134, Fire Test of Exterior Wall Assemblies. 3) Cladding on exposing building faces and on any exterior wall located above an exposing building face that encloses an attic or roof space for buildings or fire compartments where the maximum aggregate area of unprotected openings is more than 25% but not more than 50% of the exposing building face, need not be noncombustible where
18

Schedule

BUILDING CODE REGULATION

AR 117/2007

a) the limiting distance is not less than 5 m, b) the building or fire compartment is sprinklered throughout, or c) the cladding conforms to Clause 3.2.3.7.(3)(c) or (d). 4) Combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within a) 1.2 m of a property line or the centre line of a public way, or b) 2.4 m of a combustible projection on another building on the same property. 5) Where the limiting distance is not more than 0.45 m, projecting roof soffits shall not be constructed above the exposing building face. 6) Where the limiting distance is more than 0.45 m, the face of roof soffits above the exposing building face are permitted to project to not less than 0.45 m from a property line. 7) Where roof soffits project closer than 1.2 m from a property line, they shall a) have no openings, and b) be protected by one of the materials listed in Clause 3.2.3.6.(5)(b). 8) Heavy timber and steel columns need not conform to the requirements of Sentence (1), provided the limiting distance is not less than 3 m. 9) Non-loadbearing wall components need not have a minimum fire-resistance rating, where the building a) is 1 storey in building height, b) is of noncombustible construction, c) is classified as a low-hazard industrial occupancy and used only for low fire load occupancies, such as power-generating plants or plants for the manufacture or storage of noncombustible materials, and d) has a limiting distance of 3 m or more.
19

Schedule

BUILDING CODE REGULATION

AR 117/2007

(q) by striking out Articles 9.10.15.1. to 9.10.15.5. and substituting the following: 9.10.15.1. Application

1) This Subsection applies to a) buildings that contain only dwelling units and have no dwelling unit above another dwelling unit, b) buildings that contain a detached garage or accessory building facing a dwelling unit where i) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite, ii) the detached garage or accessory building is located on the same property as that dwelling unit, iii) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property, and c) buildings that contain one dwelling unit located in whole or in part above another dwelling unit, provided the buildings contain i) not more than 2 dwelling units, and ii) not more than 3 storeys, including any basements. (See Appendix A.) 2) This Subsection does not apply to hotels or motels.
9.10.15.2. Area and Location of Exposing Building Face

1) The area of an exposing building face shall be a) taken as the exterior wall area facing in one direction on any side of a building, and b) calculated as i) the total area measured from the finished ground level to the uppermost ceiling, ii) the area for each fire compartment, where a building is divided into fire compartments
20

Schedule

BUILDING CODE REGULATION

AR 117/2007

by fire separations with fire-resistance ratings not less than 45 min, or iii) the area of any number of individual vertical portions of the wall measured from the finished ground level to uppermost ceiling where Table 9.10.15.4. is used to determine the maximum aggregate area of glazed openings if the limiting distance is 2 m or more. (See A-9.10.15.4.(2) in Appendix A.) 2) For the purpose of using Table 9.10.15.4. to determine the maximum permitted area of glazed openings in an irregularly shaped or skewed exterior wall, the location of the exposing building face shall be taken as a vertical plane located so that there are no glazed openings between the vertical plane and the line to which the limiting distance is measured. (See A-3.2.3.1.(4) in Appendix A.) (3) For the purpose of using Table 9.10.15.5. to determine the required type of construction, cladding and fire-resistance rating for an irregularly shaped or skewed exterior wall, (a) the location of the exposing building face shall be taken as a vertical plane located so that no portion of the actual exposing building face is between the vertical plane and the line to which the limiting distance is measured, and (b) the value for the maximum aggregate area of glazed openings (see first column of Table 9.10.15.5.) shall be determined using the limiting distance measured from the location described in Clause (a). (See A-3.2.3.1.(4) in Appendix A.) (4) The limiting distance for an exposing building face that includes projections such as bow windows, bay windows, or flue chases of combustible construction, shall be measured from the face of the projection nearest the line to which the limiting distance is measured.
9.10.15.3. Limiting Distance where Firefighting Facilities are Inadequate

1) Except for the purpose of applying Sentence 9.10.15.5.(1), a limiting distance equal to half the actual limiting distance shall be used as input to the requirements of this Subsection, where
21

