schneider-electric.com The technical guide
This international site allows you to access all the Schneider Electric products in just 2 clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also nd illustrated overviews, news to which you can subscribe, the list of country contacts
These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.
General contents
Multi 9
Multi 9 circuit breakers from 0.5 to 125 A
A-2
A-2
NG160
Characteristics of NG160 circuit breakers and switch-disconnectors Incomer for modular switchboards
A-4
A-4 A-4
Easypact
Selection table EZC circuit breakers
A-6
A-6 A-6
Compact NSX
Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A
A-10
A-10
Compact NS
Protection of distribution systems Compact NS circuit breakers up to 630 A Compact NS circuit breakers from 630 up to 3200 A
A-12
A-12 A-12 A-14
A-16
A-16 A-16
Masterpact NT and NW
Circuit breakers andswitch-disconnectors NT06 to NT16 NW08 to NW63 Micrologic control units Overview of functions
0
A-18
A-18 A-18 A-20 A-22 A-22
A-24
A-24 A-24
Interpact INS
Switch-disconnector selection Interpact INS250-100 to 630 Interpact INS630b to 2500
A-26
A-26 A-30 A-34
Interpact INV
Switch-disconnector selection Interpact INV100 to 630 Interpact INV630b to 2500
A-38
A-38 A-38 A-43
A-46
Overview of solutions A-46 Manual source-changeover systems InterpactINS/INV and Compact NS 40 A to 630 A A-46 Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-47 Remote-operated source-changeover systems Compact NS 100 A to 1600 A A-48 Remote-operated source-changeover systems Masterpact NT/NW 630 A to 6300 A A-49
Fupact
Switch-disconnector fuses selection Fupact INFp32 to INFp160 Fupact INFp200 to INFp800 Switch-disconnector fuses selection Fupact ISFT100N to ISFT630 Fupact ISFL160 to ISFL630
A-50
A-50 A-50 A-54 A-56 A-58 A-62
Vigirex
Selection guide Protection and monitoring relays
A-66
A-66 A-66
A-1
Multi 9
056984NR_14
DPN N Vigi
1+N 4-40 400 4 230 b b 6 b b b 30-300 30 30-300 b b b b Flexible Rigid 10 16 b 36 81 70
Electrical characteristics
Rated current (A) In Rated insulation voltage (V) Ui Impulse withstand voltage (kV) Uimp Maximum operational voltage (V) Ue AC 50/60 Hz Fast closing Suitability for isolation and positive contact indication
DPN Vigi
PB100270_16
AC breaking capacity
IEC 60898 (EN 60898) IEC 60947-2 (EN 60947-2) Icn (A) Icu (kA) 230/400 V 130 V 230 V 400 V 440 V 500 V (% of Icu) B (lm = 3 to 5 ln) C (lm = 5 to 10 ln) D (lm = 10 to 14 ln) K (lm = 10 to 14 In) Z (lm = 2.4 to 3.2) MA (lm = 12 ln)
Ics
Curve type
a k
056908NR_27
AC A A si A si E
Electrical auxiliaries
Auxiliary and alarm switches (OF-SD) Shunt trip (MX); undervoltage release (MN) Emergency stop opening switch (MNx) Voltage threshold release (MSU)
Connection
Cable maxi capacity (mm2) NG125
Installation
Plug in base Terminal shieds Padlocking device Rotary handle Dimensions (mm)
W H D
A-2
Multi 9
C60N
1 0.5-63 500 6 440 b b 6000 20 10 3 75 % b b b b 10-1000 30-1000 30-1000 30-1000 b b b b 16 (y 25 A) 25 (y 25 A) b b b b 18 per pole 81 73 2-3-4
