Marley: Basic Control System
Marley: Basic Control System
Marley: Basic Control System
Warning
This manual contains vital information for the proper installation and operation of your cooling tower and the basic control system. Carefully read the manual before installation or operation of the tower. Failure to follow the instructions in this manual may result in substantial personal injury or death. Save this manual for future reference.
Table of Contents
Introduction.................................................................................................................2 Safety. ...........................................................................................................................3 Factory Installation.....................................................................................................4 Field Connection........................................................................................................6 AquaTower. ..........................................................................................................6 NC Tower Standard. ......................................................................................7 NC Tower Motor Outside Option...............................................................7 NC Tower Modular.........................................................................................8
Field Connection..................................................................................................... 10 Field Installed Systems Single Speed Motor. ....................................... 10 Field Installed Systems Two Speed Motor............................................ 11
Control System Operation.................................................................................... 12 Single Speed Manual. .................................................................................... 12 Two Speed Manual......................................................................................... 13 Single Speed Automatic............................................................................... 14 Two Speed Automatic. ................................................................................... 16
System Maintenance. ............................................................................................. 18 Contacts. ........................................................................................................... 18 Coils................................................................................................................... 18 Fuses and Thermal Overloads..................................................................... 18 Visual Inspections........................................................................................... 18
Single Speed Wiring Details 3 Phase. ........................................................... 19 Two Speed Wiring Details.................................................................................... 20 AC Starter Wiring Schematic.............................................................................. 22 Parts List Single Speed Motor....................................................................................... 31 Two Speed Motor. ...........................................................................................39
Trouble Shooting.....................................................................................................44
Introduction
The Marley Basic Control System purchased on this tower represents the most economical and reliable automatic control system available. Since the system is factory tested and all components are operationally tested, you can have condence the system will perform as specied. These instructionsas well as those offered separatelyare intended to assure that Field connections are completed properly and the control system serves you for the maximum possible time. Since product warranty may depend on your actions, please read these instructions thoroughly prior to operation. If you have questions about the operation and/or maintenance of this control system, and you do not nd the answers in this manual, please contact your Marley sales representative. When writing for information, or when ordering parts, please reference the Marley customer order number on the tag inside the door of the controlpanel.
Warning
Hazard of electrical shock or burn. Be sure to turn off power to panel before servicing. If working on equipment out of sight of panel disconnect, lockout using standard lock-out procedure.
Safety
The Marley control system uses UL listed components installed in accordance with the National Electrical Code. The location of the cooling tower and eld installation of the control system can affect the safety of those responsible for installing, operating or maintaining the tower and controls. However, since SPX Cooling Technologies does not control the tower location, or eld installation, we cannot be responsible for addressing safety issues that are affected by these items. The following safety issues should be addressed by those responsible for installation, maintenance or repair of the tower and controls: Access to and from the control panel (including the disconnectswitch). Proper grounding of electrical control circuits. Sizing and protection of branch circuits feeding the controlpanel. Qualification of persons who will install, maintain and service the electrical equipment. These are only some of the safety issues that may arise in the design and installation process. SPX strongly recommends that you consult a safety engineer to be sure that all safety considerations have been addressed. Other safety issues are addressed in literature supplied with your tower. You should closely review the literature prior to installing, maintaining or repairing your tower.
Factory Installation
The control panel bolts directly to the tower with spacers or to a bracket attached to the tower. The thermostat is bolted to the tower casing adjacent to the cold water basin depressed section. The capillary runs through a bushing in the tower casing and the bulb is installed vertically in a holder near the outlet for proper temperature measurement. The holder is glued to the cold water basin oor with a layer of sealer applied to its bottom ange and the bushing through which the capillary passes is lled with sealer to protect the capillary. A vibration limit switch is mounted near the Geareducer on larger towers and near the motor on belt driven towers. Liquid tight exible metal conduit connects all points which are to be wiredmotor, control panel, thermostat and vibration limit switch, if required. The conduit is installed with associated couplings, connectors and ttings approved for this conduit and is also supported by conduit clamps as required by code. After the completion of the conduit installation, the wiring is pulled through the conduit to each component. Pulling type ttings are used to provide access for pulling the wire and meeting the N.E.C. requirement for maximum number of bends allowed in each conduit run. All wire ends are tagged for identication and connections at each end are made at terminal blocks or by terminal connectors with fasteners.
