PowerIT High Voltage Power Capacitor CHD

Three Phase

General
The ABB capacitor unit type CHD is designed for heavy-duty operation in Fixed, Enclosed and Pole Mount Banks in all climatic conditions. The ABB capacitor unit is a three-phase power capacitor of all film design, with very low dielectric losses and a long life. Each capacitor has several elements that consist of a dielectric of polypropylene film and aluminium foil, which are connected in series and parallel groups in to an internal star or delta configuration. The capacitors are impregnated with a biodegradable, non-PCB fluid with high insulation strength to ensure excellent electrical performance. The edges of the foil electrodes are folded enabling higher electrical stress through superior electrical connections to withstand high transient currents and minimising partial discharge. The ABB capacitors have an extremely low failure rate and high reliability. The ABB capacitor unit tank is constructed from a high-grade 304 stainless steel providing excellent corrosion resistance. The seams are fully TIG welded providing superior weld quality compared with other welding processes, resulting in a much-reduced risk of leakage. In all, the ABB capacitor unit provides greater reliability and a longer service life.

Capacitor Container
Material Colour Finish Fixing brackets Stainless steel, 304 high-grade Storm grey N42 (AS 2700) Matt One or two per side

Terminations
Bushings Terminals Clamps Fixing Grey porcelain, three M16 x 3 Nickel-coated brass, !. 2x70mm2 Two 11x16mm holes, 397mm centres

Dimensions and Data (typical)


Unit rating > 3.3kV Unit rating ! 3.3kV

Quality Assurance and Environment


ABB is certified according to ISO 9001 (quality) and ISO 14001 (environment).

Standards
AS 2897, IEC 60871 or other standards on request.
kvar A 250 300 350 400 500 550 650 750 800 900 50Hz B 200 225 250 200 250 275 325 375 400 450 A 250 250 300 350 400 500 550 650 700 750 60Hz B 200 200 225 250 200 250 275 325 350 375 kg 33 36 40 44 52 56 64 72 76 84

Technical Data
Power Voltage range Frequency Current Dielectric Impregnant Discharge resistors Losses Up to 500kvar 1- 20kV 50/60Hz Max. 180A Polypropylene film Jarylec C101 (non-PCB) Built-in ! 0.15 W/kvar including resistors

50 100 150 200 250 300 350 400 450

Operating Conditions
Temperature range Location Altitude -10/+50oC Outdoor or indoor ! 1000m above sea level

500

BIL 40 60 95 150

C 115 140 215 295

ABB Australia Pty Limited ABN 68 003 337 611


88-120 Beresford Road Lilydale Vic 3140 Australia Phone: +61 3 9735 7333 Fax: +61 3 9735 3863 Internet: www.abb.com

This product has been certified by ABB Group as Industrial IT Enabled - Information Level. All product information is supplied in interactive electronic format, based on ABB Aspect Object technology. The Industrial IT commitment from ABB ensures that every enterprise building block is equipped with the integral tools necessary to install, operate, and maintain it efficiently throughout the product lifecycle. HOPEAD 6/03 #8756 While care has been taken to ensure that the information contained in this document is correct, no responsibility can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at any time in the light of technical or other developments. Technical specifications are valid under normal operating conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for indirect or consequential damages. Technical data and design can be subject to change and should be confirm prior to ordering.

2GSA 100004 ed. 01 (06-2003)

Notes: All dimensions are in millimetres Dimension D equals 115mm All dimensions are subject to change without notice