FSD Circular Letter No. 2/2006 Pressurization of Staircases To British Standard 5588: Part 4
FSD Circular Letter No. 2/2006 Pressurization of Staircases To British Standard 5588: Part 4
FSD Circular Letter No. 2/2006 Pressurization of Staircases To British Standard 5588: Part 4
Dear Sirs/Madams,
According to Section 5.21 of the Code of Practice for Minimum Fire Service
Installations and Equipment (COP), the provision of staircase pressurization system shall be
based on the requirements of the latest edition of British Standard 5588: Part 4 (BS 5588: Part
4) with changes listed therein to suit local applications.
The 1998 edition of BS 5588: Part 4 - “Code of Practice for Smoke Control Using
Pressure Differentials” incorporating Amendment No. 1 and Corrigendum No. 1 is currently in
effect. It covers a wide range of technical details and a series of examples on normative
applications which may not be entirely suitable for local application.
/….P.2
In addition, your attention is also drawn to the requirements specified in Section 5.21 of
the Code of Practice for Minimum Fire Service Installations and Equipment which should be
read in conjunction with the attachments when designing the system.
Yours faithfully,
(CHAN Chor-kam)
for Director of Fire Services
Encl.
Recommendations of the Fire Safety Standard Advisory Group (FSSAG)
BS 5588: Part 4 1998 – Code of Practice for Smoke Control Using Pressure Differentials
Except those named in the following lists, all clauses stipulated in the subject Code of
Practice including Notes, Commentary and Recommendations are to be followed: -
1.2 Clause 5.5 5.4 Class D System It is not practical to adopt these
Table 4 Table 4 – Minimum pressure differentials for Class D system requirements in local industry.
Figure 4 Figure 4 – Design conditions for Class D systems
(Page 13, 14 &
15)
1.3 Clause 5.6 5.4 Class E System It is not practical to adopt these
Table 5 Table 5 – Minimum pressure differentials for Class E system requirements in local industry.
Figure 5 Figure 5 – Design conditions for Class C systems
(Page 16 & 17)
1.4 Clause 9.2.3.3 9.2.3.3 Interaction with normal ventilation equipment It is not practical to adopt these
all paragraphs “ The purpose of a pressurization system is ............................ requirements in local industry.
(Page 41) ............. in accordance with Annex C.”
Page 1 of 1
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
List BS Clause / Context Replaced by Reason
item Paragraph /
Table (Page)
2.1 Definitions basement “Basement” means To align with the definition as
Clause 3.4 “Storey with a floor that is at some point more Any storey of a building which is below the lower or stipulated in the Code of
(Page 2) than 1.2 m below the highest level of ground lowest ground storey and from which any required Practice of Buildings
adjacent to the outside walls.” exit route is in an upward direction Department.
2.2 Definitions fire compartment “Fire compartments” means To align with the definition as
Clause 3.13 “Building or part of a building, comprising one An enclosed space in a building that is separated from stipulated in the Code of
(Page 2) or more rooms, spaces or storeys, constructed to all other parts of the building by enclosing Practice of Buildings
prevent the spread of fire to or from another construction providing a fire separation that may be Department.
part of the same building, or to an adjoining required to have a fire-resisting rating.
building.”
2.3 Definitions protected lobby “Protected lobby” means To align with the definition as
Clause 3.37 “Circulation area consisting of a lobby enclosedThe intercepted approach, to a staircase or an exit stipulated in the Code of
(Page 4) route, which acts as a fire and smoke check between a Practice of Buildings
with fire-resisting construction (other than any
part that is an external wall of a building)” storey and the staircase or the exit route, and enclosed Department.
throughout by walls and doors in accordance with the
Code of Practice for Fire Resisting Construction.
2.4 Clause 5.1 5.1 General 5.1 General To suit the current practice of
Paragraph 1 “Smoke control using pressure differentials can “Smoke control using pressure differentials can be local building industry.
& 2 (Page 8) be implemented in several different types of implemented in two different types of buildings, with
buildings, with differing requirements and differing requirements and design conditions
design conditions
For the purposes of this standard, the design
For the purposes of this standard, the design conditions have been placed into two separate systems
conditions have been placed into five separate (classes A & B) and are detailed in Table 1.”
systems (classes A, B, C, D and E) and are
detailed in Table 1.”
Page: 1 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
List BS Clause / Context Replaced by Reason
item Paragraph /
Table (Page)
2.5 clause 5.1 Table 1- Classification of buildings for smoke Table 1 – Classification of protection To suit the current practice of
Table 1 control using pressure differentials local building industry.