Factory Installation
Overload units are selected based upon the full-load current as read from the motor nameplate. Fuses are selected based upon the motor voltage and fullload current (high speed current on two speed motors) as listed in the National Electric Code. The overload units are installed into the motor starter and the time delay fuses are installed into the fuse clips with the grooved end on the bottom. (A bar in the fuse clip requires the use of a time delay fuse which has a groove to t over the bar.) The time delay relay on the two speed control panel is adjusted for a 30 second or more delay and the thermostats are preset as follows: One Speed Two Speed Cut-in Temperature 85 F Cut-out Temperature 80 F 72F
The completed factory installation is tested by cycling the fan off and on both manually and automatically with the control panel switches and the thermostat respectively.
Field Connection
Note
The factory installation by Marley has been performed in accordance with the National Electrical Code using UL Listed components. All installation and wiring performed after leaving the factory must be performed in accordance with the latest revision of the National Electrical Code and any local codes to insure safe operation. The Marley Basic Control System has been factory tested to the fullest extent possible. Some equipment selections and options require the installation be completed in the eld. The following information is provided as an overview of the eld installation for the various options. Please refer to the drawings supplied with the tower for more detailed instructions to complete the installation.
Warning
HAZARD OF ELECTRICAL SHOCK OR BURN. BE SURE TO TURN OFF POWER to panel before servicing. If working on equipment out of sight of panel disconnect, lockout using standard lock-out procedure.
AquaTower
1. Incoming power and ground lines must be run through the opening provided on the top of the control panel. Conduit must be connected to the panel using a watertight or raintight tting. Power connections are made at the top of the fusible disconnect located in the upper right hand corner of the control panel. The ground wire must be connected to the ground bar located at the bottom of the control panel cabinet. 2. After completing the electrical connections to the panel, provide power to the panel, operate the system in the manual mode and verify proper direction of fan rotation on the tower. If the direction of rotation is incorrect, turn off power supplying the panel and reverse any two power leads at the fusible disconnect switch in the control panel. 3. The temperature and differential set points have been preset at the factory. Check the settings and adjust as necessary to suit your operating requirements. Be sure to maintain adequate differential between the cut-in and cut-out settings or excessive cycling of the fan motor may occur and shorten equipment life.
Field Connection
NC TowerStandard
1. Install temperature sensing element in its nal position on the basin oor as near the basin outlet as possible. Sealer is used to attach the bracket to the basin oor. 2. Incoming power and ground lines must be run through the opening provided on the top of the control panel. Conduit must be connected to the panel using a watertight or raintight tting. Power connections are made at the top of the fusible disconnect located in the upper right hand corner of the control panel. The ground wire must be connected to the ground bar located at the bottom of the control panel cabinet. 3. After completing the electrical connections to the panel, provide power to the panel, operate the system in the manual mode and verify proper direction of fan rotation on the tower. If the direction of rotation is incorrect, turn off power supplying the panel and reverse any two power leads at the fusible disconnect switch in the control panel. 4. The temperature and differential set points have been preset at the factory. Check the settings and adjust as necessary to suit your operating requirements. Be sure to maintain adequate differential between the cut-in and cut-out settings or excessive cycling of the fan motor may occur and shorten equipment life.
Field Connection
3. Incoming power and ground lines must be run through the opening provided on the top of the control panel. Conduit is connected to the panel using a watertight or raintight tting. Power connections are made at the top of the fusible disconnect located in the upper right hand side of the control panel. The ground wire must be connected to the ground bar located at the bottom of the control panel cabinet. 4. After completing the electrical connections to the panel, operate the system in the manual mode and verify proper direction of fan rotation on the tower. If the direction of rotation is incorrect, turn off power supplying the panel and change any two power leads at the fusible disconnect switch in the control panel. 5. The temperature and differential set points have been preset at the factory. Check the settings and adjust as necessary to suit your operating requirements. Be careful to maintain adequate differential between the cut-in and cut-out settings or excessive cycling of the fan motor may occur and shorten equipment life.
