01 s0201 RCCB F 360 X
01 s0201 RCCB F 360 X
01 s0201 RCCB F 360 X
When connecting aluminium conductors, ensure that the contact surfaces of the conductors are cleaned, brushed and treated with grease. Re-tighten contacts terminals after 6 to 8 weeks' time.
Conditions for Delivery and Sale For domestic business, the Standard Terms for Delivery of Products and Services of the Electrical Industry (ABB Form 2292) shall apply in connection with the Standard Sale Terms (ABB Form 2327) in their then applicable version. For foreign business, the Standard Terms for Delivery of Products and Services of the Electrical Industry (ABB Form 2293 German-English, or ABB Form 2294 German- French) shall apply in connection with the Standard Sales Terms (ABB-Form 2381 English) in their then applicable version.
Warranty We assume warranty in accordance with the Standard Sale and Delivery Terms. Complaints shall be made in writing within eight days following receipt of the goods.
Technical information and illustrations are not binding and subject to change without notice.
2
Contents
page
Technical descriptions Technical data ........................................................................................................................... 5 Installation and operation instructions ...................................................................................... 8 Dimension drawings ................................................................................................................. 9 Usage in various types of circuits ............................................................................................. 10 Definitions ................................................................................................................................. 14
Selection tables Residual current operated circuit-breaker F 360 X, busbars ..................................................... 11 Busbar blocks, end caps ........................................................................................................... 12 Accessories ............................................................................................................................... 13
Overview
The residual current operated circuit-breaker (RCCB) F 360 X has a balancing transformer with a permanent magnet release for measuring. It detects:b a.c. fault currents and is surge proof up to 250 A Transient, excessive residual current impulses may result from ripple voltage generated by e.g. switching of fluorescent lamps, x-ray equipment, IT systems and the use of thyristor controls. In connection with an upstream type gL 100A fuse , F 360 X may withstand solid short-circuit currents of up to 10 kA ( ). It is also possible to use a STOTZ selective main circuit breaker type S 700 E 100 instead of a fuse. RCCB F 360 X is suitable for an ambient temperature range of 25 C / -13 F to + 55 C / 131 F.
F 362 X
SK 0132 B 00
b protection against electrically ignited fire (fire protection) if the rated residual current of the device is I n 300 mA .
F 364 X
Field of application
To attain a higher degree of safety in all installations, as well as in areas for which mandatory rules provide for or recommend residual current protective devices.
SK 0092 Z 94
pulse shape 8/20, = 250 A according to DIN VDE 0432 Part 2 and IEC 60-2
SK 0051 Z 95
Technical data
standards: No. of poles: rated current In: rated residual currents I n: tripping range: tripping times at surge strength: (pulse shape see page 4) rated residual making & breaking current I m: rated switching capacity Im: rated short-circuit current Inc: rated residual short-circuit current I short-circuit withstand capacity:
c
IEC 1008, EN 61 008 BS 4293 2 and 4 poles 80 and 100 A 30 mA 0.5 ... 1 I 1 I n: 5 I n: 200 ms 40 ms 250 A (impulse wave shape 8/20) 200 A (ring wave 0.5 s/100 kHz) 1000 A 1000 A 6000 A : 6000 A 10 000 A; in connection with STOTZ selective main circuit-breaker S 700 E 100 A or an upstream fuse type gL 100 A 230/400 V 50 ... 60 Hz Un + 10% 100 ... 264 V according to DIN VDE 0110 Parts 1 and 2 IV 2 6 kV 2.5 kV grey moulded plastic (RAL 7035) black black IP 20, IP 40 in the distribution board according to DIN VDE 0106, Part 100 according to DIN 43880 size code 1 any snap-on to DIN rails 1.5 to 25 mm 2 1.5 to 25 mm2
n
rated voltage Un: frequency: max. service voltage Usmax : operative range of testing equipment UT: insulation co-ordination: overvoltage category: pollution degree: surge voltage (1,2/50 s): power-frequency voltage strength (50/60 Hz): casing: operating lever: test button: degree of protection: protection against electric shock: overall dimensions: mounting position: fixing: connection cross section top: bottom: connection: terminals: serviceable life: climatic resistance according to IEC 1008 / IEC 68 Part 2-30: ambient temperature: virbration resistance: trip-free mechanism: weight:
individually or collectively via a busbar top: bottom: combined box terminal using M5-type screws box terminal using M5-type screws at least 5000 switching cycles damp heat, cyclic (28 cycles) Tmin 5 C / 23F, Tmax + 55 C / 131F according to IEC 1008, EN 61008 yes see selection table
SK 0027 B 94
SK 0030 B 94
SK 0031 B 94
SK 0029 B 94
SK 0028 B 94
SK 0032 B 94
SK 0035 B 94
SK 0036 B 94
SK 0034 B 94
SK 0033 B 94
Install in any desired mounting position by means of snap-on fastening to DIN rails EN 50 022, 35 mm.
mounting dismounting
Incoming supply from above or below. To ensure proper test button functionality of four-pole RCCBs operated as two-pole devices, connect terminals 5 and 7 or, as the case may be, 6 and 8. In the case of a 3-phase circuit with Un 127/230 V (without neutral conductor N) terminals 4 and 8 have to be bridged.
