HERIC
HERIC
HERIC
e
e
=
t u t t u t
u t t u t
ZCD ZCD
ZCD ZCD
x x
x
x d
(1)
In this equation,
ZCD
is the zero-crossings distortions
notch angle.
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
Tarak Salmi et al., Vol.2, No.1, 2012
142
Fourier analysis of this wave form is used to find the
coefficients (a
n
and b
n
) and the harmonics that cause the
electromagnetic emission and interference by the inverter,
and to design the proper filter [14].
( ) ( )
( )
=
=
|
|
.
|
\
|
+
+
+
=
1 n for , 1 2 cos
2
1
3,5,7,... n for ,
1
1 cos
1
1 cos
1
1
1
1 1
ZCD
ZCD ZCD
n
n
n
n
n
n n
a
u
t
u u
t
(2)
and
( ) ( )
( )
=
=
|
|
.
|
\
|
+
+
=
1 n for ,
2
1
3,5,7,... n for ,
1
ZCD
sin2
ZCD
2
1 n
ZCD
1 n cos
1 n
ZCD
1 n sin
b
n
t
t
(3)
The magnitude Mn of the n
th
order harmonic defined in (4) is
a function of the harmonics number n and the zero-crossing
angle
ZCD.
2 2
n n n
b a M + =
(4)
The zero-crossings distortions create inductor-voltage
spikes. These spikes are produced because of the sudden
change in the current during the zero-crossing period. For
sensitive power semiconductor devices, excessive current
can flow if the voltage spikes exceed the breakdown voltage
of the semiconductor devices.
This zero crossings distortions are due to many
phenomena, one of which is the coincidence of the switching
frequency with the filter resonance frequency [18]. However,
the control strategy of the inverter is the main source of such
distortions.
So far, different topologies were discussed in light of the
issues associated with the reviewed topologies such as
leakage current and zero-crossings distortions.
The HERIC topology that has many features will be used
as a reference hereafter. Therefore; the following section
presents a detailed study and simulation of the HERIC
inverter.
4. HERIC Transformerless Inverter Topology
4.1. HERIC topology Common Mode Current
For the HERIC topology, shown in Fig.1, the common-
mode voltage (v
cm
) and current (i
cm
) through the capacitance
CGPV between the photovoltaic array and earth are:
2
BO AO
cm
v v
v
+
=
(5)
And
dt
cm
GPV cm
dv
C i =
(6)
Voltages v
AO
and v
BO
are controlled by the four switches
(S
1
throughS
4
).
Fig.1. HERIC topology.
When the upper switch S
1
or S
3
is ON, the corresponding
voltage is v
IN
. However, when the lower switch S
2
or S
4
is
ON, the corresponding voltage is zero. During the positive
half wave, S
6
is turned ON and is used in the freewheeling
period of S
1
and S
4
. When both S
1
and S
4
are ON, v
AO
=v
IN
and v
BO
=0. Therefore, the applied common mode voltage is:
2
IN
cm
v
v =
(7)
Table 1. Exhibits the switching principle of the HERIC
inverter topology and shows that vcm is always constant.
Vector N P i
grid
<0 i
grid
>0
S1 OFF OFF OFF OFF
S2 ON OFF OFF OFF
S3 ON OFF OFF OFF
S4 OFF ON OFF OFF
S5 OFF OFF ON OFF
S6 OFF OFF OFF ON
v
AO
0 VIN NA
*
NA
*
v
BO
v
IN
0 NA
*
NA
*
v
cm
v
IN
v
IN
v
IN
v
IN
*Not Applicable (NA)
Therefore, according to equation 2, the common mode
current i
cm
is zero.
The performance of the HERIC inverter in terms of icm
and icm was simulated using non ideal power electronic
devices and the results are shown in Fig. 2.
It is clear that the common mode voltage is small and the
leakage current is low. However, if the switching actions
take place simultaneously, then the common mode voltage
would be totally eliminated [17].