NC TowerModular
1. After the modules have been assembled, run the conduit from the control panel to the motor and vibration switch. 2. Place the power leads and ground wire for the motor through the conduit opening in the motor junction box. Connect the conduit to the motor junction box. The motor power leads have been marked to match the motor leads for easy reconnection in the eld. Make pigtail connections at the motor using hardware to fasten motor lug to the ring terminal on the power lead wire from the control panel. Wrap the pigtail with insulation putty to smooth out the points and edges and wrap the pigtail completely with vinyl electrical tape. Connect the ground lead to the ground lug inside the motor conduit box. 3. If a vibration switch is installed, feed the wires through the conduit opening on the switch, connect the conduit to the threaded switch opening, connect the wires to the normally closed contacts of the vibration switch and connect the ground wire. Slope conduit away from switch if possible to avoid condensation in the switch.
10
Field Connection
4. Support the conduit at appropriate locations in accordance with the requirements of the National Electrical Code. 5. Install temperature sensing element in its nal position on the basin oor as near the basin outlet as possible. Sealer is used to attach the bracket to the basin oor. 6. Incoming power and ground lines must be run through the opening provided on the top of the control panel. Conduit must be connected to the panel using a watertight or raintight tting. Power connections are made at the top of the fusible disconnect located in the upper right hand corner of the control panel. The ground wire must be connected to the ground bar located at the bottom of the control panel cabinet. 7. After completing the electrical connections to the panel, provide power to the panel, operate the system in the manual mode and verify proper direction of fan rotation on the tower. If the direction of rotation is incorrect, turn off power supplying the panel and reverse any two power leads at the fusible disconnect switch in the control panel. 8. The temperature and differential set points have been preset at the factory. Check the settings and adjust as necessary to suit your operating requirements. Be sure to maintain adequate differential between the cut-in and cut-out settings or excessive cycling of the fan motor may occur and shorten equipment life.
11
Field Connection
Field Installed Systems Single Speed Motor
1. Mount the control panel securely in an upright position. The disconnect switch on the control panel must be within sight of the equipment being operated and within 50 feet of that equipment or a separate disconnect switch must be provided. The best location will be at the same ambient conditions as the equipment since the overload and the motor are both temperature sensitive devices. 2. Mount the temperature switch and the vibration switch (if applicable) on the tower. Refer to the drawings supplied with the tower for details on installation of the switches. 3. Install conduit from the bottom of the control panel to the individual pieces of equipment requiring wiring. All conduit connections must be completed to provide a continuous raceway for the conductors prior to pulling the conductors through the conduit. All conduit must be supported properly in accordance with the National Electrical Code. 4. Mark the ends of the conductors for identication and pull them through the conduit. Be sure to provide a ground wire to all individual pieces of equipment. Connect the conductors to the appropriate terminal points in the control panel. 5. Make pigtail connections at the motor using hardware to fasten motor lug to the ring terminal on the power lead wire from the control panel. Wrap the pigtail with insulation putty to smooth out the points and edges and wrap the pigtail completely with vinyl electrical tape. Connect the ground lead to the ground lug in the motor conduit box. 6. Connect the wires for the vibration switch (if applicable) to the normally closed contacts of the switch. Connect the ground lead inside theswitch. 7. Install temperature sensing element in its nal position on the basin oor as near the basin outlet as possible. Sealer is used to attach the bracket to the basin oor. Insert the bulb into the holder. Fill the bushing where the capillary tube goes through the casing with sealer. 8. Incoming power and ground lines must be run through the opening provided on the top of the control panel. Conduit must be connected to the panel using a watertight or raintight tting. Power connections are made at the top of the fusible disconnect located in the upper right hand corner of the control panel. The ground wire must be connected to the ground bar located at the bottom of the control panel cabinet.
12
Field Connection
9. After completing the electrical connections to the panel, provide power to the panel, operate the system in the manual mode and verify proper direction of fan rotation on the tower. If the direction of rotation is incorrect, turn off power supplying the panel and reverse any two power leads at the fusible disconnect switch in the control panel. 10. Check the temperature and differential settings and adjust as necessary to suit your operating requirements. Be sure to maintain adequate differential between the cut-in and cut-out settings or excessive cycling of the fan motor may occur and shorten equipment life.