(Page 8) Class Examples Class Examples
Residential, sheltered housing &
buildings designed for three door A Protection of escape (see 5.2)
A protection (see 5.2) B Protection of firefighting shafts (see 5.3)
B protection of firefighting shafts (see 5.3)
Commercial premises (using
C simultaneous evacuation) (see 5.4)
Hotels, hostels and instructional type
buildings, excluding buildings designed
D to meet class A (see 5.5)
E Phased evacuation (see 5.6)
2.6 clause 5.2 Class A system Class A system To suit the current practice of
paragraph 1 - “The design conditions for blocks of flats and local building industry.
4 maisonettes …………………….. “System Class “A” would be referred to Means of
(page 8) Note 1…………………… Escape (MOE) for local application. The technical
The level of fire arrangement of the inspection would be :-
compartmentation ……………… a. The air flow velocity at the door of
…………………………………………. measurement on the ‘fire zone floor’ should
Note 1 ……………………. not be less than 0.75m/s
Note 2 …………………… b. The total numbers of doors to be opened when
Note 3 …………………… the measurement was conducted should
It is unlikely………………………………. comply with the requirements of the Code of
Note 4 …………………………………. Practice for Minimum Fire service Installations
The air flow and Equipment.
through …………………………..when : c. Checking and testing on the air release required
A/. the door ………………….. by BS5588: Part 4: 1998 from the lobby and
B/. the air release …………………………. corridor would be conducted on the ‘fire zone
C/. all doors………………………………….. floor’ only.
D/. all doors ………………………………… All floors should be subject to the above tests
E/. the final exit door is closed. throughout the entire staircase.
Page: 2 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
List BS Clause / Context Replaced by Reason
item Paragraph /
Table (Page)
2.6 clause 5.2 The air flow velocity at the door of measurement on
(Cont’d) paragraph 1 - the ‘fire zone floor’ should not be less than 0.75m/s
4 when :-
(page 8)
a. The door between the lobby/corridor and the
(Cont’d) pressurized stair is open on three consecutive
levels.
b. The air release from the lobby/corridor on fire
zone is open;
c. All doors between the pressurized stair and the
lobbies/corridors are closed on all other
storeys.
d. The final exit door is open.
2.7 Figure 1 Figure 1-Design conditions for class A systems Figure 1-Design conditions for class A systems To suit the current practice of
(page 9) (see Appendix I ) local building industry.
2.8 Clause 6.3 Table 6 – Minimum temperature/time design criteria for Table 6 – Minimum temperature/time design criteria for To suit the current practice of local
Table 6 fans and HVAC ductwork used for air/smoke release fans and HVAC ductwork used for air/smoke release building industry.
(page 19) Features
of building design Min Temp Features
fire Life of protection Min Temp
Phased fighting safety and time design Means of Means of Sprinklers and time design
evacuation shaft sprinklers criteria escape fire fighting building criteria
Yes No No 600oC for 2 h Yes - No 600oC for 2 h
Yes Yes No 600oC for 2 h Yes - Yes 250oC for 1 h
Yes Yes Yes 300oC for 2 h - Yes No 600oC for 2 h
Yes No Yes 300oC for 2 h - Yes Yes 250oC for 1 h
No No Yes 300oC for 1 h
No No No 600oC for 1 h
No Yes Yes 300oC for 2 h
No Yes No 600oC for 2 h
Page: 3 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
Page: 4 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
Page: 5 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
List BS Clause / Context Replaced by Reason
item Paragraph /
Table (Page)
2.11 Clause 7 “Where a pressure differential system is required “Where a pressure differential system is required to To align with the amendment in
Paragraph 6 to protect both : protect both : list item 2.5.
(page 20) a. The means of escape prior to the arrival of a. The means of escape prior to the arrival of
the fire brigade (Class A, C, D or E systems); the fire brigade (Class A system); and
and
b. The fire brigade during firefighting b. The fire brigade during firefighting
operations (Class B system)” operations (Class B system)”
2.12 Clause 7 “The enforcing authority may agree that the “The enforcing authority may agree that the To align with the amendment in
Paragraph 8 pressure differential system should be started pressure differential system should be started list item 2.5.