During the freewheeling period, S1 and S4 are turned
off, vAO decreases to zero and vBO increases until the diode
of S5 switches ON. If during the switching process, the
magnitude of the increase in vBO is equal to that of the vAO
decrease, then Vcm satisfies equation (7).
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
Tarak Salmi et al., Vol.2, No.1, 2012
143
During toff, the inductor current flows through S6 and
the diode of S5. The voltage applied to the inductor is (-
vgrid) [8], vAO=0, vBO=vIN and the common mode voltage
is:
2
IN
cm
v
v =
(8)
Fig.2. HERIC topology simulation results.
4.2. HERIC topology Zero Crossings Distortions
For the HERIC inverter topology, the simulation results
depicted in Fig. 2 (b and e) show a short break of 0.8 ms at
the current zero-crossings. In this topology, the main
switches utilize the PWM control strategy. The AC bypass
branch operates at the line-frequency switching order.
Despite the fact that this reduces losses, it also interrupts the
current flow near the zero crossings and the current may not
be well controlled there, which results in a distorted
waveform and inductor voltage spikes as shown in Fig.2 (a).
However, these issues can be solved with improved
control strategies and topologies that present smooth four-
quadrant operation near the zero crossings [14].
5. Proposed Transformerless Inverter Topology
5.1. Topology and Principles of Operation
The proposed topology is shown in Fig. 3 and consists of
six IGBTs, six freewheeling diodes and one diode-bridge on
the AC side.
The switching principles are similar to those of the
HERIC topology presented in Table 1, except for the high
switching frequency of S5 and S6. During the positive grid
period, S1 and S4 are switched ON and OFF at a high
switching frequency, while S6 is OFF and ON, respectively.
In this case, when S1 and S4 are turned OFF, the
freewheeling current finds its path through D3, S6 and D2 as
indicated by the dotted line in Fig. 4 and Fig.5. For the
negative half cycle, the freewheeling path is through D1, S5
and D4.
Fig.3. Proposed transformerless inverter topology.
Fig.4. Proposed topology showing the current path during
the positive half cycle (dotted line).
5.2. Leakage Current and Zero Crossing Distortions
For the proposed inverter topology, the simulation
results are included in Fig. 6 and show that the leakage
current does not exceed 21.10 mA, which is within the 30
mA limit set by the DIN VDE 0126-1-1standard.In fact, the
common mode voltage varies from 165 V to 184 V. This
variation is low and leads, therefore, to a low leakage current
level. In addition, the zero crossings distortions are
eliminated.
Fig.5. Proposed topology showing the current path during
the freewheeling period of S1-S4 (dotted line).
In the AC side, the bypass branch switches at the same
frequency of S1-S4.This means no sudden switching exists at
the end of each half cycle and the bypass branch does not
interrupt the flow of current. Therefore, the inductor voltage
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
Tarak Salmi et al., Vol.2, No.1, 2012
144
spikes would not appear as shown in Fig.6 (a). Such a control
strategy also eliminates the zero-crossings distortions as
shown in Fig. 6 (b and e), but at the expense of a small
increase in the current ripples which can be easily removed
using a simple EMI filter.
5.3. Efficiency
The efficiency of the proposed topology was estimated
based on the power switches losses: switching, and ON-state
losses.
Fig.6. Proposed topology simulation results.
IGBT Switching Losses
The total switching power losses (P
tot-sw
) can be defined
as the ratio of the total switching energy losses (E
tot
) over the
switching period. E
tot
is usually specified in the device
datasheet and includes both switching and diode reverse
recovery energy losses. Then, P
tot-sw
can be defined as:
tot s
sw tot
E f P =
(9)
By convention, the switching energy available in the
datasheets is for a specified test voltage and current (V
test
and
I
test
). To account for actual operating voltage and current, a
correction coefficient (Y
0
) is needed and the switching losses
are expressed as [19, 20]:
( )
0
Y P P
Datasheet tot tot
=
(10)
With:
1
0
0
t
= =
test test
bus
g
I
I
V
V
K Y
(11)
Where K
g
, V
bus
and I
0
are the correction factor, bus
voltage and peak load current, respectively.