Schedule

BUILDING CODE REGULATION

AR 117/2007

a) the time from receipt of notification of a fire by the fire department until the first fire department vehicle capable of beginning suppression activities arrives at the building is greater than 10 minutes in not less than 10% of all calls to the building, and b) any storey in the building is not sprinklered. (See A-3.2.3.1. and A-3.2.3.1.(8) in Appendix A.)
9.10.15.4. Glazed Openings in Exposing Building Face

1) Except as provided in Sentence (6), the maximum aggregate area of glazed openings in an exposing building face shall a) conform to Table 9.10.15.4., b) conform to Subsection 3.2.3., or c) be equal to or less than the limiting distance squared, where the limiting distance is not less than 1.2 m. 2) Where the limits on the area of glazed openings are determined for individual portions of the exterior wall, as described in Subclause 9.10.15.2.(1)(b)(iii), the maximum aggregate area of glazed openings for any portion shall conform to the values in the row of Table 9.10.15.4. corresponding to the maximum total area of exposing building face (see column 1 of the Table) that is equal to the sum of all portions of the exposing building face. (See Appendix A.) 3) Individual glazed openings in an exposing building face shall have a projected area that is not more than 50% of the maximum allowable aggregate area of glazed openings determined in Sentence (1), unless a) the building is sprinklered throughout, or b) the limiting distance is more than 2m. 4) An individual glazed opening described in Sentence (3) shall be separated by not less than 2 m horizontally and 2 m vertically from any other glazed opening that is located on the same exposing building face and within the same fire compartment. (See A-3.2.3.1.(6) in Appendix A.) 5) For the purposes of Sentence (4),

22

Schedule

BUILDING CODE REGULATION

AR 117/2007

a) two adjacent spaces are permitted to be considered as separate fire compartments where there is a full-height wall extending not less than 1.5 m from the interior face of the exterior wall, finished in accordance with Subsection 9.29.4. or 9.29.5., and b) two stacked spaces shall be considered to be a single room or space where the spaces are on the same storey. 6) The limits on the area of glazed openings shall not apply to the exposing building face of a dwelling unit facing a detached garage or accessory building, where a) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite, b) the detached garage or accessory building is located on the same property as that dwelling unit, and c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.

23

Schedule

Table 9.10.15.4. Maximum Area of Glazed Openings in Exterior Walls Forming Part of Sentence 9.10.15.4.(1)
Maximum Aggregate Area of Glazed Openings, % of Exposing Building Face Area Limiting Distance, m Less than 1.2 1.2 7 7 7 7 7 84 40 9 8 8 8 7 12 11 10 9 8 39 32 28 18 12 88 69 57 34 19 100 100 100 56 28 100 55 1.5 2.0 4.0 6.0 8.0 10.0 12.0 0 0 0 0 0 16.0 92 20.0 100 25.0 -

BUILDING CODE REGULATION

24

Maximum Total Area of Exposing Building Face, m 30 40 50 100 Over 100

AR 117/2007

Schedule

BUILDING CODE REGULATION

AR 117/2007

9.10.15.5. Construction of Exposing Building Face of Houses

1) Except as provided in Sentences (4) and (6), each exposing building face and any exterior wall located above an exposing building face that encloses an attic or roof space shall be constructed in conformance with Sentence (2) or (3) a) for the exposing building face as a whole, or b) for any number of separate portions of the exposing building face. (See Subclause 9.10.15.2.(1)(b)(iii), Sentence 9.10.15.4.(2), and Appendix Note A-9.10.15.4.(2) in Appendix A. See also Subsection 9.10.8.). 2) Except as provided in Sentence (4), where the limiting distance is less than 0.6 m, the exposing building face and any exterior wall located above the exposing building face that encloses an attic or roof space shall have a fire-resistance rating of not less than 45 min and a) the cladding shall i) be of a noncombustible material conforming to Sections 9.20., 9.27. or 9.28. (See Appendix Note A-9.10.14.5.(1) in Appendix A.), or ii) conform to Clause 3.2.3.7.(3)(d), or b) the wall assembly shall satisfy the criteria of Sentences 3.1.5.5.(2) and (3) when subjected to testing in conformance with CAN/ULC S134, Fire Test of Exterior Wall Assemblies. 3) Except as provided in Sentence (4), where the limiting distance is not less than 0.6 m and less than 1.2 m, the exposing building face and any exterior wall located above the exposing building face that encloses an attic or roof space shall have a fire-resistance rating of not less than 45 min and a) the cladding shall i) be of a noncombustible material conforming to Sections 9.20., 9.27. or 9.28. (See Appendix Note A-9.10.14.5.(1) in Appendix A.), or
25