3. Operation
SK 0272 Z 98
on
off
4. Operating test No maintenace other than the monthly operating test is required. 5. Test of effectiveness of protection
To carry out the operating test, the circuit-breaker must be properly installed. Press the test button in the ON position, and the RCCB must trip immediately (the operating lever jumps from position I to 0). In addition to the operating test, test the effectiveness of the circuit-breaker's protection of the installation according to the applicable code of practice. The maximum permissible earth/ electrode resistance for rcd protection is as follows: max permissible touch voltage UL 25 V 50 V max. permissible earth-electrode resistance if rated residual current is 30 mA 100 mA 300 mA 833 1666 250 500 83 166
6. Cleaning
Dirty RCCBs may be cleaned with a damp cloth moistened with soapy water if dry cleaning is impossible. Never use caustic detergents or solvents.
7. Malfunctioning
The high-quality STOTZ residual current operated circuit-breakers are throurougly adjusted and tested in our works. Where damage occurs (caused e.g. by transport, storage , etc.) no repair work must be undertaken. If the device responds immediately after putting the RCCB into operation, check the downstream active circuit and any connected current-consuming appartus for earth fault current. Remove insulation faults or connections between the neutral conductor and the protective conductor existing in load circuit. Where the RCCB does not trip in the first operating test after pressing the test button, check first whether the test circuit is connected correctly. Where none of the above causes apply, or should the operating test be completed unsuccessfully, the RCCB must be replaced. Opening the device will lead to a loss of warranty.
SK 0213 Z 00
SK 0012 Z 96
F 362 X, F 364 X
F 362 X
F 364 X
Terminal covers
PCD 2 N
SK 0136 Z 96
PCD 4 N
PCD 6 N
SK 0137 Z 96
PCD 8 N
SK 0138 Z 96
QES 4/3 N
SK 0078 Z98
QES 6/3 N
Mounting rails
code
SK 0150 Z 93
SK 0079 Z98
A1 15 20 37.5 55 90 9
DSW 4 and 6
SK 0212 Z 00
Residual current operated circuit-breaker Examples for protection against electric shock
SK 0038 Z 94
TN-S system separate neutral and protective conductors throughout the network
TN-C-S system neutral and protective conductor (PEN) combined in one part of the network
TT system
IT system The residual current operated circuit-breaker trips if a double fault occurs, as e.g. is indicated as fault 1 and fault 2 above.
Explanation of abbreviations L1, L2, L3 PE N PEN T line outer conductor protection earth protective conductor neutral PE and N combined terre direct bond to earth ... terms used in international IEC standards I C S isolation combined PE and N (PEN) in the network separated PE and N in the network
10
SK 0017 Z 95
SK 0040 Z 94
SK 0005 Z 97
type code
F 360 X series
SK 0133 B 00
Residual current operated circuit-breaker F 362 X, 2 poles 30 80 100 F 362- 80/0,03 F 362-100/0,03 GH F362 0046 R2620 GH F362 0046 R2630 0.280 1 0.280
F 362 X
Residual current operated circuit-breaker F 364 X, 4 poles 30 80 100 F 364- 80/0,03 F 364-100/0,03 GH F364 0046 R2620 GH F364 0046 R2630 0.430 1 0.430
F364 X
SK 0135 B 00
Busbars
cross section mm2 length mm no. of poles order details type code order code bbn 40 12233 EAN price 1 piece DM price weight pack group 1 pc. unit kg pc.
Universal comb busbars for cross-wiring STOTZ RCCBs F 360 X from below with STOTZ MCB S 2 Single-phase feeder Mounting comb busbars in no way affects protection against unintentional touch of live parts according to DIN VDE 0106 Part 100.