13
Note
When operating in the automatic mode care must be taken not to exceed ve starts per hour on the fan motor. For two-speed motors each speed is considered one start. Excessive cycling of the motor may reduce the life of the motor starter, motor and driven mechanical equipment. When operating in subfreezing weather, the opportunity exists for ice to form in the colder regions of the cooling tower. Your primary concern is to prevent the formation of destructive ice in the cooling tower ll. Care must be taken not to allow temperature control settings below 40 for automatic operation or unattended manual operation in subfreezing weather. Your understanding of cold weather operation will be enhanced if you read Marley Technical Report #H-003 Operating Cooling Towers in Freezing Weather and your cooling towers Installation, Operation, and Maintenance Instructions manual. Failure to comply with these instructions will result in damage to yourtower.
Note
Note
A jumper or a normally closed device must be installed between points 5 and 7 (1 and 3 on single phase control panel) on the terminal block or the system will not operate. 3. Close and latch the control panel door. 4. Press the reset button on the outside door to reset all overloads to the operating condition. 5. Turn the Hand-Off-Auto selector switch to the Off position (centerposition).
14
15
16
RISING TEMPERATURE
MOTOR OFF
11. Rotate the Hand-Off-Auto selector switch to the Auto position. The fan will now start and stop automatically based on cold watertemperature. The water is colder on the louver face than on the eliminator face of the ll in the cooling tower. The actual cold water temperature will be between these two extremes. For best accuracy we recommend the temperature measuring bulb be located near the basin exit in a vertical position. 12. Check to be sure the fan rotation is correct. (You may need to operate the system manually to verify fan rotation if the cold water temperature is below the cut-in set point.) 13. Rotate the Hand-Off-Auto selector switch to the Off position to stop thefan.
FALLING TEMPERATURE
17
Note
The differential is built into the switch such that the cut-out temperature will be the temperature you read on the dial. See Figure 2.
Figure 2
5 F 8 F RISING TEMPERATURE
ON LOW SPEED 8 F 5 F
18
Note
The water is colder on the louver face than on the eliminator face of the ll in the cooling tower. The actual cold water temperature will be between these two extremes. For best accuracy we recommend the temperature measuring bulb be located near the basin exit in a vertical position. 12. Check to be sure the fan rotation is correct. (You may need to operate the system manually to verify fan rotation if the cold water temperature is below the cut-in set point.) 13. Rotate the Hand-Off-Auto selector switch to the Off position to stop thefan.
19
System Maintenance
Warning
Hazard of electrical shock or burn. Be sure to turn off power to panel before servicing. If working on equipment out of sight of panel disconnect, lock out using standard lock-out procedure.
Contacts
The contacts inside the electromagnetic contactor, which connect the motor to the power source are the only components that experience wear in normal service requiring periodic replacement. Two years is not considered unusual for the service life of silver-alloy contacts. All service work such as replacement of the contacts should be performed by a qualiedelectrician.
Note
Contacts are replaced many times when this expense is not necessary. Contacts are not harmed by discoloration of the surface or slight pitting. We do not recommend ling them as dressing only removes contact material which is wasteful. Replacement is necessary only when the contact has worn thin.
Coils
Coils have an indenite service life under normal operating conditions. Coils generally operate improperly or fail because of unacceptable voltage or from mechanical abuse.
Visual Inspections
Visual inspections should be conducted during installation and at six month intervals. Check all connections for tightness. Vibration or improper installation can cause loose connections resulting in increased resistance to current ow. We recommend the use of copper wire only. During the visual inspection we recommend the use of compressed air and brushes to clean dirt from magnetic pole faces and contacts.
20
NORMALLY CLOSED VIBRATION SWITCH (OR JUMPER AT 5 TO 7) NORMALLY OPEN CONTACTS FOR CUSTOMER SUPPLIED OVERLOAD TRIP ALARM (OPTIONAL) RANGE ADJUSTMENT SCREW
RED RED
5 7 6 12 9 11
GROUND
GREEN
Note: Terminal block numbers are shown out of order. Actual terminals are numbered in sequential order.
