Instru
Instru
Instru
INTRODUCTION
In the world of cables for industrial applications, INSTRUMENTATION CABLES certainly form one of the most specialized product families. The existing national and international cable standards only present partial solutions, often not sufficient to design an INSTRUMENTATION CABLE which meets customers specific expectations and withstands the often rude conditions on site. A combination of expertise in special materials, diversified production facilities and a long lasting experience with national and international cable standards allow KABELWERK EUPEN to offer INSTRUMENTATION CABLES, taylored to customers specific requirements, but solidely based on internationally recognized standards. KABELWERK EUPEN also has the appropriate human ressources and technical facilities to provide a full PROJECT SUPPORT: * TECHNICAL SUPPORT during cable design stage * Large IN-HOUSE TESTING FACILITIES * COMMERCIAL STAFF experienced in project handling
CHAPTER
1
Overview of the most common CABLE CONSTRUCTION ELEMENTS which can be combined to form an INSTRUMENTATION CABLE and summary of ABBREVIATIONS
CHAPTER
CHAPTER
CHAPTER
2 3 4
11
26
37
CABLE CONSTRUCTION SHEET, allowing to summarize the MSR cable for YOUR specific application
1
2
CONSTRUCTION ELEMENTS
INSTRUMENTATION CABLES
1) APPLICABLE STANDARDS
- Cable constructions & properties can be based on the following standards: IEC BS VDE NF 502 5308 0815/0816 M87-202
- The behaviour of the cable when affected by fire can be defined according to the following standards:
Scope IEC BS VDE
a) Circuit integrity 3 hours b) Fire retardance test on cable bundles c) Flame retardance test on single cables or single insulated cores d) Smoke density test e) Corrosivity of combustion gases (halogen content ...)
N.B.
0472 Pt. 814 0472 Pt. 804 C 0472 Pt. 804 A+B 0472 Pt. 816 0472 Pt. 813
For more information regarding a.m. test methods please revert to our EUCASAFE Safety Cable Catalogue.
HALOGENFREE, FIRE RETARDANT SAFETY CABLES are one of KABELWERK EUPEN AGs specialities
INSTRUMENTATION CABLES
2) CONDUCTORS
According to IEC 228: * Solid * Stranded * Flexible (Class 1) (Class 2) (Class 5)
Typical constructions:
Conductor size Solid mm Stranded mm Diam. mm Flexible mm Diam. mm
0,50 mm2 0,75 mm2 1,00 mm2 1,50 mm2 2,50 mm2
3) INSULATION MATERIALS
* 2Y * 2X *Y *H * HX *R : : : : : : Polyethylene (PE) Polyethylene Foamskin Crosslinked Polyethylene (XLPE) Polyvinylchloride (PVC) Halogen free, fire retardant compound Cross-linked halogen free fire retardant compound EPR rubber (EPR)
* 02YS :
INSTRUMENTATION CABLES
max. 160 nF/km at 1 kHz max. 250 nF/km at 1 kHz max. 75 nF/km at 1 kHz max. 140 nF/km at 1 kHz max. 120 nF/km at 1 kHz
5) SCREENING
Screenings are applied to prevent or reduce the following interferences: * Internal interferences caused by neighbouring line-circuits inside the cable * External interferences caused by electric devices, motors, machineries or power cables Hereafter the most common screening constructions: * (St) * (C) * (St)C * (CuB) : : : : Aluminium laminated synthetic foil in contact with a tinned copper drain wire Tinned copper wire braid Aluminium foil + Tinned copper wire braid Copper tape
INSTRUMENTATION CABLES
6) CABLING
Presentation and abbreviations for cabling elements: - A CORE consisting of one insulated conductor - A PAIR consisting of 2 stranded cores froming a loop - A TRIPLE consisting of 3 stranded cores - A STAR-QUAD consisting of 4 stranded cores, 2 diametrically opposed cores forming a loop INDIVIDUALLY SCREENED cabling elements are expressed as follows: * PIMF * TIMF * QIMF : : : PAIR In Metal Foil TRIPLE In Metal Foil QUAD In Metal Foil
Standard IDENTIFICATION of cabling elements (others on request): a) Unscreened or overall screened cables: - CORE - PAIR - TRIPLE - QUAD : : : : WHITE, each core continuously numbered BLACK / WHITE, each core numbered BLACK / WHITE / RED, each core numbered BLACK / WHITE / RED / BROWN, 2 diametrically opposed cores numbered with the same number
b) Individually sreened cabling elements: - Colour code as a) - Identification of each individually screened cabling element by means of a numbered tape The stranding elements need to be balanced-out in order to reduce crosstalk, therefore Pairs, Triples and Quads are twisted with a different pitch.