Schedule

BUILDING CODE REGULATION

AR 117/2007

ii) conform to Clause 3.2.3.7.(3)(c) or (d), or b) the wall assembly shall satisfy the criteria of Sentences 3.1.5.5.(2) and (3) when subjected to testing in conformance with CAN/ULC S134, Fire Test of Exterior Wall Assemblies. 4) The requirements regarding fire-resistance rating and type of cladding-sheathing assemblies shall not apply to an exposing building face, or to a projection from an exposing building face, where a) the exposing building face or projection is part of a dwelling unit and faces a detached garage or accessory building, or is part of a garage or accessory building and faces a dwelling unit, b) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite, c) the detached garage or accessory building is located on the same property as that dwelling unit, and d) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property. 5) Except as provided in Sentence (6), combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within a) 1.2 m of a property line or the centre line of a public way, or b) 2.4 m of a combustible projection on another building on the same property. 6) Sentence (5) shall not apply to a) buildings containing 1 or 2 dwelling units only, and b) detached garages or accessory buildings, where i) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite,
26

Schedule

BUILDING CODE REGULATION

AR 117/2007

ii) the detached garage or accessory building is located on the same property as that dwelling unit, and iii) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property. (See Appendix A.) 7) Where combustible projections from an exposing building face are permitted by Sentence (6) and are totally enclosed and constructed with solid faces, such as for fireplaces and chimneys, and extend within 1.2 m of a property line, a) the construction of the face of the projection shall comply with the corresponding requirements for exposing building faces for limiting distances less than 1.2 m in Sentence (2) or (3), b) the construction required for the face of the projection shall also apply to the sides of the projection, and c) the underside of the projection shall be protected by one of the materials listed in Clause 3.2.3.6.(5)(b), if it is more than 0.6m above finished ground level. (See Appendix A.) 8) Where the limiting distance is not more than 0.45 m, projecting roof soffits shall not be constructed above an exposing building face. 9) Where the limiting distance is more than 0.45 m, the face of roof soffits above an exposing building face are permitted to project to not less than 0.45 m from a property line. 10) Where roof soffits project closer than 1.2 m from a property line, they shall a) have no openings, and b) be protected by one of the materials listed in Clause 3.2.3.6.(5)(b). 11) Heavy timber and steel columns need not conform to the requirements of Sentence (1), provided the limiting distance is not less than 3 m.
27

Schedule

BUILDING CODE REGULATION

AR 117/2007

(r) in Sentence 9.35.1.1.(1) by adding or a primary dwelling unit with a secondary suite after dwelling

unit;

(s) by striking out Walls and Columns in the heading for Article 9.35.4.1. and substituting Walls, Columns and Ceilings; (t) in Sentence 9.35.4.1.(1) by striking out Interior and substituting Except as required by Sentence (2),

interior;

(u) by adding the following after Sentence 9.35.4.1.(1):

2) The walls and ceilings of an attached garage shall have an interior finish consisting of a) not less than 12.7 mm thick gypsum board conforming to Subsection 9.29.5., b) lath and plaster conforming to Subsection 9.29.4., or c) any material that can be shown to remain in place and prevent the passage of flames for not less than 15 min when subjected to the standard fire exposure in CAN/ULC-S101, Fire Endurance Tests of Building Construction and Materials.
(v) by adding the following after Sentence 9.35.4.3.(1).: 9.35.4.4. Thermal Insulation

1) The walls and ceilings of an attached garage shall be provided with thermal insulation that conforms to Subsection 9.25.2.
(w) in Appendix A, Explanatory Material, (i) in Table A-1.3.1.2. by adding the following after the line that refers to NFPA document 1142-2001, Water Supplies for Suburban and Rural Fire Fighting": NFPA 1710-2004 Standard for the Organization and Deployment of Fire Suppression Operations, Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments 28 A-3.2.3.1.(8)

Schedule

BUILDING CODE REGULATION

AR 117/2007

(ii) by adding the following after Appendix Note A-3.2.2.35.(4): A-3.2.3.1. Fire Protection Related to Limiting Distance versus Separation Between Buildings.

