Power System Problem
Power System Problem
Calano
Problem 1
The 3-phase loads are connected in parallel. One is a purely resistive load connected in wye. It consumes 300kW. The second is a purely inductive 300kVAR load connected in wye. The third is a purely capacitive 300kVAR load connected in wye. The line-to-line voltage at the load is 5kV. A 3-phase distribution line supplying this load has an impedance of 10+j5 ohms per phase. (a) Calculate the currents drawn by each load (magnitude and phase). (b) Indicate the power factor of each load. Remember that non-unity power factors must also include whether they are lagging or leading. (c) What is the power factor of the entire load? That is, what is the power factor seen by the transmission line at the load end? (d) Calculate the real and reactive power supplied at the sending end of the distribution line.
Solution to problem 1
10 + j 5
VLN = 2886.8V
VS
I1
I2
I3
(a)
VLoad =
Note that:
5kV = 2886.80 3
S S S = V I I = , S = 3 3 V
Therefore:
S1 = 100 10 3 W , S 2 = j100 10 3 VAR, S 3 = j100 10 3 VAR.
S1 100 103 I1 = = 2886.8 = 34.640 A VLoad S2 j100 103 I2 = V = 2886.8 = 34.64 90 A Load
S3 I3 = VLoad
Note in the above that for the resistive load, the current and voltage are in phase, for the inductive, the current lags by 90 deg, and for the capacitive, the current leads by 90 deg. (b) Load 1 : pf 1 = 1.0 Load 2 : pf 2 = 0 lagging Load 3 : pf 3 = 0 leading (c) Need current angle with respect to
I Load
so
(d)
Vs = VLoad + I Load (Z t ) = 2886.8 + (34.640) (10 + j 5) = 3237.83.07 S3 = 3Vs I Load = 3 (3237.83.07) (34.640) = 336,4723.07VA
P3 = 335.99kW , Q3 = 18.02kVAR
A three phase load has a per phase impedance, connected in Y, of 100 + j 30 . The line-to-line voltage magnitude at the load is 1500V. The three-phase distribution line supplying this load has an impedance of 10 + j 5 / . (a) Calculate the line-to-line voltage magnitude at the sending end of the distribution line. (b) Calculate the real and reactive power supplied at the sending end of the distribution line.
Problem 2
Solution to problem 2
(a)
V AN =
Vsending ,AN = V AN + I A Z Line = 866.0250 + (8.295 16.7) (10 + j 5) = 957.39 + j15.89 = 957.530.95V VSending ,AB = 957.53 3 = 1658.5V
(b) S = 3 V sending , AN I a = 3 (957.530.95 ) (8.29516.7 ) = 22 ,706.5 + j 7224.7VA
P = 22.706kW , Q = 7.225kVAR
Problem 3
A three-phase load consumes 100kVA at 0.7 pf lagging. The line-to-line voltage magnitude at the load is 1500V. The three-phase distribution line supplying this load has an impedance of 10 + j5 / (a) Calculate the line-to-line voltage magnitude at the sending end of the distribution line. (b) Calculate the real and reactive power supplied at the sending end of the distribution line.
Solution to problem 3
(a) Note that =cos-1(0.7)=45.57 deg (the angle is positive because the pf is lagging), and sin(45.7)=0.714.
S1 33.3 10 3 (0.7 j 0.714 ) IL = = 38.45 45.57 A V = 866.025 an Vsending ,an = Van + I L Z L = 866.0250 + 38.45 45.57 (10 + j 5) = 1279.2 6.211 Vsending ,AB = 3 1279.2 = 2215.3V
(b)
Problem 4
The complex power absorbed by a three-phase load is 1500kVA at 0.8 pf lag
P/ =
Q/ =
If the Line voltage at the load in problem 1 is 8660.2540 V, what is the voltage magnitude across each phase of the load, if the load is connected as follows,
Vd =
What is the magnitude of line current drawn by this load?
Vy =
IL =
Solution to problem 4 The complex power absorbed by a three-phase load is 1500kVA at 0.8 pf lag
Note that =cos-1(0.8)=36.87 deg (the angle is positive because the pf is lagging), and sin(36.87)=0.6. Then P1=1500(0.8)/3=400 kW, Q1=1500(0.6)/3=300 kW.