INSTRUMENTATION CABLES
Selection criteria:
* Temperature rating (during installation and operation) * Site conditions (oil resistant, termite repellent ...) * PREFERENTIAL COLOURS FOR OUTER-SHEATHS: BLACK : BLUE : GREY OTHERS : Best UV-resistance For intrinsically safe circuits On request
INSTRUMENTATION CABLES
MSR - : EUPEN-code for INSTRUMENTATION CABLES JE RD : cable for INDUSTRIAL ELECTRONICS : cable for CONTROL SYSTEMS
METALLIC BARRIERS:
K (L) : Lead alloy sheath : Alu-Laminated sheath, also called composite layer sheath (Copolymer coated Alu-tape, laminated to the 2Y- or H-sheath)
INSULATION MATERIALS:
2Y
2X
: Polyethylene (PE) : Crosslinked Polyethylene (XLPE) : Polyvinylchloride (PVC) : Heat resistant PVC (max. 90C) : Halogen free, fire retardant compound : Cross-linked halogen free fire-retardant compound : EPR rubber (EPR)
METALLIC ARMOURINGS:
B Q Z R FG : : : : : Double steel tape armour Galvanized steel wire braid Galvanized flat steel wire braid Galvanized round steel wire armour Galvanized flat steel wire armour with a steel tape counter-helix
INDIVIDUAL SCREENS:
PIMF : PAIR In Metal Foil TIMF : TRIPLE In Metal Foil QIMF : QUAD In Metal Foil
OVERALL SCREENS:
(St) : Aluminium laminated synthetic foil in contact with a tinned copper drain wire (C) : Copper wire braid (St)C : Aluminium foil + tinned copper wire braid (CuB) : Copper tape
CABLING:
Bd : Cabling elements forming a bundle and bundles assembled together Bd Z : Bundles identified by means of a numbered tape Bd Si : SIMATIC ring-coding of bundels
10
INSTRUMENTATION CABLES
MSR - 2Y(St)Y
MSR - Y(St)Y
300 V
Construction:
1. 2. 3. 4. 5. MSR
Conductors
2Y Y
Laying-up
: : : : : : :
(St) Y
Instrumentation cable Bare, stranded copper conductors (Class 2 acc. to IEC 228) Polyethylene insulation (compound type 2YI1 acc. to VDE 0207) PVC insulation (compound type Yl3 acc. to VDE 0207) Pairs BLACK / WHITE with continuous numbering, pairs twisted in concentric layers Overall screen consisting of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm PVC outer sheath (compound type YM1 acc. to VDE 0207) BLACK resp. BLUE (for Exi circuits). Other colours on request ex. EUPEN MSR-2Y(St)Y 2 x 2 x 0,75 mm2 300 V
Nominal voltage Test voltage 50 Hz/1m Conductor resistance, Insulation resistance PE insulated PVC insulated Capacitance at 800 Hz PE insulated PVC insulated L/R ratio
Ueff (V) core/core (V) core/screen (V) max. (/km) min. (M.km)
max. 300 2000 1000 39,2 24,6 5000 100 18,4 12,6
max.
max.