C60H
1 0.5-63 500 6 440 b b 10000 30 15 4 50 % b b b b 10-1000 30-1000 30-1000 30-1000 b b b b 25 (> 25 A) 35 (> 25 A) b b b b 18 per pole 81 73 2-3-4
C60L
1 0.5-25 500 6 440 b b 50 25 6 50 % 2-3-4 1 32-40 500 6 440 b b 50 20 5 50 % b b b b b b 30-1000 30-300 30 30-300 b b b b 2-3-4 1 50-63 500 6 440 b b 50 15 4 50 % b b b b b b 30-1000 30-1000 30-1000 30-1000 b b b b 2-3-4
C120N
1 63-125 500 6 440 b b 10000 20 10 3 75 % b b b b 30-1000 30-1000 30-1000 30-1000 b b b b 16 25 2-3-4
C120H
1 10-125 500 6 440 b b 15000 30 15 4.5 50 % b b b b 30-1000 30-1000 30-1000 30-1000 b b b b 25 35 b y 63 A b b b 27 per pole 81 73 2-3-4
NG125N
1 10-125 690 8 500 b b 50 25 6 6 75 % b b b b 30-300 30-3000 30-3000 b b b 25 35 b b b 27 per pole 103 81 2-3-4
NG125H
1 10-80 690 8 500 b b 70 36 9 6 75 % b b 30-300 30-3000 30-3000 b b b 35 50 b b b 27 per pole 103 81 2-3-4
NG125L
1 10-80 690 8 500 b b 100 50 12.5 6 75 % b b b b 30-300 30-3000 30-3000 b b b 35 50 b b b 27 per pole 103 81 2-3-4
20 10 6 -
30 15 10 -
50 25 20 -
40 20 15 -
30 15 10 -
20 10 6 -
30 15 10 -
50 25 20 8
70 36 30 10
100 50 40 12
b b b b b b y 40 A b 10-1000 30-500 30 30 b b b b
b b b b 18 per pole 81 73
b b b b 18 per pole 81 73
b b b b 18 per pole 81 73
b y 63 A b b b 27 per pole 81 73
A-3
NG160
Ics
N 40 25 16 10
H 50 36 22 15
Protection
PB103512-40
16 25 32 40 fixed threshold
50
63 800
80
100
125
160
NG160NA switch-disconnector
Electrical characteristics as per IEC 60947-3
Conventional thermal current (A) Rated insulation voltage (V) Rated impulse withstand voltage (kV) Rated operational voltage (V) Rated operational current Ith Ui Uimp Ue Ie 40 C 160 800 8 500 AC22A 160 160 160 160 2.1
lcm
Icw
AC 50/60 Hz AC 50/60 Hz 220/240 V 380/415 V 440/480 V 500 V (kA peak) min. for switchdisconnector alone max. with protection by upstream circuit breaker (A rms) 1s 3s
330
1500 1500 b
Upstream protection
NG160NA downstream Isc max 380 - 415 V Making capacity Isc max 440 V Making capacity
H
70 154 65 143
A-4
NG160
Width in 9 mm modules 10 14 24 27
A-5
Easypact
Selection table
In
at 40 C
Rated insulation voltage (V) Rated impulse withstand voltage (kV) Rated operational voltage (V) EZC100-1P.
Ui Uimp Ue
AC 50/60 Hz DC AC 50/60 Hz 110/130 V 220/230/240 V 380 V 400/415 V 440 V 550 V DC 125 V (1P) 250 V (2P in series) % Icu 110-400 V 415-550 V
PB101840-15
Rated service breaking capacity (kA rms) Suitability for isolation Utilisation category Pollution degree Endurance (C-O cycles)
Ics
EZC100-2P.
PB101843-22
Protection
Overload protection Instantaneous protection Bimetal Magnetic Auxiliary switch Alarm switch Combined AX + AL Shunt trip release Undervoltage release Crimp lugs/bars Box lugs for bare cables Rotary handles Terminal extensions Spreaders Phase barriers Terminal shields Padlocking system DIN rail adaptor Fixed (20 %) AX AL AXAL SHT UVR
Auxiliaries
Indication contacts EZC100-3P. Voltage releases
Installation
PB102172-27
Connection Accessories
Direct Extended
EZC100-4P.
PB101845-29
Weight (kg)
EZC250-3P.