Requirements in the Code for protection against fire spread from building to building are related to the limiting distance for a building, measured to a property line, the centre line of a street or an imaginary line between buildings, rather than the distance between adjacent buildings. (See definition for limiting distance.) The Code does not provide requirements based on the distance between buildings, for buildings on separate properties, since this would result in situations where the design and construction of a building on one property would affect the design and construction of a building on an adjacent property. The Code requirements for reducing the probability of building-to-building fire spread were originally developed based on an assumption that the exposing building faces of adjacent buildings are of similar size and configuration, and are placed equidistant from the property line. Where buildings are different sizes, the smaller building may be subject to higher heat flux in the case of a fire compared to the larger building. Where buildings are closely spaced and not equidistant from property lines, the construction of the building with the greater limiting distance does not recognize the proximity of the building with the lesser limiting distance. At lesser limiting distances, the Code has more stringent requirements for maximum area and spacing of unprotected openings, and for construction, cladding and fire resistance of walls. This recognizes that fire hazard is greater where buildings are closer together and that adjacent buildings may have exposing building faces of different sizes, configurations or limiting distances, which could further increase the hazard. Limiting distances may also be addressed by the authority having jurisdiction through legal agreements where the parties agree that the limiting distance be measured to a line that is not the property line. Such agreements would normally be registered with the titles of both properties.
(iii) by striking out Appendix Note A-3.2.3.3.(7) and substituting the following:

29

Schedule

BUILDING CODE REGULATION

AR 117/2007

A-3.2.3.1.(6) Spacing between Individual Unprotected Openings

The spacing values of 2 m horizontally and 2 m vertically given in Sentences 3.2.3.1.(6), 9.10.14.4.(4) and 9.10.15.4.(4) are not meant to apply at distances from the unprotected openings greater than 2 m. Figure A-3.2.3.1.(6) illustrates the area around an individual unprotected opening that would be considered off-limits for another unprotected opening. Other individual unprotected openings would be permitted, for example, directly above the window shown, provided the second window is more than 2 m above the first window.

X+4m X 2m Y Y+4m

2m

Figure A-3.2.3.1.(6) Spacing between Individual Unprotected Openings A-3.2.3.1.(8) Intervention Time and Limiting Distance

The total time from the start of a fire until fire suppression by the fire department begins depends on the times taken for a series of actions. Sentence 3.2.3.1.(8) is concerned only with the time from receipt of notification of a fire by the fire department until the first fire department vehicle arrives at the building. Sentence 3.2.3.1.(8) specifies a 10 minute time limit that must be met in at least 90% of the calls to the building served by the fire department. This reliability rate and provision for flexibility is essentially consistent with NFPA 1710, Standard for the Organization and Deployment of Fire Suppression Operations, Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments. While providing some guidance, NFPA 1710 does not cover all situations.

30

Schedule

BUILDING CODE REGULATION

AR 117/2007

NFPA 1710 establishes time objectives for fire incidents as follows: 1 minute (60 seconds) for turn-out of responders after receipt of notification of a fire, and 4 minutes (240 seconds) or less for arrival of the first arriving engine company at a fire suppression incident and/or 8 minutes (480 seconds) or less for the deployment of a full first alarm assignment at a fire suppression incident.(1) The standard requires that the fire department establish a performance objective of not less than 90% for each response time objective. This reliability level is referred to in NFPA 1710 as a performance objective. Where the 10 minute limit cannot be met by the fire department at least 90% of the time, Sentence 3.2.3.1.(8) specifies that requirements that depend on limiting distance to define other criteria are to use a value that is half of the actual limiting distance. The same applies in Part 9 as stated in Sentence 9.10.14.3.(1) and 9.10.15.3.(1). (1) Reference: Clause 4.1.2.1. of NFPA 1710, Standard for the Organization and Deployment of Fire Suppression Operations, Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments, 2004.
A-3.2.3.8.(3) Noncombustible Cladding

The requirement for the exterior protection of foamed plastic insulation in an exposing building face is intended to limit the exposure of the insulation to flames, thereby reducing the possibility of increased radiation to an exposed building. The permission to use combustible cladding systems conforming to Article 3.1.5.5. does not waive the requirements for noncombustible construction or noncombustible cladding in Sentences 3.2.3.7.(1).
(iv) adding the following after Appendix Note A-9.10.12.4.(3): A-9.10.12.5. Protection of Balconies

This Article is intended to apply only to multi-family, multi-storey residential occupancies and multi-storey hotels
31