T 1 T 2T 3
RED
RED
GROUND
BLACK
BLACK
LINE M2
BLACK
RE
EN
GREEN
MOTOR
21
TERMINAL BLOCK NORMALLY CLOSED VIBRATION SWITCH (OR JUMPER AT 6 TO 7) NORMALLY OPEN CONTACTS FOR CUSTOMER SUPPLIED HIGH SPEED OVERLOAD TRIP ALARM (OPTIONAL) NORMALLY OPEN CONTACTS FOR CUSTOMER SUPPLIED LOW SPEED OVERLOAD TRIP ALARM (OPTIONAL) GREEN RED RED
GROUND
ADJUSTING SCREW
RED RED
6 7 17 5 5 18 9 14 16
LOW SPEED
T1 T2 T3
T6 T4 T5
HIGH SPEED
Note: Terminal block numbers are shown out of order. Actual terminals are numbered in sequential order.
GROUND
PANEL
TEMPERATURE DIAL
Y B R
Y B R GREEN GREEN T1 T2 T3 T6 T4 T5
22
TERMINAL BLOCK NORMALLY CLOSED VIBRATION SWITCH (OR JUMPER AT 6 TO 7) NORMALLY OPEN CONTACTS FOR CUSTOMER SUPPLIED HIGH SPEED OVERLOAD TRIP ALARM (OPTIONAL) NORMALLY OPEN CONTACTS FOR CUSTOMER SUPPLIED LOW SPEED OVERLOAD TRIP ALARM (OPTIONAL) GREEN RED RED
GROUND
ADJUSTING SCREW
RED RED
6 7 17 5 5 18 9 14 16
LOW SPEED
T1 T2 T3
T11T12T13
HIGH SPEED
Note: Terminal block numbers are shown out of order. Actual terminals are numbered in sequential order.
GROUND
PANEL
TEMPERATURE DIAL
Y B R
23
AC Combination Starter
3 Phase, Single Speed
TB 5 5 6 6 7 9 11 12
(H1) PRI
L1
L2
L3
L1 L2 1
M M
T1 T2 T3
MOTOR
L3
3 TS
F U 2 3 (H1) PRI 2 4
F U 3
1 L1 8
2 L2 L3
5 (X1) SEC
10
(5)
8 (11) 3 TS
10
OL
5 6
12 10 T2 T3 ALARM
OL T1
12
Connection Diagram Notes 1 Disconnecting means provided with controller. 2 Input Voltage Primary Connections per Transformer Nameplate. 3 Customers Remote Located Equipment
Grounding Service Conductor and Grounding Electrode Conductor Terminals Located in Bottom ofCabinet Field wiring by others
24
AC Combination Starter
208V and 230V, Single Phase, Single Speed
L1
L3
L1
1
T1
TB 5 5 6 6 7 9 11 12
MOTOR
L2
T2
F U 2 3 (H1) PRI
2
TS
1 L1 F U 2 (H1) 3 1 3 PRI F U 3 2 4 8
2 L2
3
5 (X1) SEC
2 4
10
(5)
VIB. SW.
START M
3
10
OL 6
TS
Connection Diagram Notes 1 Disconnecting means provided with controller. 2 Input Voltage Primary Connections per Transformer Nameplate. 3 Customers Remote Located Equipment Field wiring by others
25
AC Combination Starter
120V Single Phase, Single Speed
L1
L2
L1 1
T1
MOTOR 2 M T2
1 L2
TB 1 1 2 2 3 5 7 8 1 L1 4 2 VIB. SW. 1 2 L2
TS
(1)
(3)
4 (7)
START
OL
M 3 TS
5 (5)
1 2
ALARM OL
8 6 T2 1 ALARM 8
T1
MOTOR
Connection Diagram Notes 1 Disconnecting means provided with controller. 2 Customers Remote Located Equipment Field wiring by others
26
AC Combination Starter
3 Phase, Two Speed, One Winding
9 (65)
(66) (31) (43)
L1
L2
L3
(13) (21)
(58)
15
(14) (22) (A1) TB 5 5 5 6 6 7 9 14 16 17 18
TR
12
(A2) (32) (44) FU2
(H1)
4 19
FU3 FU1
PRI
4 CPT
2 6
1 1 L1 2 L2 L3
15
12
11
11
12
14
10
15
17 HOL 13
ALARM
6 18 LOL 12 13
LI
Connection Diagram Notes 1 Disconnecting means provided with controller. 2 Input Voltage Primary Connections per Transformer Nameplate. 3 Customers Remote Located Equipment Field wiring by others
T6
L2
L3
LI
T4
T5
T1
L2
L3
T2
T3
TO MOTOR
Connection Diagram
See page 26 for Elementary Diagram.