Combining the above three equations yields the
following equation for the IGBT switching power losses:
) (
t
Datasheet tot
sw tot
E
s
f
P =
(12)
IGBT Conduction Losses
The ON-state power losses for one switch and for the
freewheeling diodes are [21]:
( ) )) ( (
off d
on d
f r ce L
g
t t t t dT V I
T
N
s
P
+ + + = (13)
And
( ) )) ( ) 1 ((
off d
on d
f r L
g
t t t t T d
F
V I
T
N
fd
P
+ + + = (14)
where:
I
L
: load current, RMS value.
V
ce
: IGBT emitter to collector voltage.
d: duty cycle.
f
s
: switching frequency.
T
s
: switching period.
T
g
: grid period.
t
r
: rise time.
t
f
: fall time.
t
d-off
: turn-off delay time.
t
d-on
: turn-on delay time.
V
F
: diode forward voltage drop.
N: Switching times per grid cycle.
Diode Power Losses
Since the power dissipated by each diode during one
switching period is not provided in the datasheet, it must be
estimated. In fact, the power dissipated in one diode is the
sum of the power dissipated during the on-state phase, the
off-state phase and the commutation phase [22,23].The diode
power losses during the ON-state and the OFF state and the
diode reverse recovery losses are respectively:
F
d V I P
F on
=
(15)
) 1 (
R
d V I P
R off
=
(16)
2
1
rr
f Q V P
R rec
=
(17)
Where Q
rr
is provided in the device datasheet and
defined as [23]:
F Qr rr
I K Q =
(18)
where:
K
Qr
: a function of di/dt.
I
F
: diode forward current.
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
Tarak Salmi et al., Vol.2, No.1, 2012
145
V
F
: diode forward voltage.
I
R
: diode reverse current.
V
R
: diode reverse voltage.
Q
rr
: reverse recovery charge.
f
s
: switching frequency.
Combining (12) through (19) yields the total power
losses of the semiconductor devices-IGBT and AC bridge
diodes, as shown below:
( ) )
2
1
1 ( 2
3 3 3
s rr R R R F L
sw tot total
f Q V d V I d V I
fd
P
s
P P P
+ + +
+ + =
(19)
6. Results
The above equations are used to estimate the losses of
the proposed topology as well as those of the HERIC
topology. In the losses estimation, six non-ideal IGBTs
(IRG4PH50KD) and four non ideal diodes (HFA30PB120)
from the HEXFRED family are used. The parameters of
selected switching devices are listed in Table 2 while the
estimated losses are given in Table 3.
Table 2. Power Loss Estimation Parameters
Parameter Value Unit
I
L,rms
25.22 A
V
ce
2.77 V
d 50.00 %
T
g
20.00 ms
t
f
390 ns
t
d-off
67 ns
I
PV,avg
14.38 A
V
DC
350 V
t
d-on
310 ns
V
F
2.30 V
N 160
I
R
1.50 mA
V
R
800 V
Q
rr
1838 nC
f
s
8 kHz
t
r
0.72 ns
From Table 3, it is clear that the conduction losses for
the proposed topology are lower than those of the HERIC
topology. This is due to the fact that, for the HERIC
topology, one switch (S
5
or S
6
) and one freewheeling diode
remain ON during the entire grid half cycle. However, in the
proposed topology, these switches are subject to grid current
for much shorter time. On the other hand, even though there
are additional diodes losses, the overall losses in the
proposed topology were almost equal to and even a bit lower
than those of the HERIC and therefore, a slight improvement
in the overall efficiency is obtained. Further improvement is
possible to achieve if better diodes with lower power losses
are used.
The proposed inverter topology has several features,
namely the elimination of the zero crossings distortions, low
THD, high efficiency and low leakage current. The
analytical and simulation results showed that this topology
has an efficiency of 94.14%, a THD of 2.62% and a leakage
current of 22.10mA. For the HERIC topology, the efficiency
and THD are 94.13% and 3.26%, respectively.
