76.1390 Installations contracted for prior to January 1, 1962. (a) Installations contracted for prior to July 1, 1935, shall meet the following requirements: (1) Existing arrangements, materials, and facilities previously approved will be considered satisfactory so long as they meet the minimum requirements of this paragraph and they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection. Minor repairs and alterations may be made to the same standard as the original installation. (2) The main pipes and their branches to the cargo compartments and similar spaces shall be not less than 112-inch pipe size and shall emanate from not more than two stations in easily accessible locations. If located on the open deck, the distribution manifolds shall be suitably protected by an enclosing cabinet or casing which shall be marked as required by 78.4717 of this subchapter. Each branch line shall have a valve at the manifold which shall be marked as required by 78.47 15 of this subchapter. (3) Branches to paint lockers and similar small spaces may be taken from the nearest stream supply line and shall be not less than 34-inch pipe size. The valve shall be marked as required by 78.4715 of this subchapter. (b) Installations contracted for on or after July 1, 1935, but prior to November 19, 1952, shall meet the following requirements: (1) Existing arrangements, materials and facilities previously approved will be considered satisfactory so long as they meet the minimum requirements of this paragraph and they are maintained in good condition to the satis-
TABLE 76.1390(b)(4)
Volume of compartment in cubic feet Over ........................................ 30,000 ............................ 46,000 ............................ 67,000 ............................ 94,000 ............................ 135,000 .......................... Not over 30,000 46,000 67,000 94,000 135,000 203,000 Number of branches to compartment 1 1 1 ................ 2 3 Pipe size of each branch, inches 1 114 112 114 112 112
(5) The minimum size of the steam supply line from the boiler to the distribution and manifold shall be as given by the following formula: D=C/60,000 (2)
where: D=Diameter of pipe in inches. C=Volume of all compartments in cubic feet.
(c) Installations contracted for on or after November 19, 1952, but prior to January 1, 1962, shall meet the following requirements: (1) Existing arrangements, materials and facilities previously approved will be considered satisfactory so long as they meet the minimum requirements of this paragraph and they are maintained in good condition to the satisfaction of the Officer in Charge, Marine