(page 20) automatically on detection of smoke within space automatically on detection of smoke within space in
in the: the:
a. Means of escape mode (Class A, C, D or E a. Means of escape mode (Class A system) and
systems) and subsequently, on arrival of the subsequently, on arrival of the fire
fire brigade……………….operational mode brigade .. ……
(Class B system); or …….operational mode (Class B system); or
b. Firefighting mode (Class B system), with no b. Firefighting mode (Class B system), with no
subsequent change of operation of the subsequent change of operation of the system.”
system.”
2.13 Clause 7 “Manual system-override switches for the “Manual system-override switches for the To suit the current practice of
Paragraph 9 pressurization system should be situated at the pressurization system should be situated at the local building industry.
(page 20) following locations: following locations:
a. The building services plant room and the a. The pressure differential system equipment
pressure differential system equipment plant plant room; and Where
room (where separate); and Where b. Near the building entrance at a location agree
b. Near the building entrance at a location agree with the fire authority or Staircase
with the fire authority” pressurization supervisory panel at the F.S.
control room”
Page: 6 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
2.15 Clause 8.2 “The supply to these isolating protective devices “The supply to these isolating protective devices To suit the current practice of
Paragraph 7 should be independent of the main power switch should be independent of other circuits from main local building industry.
(page 21) for the building and should be appropriately switchboard for the building and should be
labelled in accordance with 16.2 of BS 5839- appropriately labelled in accordance with 16.2 of
1:1988” BS 5839-1:1988.”
2.16 Clause 8.4 “8.4 Secondary power supplies “8.4 Secondary power supplies To align with the requirements
All “It is essential that a secondary power The provision of secondary power supply shall be as stipulated under FSD
paragraphs supply………… complied with HKFSD Circular Letter No.4/96 Part Circular Letter No 4/96 &
(page 22) …………………………………………………… IX and HKFSD Circular Letter No.1/2000. 1/2000.
…………………………………………. Note1- the original paragraphs are only used for
…………………………………………………… reference.”
……
…..and fire protection installations.”
2.17 Clause 9.1.3 “9.1.3 Minimum pressure differentials “9.1.3 Minimum pressure differentials To align with the amendment in
Paragraph 1 To ensure that a system To ensure that a system list item 2.5.
(page 27) performs………………………. performs……………………….
……………. during a fire. The minimum ……………. during a fire. The minimum pressure
pressure difference required can depend on the difference required can depend on the nature of the
nature of the building and its usage (see clause 5). building and its usage (see clause 5). See also 5.2
See also 5.2, 5.3, 5.4, 5.5 and 5.6 for the values of and 5.3 for the values of minimum pressure
minimum pressure differential appropriate to differential appropriate to design and to acceptance
design and to acceptance testing.” testing.”
Page: 7 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
2.20 Clause 11.1 “Where air intake is not at roof level a smoke “A smoke detector should be provided in the intake To suit the current practice of
Paragraph 11 detector should be provided in the intake duct or duct or within the immediate vicinity of the supply local building industry.
(page 50) within the immediate vicinity of the supply ductwork in order to cause the automatic shut down
ductwork in order to cause the automatic shut of the staircase pressurization system if substantial
down of the pressure differential system if quantities of smoke are present in the supply. An
substantial quantities of smoke are present in the override switch to resume the staircase
supply. An override switch to reopen the closed pressurization system should be provided for fire
damper should be provided for fire brigade use in brigade use in the positions stated in clause 7.”
the positions stated in clause 7.”
2.21 Clause 12.1 “The entire pressure “The entire pressure To align with the amendment in
Paragraph 3 differential………………………. differential………………………. list-item 2.5.
(page 51) …for the specified class (see 5.2, 5.3, 5.4, 5.5 and …for the specified class (see 5.2 and 5.3), and
5.6), and secondly
secondly………………………………………… …………….………………………………………
… ……
………..when a door is opened between the ………..when a door is opened between the
spaces.” spaces.”
Page: 8 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
2.23 Clause 12.1 “All test equipment should be accurate to + 5%. “All test equipment should be accurate to + 2%. The To align with the definition as
Paragraph 5 The calibration of all test calibration of all test stipulated in the Code of
(page 51) equipment……………………….. equipment……………………….. Practice of Fire Services
………, in the UK, are the responsibility of the ………, in the UK, are the responsibility of the Department.
National Physical Laboratory.” National Physical Laboratory.”