P1 = 400 kW
Q/ = 300 kVAR
If the Line voltage at the load in problem 1 is 8660.2540 V, what is the voltage magnitude across each phase of the load, if the load is connected as follows,
V = 8660.254 V
V y = 5000 V=
8660.254 3
Problem 5
In the circuit shown below, Van = 12,000 + j 0 V (rms). Assume positive phase sequence. The balanced source supplies 1.5 MW and 0.3 MVAR to the three phase balanced load. Find: a) The rms line current. b) Z p
Aa
15
VAB
ZP
VCA
BC
+
C
+V
ZP
1 S1 = ( 1.5 + j 0.3 )* 106VA 3 * * Van I an = S1 = 12 ,000 I an ( 1.5 + j 0.3 )x106 * = 42.49211.31o A I an = 3 12 ,000 I an = 42.492 11.31o A
(b) Z p = 3Z py
Z py =
Van I aA
Problem 6
A three phase source is supplying a balanced three phase load over a transmission line having impedance of ZL=2+j20 ohms per phase. The voltage at the source end of the transmission line is 2887 0 volts line to neutral. The current supplied through the transmission line is IL=100 -30 amperes. 1. Determine the power factor seen by the source, and specify whether it is leading or lagging. 2. Determine the voltage (line to neutral) at the load. 3. Determine the power factor of the load, and specify whether the load is a. leading or lagging b. inductive or capacitive 4. Determine the real and reactive power consumed by the load.
Solution to problem 6
1. 2. 3. pf=cos(30)=0.8660, and it is lagging. VLOAD=28870-100-30(2+j20)=713.8-j1632=2366.5-43.6 pf angle=angle at which voltage leads the current=-43.6-(-30)=-13.6, so pf=cos(-13.6)=0.972, and the current is leading the voltage! This means the power factor is leading (part a) and the load must be capacitive (part b). S=3VLOAD (I)*=3(2366.5-43.6)(100+30)=690044-j166939=709.950-13.6 kVA
4.
Problem 7
A balanced, three-phase load having a power factor of 0.8 lagging is supplied by a transmission line carrying 300 amps at 115 kV line-to-line. Compute the three-phase real and reactive power delivered to the load.
Solution to problem 7
S 3 = 3 V LL I =
Problem 8
A balanced, three-phase, delta-connected load consumes 50-j20 kVA at a line-to-line voltage of 13.8 kV. Compute the per-phase impedance of this load assuming a series connection between R and X.
Solution to problem 8
VLL VLL ( 13.8 10 3 )2 S= * Z = * = = 3283 j1313 3 Z S ( 50 + j 20 ) 10 Z = 3 Z Y Z = 3 ( 3283 j1313 ) = 9849 j 3939 R = 9849 X = 3939( Capacitive )
Problem 9
A three-phase wye-connected load having impedance of Z1=200+j50 ohms per phase is connected in parallel with a three phase delta-connected load having impedance of Z2=600+j300 ohms per phase. The load is supplied by a three-phase wye-connected generator that is directly interconnected with the loads (i.e., there is no transmission line between the generator and the loads). The voltage magnitude of the generator is 13.8 kV line-to-line. Assume that the phase to neutral voltage at the generator is the angle reference. 1. Draw the three-phase circuit. Clearly identify the numerical values of one line to neutral source voltage phasor and one-phase impedance for each of loads 1 and 2. 2. Draw the per-phase circuit. Clearly identify the numerical values of the source voltage phasor and the per-phase impedances of loads 1 and 2. 3. Compute the three-phase complex power consumed by each load and the total, complex three-phase power consumed by the two loads. 4. Show that the total, complex three-phase power consumed by the two loads can be computed using the line current and the line-to-line value of the source voltage.
Solution to problem 9
1. VAN= 7967v Z1=200+j50 Z2=600+j300
2. Z1=200+j50 Z2=200+j100
VAN= 7967v
3.
We could use S1 =3|VAN|2/Z1* , S2 = 3|VAN|2/Z2* , or we could get the current instead. Lets do it by getting the current. I1=VAN/Z1=7967/(200+j50)= 37.4918 - j9.3729, S1=3VAN(I1)*=3(7967)( 37.4918 + j9.3729)= (896.09 +j224.02)kva P1=896.1 kW, Q1=224.0 kVAR I2=VAN/Z2=7967/(200+j100)= 31.8680 -j15.9340 S2=3VAN(I2)*=3(7967)(31.8680 +j15.9340)= (761.68e+j380.84)kva P2=761.7 kW, Q2=380.8 kVAR STotal=S1+S2=1657.8+j604.86 PTotal=1657.8 kW, QTotal=604.9 kVAR IT=I1+I2= 69.3598 -j25.3069= 73.83 -20.05, |VLine|=13,800 STotal=(3)(13,800)(73.83){cos(20.05)+jsin(20.05)}= 1657.8+j604.9
4.
