Standards
The GSA bushing is designed and tested according to IEC 60137 and
IEEE C57.19.00/01 in applicable parts.
Design
GSA-OA is a Resin Impregnated Paper (RIP) bushing with Silicone
Rubber (SiR) insulator. The condenser body is bonded directly to the
silicone rubber to give a compact and lightweight bushing, containing no
gas, oil or other liquids.
The GSA bushings are produced by winding a crêped paper web onto
a mandrel, with aluminium foil inserts for electrical stress control. The
body is impregnated and cured under vacuum, giving a partial discharge
free bushing with low tan d (dissipation factor). After curing, the body is
machined and the flange is fitted.
The inner terminal is fixed to the top piece with a divided ring (patented
by ABB) and can be connected to leads by brazing. For maximum current
rating, a solid copper rod is used.
Outer terminals are available in a number of standard configurations in
aluminium and copper, but can also be modified to suit any connection
need.
The standard colour of the mounting flange and of the insulator is RAL
7035, light grey.
Outer terminal
Test tap
Mounting flange
RIP body
Solid conductor
gsa_0001
Test tap
The outer conducting layer of the condenser body is connected to an
insulated test tap on the flange. During operation the protective cap must
be fitted to earth the outer layer to the flange. The maximum test voltage
is 2 kV, 50 Hz for 1 minute. The maximum service voltage is 600 V.
gsa_0042
Features Benefits
Solid Reduced risk for fire, any mounting angle possible, oil leakage from
the bushing eliminated, no monitoring of pressure and oil level.
Seals the transformer Reduced risk for fire, risk for oil leakage from the transformer
reduced.
Non-shattering materials Protection of personnell and equipment, easy handling, safe
transport - also when mounted on the transformer, high seismic
withstand.
Light weight, compact Easy handling, small requirements on space inside transformer, low
life cycle environmental impact.
Silicone rubber insulator Superior electrical performance, cleaning normally not needed.
Testing
Routine testing
The bushing is routine tested according to applicable standards.
The tests include measurement of partial discharge quantity, tan δ,
capacitance, dry power frequency voltage withstand test. The flange is
separately tightness tested with helium. A visual inspection is performed.
An individual routine test protocol is delivered with each bushing from
ABB.
Type tests
Complete type tests have been performed and reports are available on
request.
Special tests
A number of tests not specified by international standards have also been
performed and reports are available on request.
1ZSE 2750-111 en, Rev. 5 7
goh_0011
Electrical data
Ratings GSA-OA 52 73 123 145 170
Rated voltage IEC (kV) 52 72.5 123-170 145-170 170
Rated phase-to-earth voltage IEC (kV) 30 42 98 98 98
Insulation class IEEE (kV) 46 69 115 138 161
Rated line-to-ground voltage IEEE (kV) 29 44 88 88 102
Basic Insulation Level (kV) 250 350 550 650 750
(Equal to dry lightning impulse withstand
voltage.)
Rated current (A) 2000 2000 1600 1600 1600
Draw lead current (A) 1250 1250 1250 1250 1250
Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60
Temporary over voltage (kV) 52 73 170 170 170
Wet power frequency AC (kV) 95 140 230 275 325
Routine test 1 minute dry (kV) 120 160 260 310 365
Nominal capacitance between conductor and 224/430/559 351/546/682 213/314/380 251/314/380 301/395/465
test tap C1 ±10 % (pF)
Space for current transformer (mm) 0/300/500
8 1ZSE 2750-111 en, Rev. 5
Dimensions D8
D9
L5
R8
7° R8 R2
L7
L2 L4
R5
R2 24
R5
L 18°
L8
60
7°
18°
D1
33
D2
L1 60 gsa_0009
ø15 x n1
Hole design for 2
GSA 123 - 170 Fig. 5. Dimensions.