25
40
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
12
INSTRUMENTATION CABLES
Conductor stranding
Insulation thickness mm
2 x 2 x 0,5 4 x 2 x 0,5 6 x 2 x 0,5 8 x 2 x 0,5 10 x 2 x 0,5 12 x 2 x 0,5 16 x 2 x 0,5 20 x 2 x 0,5 24 x 2 x 0,5 2 x 2 x 0,75 4 x 2 x 0,75 6 x 2 x 0,75 8 x 2 x 0,75 10 x 2 x 0,75 12 x 2 x 0,75 16 x 2 x 0,75 20 x 2 x 0,75 24 x 2 x 0,75 2x2x1 4x2x1 6x2x1 8x2x1 10 x 2 x 1 12 x 2 x 1 16 x 2 x 1 20 x 2 x 1 24 x 2 x 1 2 x 2 x 1,5 4 x 2 x 1,5 6 x 2 x 1,5 8 x 2 x 1,5 10 x 2 x 1,5 12 x 2 x 1,5 16 x 2 x 1,5 20 x 2 x 1,5 24 x 2 x 1,5
7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53
0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50
1,2 1,2 1,2 1,2 1,2 1,2 1,5 1,8 1,8 1,2 1,2 1,2 1,2 1,5 1,5 1,8 1,8 1,8 1,2 1,2 1,2 1,2 1,5 1,8 1,8 1,8 2,1 1,2 1,2 1,5 1,8 1,8 1,8 2,1 2,1 2,4
8,8 10,0 11,7 12,7 14,6 15,0 17,2 19,5 21,5 9,4 10,7 12,6 13,7 16,4 16,9 19,2 21,2 23,4 10,2 11,7 13,8 15,1 18,0 19,1 21,1 23,3 26,4 11,8 13,6 16,8 18,9 21,8 22,5 25,5 28,1 31,8
24 44 64 84 103 123 163 202 242 34 64 94 124 154 184 244 304 364 45 86 126 167 208 248 330 411 493 66 128 189 251 312 374 497 620 744
85 115 160 185 225 255 345 440 510 105 145 200 235 310 350 470 560 652 118 164 235 285 370 450 565 675 835 165 235 365 465 570 645 865 1030 1260
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays, or in pipes Cables with reinforced outer-sheath Yv or additional outer sheath YY for laying in earth on request
Alternatives constructions:
- Cores laid up in triples or quads - Other possibilities for overall screen: copper wire braid (C) or copper tape (CuB) - Lead sheath K or alternative solutions for refinery applications - SAFETY CABLES, halogen-free and fire retardant
13
INSTRUMENTATION CABLES
300 V
Construction:
1. 2. 3. 4. 5. 6. MSR
Conductors
2Y Y
Laying-up
: : : : : : : :
(St) Y PIMF
Instrumentation cable Bare, stranded copper conductors (Class 2 acc. to IEC 228) Polyethylene insulation (compound type 2YI1 acc. to VDE 0207) PVC insulation (compound type Yl3 acc. to VDE 0207) Pairs BLACK / WHITE with continuous numbering, pairs twisted in concentric layers Overall screen consisting of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm PVC outer sheath (compound type YM1 acc. to VDE 0207) Pairs In Metal Foil (Individual screening of pairs by means of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm) BLACK resp. BLUE (for Exi circuits). Other colours on request ex. EUPEN MSR-2Y(St)Y - PIMF 2 x 2 x 0,75 mm2 300 V
max.
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
14
INSTRUMENTATION CABLES
Conductor stranding
Insulation thickness mm
2 x 2 x 0,5 4 x 2 x 0,5 6 x 2 x 0,5 8 x 2 x 0,5 10 x 2 x 0,5 12 x 2 x 0,5 16 x 2 x 0,5 20 x 2 x 0,5 24 x 2 x 0,5 2 x 2 x 0,75 4 x 2 x 0,75 6 x 2 x 0,75 8 x 2 x 0,75 10 x 2 x 0,75 12 x 2 x 0,75 16 x 2 x 0,75 20 x 2 x 0,75 24 x 2 x 0,75 2x2x1 4x2x1 6x2x1 8x2x1 10 x 2 x 1 12 x 2 x 1 16 x 2 x 1 20 x 2 x 1 24 x 2 x 1 2 x 2 x 1,5 4 x 2 x 1,5 6 x 2 x 1,5 8 x 2 x 1,5 10 x 2 x 1,5 12 x 2 x 1,5 16 x 2 x 1,5 20 x 2 x 1,5 24 x 2 x 1,5
7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53
0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50 0,50
1,2 1,2 1,2 1,2 1,2 1,2 1,5 1,8 1,8 1,2 1,2 1,2 1,2 1,5 1,5 1,8 1,8 1,8 1,2 1,2 1,2 1,2 1,2 1,2 1,5 1,8 2,1 1,2 1,2 1,5 1,8 1,8 1,8 2,1 2,1 2,4
9,8 11,2 13,2 14,4 17,2 17,7 20,2 22,2 25,2 10,4 11,9 14,1 15,4 19,0 19,6 21,6 24,4 27,0 11,2 12,9 15,3 17,3 20,6 21,2 23,5 26,5 30,0 13,0 15,1 19,2 21,0 24,8 25,6 28,3 31,9 36,0