Schedule

BUILDING CODE REGULATION

AR 117/2007

or motels. It would not be appropriate to apply the requirements of this Article to row housing or single-family dwellings with or without secondary suites. The popularity of exterior balconies as a place to smoke or barbecue, combined with combustible furnishing, propane, increased use of combustible cladding such as vinyl siding and lack of balcony sprinkler protection, has contributed to the potential for high intensity residential fires. Provided that the fire department is notified in an appropriate time frame, protecting the exterior wall assembly with some form of fire-resistant construction (either noncombustible cladding or a fire-resistant sheathing material) around the entire balcony will decrease the likelihood of a balcony fire propagating into the interior of a building or into a concealed space within the building prior to the arrival of fire fighting personnel. Extending the protection 1.2 m on either side of the balcony should ensure that any flame extension from a balcony fire is not able to compromise the protection provided under windy conditions that pull the flame around the edge of a balcony or further down the side of the wall.
(v) adding the following after Appendix Note A-9.10.13.2.(1): A-9.10.14.5.(1) Minor Combustible Cladding Elements

Where the cladding is required to be noncombustible, minor elements are permitted to be of combustible material. These elements are intended to be distributed over the building face and not concentrated in one area.
(vi) by striking out Appendix Note A-9.10.18.6.(1) and substituting the following: A-9.10.15.5.(6) Permitted Projections

The definition of exposing building face provided in Sentence 1.4.1.2.(1) of Division A refers to that part of the exterior wall of a building or, where a building is divided into fire compartments, the exterior wall of a fire compartment . Because exposing building face is defined with respect to the exterior wall, projections from exposing building faces are elements that do not incorporate exterior walls. Depending on their specific configurations, examples of constructions that would normally be permitted by Sentence 9.10.15.5.(6) are balconies, platforms, canopies, eave projections and stairs. However, if a balcony, platform or stair is enclosed, its exterior wall would become part of an exposing building face and the
32

Schedule

BUILDING CODE REGULATION

AR 117/2007

construction could not be considered to be a projection from the exposing building face.
A-9.10.15.5.(7) Protection at Projections

Sentence 9.10.14.5.(7) permits certain projections from exposing building faces where the constructions do not have exterior walls and thus clearly do not constitute part of the exposing building face. Sentence 9.10.14.5.(8) refers to other types of projections from the exposing building face, such as for fireplaces and chimneys. It is recognized that these present more vertical surface area compared to platforms, canopies and eave projections, and may be enclosed by constructions that are essentially the same as exterior walls. These constructions, however, do not enclose habitable space, are of limited width and may not extend a full storey in height. Consequently, Sentence (8) allows these projections beyond the exposing building face of buildings identified in Sentence (6) provided additional fire protection is installed on the projection. Figure A-9.10.14.5.(8) illustrates projections that extends within 0.6 m or 1.2 m of the property line where additional protection must be provided. Where a projection extends within 0.6 m of the property line, it must be protected to the same degree as an exposing building face that has a limiting distance of less than 0.6 m. Where a projection extends within 1.2 m but not within 0.6 m of the property line, it must be protected to the same degree as an exposing building face that has a limiting distance of less than 1.2 m. Protection is also required on the under-side of the projection where the projection is more than 0.6 m above finished ground level, measured at the exposing building face.

Figure A-9.10.14.5.(7) Protection of projections

33

Schedule

BUILDING CODE REGULATION

AR 117/2007

_____ normal cladding-sheathing assembly

cladding-sheathing assemblies providing additional fire protection


A-9.10.18.6.(1) Fire Alarm, Fire Detection and Smoke Detection Devices and Systems

A number of provisions captured by the cross-reference to Subsection 3.2.4. address issues already addressed in Subsection 9.10.18. and so are not applicable to Part 9 buildings. For example, Articles 9.10.18.2. and 9.10.18.8. identify the Part 9 buildings where fire alarm systems are required, so Article 3.2.4.1. does not apply. Note that, because the cross-reference relating to sprinkler systems in Sentence 9.10.1.2.(8) refers only to Subsection 3.2.5., the requirements of Subsection 3.2.4. regarding electrical supervision and monitoring do not normally apply to sprinkler systems in Part 9 buildings. However, where a sprinkler system is installed in lieu of heat and smoke detectors according to Sentence 9.10.18.3.(3), electrical supervision and monitoring of the sprinkler system must comply with the provisions in Subsection 3.2.4.
5 Notwithstanding this Regulation, the Building Code Regulation (AR 117/2007), as it read immediately before the coming into force of this Regulation, remains in force for work in respect of which

(a) a permit is issued after September 2, 2007 but prior to May 3, 2009, by a safety codes officer or other person designated by an Administrator pursuant to section 44 of the Safety Codes Act, or (b) a permit application is submitted after September 2, 2007 but prior to May 3, 2009, to a safety codes officer or other person designated by an Administrator pursuant to section 44 of the Safety Codes Act, until that work has been completed or the permit has expired or been revoked.
AR 49/2009 s4;265/2009