T 1000 PLUS: Secondary Injection Relay Test Set
T 1000 PLUS: Secondary Injection Relay Test Set
T 1000 PLUS: Secondary Injection Relay Test Set
Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory High power outputs Oscilloscope function for current and voltage Large graphical display Compact and lightweight Possibility to synchronize several T 1000 PLUS test sets USB interface 2 auxiliary contacts for the test of autoreclosers
The relay test set T 1000 PLUS is suited for the testing of the following types of relays:
RELAY TYPE
Distance relay (3 sets) Synchronizing device Thermal Under/over-voltage relay Directional Power relay Undercorrent Negative sequence over-currrent Phase sequence voltage relay Incomplete sequence relay Definite time over-current relay Inverse time over-current relay Power factor relay Voltage balance relay Ground detector relay Directional over-current relay Directional earth fault Automatic reclosing Frequency relay Load shed Pilot wire receiver relay Motor protection Differential protection relay (TD 1000) Voltage directional relay Tripping relay
IEEE NO
21 25 26 27/59 32/92 37 46 47 48 50/50N 51/51N 55 60 64 67 67N 79 81>/81< 81R 85 86 87 91 94
T 1000 PLUS
The instrument contains three separate generators: . Main generator, that generates either AC current, AC voltage; DC voltage; . Auxiliary AC voltage generator, that generates an independent, phase shiftable AC voltage; . Auxiliary DC voltage generator, that generates the DC voltage that powers the relay under test. All outputs are adjustable and metered at the same time on the large, graphic LCD display. T 1000 PLUS can operate without connection to a PC. With the multi-purpose knob and the LCD display it is possible to enter the MENU mode, that allows to set many functions, that make T 1000 PLUS a very powerful testing device, with manual and semi-automatic testing capabilities, and with the possibility to transfer test results to a PC via USB interface. These results can be recorded, displayed and analysed by the powerful TDMS software, that operates with all WINDOWS versions, starting from WINDOWS 98 included.
DC voltage outputs RANGE VOLTAGE V OUTPUT DC V 300 300 300 MAXIMUM POWER W 300 500 LOAD TIME s steady 10 RECOVERY TIME min 45
40 10
T 1000 PLUS
Voltage measurement OUTPUT 250 V AC RANGE RESOLUTION 10 100 300 10 100 300 10 100 10 100 300 10 100 10 100 300 mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV mV ACCURACY (1% + 50 mV) (1% + 200 mV) (1% + 300 mV) (0.5% + 50 mV) (0.5% + 200 mV) (0.5% + 300 mV) (1% + 20 mV) (1% + 200 mV) (1% + 20 mV) (1% + 200 mV) (1% + 300 mV) (0.5% + 20 mV) (0.5% + 200 mV) (0.5% + 20 mV) (0.5% + 200 mV) (0.5% + 300 mV)
Timer
The electronic digital timer has a fully automatic start and stop, both for make and break of the input, that can be either a clean (dry) contact or a contact under voltage (wet). . Metering range, can also be performed in cycles. . Possibility to test automatic reclosers. . Maximum number of reclosing commands: 99.
RANGE From 0 to 9.999 s From 10.0 to 99.99 s From 100.0 to 999.9 s From 1.000 to 9.999 s
RESOLUTION 1 ms 10 ms 100 ms 1s
19.99 V 199.9 V 299.9 V 300 V DC 19.99 V 199.9 V 399.9 V 65,130 V AC 19.99 V 199.9 V 260 V AC 19.99 V 199.9 V 299.9 V 130 V DC 19.99 V 199.9 V 260 V DC 19.99 V 199.9 V 299.9 V
Other measurements
MEASUREMENT Active Power, P = I*V*cos (j) Reactive Power, Q = I*V*sin(j) Apparent Power, S = I*V Impedance, Z = V/I Active Impedance Component, R = Z* cos(j) Reactive Impedance Component, X = Z* sin(j) UNIT W VAr VA Ohm, Ohm Ohm
T 1000 PLUS
. Range, resolution, accuracy: see table below. INPUT 20 mA 10 A 10 A 10 A 10 A RANGE 0.02 A DC 1.999 A AC 9.99 A AC 1.999 A DC 9.99 A DC RESOLUTION 0.1 1 10 1 10 mA mA mA mA mA ACCURACY (0.5% + 0.1 mA) (1% + 2 mA) (1% + 20 mA) (0.5% + 2 mA) (0.5% + 20 mA)
Power supply
. Mains supply to be clearly indicated in purchase order: 230 V 15% 50-60 Hz or 120 V 15%50-60 Hz . Maximum supply current: 5 A.
Standard accessories
The instrument comes complete with the following items: . Set of standard test cables; . Mains cable; . USB cable; . Users manual; . Spare fuses (no. 5), T5A. . Software TDMS with serial cable.