27
AC Combination Starter
3 Phase, Two Speed, One Winding
L1 L2 14 L3
1
L L HOL
H H
LOL
T1 T2 T3 T6 T4 T5 MOTOR
F U 2 3 (H1) PRI
2
H H
BULB SENSOR
(X1) SEC
BLUE
9 (6)
VIB. SW.
HIGH
LOW X
(9)
TR 10 H 11
12
LOL HOL 13
X
3
14 (14)
3
15
18
LOW ALARM
Elementary Diagram
See Page 25 for Connection Diagram.
L1 T1 T6
L2 T2 T4
L3 T3 T5
28
AC Combination Starter
3 Phase, Two Speed, Two Winding
TIME DELAY RELAY (57) 9 (65) (66) (31) (43) 12 (A2) (32) (44) 3
2 1
(13) (21)
(58) 15
L1
L2
L3
TR
TB 5 5 5 6 6 7 9 14 16 17 18 1 L1
3 4 19
1 2 6
(H1)
PRI
4 CPT
1 2 L2 L3
15
12
11
11
12
14
10
15
17 HOL 13 L2 L3
6 18 LOL 12 13 LI
POWER TERMINAL BLOCK
LI
Connection Diagram Notes 1 Disconnecting means provided with controller. 2 Input Voltage Primary Connections per Transformer Nameplate. 3 Customers Remote Located Equipment Field wiring by others
T11
L2
L3
T12
T13
T1
T2
T3
TO MOTOR
Connection Diagram
See Page 28 for Elementary Diagram.
29
AC Combination Starter
3 Phase, Two Speed, Two Winding
L1 L2 14 L3
1
L L HOL
LOL
T1 T2 T3 MOTOR
F U 2 3 (H1) PRI
2
H H
BULB SENSOR
(X1) SEC
BLUE
9 (6)
VIB. SW.
HIGH
LOW X
(9)
TR 10 H 11
12
LOL HOL 13
X
3
(14)
3
14
15
18
LOW ALARM
Elementary Diagram
See Page 27 for Connection Diagram.
L1 T1 T11
L2 T2 T12
L3 T3 T13
30
31
Parts Schematic
Single Speed, Single Phase
3 1 6
9 8 2
32
Parts List
1/3 hp through 3/4 hp, Single Speed, 120V and 230V, Single Phase
Item Description
1 2 3 4 5 6 7 8 9 Contact Kit Melting Alloy Overload Contact Unit with Alarm Circuit Magnet Coil (Starter) Fuse Clips (for 250V and 0-30 Amps) Transformer (Transformer not included on 120V systems) Terminal Blocks Fuse Blocks (not included on 120V systems) H-O-A Selector Switch Contact Blocks (for Selector Switch) 1 1 A74955 A74956 6 A74952
Quan.
1
Part No.
A74930
1 1 1
33
Parts Schematic
Single Speed, Three Phase
3 1 6
9 8 2
34
Parts List
1/3 hp through 3/4 hp, Single Speed, 208V, 230V and 460V, Three Phase
Item Description
1 2 Contact Kit Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 4 5 6 7 8 9 Magnet Coil (Starter) Fuse Clips (for 250V and 0-30 Amps) Transformer 240 or 480 Volts 208 Volts Terminal Blocks Fuse Blocks H-O-A Selector Switch Contact Blocks (for Selector Switch) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
1
Part No.
A74930
1 1 6 2 1 1
35
Parts List
1 hp through 7 1/2 hp, 208V, Single Speed 1 hp through 10 hp, 240V, Single Speed 1 hp through 15 hp, 480V, Single Speed
Item Description
1 2 Contact Kit Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 4 5 6 7 8 9 Magnet Coil (Starter) Fuse Clips (250V and 0-30 Amps) (600V and 0-30 Amps) (250V and 31-60 Amps) Transformer (240 or 480 Volts) (208 Volts) Terminal Blocks Fuse Blocks H-O-A Selector Switch Contact Blocks (for Selector Switch) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
1
Part No.
