Cable Schedule-MV SLD
Cable Schedule-MV SLD
Cable Schedule-MV SLD
DUCAB Cables 6/10 (12) kV Three Core Copper Conductors XLPE Insulated to IEC 60502-2 Steel Tape Armoured Sr. No 1 2 3 4 5 6 Voltage (V) 11000 11000 11000 11000 11000 11000 Current in Amps 269.00 269.00 22.31 22.31 22.31 22.31 Length (mtr) 300 300 20 20 20 20 voltage Drop (V) 3.95 3.95 0.04 0.04 0.04 0.04
From
To
Load (KW)
Power Cable Size 2R- 3C x 240 sqmm XLPE/SWA/PVC 2R- 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC
Cable Type
V/A/km
MV Panel MV Panel VFD Panel-1 VFD Panel-2 VFD Panel-3 VFD Panel-4
PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN
I I
Sq.mm kA kA A A
K1 K2 K3 K4 K IZ IL IMD
Result :
The Above selected 2 runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Short Circuit Current Curves for 11kV MV cable 2. Datasheet of the cable attached for reference
Cable catalogue
PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN
CABLE SELECTION 1 2 3 4 5 6 a) b) c) d) Number of Cable Runs Cable Size Selected :- 3 Core XLPE/SWA/PVC Cu Cable Current Carrying Capacity in Ground One Second Short Circuit current Rating of Conductor Cable Installation Type Derating Factors Ground Temperature at 35oC Thermal Resistivity of Soil at 2.5oCm/W Depth at 0.8 Meter Group factor (0.45 m spacing) Total Derating 7 8 9 Derated Current Rating for 2 Runs of Maximum connected load current Maximum Demand current 3x50 Sq. mm K1 K2 K3 K4 K IZ IL IMD R I kA = = = = = = = = = = = = = = = 1 3C*240 Sq.mm 436 A 34.4 Ground 0.96 0.74 1 0.72 (K1 x K2 x K3 x K4) 0.5 (I x K x R) 223.01 A 22.31 A 22.31 A
Result :
The Above selected 1runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Datasheet of the cable attached for reference 2. Maximum permitted release time is 100 msec.
PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN
CABLE SELECTION 1 2 3 4 5 6 a) b) c) d) Number of Cable Runs Cable Size Selected :- 3 Core XLPE/SWA/PVC Cu Cable Current Carrying Capacity in Ground One Second Short Circuit current Rating of Conductor Cable Installation Type Derating Factors Ground Temperature at 35oC Thermal Resistivity of Soil at 2.5oCm/W Depth at 0.8 Meter Group factor (0.45 m spacing) Total Derating 7 8 9 Derated Current Rating for 2 Runs of Maximum connected load current Maximum Demand current 3x50 Sq. mm K1 K2 K3 K4 K IZ IL IMD R I kA = = = = = = = = = = = = = = = 1 3C*240 Sq.mm 436 A 34.4 Ground 0.96 0.74 1 0.72 (K1 x K2 x K3 x K4) 0.5 (I x K x R) 223.01 A 74.36 A 74.36 A
Result :
The Above selected 1 runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Datasheet of the cable attached for reference 2. Maximum permitted release time is 100 msec.
hree Core Copper Conductors XLPE Insulated to IEC 60502-2 Steel Tape Armoured voltage Drop Vd % 0.036 0.036 0.001 0.001 0.001 0.001
(K1 x K2 x K3 x K4)
(K1 x K2 x K3 x K4)
(K1 x K2 x K3 x K4)