From power quality point of view and based on the
analysis presented in Section III, it is anticipated that the low
frequency harmonics are significantly reduced as shown in
Fig. 7.
Fig.7. Comparison of low order harmonics in the HERIC and
proposed topologies.
It is obvious that, for the proposed topology, low order
harmonics are much less than those of the HERIC topology.
This represents another advantage for the proposed topology.
Table 3. Losses Breakdown for the HERIC and the Proposed
Topologies
HERIC Proposed
Conduction losses (W) 295.75 220.30
Switching losses (W) 112.80 111.00
Diodes losses (W) 0.00 74.77
Total losses (W) 297.55 295.07
Input power (W) 5034.00 5034.00
Efficiency (%) 94.09 94.14
7. Conclusion
In this paper, major transformerless topologies were
reviewed in terms of their advantages and disadvantages. It
was found that these topologies suffer from some drawbacks
such as the leakage current and zero crossings distortions.
The leakage current is generated when the transformer is
omitted. However, the zero crossings distortions are due to
the applied control strategies. Accordingly, a novel
transformerless inverter topology was developed and a
detailed analysis of its efficiency was carried out. It was
found that the adopted topology as well as the control
strategy has revealed that the zero crossings distortion was
definitely eliminated, the efficiency has been improved and
the low frequency harmonics were significantly reduced.
Following these preliminary results, a prototype is under
design to confirm experimentally the above mentioned
features of the proposed topology.
References
[1] Fritz Schimpf, Lars E. Norum, Grid Connected
Converters for Photovoltaic, State of the Art, Ideas for
Improvement of Transformerless Inverters,
NORPIE/2008, Nordic Workshop on Power and
Industrial Electronics, June 9-11, 2008, pp.1-5.
INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH
Tarak Salmi et al., Vol.2, No.1, 2012
146
[2] T. Kerekes, R. Teodorescu, M. Liserre, Common Mode
Voltage in case of Transformerless PV Inverters
Connected to the Grid, IEEE International Symposium
on Industrial Electronics, June 30th- July 2nd 2008, pp.
2390 - 2395.
[3] W.T. Franke, N. Oestreich, F.W. Fuchs, "Comparison of
Transformerless Converter Topologies for Photovoltaic
Application Concerning Efficiency and Mechanical
Volume", IEEE International Symposium on Industrial
Electronics, 2010, pp.724-729.
[4] Oscar Lopez, Remus Teodorescu, Francisco Freijedo,
Jesus Doval-Gandoy, "Eliminating Ground Current in a
Transformerless Photovoltaic Application", IEEE
Transactions on Energy Conversion, Vol. 25, No 1, Mar.
2010, pp. 140-147.
[5] W. Bower and J. Wiles, Investigation of Ground-Fault
Protection Devices for Photovoltaic Power System
Applications, Proceedings of the 28th IEEE Conference
on Photovoltaic Specialists, 2000, pp. 1378-1383.
[6] Roberto Gonzlez, Eugenio Guba, Jess Lpez, and Luis
Marroyo, Transformerless Single-Phase Multilevel-
Based Photovoltaic Inverter, IEEE Transactions on
Industrial Electronics, Vol. 55, No. 7, July 2008,
pp.2694-2702.
[7] Lin Ma, Fen Tang, Fei Zhou, Xinmin Jin and Yibin Tong,
"Leakage Current Analysis of a Single-Phase
Transformer-less PV inverter connected to the grid",
Proceedings of the IEEE International Conference on
Sustainable Energy Technologies, 24-27 Nov. 2008,
pp.285-289.
[8] Roberto Gonzalez, Jesus Lopez, Pablo Sanchis, Eugenio
Gubia, Alfredo Ursua and Luis Marroy, High-Efficiency
Transformerless Single-phase Photovoltaic Inverter,
Proceedings of the 12th IEEE Conference on Power
Electronics and Motion Control, 30 Sep. 2006, pp.1895-
1900.