A74931
1 1 1
1 1 6 2 1 1
36
Parts List
10 hp, 15 hp, and 20 hp, 208V, Single Speed 15 hp and 20 hp, 240V, Single Speed 20 hp, 25 hp, and 30 hp, 480V, Single Speed
Item Description
1 2 Contact Kit Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 4 5 6 7 8 9 Magnet Coil (Starter) Fuse Clips (600V and 0-30 Amps) (250V and 31-60 Amps) (600V and 31-60 Amps) Transformer (240 or 480 Volts) (208 Volts) Terminal Blocks Fuse Blocks H-O-A Selector Switch Contact Blocks (for Selector Switch) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
1
Part No.
A74932
1 1 1
1 1 6 2 1 1
37
Parts List
25 hp, 208V, Single Speed 25 hp and 30 hp, 240V, Single Speed 40 hp through 100 hp, 480V, Single Speed
Item Description
1 2 Contact Kit Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 4 5 6 7 8 9 Magnet Coil (Starter) Fuse Clips (250V and 61-200 Amps) (600V and 200 Amps) Transformer (240 or 480 Volts) (208 Volts) Terminal Blocks Fuse Blocks H-O-A Selector Switch Contact Blocks (for Selector Switch) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
1
Part No.
A74933
1 1
A74943 A74943
1 1 6 2 1 1
38
39
Parts Schematic
Two Speed
10
5 6
7 3 1 13 11
12 13 2
40
Parts List
1 hp through 3 hp, 208V, Two Speed 1 hp through 3 hp, 240V, Two Speed 1 hp through 5 hp, 460V, Two Speed
Item Description
1 Contact Kit 2 Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 Magnet Coil (Starter) 4 Pneumatic Timing Relay, 120V, 60Hz 5 Magnet Coil (Timing Relay) 6 Snap Switch (Timing Relay) 7 Fuse Clips (250V and 0-30 Amps) (600V and 0-30 Amps) (250V and 31-60 Amps) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
2
Part No.
A74930
C00683 C00682 B56497 B56498 B56499 B56500 B56501 2 1 1 1 A74936 A74958 A74959 A74960
1 1 1
8 Transformer (240 or 480 Volts) (208 Volts) 1 1 9 2 1 1 2 A74946 A74947 A74952 A74953 A74961 A74955 A74956
9 Terminal Blocks 10 Fuse Blocks 11 High/Low Selector Switch 12 H-O-A Selector Switch 13 Contact Blocks (for Selector Switch)
41
Parts List
5 hp and 7 1/2 hp, 208V, Two Speed 5 hp and 7 1/2 hp, 240V, Two Speed 7 1/2 hp and 10 hp, 480V, Two Speed
Item Description
1 Contact Kit 2 Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 Magnet Coil (Starter) 4 Pneumatic Timing Relay, 120V, 60Hz 5 Magnet Coil (Timing Relay) 6 Snap Switch (Timing Relay) 7 Fuse Clips (250V and 0-30 Amps) (600V and 0-30 Amps) (250V and 31-60 Amps) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
2
Part No.
A74931
C00683 C00682 B56497 B56498 B56499 B56500 B56501 2 1 1 1 A74936 A74958 A74959 A74960
1 1 1
8 Transformer (240 or 480 Volts) (208 Volts) 1 1 9 2 1 1 2 A74946 A74947 A74952 A74953 A74961 A74955 A74956
9 Terminal Blocks 10 Fuse Blocks 11 High/Low Selector Switch 12 H-O-A Selector Switch 13 Contact Blocks (for Selector Switch)
42
Parts List
10 hp, 208V, Two Speed 10 hp and 15 hp, 240V, Two Speed 15 hp, 20 hp and 25 hp, 480V, Two Speed
Item Description
1 Contact Kit 2 Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 Magnet Coil (Starter) 4 Pneumatic Timing Relay, 120 V, 60 Hz 5 Magnet Coil (Timing Relay) 6 Snap Switch (Timing Relay) 7 Fuse Clips (250V, 31-60 Amps; 600V, 0-30 Amps) (600V and 31-60 Amps) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
2
Part No.