OTHER CHARACTERISTICS
T 1000 PLUS local memory
. Test settings can be stored and recalled from the T 1000 PLUS local memory: up to 10 test settings. . Test results can be saved into a permanent local memory: up to 500 test results saved. . When the PC is connected setting can also be created and transferred into T 1000 PLUS using the software TDMS. . When the PC is connected test results can be transferred to the PC via USB port using the software TDMS, for saving and printing.
Resistors
A set of resistors is supplied for the test of low impedance relays. Available values: RESISTANCE OHM 0,5 1 22 470 1000 2200 POWER W 50 50 50 50 50 50 MAX CURRENT A 10 7 2.15 0.33 0.22 0.15
Case
Alluminium case with cover and handle.
Interface
. Interfaces for connection to PC: USB.
4
T 1000 PLUS
TD 1000 PLUS
With two current outputs to test differential relay
TD 1000 PLUS 15 HZ
With two current outputs to test differential relay and with high power at 15 Hz
TD 1000 Plus 15 Hz is identical to TD 1000 Plus except for the high power and full range at 15 Hz. This allows testing old railway and generator protection relays. TD 1000 Plus 15 Hz does NOT have the DC battery simulator.
TD 1000 Plus has two current outputs to test differential relay characteristic curve and not only the pick-up current. In addition, the frequency of this current can be changed as with voltages: this allows to test the second harmonic restraint characteristic of the differential relay. Last, the steady voltage output power is increased from 30 VA to 50 VA. . Auxiliary AC voltage. Power: 40 VA, continuous duty, at full range; 50 VA for 1 minute. For lower voltages the limiting current is the following. . Power at 15 Hz: 25 VA on all ranges. . No Auxiliary DC voltage supply. . Weight: 21 kg. All other performances are the same as T 1000 Plus. The request of this model must be specified at order.
MAX CURRENT A 20
VOLTAGE V 3
All other performances are the same as T 1000 Plus. The request of this model must be specified at order.
T 1000 PLUS
T 1000-E PLUS
Higher AC voltage outputs
In this model, AC voltage outputs are higher than in the standard version. . Main AC voltage output. . Auxiliary AC voltage. Power: 30 VA, continuous duty, at full range; 40 VA for 1 minute. For lower voltages the limiting current is the following. RANGE V 65 130 500 MAX CURRENT mA 500 250 62
T 1000 PLUS - Standard cable kit
All other performances are the same. The request of this model must be specified at order.
OPTIONS
Heavy duty transport case
Heavy duty transport case in black plastics, with wheels, cover and handle.
Connection cables
The kit includes cables for any kind of connection.
T 1000 PLUS
APPLICABLE STANDARDS
The test set conforms to the EEC directives regarding Electromagnetic Compatibility and Low Voltage instruments. A) Electromagnetic Compatibility: Directive no. 2004/108/EC B) Low Voltage Directive: Directive n. 2006/95/EC. Applicable standards, for a class I instrument, pollution degree 2, Installation category II: . CEI EN 61010-1. In particular: . Inputs/outputs protection: IP 2X - CEI 70-1. . Operating temperature: 0 to 50C; storage: -40C to 70C. . Relative humidity: 10 - 80% without condensing.
T 1000 PLUS
ORDERING INFORMATION
CODE 91093 81093 94093 96093 93093 MODULE T 1000 PLUS complete with Software TDMS and standard set of cables - 230V T 1000 PLUS complete with Software TDMS and standard set of cables - 120V TD 1000 PLUS complete with Software TDMS and standard set of cables - 230V TD 1000 PLUS complete with Software TDMS and standard set of cables - 120V TD 1000 PLUS 15 Hz complete with Software TDMS and standard set of cables 230V TD 1000 PLUS 15 Hz complete with Software TDMS and standard set of cables 120V T 1000-E PLUS (500V Aux Voltage outputs) complete with Software TDMS and standard set of cables- 230 V CODE 17093 18093 MODULE Heavy Duty Transport Case Set of additional test cables for models T 1000 PLUS / T 1000-E PLUS / TD 1000 PLUS D 1000 differential relay test module FT 1000 Mains Filter Unit SHA 1000 scanning head Outputs transducer with interface connector and cables Connection cable and RJ-45 connector for ABB relays (REF542PLUS and REF601) Connection cable for THYTRONIC relays (Thysensor series)
95093
92093
T 1000 PLUS / T 1000-E PLUS / TD 1000 PLUS FAMILY - FEATURES COMPARISON TABLE MAIN I AC MAX A
T 1000 Plus 120 V T 1000 Plus 230 V T 1000- E Plus TD 1000 Plus 120 V TD 1000 Plus 230 V TD 1000 Plus 15 Hz 120 V TD 1000 Plus 15 Hz 230 V 160 250 250 160 250 160 250
MAIN V AC MAX V
250 250 500 250 250 250 250
MAIN V DC MAX V
300 300 300 300 300 300 300
AUX V AC MAX V
250 250 500 250 250 250 250
AUX I AC
20 20 20 20
AUX V DC MAX V
240 240 240 240 240 -