33 62 90 119 147 176 233 290 348 43 82 121 160 198 237 315 392 470 54 103 153 202 252 301 400 499 598 75 145 216 286 356 427 568 708 849
100 150 209 245 325 370 495 590 725 115 175 250 295 420 475 600 750 875 135 205 294 380 495 565 715 895 1095 170 275 455 540 700 795 1010 1255 1530
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays, or in pipes Cables with reinforced outer-sheath Yv or additional outer sheath YY for laying in earth on request
Alternatives constructions:
- Cores laid up in triples or quads with individual screening (TIMF Triples In Metal Foil resp. QIMF Quads In Metal Foil) - Other possibilities for overall screen: copper wire braid (C) or copper tape (CuB) - Lead sheath K or alternative solutions for refinery applications - SAFETY CABLES, halogen-free and fire retardant
15
INSTRUMENTATION CABLES
MSR - 2Y(St)2YRY
MSR - Y(St)YRY
300 V
Construction:
1. 2. 3. 4. 5. 6. 7. MSR
Conductors
2Y Y
Laying-up
: : : : : : : : :
(St) Y 2Y R Y
Instrumentation cable Bare, stranded copper conductors (Class 2 acc. to IEC 228) Polyethylene insulation (compound type 2YI1 acc. to VDE 0207) PVC insulation (compound type Yl3 acc. to VDE 0207) Pairs BLACK / WHITE with continuous numbering, pairs twisted in concentric layers Overall screen consisting of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm PVC inner sheath (compound type YM1 acc. to VDE 0207) PE inner sheath (compound type 2YM1 acc. to VDE 0207) Round, galvanized steel wire armour PVC outer sheath (compound type YM1 acc. to VDE 0207) BLACK resp. BLUE (for Exi circuits). Other colours on request ex. EUPEN MSR-2Y(St)2YRY 2 x 2 x 0,75 mm2 300 V
0,75 mm2
1,0 mm2
1,5 mm2
Nominal voltage Test voltage 50 Hz/1m Conductor resistance, Insulation resistance PE insulated PVC insulated Capacitance at 800 Hz PE insulated PVC insulated L/R ratio
Ueff (V) core/core (V) core/screen (V) max. (/km) min. (M.km)
max. 300 2000 1000 39,2 24,6 5000 100 18,4 12,6
max.
max.
25
40
16
INSTRUMENTATION CABLES
Conductor stranding
Insulation thickness mm
Inner sheath Diameter of Outher sheath Approx. thickness armour wires thickness outer diameter mm mm mm mm
2 x 2 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 12 x 2 x 0,5 16 x 2 x 0,5 24 x 2 x 0,5 2 x 2 x 0,75 4 x 2 x 0,75 8 x 2 x 0,75 12 x 2 x 0,75 16 x 2 x 0,75 24 x 2 x 0,75 2x2x1 4x2x1 8x2x1 12 x 2 x 1 16 x 2 x 1 24 x 2 x 1 2 x 2 x 1,5 4 x 2 x 1,5 8 x 2 x 1,5 12 x 2 x 1,5 16 x 2 x 1,5 24 x 2 x 1,5
7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53
0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,50 0,50 0,50 0,50 0,50 0,50
0,8 0,8 1,0 1,0 1,0 1,2 0,8 1,0 1,0 1,0 1,2 1,2 0,8 0,8 1,0 1,2 1,2 1,4 0,8 1,0 1,2 1,2 1,4 1,6
1,0 1,0 1,2 1,2 1,6 1,6 1,0 1,0 1,2 1,6 1,6 1,6 1,0 1,2 1,2 1,6 1,6 1,6 1,2 1,2 1,6 1,6 1,6 2,5
1,2 1,2 1,5 1,8 1,8 2,1 1,2 1,2 1,8 1,8 2,1 2,4 1,2 1,5 1,8 2,1 2,1 2,4 1,5 1,8 2,1 2,1 2,4 3,1
12,4 13,6 17,8 20,7 23,0 27,7 13,0 14,3 19,5 23,0 25,5 30,5 13,6 16,4 20,8 25,3 27,3 33,0 16,5 19,3 25,1 28,7 32,1 41,5
24 44 84 123 163 242 34 64 124 184 244 364 45 86 167 248 330 493 66 128 251 374 497 744
300 360 590 760 1030 1370 330 400 700 1020 1240 1620 375 535 795 1230 1425 1900 525 690 1230 1530 1885 3270
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays, or in pipes or in earth
Alternatives constructions:
- Cores laid up in triples or quads - Other possibilities for overall screen: copper wire braid (C) or copper tape (CuB) - Lead sheath K or alternative solutions for refinery applications - Other types of armouring galvanized steel tape armour B, resp. round or flat steel wire braid (Q resp. Z) - SAFETY CABLES, halogen-free and fire retardant
17
INSTRUMENTATION CABLES
300 V
Construction:
1. 2. 3. 4. 5. 6. 7. 8. MSR
Conductors
2Y Y
Laying-up
: : : : : : : : : :
(St) Y 2Y R Y PIMF
Instrumentation cable Bare, stranded copper conductors (Class 2 acc. to IEC 228) Polyethylene insulation (compound type 2YI1 acc. to VDE 0207) PVC insulation (compound type Yl3 acc. to VDE 0207) Pairs BLACK / WHITE with continuous numbering, pairs twisted in concentric layers Overall screen consisting of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm PVC inner sheath (compound type YM1 acc. to VDE 0207) PE inner sheath (compound type 2YM1 acc. to VDE 0207) Round, galvanized steel wire armour PVC outer sheath (compound type YM1 acc. to VDE 0207) Pairs In Metal Foil (Individual screening of pairs by means of an aluminium laminated synthetic foil in contact with a tinned, stranded copper drain wire 7 x 0,30 mm) BLACK resp. BLUE (for Exi circuits). Other colours on request ex. EUPEN MSR-2Y(St)2YRY - PIMF 2 x 2 x 0,75 mm2 300 V
0,75 mm2
1,0 mm2
1,5 mm2
Nominal voltage Test voltage 50 Hz/1m Conductor resistance Insulation resistance PE insulated PVC insulated Capacitance at 800 Hz PE insulated PVC insulated L/R ratio
Ueff (V) core/core (V) core/screen (V) max. (/km) min. (M.km)
max. 300 2000 1000 39,2 24,6 5000 100 18,4 12,6
max.
max.
18
INSTRUMENTATION CABLES
Conductor stranding
Insulation thickness mm
Inner sheath Diameter of Outher sheath Approx. thickness armour wires thickness outer diameter mm mm mm mm
2 x 2 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 12 x 2 x 0,5 16 x 2 x 0,5 24 x 2 x 0,5 2 x 2 x 0,75 4 x 2 x 0,75 8 x 2 x 0,75 12 x 2 x 0,75 16 x 2 x 0,75 24 x 2 x 0,75 2x2x1 4x2x1 8x2x1 12 x 2 x 1 16 x 2 x 1 24 x 2 x 1 2 x 2 x 1,5 4 x 2 x 1,5 8 x 2 x 1,5 12 x 2 x 1,5 16 x 2 x 1,5 24 x 2 x 1,5
7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,37 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,43 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53 7 x 0,53
0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,40 0,50 0,50 0,50 0,50 0,50 0,50
0,8 0,8 1,0 1,0 1,2 1,4 0,8 0,8 1,0 1,2 1,2 1,4 0,8 1,0 1,0 1,2 1,2 1,6 1,0 1,0 1,2 1,4 1,4 1,8
1,0 1,2 1,2 1,6 1,6 1,6 1,0 1,2 1,2 1,6 1,6 2,5 1,2 1,2 1,6 1,6 1,6 2,5 1,2 1,2 1,6 1,6 2,5 2,5
1,2 1,2 1,8 1,8 2,1 2,4 1,2 1,5 1,8 2,1 2,1 2,7 1,2 1,5 1,8 2,1 2,4 2,7 1,5 1,8 2,1 2,4 2,7 3,1
13,2 15,3 20,1 23,5 26,4 31,8 13,8 16,6 21,1 25,8 27,8 36 15,3 18,0 23,1 27,4 30,3 38,8 18 20,8 27,2 32,2 37,3 45,4
33 62 119 176 233 348 43 82 160 237 315 470 54 103 202 301 400 598 75 145 286 427 568 849
340 475 735 1075 1300 1730 370 545 820 1260 1460 2600 455 630 1065 1405 1680 2950 590 780 1385 1815 2790 3720
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays, or in pipes or in earth
Alternatives constructions:
- Cores laid up in triples or quads with individual screening (TIMF Triples In Metal Foil resp. QIMF Quads In Metal Foil) - Other possibilities for overall screen: copper wire braid (C) or copper tape (CuB) - Lead sheath K or alternative solutions for referency applications - Other types of armouring galvanized steel tape armour B, resp. round or flat steel wire braid (Q resp. Z) - SAFETY CABLES, halogen-free and fire retardant
19
INSTRUMENTATION CABLES
JE-Y(St)Y... Bd
max. 225 V
Construction:
1. 2. 3. 4. 5. 6. 7. 8.