T
90°
17.5
M12
D5
Hole design for
GSA 52 - 73 D6
15
D7
gsa_0044 gsa_0010
Dimensions in mm
Space for
current
Rated trans- Net Draw Arcing Flange Condenser
Type current former mass Total Oil side Air side lead Top part distance height body outer
GSA (A) Cat. No. (mm) (kg) L L1 L2 L4 L5 L7 L8 D1
52 2000 LF 130 052-BA 0 13 734 145 589 583 56 467 101 96
-BB 300 16 1034 445
-BC 500 17 1234 645
73 2000 LF 130 073-BA 0 18 1029 260 769 763 56 647 101 96
-BB 300 20 1329 560
-BC 500 21 1529 760
123 1600 LF 130 123-BA 0 45 1444 255 1189 1183 56 1067 101 136
-BB 300 50 1744 555
-BC 500 53 1944 755
145 1600 LF 130 145-BA 0 52 1731 362 1369 1363 56 1247 101 136
-BB 300 57 2031 662
-BC 500 60 2231 862
170 1600 LF 130 170-BA 0 61 2019 410 1609 1603 56 1487 101 136
-BB 300 66 2319 710
-BC 500 69 2519 910
1ZSE 2750-111 en, Rev. 5 9
Common specifications
Application: Transformers
Classification: Resin impregnated paper, capacitance graded, outdoor
immersed bushing
Ambient temperature: +40 °C to -40 °C, minimum value acc. to temperature class
2 of IEC 60137
Altitude of site: < 1000 m
Level of rain and humidity: 1-2 mm rain/min. horizontally and vertically, as per IEC
60060-1, and 5 mm/min. as per IEEE
Pollution level: Acc. to specific creepage distance and IEC 60815
("Guide for selection of insulators with respect to polluted
conditions")
Immersion medium: Transformer oil. Max oil temperature acc. to the Installation
and Maintenance Guide.
Oil level in transformer: Not lower than 25 mm from the bushing flange
Max pressure of medium: 100 kPa (over pressure)
Angle of mounting: Horizontal to vertical
Test tap: Test tap with 4 mm male contact pin
Capacitance C2 of test tap: < 5000 pF
Arcing horns: Optional
Conductor: Solid or flexible draw lead conductor
Markings: Conforming to IEC/IEEE.
Cantilever load
Max. permitted loading
Min.
perpendicular to the
gasket
Creepage distance terminal
surface Top
Centre inner Hole Insulator piece Number Flange
hole diameter circle Flange sheds diameter of holes thickness total protected
D2 D5 D6 D7 D8 D9 n1 T (mm) (mm) (N) Test (N)
51 110 185 225 230 120 6 15 1642 700 1250 2500
Connection details
The outer terminal needs to be specified in each case. The outer
terminal is then used together with either a solid rod, for maximum
current capacity, or a flexible lead for greater ease of assembly, when the
required current capacity is lower.
Outer terminal D
The outer terminal is available in a number of
standard configurations. Other configurations can
be supplied on request. Terminal
125 stud
O-ring
Divided
Tightening ring
ring
Inner terminal
The inner terminal is made of copper for connection of a draw lead.
47 Insulate Insulate
35 60
up to up to
35
here here
gsa_0008
ø 43 ø 56
ø 49 ø 62
gsa_0043
1600 A 2000 A
Arcing horns
Arcing horns made of galvanised steel can be
mounted on the bushing. The arcing horns are
available for stud with ø 30 mm.
C
The lower rod is fastened onto the flange with one K
of the fixing screws and the upper rod by means of
a bracket on the outer terminal.
H
The gap distances for standard arcing horns are
shown in the table. Other gap distances on request. gsa_0011
Conductor loading
The GSA bushings fulfil the temperature rise test requirements according
to IEC and IEEE for the currents below:
Bushing type Conductor Permissible current
GSA-OA
IEC (A) IEEE (A)
52-73 kV Solid rod 2000 2000
123-170 kV Solid rod 1600 1600
All types Stranded cable
185 mm2 400 400
740 mm2 1250 1250
Overloading of bushings
If the conductor for the bushing is selected with 120 % of the rated current
of the transformer, the bushing is considered to be able to withstand the
overload conditions stated in IEC 60354 without further clarifications or
tests, according to IEC 60137.
Short-time current
The rated thermal short-time current (Ith) is calculated according to IEC
60137.
Conductor Rated Area mm2 Short-time current (Ith) Dynamic
current A kA, rms current (Id)
kA, peak
1s 2s
Solid rod 2000.. 1600 1886 100 96 240
Ø 49 mm Cu
Stranded draw-lead 1250 740 61 43 107
Ordering particulars
When ordering, please state:
• Type and catalogue number for bushing.
• Catalogue number for inner terminal or conductor, lower and upper
part.
• Catalogue number for outer terminal.
• Additional accessories or modifications.
• Test required, in addition to the normal routine tests.
R min 2
45°
R min 5
60° Earthed layer
Distance to flat
surface e.g. tank or
core clamp R
gsa_0057