Page: 9 of 10
List Two : Clauses to be replaced by modified conditions
(Schedule for the use of BS5588 : Part 4 : 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
Page: 10 of 10
List Three : Clauses with acceptable alternatives
(Schedule for the use of BS5588: Part 4: 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
3.2 Clause 7 “Point type smoke detectors should be used, “Point type smoke detectors should be used, To align with the requirements
Paragraph 2 mounted in the accommodation area adjacent to mounted in the accommodation area adjacent to as stipulated in the Code of
(Page 20) the doors; leading to the protected space at each the doors leading to the protected space at each Practice of Fire Services
storey served by the system. Location of the smoke storey served by the system. Location of the smoke Department.
detectors should be in accordance with clause 12 of detectors should be in accordance with clause 12 of
BS5839-1:1988.” BS5839-1:1988 or installed at a distance within 1.0
m from the doors leading to the protected space at
each storey served by the system.”
Note : For the simple lobby, the smoke detector
should be mounted in the accommodation area
adjacent to the door of simple lobby.
Page 1 of 1
List Four : Clauses to be taken as reference only
(Schedule for the use of BS5588: Part 4: 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
4.2 Clause 9.2.2.3. 9.2.2.3 Pressurizing stair and lift There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 36)
4.3 Clause 9.2.2.5 9.2.2.5 Pressurization of lift wells There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 36)
4.4 Clause 9.2.2.7 9.2.2.7 Pressurization of evacuation lift wells There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 36)
4.5 Clause 9.2.2.8 9.2.2.7 Pressurization of refuges and central control rooms. There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 39)
4.6 Clause 9.2.3.2. 9.2.3.2 Pressurized escape routes and other pressurized spaces in the same building. There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 39)
4.9 Clause 10.2 10.2 Depressurization systems There is no such requirement in the Code
All paragraphs of Practice of Fire Services Department.
(Page 48 & 49)
Page 1 of 2
List Four : Clauses to be taken as reference only
(Schedule for the use of BS5588: Part 4: 1998 Incorporating Amendment No. 1 and Corrigendum No. 1)
4.12 Figure 11 Figure 11 – Features of a depressurization system There is no such requirement in the Code
of Practice of Fire Services Department.
(Page 42)
Page 2 of 2
Checklist for Staircase Pressurization System
Reference
Section I –General items for all staircase pressurization systems installed in the building
1.1 Measuring and Testing Instrument / Equipment Calibration
Measuring instrument used for testing purpose shall be provided in duplicate and calibrated in the past 3 months.
1.2 Documentation
Yes No Remark
a. Equipment list of staircase pressurization system c/w related
test report is attached. [ ] [ ]
b. Equipment list of builder’s work (such as doorset, door closer
& etc) c/w related test report is attached. [ ] [ ]
c. Certifying the building air tightness condition during the
testing is equivalent to the occupation condition. [ ] [ ]
* -Delete as appropriate
1.1 Description
Appendix Remark
a. Pressure test report of all ductwork (including builder’s
work, ducts, shafts or other construction)
b. Air velocity measurement report
c. Door opening force measurement report
d. Differential pressure measurement report
e. System performance test report
h Functional test
h.1 Performance test is carried out and the result is satisfactory. [ ] [ ] [ ]
h.2 Measurement of door opening force is carried out and result is
satisfactory. [ ] [ ] [ ]
h.3 Measurement of differential pressure across the pressurized space and
accommodation is carried out and the result is satisfactory. [ ] [ ] [ ]
h.4 Measurement of pressurized air flow is carried out and the result is
satisfactory. [ ] [ ] [ ]
h.5 Air intake fire/smoke damper is closed when the duct type smoke
detector is activated ;
or [ ] [ ] [ ]
Staircase pressurization system is shut down when the duct smoke
detector at air intake is activated (for the air intake only facing in one
direction) [ ] [ ] [ ]
h.6 In order to prevent overpressure in pressurized space, fail safe
protection for over-pressure release is provided on conditions of :-
- Failure of controller. [ ] [ ] [ ]
- Failure of pressure switch. [ ] [ ] [ ]
- Failure of wiring of pressure switch. [ ] [ ] [ ]
- Failure of actuator of by-pass damper. [ ] [ ] [ ]
- Failure of wiring of actuator (by-pass damper). [ ] [ ] [ ]
- Failure of over pressure exhaust fan. [ ] [ ] [ ]
Section III –For all staircase pressurization system installed in the building
1. The checklist is totally _______ pages (including attached copies for each additional staircase pressurization
system).
2. Attached ______________ number(s) of appendix.
Tested by :
Signature :
Name of installation
contractor :
Company chop :
Date :
Certified by :
Signature :
Register number of
engineer :
Company chop :
Date :