Conductors
Y (St) Y Bd Z Si
: : : : : : : :
Bare, solid copper conductors PVC insulation (compound type YI1 acc. to VDE 0207) Pair twisting Aluminium laminated synthetic foil in contact with a tinned copper drain wire 1 x 0,80 mm PVC outer sheath (compound type YM1 acc. to VDE 0207) Stranding into units of 4 pairs The units are marked by means of a numbered helix The units are marked by means of SIMATIC ring-coding GREY or BLUE (for Exi circuits)
Ueff (V) core/core (V) core/screen (V) Conductor resistance, (loop) max. (/km) Insulation resistance min. (M.km) Capacitance at 800 Hz max. (nF/km) Capacitance unbalance between pairs at 800 Hz max. (pF/100m)
* + 20% for cables up to 4 pairs ** 20% for measured values or min. one value may be 400
20
INSTRUMENTATION CABLES
1 x 4 x 0,8 4 x 2 x 0,8 8 x 2 x 0,8 12 x 2 x 0,8 16 x 2 x 0,8 20 x 2 x 0,8 24 x 2 x 0,8 32 x 2 x 0,8 40 x 2 x 0,8 48 x 2 x 0,8 80 x 2 x 0,8 100 x 2 x 0,8
Further dimensions on request
1,0 1,0 1,0 1,0 1,2 1,2 1,2 1,4 1,4 1,4 2,0 2,0
6,5 8,5 10,5 12,0 14,0 15,0 16,0 19,0 20,5 23,0 29,0 32,0
55 95 150 210 285 340 400 530 645 750 1300 1550
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays or in pipes Cables with reinforced outer sheath Yv or additional outer sheath YY for laying in earth on request
Alternative constructions:
- Cables can be supplied with armouring (R, B, Q, Z) on request - SAFETY CABLES, halogen-free and fire retardant
21
INSTRUMENTATION CABLES
JE-LiYCY... Bd
max. 225 V
Construction:
1. 2. 3. 4. 5. 6. 7. 8. 9.
Conductors
C Y Bd Z Si
: : : : : : : : :
Stranded copper conductor PVC insulation (compound type YI3 acc. to VDE 0207) Pair twisting Wrapping Copper wire braid PVC outer sheath Type YM1 acc. to VDE 0207 Stranding into units of 4 pairs The units are marked by means of a numbered helix The units are marked by means of SIMATIC ring-coding GREY or BLUE (for Exi circuits)
Ueff (V) core/core (V) core/screen (V) Conductor resistance, (loop) max. (/km) Insulation resistance min. (M.km) Capacitance at 800 Hz max. (nF/km) Capacitance unbalance between pairs at 800 Hz max. (pF/100m)
* + 20% for cables up to 4 pairs ** 20% for measured values or min. one value may be 400
22
INSTRUMENTATION CABLES
Conductor stranding
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter
Applications:
Transmission of analog and digital signals in instrumentation systems The cables are suitable to be laid indoors and outdoors, on cable trays or in pipes Cables with reinforced outer sheath Yv or additional outer sheath YY for laying in earth on request
Alternative constructions:
- Cables can be supplied with armouring (R, B, Q, Z) on request - SAFETY CABLES, halogen-free and fire retardant
23
INSTRUMENTATION CABLES
RD-Y(St)Y... Bd Z
max. 600 V
Construction:
1. 2. 3. 4. 5. 6. 7.