A74932
C00683 C00682 B56497 B56498 B56499 B56500 B56501 2 1 1 1 A74937 A74958 A74959 A74960
1 1
A74941 A74942
8 Transformer (240 or 480 Volts) (208 Volts) 1 1 9 2 1 1 2 A74946 A74947 A74952 A74953 A74961 A74955 A74956
9 Terminal Blocks 10 Fuse Blocks 11 High/Low Selector Switch 12 H-O-A Selector Switch 13 Contact Blocks (For Selector Switch)
43
Parts List
15 hp, 20 hp and 25 hp, 208V Two Speed 20 hp, 25 hp and 30 hp, 240V Two Speed 30 hp, 40 hp and 50 hp, 480V Two Speed
IItem Description
1 Contact Kit 2 Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 Magnet Coil (Starter) 4 Pneumatic Timing Relay, 120 V, 60 Hz 5 Magnet Coil (Timing Relay) 6 Snap Switch (Timing Relay) 7 Fuse Clips (250V, 61-200 Amps) (600V, 61-200 Amps) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
2
Part No.
A74933
C00683 C00682 B56497 B56498 B56499 B56500 B56501 2 1 1 1 A74938 A74958 A74959 A74960
1 1
A74943 A74943
8 Transformer (240 or 480 Volts) (208 Volts) 1 1 9 2 1 1 2 A74950 A74951 A74952 A74953 A74961 A74955 A74956
9 Terminal Blocks 10 Fuse Blocks 11 High/Low Selector Switch 12 H-O-A Selector Switch 13 Contact Blocks (For Selector Switch)
44
Parts List
30 hp and 40 hp, 208V Two Speed 40 hp and 50 hp, 240V Two Speed 60 hp, 75 hp and 100 hp, 480V Two Speed
IItem Description
1 Contact Kit 2 Solid State Overload Relay (SQ. D Number) Type SFB20 Type SSC20 Type SS020 Type SS120 Type SS220 Type SS320 Type SS420 3 Magnet Coil (Starter) 4 Pneumatic Timing Relay, 120V, 60 Hz 5 Magnet Coil (Timing Relay) 6 Snap Switch (Timing Relay) 7 Fuse Clips (250V, 61-200 Amps) (600V, 61-200 Amps) FLA 1.5A-4.5A FLA 3A-9A FLA 6A-18A FLA 9A-27A FLA 15A-45A FLA 30A-90A FLA 45A-135A
Quan.
2
Part No.
A74934
C00683 C00682 B56497 B56498 B56499 B56500 B56501 2 1 1 1 A74939 A74958 A74959 A74960
1 1
A74943 A74943
8 Transformer (240 or 480 Volts) (208 Volts) 1 1 9 2 1 1 2 A74950 A74951 A74952 A74953 A74961 A74955 A74956
9 Terminal Blocks 10 Fuse Blocks 11 High/Low Selector Switch 12 H-O-A Selector Switch 13 Contact Blocks (For Selector Switch)
45
Troubleshooting Guide
Fan Does Not Start Power disconnected. Fuses blown. Overloads tripped. Vibration switch tripped or jumper wire missing
Nuisance Tripping
Sustained overload. Check for equipment grounds or shorts. Check motor winding resistance, fan pitch, drive reduction ratios, air ow restrictions on tower fans and tower loading. Loose connections. Excessive motor cycling. Increase temperature differential until a maximum of ve starts per hour is achieved on the fanmotor.
Contact Chatter
Contact Welding
Abnormal inrush of current. Check for grounds, shorts or excessive overload currents. Insufficient tip pressure. Replace contact springs. Low voltage preventing magnet from sealing. Chattering contacts.
Filing or dressing. Excessive cycling of fan motor. Increase temperature differential on temperature switch. Weak contact pressure. Replace contact spring. Short circuits. Loose connections.
46
Troubleshooting Guide
Cooked Coil Sustained overload. Overvoltage or undervoltage condition. Mechanical damage resulting in shorted turns. Dirt or rust on pole faces increasing air gap. Loose connections in control circuit. Intermittent supply voltage causing chattering. Transient voltage spikes.
47
7401 WEST 129 STREET | OVERLAND PARK, KANSAS 66213 UNITED STATES | 913 664 7400 | spxcooling@spx.com | spxcooling.com
In the interest of technological progress, all products are subject to design and/or material change without notice. 2010 SPX Cooling Technologies, Inc. | Printed in USA
Manual 92-1320E