Consider a balanced three-phase source supplying a balanced Y- or - connected load with the following instantaneous voltages and currents.
Problem 10
where |Vp| and |Ip| are the magnitudes of the rms phase voltage and current, respectively. Show that the total instantaneous power provided to the load, as the sum of the instantaneous powers of each phase, is a constant.
Consider a balanced three-phase source supplying a balanced Y- or - connected load with the following instantaneous voltages
v an = 2 V p cos( t + v )
ia = 2 I p cos( t + i )
(2.41)
where
V p and I p are the magnitudes of the rms phase voltage and current, respectively. The total p3 = v an ia + vbn ib + vcn ic
instantaneous power is the sum of the instantaneous power of each phase, given by Substituting for the instantaneous voltages and currents
( cos( t +
) ( 240 )cos( t +
o
) 240 )
o
p3 = V p I p [cos( v i ) + cos(2 t + v + i )] + Vp I p
[ [cos(
i ) + cos(2 t + v + i
] 480 )]
o
The three double frequency cosine terms are out of phase with each other by 120 and add up to zero, and the three-phase instantaneous power is
p3 = 3 V p I p cos
= v i
is the angle between phase voltage and phase current or the impedance angle.
Problem 11
A three-phase line has an impedance of 2+j4 ohms/phase, and the line feeds two balanced three-phase loads that are connected in parallel. The first load is Y-connected and has an impedance of 30+j40 ohms/phase. The second load is delta-connected and has an impedance of 60-j45 ohms/phase. The line is energized at the sending end from a three-phase balanced supply of line voltage 207.85 volts. Taking the phase voltage Va as reference, determine: a. The current, real power, and reactive power drawn from the supply. b. The line voltage at the combined loads. c. The current per phase in each load. d. The total real and reactive powers in each load and the line.
(a) The -connected load is transformed into an equivalent Y. The impedance per phase of the equivalent Y is
Z2 = V1 =
Z = 2 + j4 +
= 2 + j 4 + 22 j 4 = 24 with the phase voltage Van as reference, the current in phase a is V1 1200 o = =5A I= 24 Z
The three-phase power supplied is
(c) The current per phase in the Y-connected load and in the equivalent Y of the load is
V2 110 j 20 = 1 j 2 = 2.236 63.4 o A = 30 + j 40 Z1 V 110 j 20 = 4 + j 2 = 4.47226.56 o A I2 = 2 = 20 j15 Z2 The phase current in the original -connected load, i.e., I ab is given by
I ab =
I2 3 30
o
4.47226.56 o 3 30
o
= 2.58256.56 o A
S1 = 3V2 I 1* = 3(111.8 10.3o )(2.23663.4 o ) = 450 W + j 600 var * S 2 = 3V2 I 2 = 3(111.8 10.3o )(4.472 26.56 o ) = 1200 W - j 900 var
S L = 3(RL + jX L ) I
It is clear that the sum of load powers and line losses is equal to the power delivered from the supply, i.e.,
Problem 12
A three-phase line has an impedance of 0.4+j2.7 ohms per phase. The line feeds two balanced three-phase loads that are connected in parallel. The first load is absorbing 560.1kVA at 0.707 power factor lagging. The second load absorbs 132 kW at unity power factor. The line-to-line voltage at the load end of the line is 3810.5 volts. Determine: a. The magnitude of the line voltage at the source end of the line. b. Total real and reactive power loss in the line. c. Real power and reactive power supplied at the sending end of the line.
V2 =
3810.5 3
= 2200 V
I=
* SR (3 )
3V2*
The magnitude of the line voltage at the sending end of the line is (b) The three-phase power loss in the line is
S L (3 ) = 3R I + j 3 X I
(c) The three-phase sending power is
= 12 kW + j81 kvar
S S (3 ) = 3V1 I * = 3 2401.74.58 o 10036.87 o = 540 kW + j 477 kvar
It is clear that the sum of load powers and the line losses is equal to the power delivered from the supply, i.e.,
)(