SZ-KS 1/12 SZ-KS 2/12 SK 0014 Z 01
12 24
210 210
12 x 1 12 x 1
59790 1 59810 6
SK 0091 B 93
Mounting rails (EN 50 022 35 x 7.5) mounted individually with 2 screws on an even surface (1 module = 17.5 mm) for 2 modules for 3 modules for 4 modules for 6 modules DSW 2 DSW 3 DSW 4 DSW 6 GH S210 1926 R0002 GH S210 1926 R0003 GH S210 1926 R0004 GH S210 1926 R0006 13590 5 13600 1 13610 0 13620 9 0.012 0.018 0.024 0.030 10 10 10 10
DSW 2 ... 6
11
cross section mm
length mm
no. of x poles
order code
price 1 pc. DM
weight 1 pc. kg
type F 362 X,
6x2 29 x 2 6x2 29 x 2 SZ-PSB 53 N SZ-PSB 54 N SZ-PSB 55 N SZ-PSB 56 N
2 poles 1 phase + N
GH V036 0874 R0031 GH V036 0874 R0032 GH V036 0874 R0033 GH V036 0874 R0034 54940 5 54950 4 54960 3 54970 2 0.078 0.403 0.106 0.534
10 10 16 16
30 10 30 10
type F 364 X,
10 10
SK 0120 Z 96
4 poles 3 phases + N
GH V036 0874 R0039 GH V036 0874 R0040 GH V036 0874 R0041 GH V036 0874 R0042 55020 3 55030 2 55040 1 55050 0 0.112 0.650 0.156 0.884
3x4 15 x 4 3x4 15 x 4
30 10 30 10
16 16
213 1018
3x3+2x1 15 x 4
30 10
3x3+2x1(N recess)
GH L520 1921 R0005 GH L520 1921 R0006 GH V036 1325 R0001 GH V036 1352 R0002
50 50 50 50
PSB-END 3 PSB-END 4
12
SK 0074 Z 91
description
price 1 piece DM
weight 1 pc. kg
The terminal cover is snapped onto the base plate and is sealable. The base plate has an integrated top-hat mounting rail. for 2 modules for 4 modules for 6 modules for 8 modules earth (PE) rail PCD PCD PCD PCD ES BP 2 4 6 8 N N N N GH S270 1921 R0002 GH S270 1921 R0004 GH S270 1921 R0006 GH S270 1921 R0008 GH S270 1912 R0001 GH S270 1913 R0001 12402 12404 12406 12408 6 0 4 8 0.08 0.14 0.175 0.63 0.08 0.005 1 1 1 1 10 10
PCD 4 N
36660 6 12857 4
SK 0079 B 96
PCD 8 N
with 2 grommets
QES 4/3 N
12644 0
0.330
for 6 modules, knockouts: 3 x Pg 21 on each top and bottom with 2 grommets QES 6/3 N GH L111 2306 R0013 12646 4 0.420 1
13
Protection ensured by types AC, A and B residual current devices (RCD) according to CEI IEC 755
form of residual current sinusodial a.c. suddenly applied slowly rising pulsating d.c. suddenly applied with and without superimosed smooth d.c. of 6 mA
SK 0005 Z 96
SK 0003 Z 96
1)
14
Notes
15
ABB STOTZ-KONTAKT, the Heidelberg-based company, develops, manufactures and sells highly modern, modular systems for electrical building installations. It offers complete installation ranges for a wide variety of applications:
System pro M
For classic installation applications
The modular System pro M for installation on DIN rails incorporates Europes best-selling miniature circuit-breakers and residual-current-operated circuit-breakers as well as a complete range of built-in devices. The system components have been designed with various functions and performance capabilities and are therefore able to optimally cover the complete range of applications in building installation: b b b b b conventional domestic electrical installations industrial and commercial installations protection and switch functions checking and monitoring tasks control and time-dependent tasks etc.
The new plug-in connection technology for the devices and apparatus rack ensures quick and reliable installations: assembly, connection of the devices and cross wiring are carried out time-effectively in one single step. If need be, component sets may still be changed quickly and flexibly right until transfer takes place; devices may also be exchanged easily at some later date, and economically in terms of both money and time, at that. The entire System Connect was developed by ABB STOTZKONTAKT and Striebel & John, within the framework of their successful system partnership.
System for retrofitting in existing buildings. Transfer of information via the existing network.
Security Systems
All-in-one Protection
Wide range of security systems and components: intruder and fire alarm systems, radio-controlled alarm systems, door locking system and signalling components. During the century-long experience of the company, it has always contributed pioneering solutions to the safe application of electricity. Today, ABB STOTZ-KONTAKT GmbH is an integral part of the ABB Group, a major player on the electrical and electronic markets.
System Connect
This pioneering system concept contains seamlessly integrated system units consisting of miniature circuitbreakers and residual-current-operated circuit-breakers as well as apparatus racks and flush-mounted wall boxes - was designed to suit the special requirements of domestic electrical
ABB STOTZ-KONTAKT GmbH P.O. Box 10 16 80 D-69006 Heidelberg Germany Phone ++ 49 ( 62 21) 701 - 0 Fax ++ 49 ( 62 21) 701 - 723 www.abb-stotz-kontakt.de