Conductors
Y (St) Y Bd Z
: : : : : : :
Stranded copper conductor PVC insulation Pair twisting Aluminium laminated synthetic foil and tinned copper drain wire PVC outer sheath Stranding into units of 4 pairs The units are marked by means of a numbered helix GREY, BLUE (for Exi circuits) or BLACK for cables with reinforced outer sheath ex. EUPEN VDE-Reg. Nr.
Nominal voltage (peak value) Ueff (V) Test voltage 50 Hz/2min core/core (V) core/screen (V) Conductor resistance, (loop) max. (/km) Insulation resistance min. (M.km) Capacitance at 800 Hz max. (nF/km) Capacitance unbalance between pairs at 800 Hz max. (nF/100m) Line attenuation at 1 kHz (dB/km) 10 kHz Crosstalk attenuation at 10 kHz/500 m (dB) Characteristic impedanc 1 kHz () 10 kHz
* + 20% for cables up to 4 pairs ** 20% for measured values or min. one value may be 400
max. 600 2000 2000 73,6 100 100* 200** 1,2 3,0 60 approx. 370 approx. 130
24
INSTRUMENTATION CABLES
Conductor stranding
1 x 4 x 0,5 4 x 2 x 0,5 8 x 2 x 0,5 12 x 2 x 0,5 16 x 2 x 0,5 20 x 2 x 0,5 24 x 2 x 0,5 32 x 2 x 0,5 48 x 2 x 0,5 96 x 2 x 0,5
7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30 7 x 0,30
1,0 1,0 1,0 1,0 1,2 1,2 1,2 1,4 1,6 1,8
6,5 9,0 11,5 13,5 15,5 16,1 19,0 21,0 25,5 34,0
Other properties:
- Flame retardant acc. to IEC 332-1 (Fire retardant version acc. to IEC 332-3 C available on request) - Temperature range - 30C up to + 70C (- 5C up to + 50C during installation) - Minimum bending radius 7,5 x outer diameter - Suitable for MAXI-TERMI-POINT terminations
Applications:
Transmission of analog and digital signals up to 10 kHz in instrumentation systems in power plants or other industrial applications The cables are suitable to be laid indoors and outdoors, on cable trays or in pipes Cables with reinforced outer sheath Yv or additional outer sheath YY for laying in earth on request
Alternative constructions:
- Cables with heat resistant insulation and sheathing (max. 90C) on request - Cables can be supplied with armouring (R, B, Q, Z) on request - SAFETY CABLES, halogen-free and fire retardant
25
3
26
APPLICATIONS
Telefax from : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
to
KABELWERK EUPEN AG
Cable construction sheet
SERVICE VOLTAGE UO/U
150/250 V 300/500 V 600/1000 V other ............ V
0,75 stranded CL 2 / IEC 228 bare PE 2Y pairs Cu-tape 0,75 stranded CL 2 / IEC 228 bare
2,5
other ............
mm2
INSULATION MATERIAL
Foam skin 02YS XLPE 2X triples other ............ 1,0 flexible CL 5 / IEC 228 1,5 other ............ PVC Y quads N.A. 2,5 other ............ mm2 O. HAL H CROSSL. O. HAL. HX EPR R
STRANDING ELEMENTS
cores
INDIVIDUAL SCREENING
Alu-lam. synth. foil
DRAIN WIRE
0,5 solid CL 1 / IEC 228 tinned
COMMON SCREEN
Alu-lam. synth. foil (St) Alu foil + copper braid (St)C tinned copper braid (C) Cu-tape (CuB) 0,75 stranded CL 2 / IEC 228 bare lead alloy E sheath K round steel wires R galv. flat steel wire braid Z HDPE 2Y PUR 11Y blue PVC Y reinforced v grey other ............ flame retardant IEC 332-1 RH PVC Y O. HAL H CPE CM lead alloy sheath Kb-Pb K flat steel wires + c-helix FG 1,0 flexible CL 5 / IEC 228 1,5 other ............ 2,5 other ............ mm2 N.A.
DRAIN WIRE
0,5 solid CL 1 / IEC 228 tinned
METALLIC SHEATH
Alu-laminated sheath (L)
ARMOURING
double steel tapes B galv. steel wire braid Q
OTHER SHEATH
PE 2Y CSP CSM
COLOUR
black