[9] Valentini, M. Raducu, A. Sera, D. Teodorescu, R., PV
inverter test setup for European efficiency, static and
dynamic MPPT efficiency evaluation, Proceedings
of11th International Conference on Optimization of
Electrical and Electronic Equipment, OPTIM 2008,
Printed on CD.
[10] T. Kerekes, R. Teodorescu, and U. Borup,
Transformerless Photovoltaic Inverters Connected to the
Grid, Proceedings of the APEC 2007, Feb. 25 - March
01, pp. 1733-1737.
[11] Rodrguez, Gerardo Vzquez, Emiliano Aldabas, A
new high-efficiency single-phase transformerless PV
inverter topology, IEEE Transactions on Industrial
Electronics, June 2009, pp.1-5.
[12] Huafeng Xiao, Shaojun Xie, Leakage current
analytical model and application in single-phase
Transformerless photovoltaic grid-connected inverter,
IEEE Transaction on Electromagnetic Compatibility,
Vol.52, No. 4, Nov 2010, pp.902-913.
[13] IEEE Recommended Practices and Requirements
for Harmonic control in Electrical Power Systems, IEEE
Standard 519-1992.
[14] Andrew Kotsopolos, Peter J.M. Heskes, Mark
J.Jasen, Zero-Crossing Distortion In Grid-Connected PV
Inverters, IEEE Transactions on Industrial Electronics,
Vol. 52, No.2, April 2005, pp. 558-565.
[15] J. Myrzik, M. Calais, "String and Module Integrated
Inverters for Single Phase Grid Connected Photovoltaic
Systems- A Review", Proceedings of the IEEE
Conference on Power Tech, Bologna, Italy, 23-26 June
2003, Vol.2.
[16] Samuel Vasconcelos, Araujo, Peter Zacharias,
Regine Mallwitz, High Efficient Single-Phase
Transformerless Inverter for Grid-Connected
Photovoltaic Systems, IEEE Transactions on Industrial
Electronics, Vol. 57, No. 9, Sep. 2010, pp. 3118-3128.
[17] G. Buticchi, G. Franceschini, E. Lorenzani,
"Compensation Strategy of Actual Commutations for PV
Transformerless Grid-Connected Converters",
Proceedings of the XIX International Conference on
Electrical Machines, Rome 6-8 Sept.2010, pp. 1-5.
[18] Sushant Kumar Pattnaik, K.K Mahapatra, Power
loss Estimation for PWM and Soft-switching Inverter
using RDCLI, On Proceeding of IMECS, Vol. 2, Mar
17th-19th 2010.
[19] F. Casanellas, Losses in PWM Inverters Using
IGBTs, Proceedings in IEEE Power Electronics
Applications, Vol. 141, No. 5, Sept. 1994, pp. 235-239.
[20] Alberto Guerra, Kohji Andoh, Silvestro Fimiani,
Ultra-Fast Recovery Diodes Meet Todays
Requirements For High Frequency Operation and Power
Ratings in SMPS Applications, International Rectifier,
Jul. 14th 2000, pp. 1-9.
[21] H.F Xiao, S.J. Xie, C. Yang, R.H. Huang, "An
Optimized Transformerless Photovoltaic Grid-Connected
Inverter", IEEE Transactions on Industrial Electronics,
Vol.99, June 2010, pp. 1-9.
[22] YUAN Liqiang, ZHAO Zhengming, YANG Zhi,
Power Losses for IGCTs and Diodes in MV Three-level
Inverters, Proceedings of the IEEE International
Conference on Electronics and Drives Systems, Nov.
2005, pp. 205-208.
[23] Tanel Jalakas, Dmitri Vinnikov, Prediction of
Semiconductor Losses in a High-Power High-Voltage
DC/DC Converter, Doctoral School of Energy-and Geo-
Technology, Jan. 15th-20th 2007, Kuressaare, Estonia,
pp. 114-117.