Aisladores ABB - GSA
Aisladores ABB - GSA
Aisladores ABB - GSA
The information provided in this document is intended to be general and does not
cover all possible applications. Any specific application not covered should be
referred directly to ABB, or its authorized representative.
This document must not be copied without our written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized
purpose. Contravention will be prosecuted.
Content
Design............................................................................................................................. 4
Standards.................................................................................................................. 4
Features and benefits................................................................................................. 4
Transportation and long term storage......................................................................... 5
General specifications................................................................................................ 5
Testing............................................................................................................................. 6
Routine testing........................................................................................................... 6
Type tests.................................................................................................................. 6
Special tests.............................................................................................................. 6
Test tap...................................................................................................................... 6
Test tap adapter......................................................................................................... 6
Electrical data.................................................................................................................. 7
Dimensions...................................................................................................................... 8
Connection details........................................................................................................... 10
Outer terminal............................................................................................................ 10
Inner terminal............................................................................................................. 10
Solid rod conductor................................................................................................... 11
Ordering particulars for solid rod conductor............................................................... 11
Conductor insulation.................................................................................................. 11
Separate terminal plate with bolts.............................................................................. 12
Arcing horns.............................................................................................................. 12
Conductor loading........................................................................................................... 13
Overloading of bushings............................................................................................ 13
Short-time current...................................................................................................... 13
Ordering particulars......................................................................................................... 14
Recommendations for positioning................................................................................... 15
Design
The inner terminal is fixed to the top piece with a divided ring Silicone rubber insulator
(patented by ABB) and can be connected to leads by brazing.
For maximum current rating, a solid copper rod is used.
The standard colour of the mounting flange and of the Mounting flange
insulator is RAL 7035, light grey.
Non-shattering materials
Protection of personnell and equipment, easy handling, safe
transport - also when mounted on the transformer, high
seismic withstand
General specifications
For conditions exceeding the standard specification, please
consult the supplier.
Application: Transformers
Classification: Resin impregnated paper, capacitance graded,
outdoor immersed bushing
Ambient temperature: +40 °C to -40 °C, minimum value acc. to
temperature class 3 of IEC 60137
Altitude of site: < 1000 m
Level of rain and 1-2 mm rain/min. horizontally and vertically, as
humidity: per IEC 60060-1, and 5 mm/min. as per IEEE
Pollution level: According to specific creepage distance and
IEC 60815
Immersion medium: Transformer oil. Maximum daily mean oil
temperature +90 °C. Maximum temporary oil
temperature +115 °C.
Oil level in transformer: Not lower than 25 mm from the bushing flange
Max pressure of 100 kPa (over pressure)
medium:
Angle of mounting: Horizontal to vertical
Test tap: Test tap with 4 mm male contact pin
Capacitance C2 of test < 5000 pF
tap:
Arcing horns: Optional
Conductor: Solid or flexible draw lead conductor
Markings: Conforming to IEC/IEEE.
Routine testing
The bushing is routine tested according to applicable
standards. The tests include measurement of partial
discharge quantity, tan δ, capacitance, dry power frequency
voltage withstand test. The flange is separately tightness
tested with helium. A visual inspection is performed.
Type tests
Complete type tests have been performed and reports are Fig. 2. Test tap.
available on request.
Special tests
A number of tests not specified by international standards
have also been performed and reports are available on
request.
Test tap
The outer conducting layer of the condenser core is
connected to an insulated test tap on the flange. During
operation the protective cap must be fitted to earth the outer
layer to the flange. The maximum test voltage is 2 kV, 50 Hz
for 1 minute. The maximum service voltage is 600 V. Fig. 3. Test tap adapter, 1ZSC003881-AAC.
Dimensions in mm
Total L Oil Air Draw Top Arcing Flange Condenser Centre Min. Hole Flange Insulator Top
side side lead part distance height core outer hole gasket circle D7 sheds piece
L1 L2 L4 L5 L7 L8 D1 D2 surface D6 D8 diameter
inner D9
Type diameter
GSA Cat. No. D5
52 LF 130 052-BA 734 145 589 583 56 467 101 96 51 110 185 225 230 120
-BB 1034 445
-BC 1234 645
73 LF 130 073-BA 1029 260 769 763 56 647 101 96 51 110 185 225 230 120
-BB 1329 560
-BC 1529 760
123 LF 130 123-BA 1444 255 1189 1183 56 1067 101 136 51 150 250 290 270 160
-BB 1744 555
-BC 1944 755
145 LF 130 145-BA 1731 362 1369 1363 56 1247 101 136 51 150 250 290 270 160
-BB 2031 662
-BC 2231 862
170 LF 130 170-BA 2019 410 1609 1603 56 1487 101 136 51 150 250 290 270 160
-BB 2319 710
-BC 2519 910
Cantilever load
Max. permitted loading
Space for perpendicular to the
current Net Number Flange Creepage distance terminal
Type Rated transformer mass of holes thickness total protected
GSA current (A) Cat. No. (mm) (kg) n1 T (mm) (mm) (N) Test (N)
L5
R8
R8 R2
7°
L7
L2 L4
R5
R2 24
R5
L 18°
L8
60
7°
18°
D1
33
D2
L1
60
ø15 x n1
90°
17.5
M12
D5
Hole design for
GSA 52 - 73 D6
15
D7
Fig. 5. Dimensions.
Outer terminal
D
The outer terminal needs to be specified in each case. The
outer terminal is then used together with either a solid rod, for
maximum current capacity, or a flexible lead for greater ease Terminal stud
of assembly, when the required current capacity is lower. 125
Inner terminal
The inner terminal is made of copper for connection of a draw
M8
lead.
13
Material and design Conductor Cat. No. Mass
diameter (mm) LF 170 080 (kg)
Copper for brazing 5 (pilot hole) -A 1
11 -B 1
13 -C 1
35
15 -D 1
18 -E 1
30 -F 1 ø D_cable
42 -G 1 ø 49
45 -H 1
D1 D1
D2 D2
47 Insulate up Insulate
35 60 up to here
to here
35
ø 43 ø 56
ø 49 ø 62
1600 A 2000 A
Arcing horns
Arcing horns made of galvanised steel can be mounted on
the bushing. The arcing horns are available for stud with
ø 30 mm.
The lower rod is fastened onto the flange with one of the
fixing screws and the upper rod by means of a bracket on the C
outer terminal. K
The gap distances for standard arcing horns are shown in the H
table. Other gap distances on request.
Overloading of bushings
If the conductor for the bushing is selected with 120 % of the
rated current of the transformer, the bushing is considered
to be able to withstand the overload conditions stated in
IEC 60354 without further clarifications or tests, according to
IEC 60137.
Short-time current
The rated thermal short-time current (Ith) is calculated
according to IEC 60137.
Type GSA Internal insulation level of Distance to earthed parts Space for current
transformers
transformer (kV) R (mm)
52 250-95 75
73 350-140 90 R min 2
123 550-230 145
45°
145 650-275 165
170 750-325 190 R min 5
60° Earthed layer
ABB AB
© Copyright 2014 ABB, All rights reserved. 1ZSE 2750-111 en, Rev. 8, 2014-10-30