A-6
Easypact
Selection table
EZC100B
3 15, 16, 20, 25, 30, 32, 40, 45, 50, 60 690 6 550 10 10 7.5 7.5 5 2.5 25 % 25 % b A 3 8 500 1 500 fixed fixed b b b b b b b b b b b b b b 60 x 130 75
EZC100F
3 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 25 25 10 10 7.5 5 5 5 50 % 50 % b A 3 8 500 1 500 fixed fixed b b b b b b b b b b b b b b 60 x 130 75
EZC100N
1 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 415 125 25 18 2.5 2.5 5 50 % 50 % b A 3 8 500 1 500 10 10 (2) fixed fixed b b b b b 60 x 130 25 3-4 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 25 25 18 15 10 5 5 5 50 % 50 % b A 3 8 500 1 500 25 10 fixed fixed b b b b b b b b b b b b b b 60 x 130 75 (3P), 100 (4P) 0.78 (3P), 1.0 (4P)
EZC100H
1 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 415 125 50 25 5 5 10 50 % 50 % b A 3 8 500 1 500 18 18 (2) fixed fixed b b b b b 60 x 130 25 2-3-4 15, 16, 20, 25, 30, 32, 40, 45, 50, 60, 63, 75, 80, 100 690 6 550 250 100 100 (1) 30 30 20 10 10 10 50 % 25 % b A 3 8 500 1 500 100 18 (3) fixed fixed b b b b b b b b (3) b (3) b b b (3) b b 60 x 130 50 (2P), 75 (3P), 100 (4P) 0.6 (2P), 0.78 (3P), 1.0 (4P)
EZC250F
3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 25 25 18 18 15 5 5 5 50 % 50 % b A 3 10 000 5 000 25 15 fixed 10 In b b b b b b b b b b b b b b 60 x 165 105
EZC250N
3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 50 50 25 25 20 8 20 20 50 % 50 % b A 3 10 000 5 000 50 18 fixed 10 In b b b b b b b b b b b b b b 60 x 165 105
EZC250H
2-3 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 85 85 36 36 25 10 30 30 50 % 50 % b A 3 10 000 5 000 85 25 (3) fixed 10 In b b b b b b b b b b b b b b 60 x 165 105
0.78
0.78
0.28
0.28
1.3
1.3
(1) 50 kA for 2 poles. (2) For 277 V only. (3) For 3 poles only.
A-7
Easypact
Selection table
In
at 40C
Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue
AC 50/60 Hz DC AC 50/60 Hz 220/230/240 V 380 V 400/415 V 440 V 550 V DC 125 V (1P) 250 V (2P in series) % Icu In/415 V
PB101854-34
Rated service breaking capacity (kA rms) Suitability for isolation Utilisation category Pollution degree Endurance (C-O cycles)
Protection
PB102114-28
Bimetal Magnetic
fixed ( 20 %)
Earth-leakage protection
Sensitivity (A) Time-delay (ms) Max. breaking time (s)
IDn Dt at 2 IDn
adjustable adjustable
Auxiliaries
Indication contacts
Auxiliary switch Alarm switch Combined AX + AL Earth-alarm switch Shunt trip release Undervoltage release
Voltage releases
Installation
EZC400-3P. Connection Accessories
Crimp lugs / bars Box lugs for bare cables Rotary handles Direct Extended Terminal extensions Spreaders Phase barriers Terminal shields Padlocking system
PB102115-36
DxH W
Weight (kg)
EZC400-4P.
A-8
Easypact
Selection table
EZC250N
4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 50 25 25 20 8 20 20 50 % b A 3 10 000 5 000 50 18 fixed 10 In
EZC250H
4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 690 6 550 250 85 36 36 25 10 30 30 50 % b A 3 10 000 5 000 85 25 fixed 10 In b b b b b b b b b b b b b b 68 x 165 140 1.8
EZCV250N
3-4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 440 6 440 85 25 25 20 50 % b A 3 10 000 5 000 50 fixed 10 In 0.1/0.3/0.5/1 0/200/500/1000 0.15/0.4/1/2 b b b b b b b b b b b b b b b 68 x 165 105 (3P) 140 (4P) 1.6 (3P) 2.1 (4P)
EZCV250H
3-4 63, 80, 100, 125, 150, 160, 175, 200, 225, 250 440 6 440 -
EZC400N
3-4 250, 300, 320, 350, 400 690 8 550 250 85 36 36 36 15 20 50 % b A 3 4 000 1 000 50 25 fixed 10 In b b b b b b b b b b b b b 103 x 257 140 (3P) 185 (4P) 5 (3P) 7.5 (4P)
EZC400H
3-4 250, 300, 320, 350, 400 690 8 550 250 100 50 50 50 20 40 50 % b A 3 4 000 1 000 85 35
fixed 10 In
fixed 10 In
b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b
b b b b b b b b b b b b b
A-9
Compact NSX
Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A
Common characteristics
Rated voltages Insulation voltage (V) Impulse withstand voltage (kV) Operational voltage (V) Suitability for isolation Utilisation category Pollution degree IEC 60664-1 Ui Uimp Ue AC 50/60 Hz IEC/EN 60947-2 800 8 690 yes A 3
PB103354-40
Circuit breakers
Breaking capacity levels Electrical characteristics as per IEC 60947-2
Rated current (A) Compact NSX100/160/250. Number of poles Breaking capacity (kA rms) lcu AC 50/60 Hz 220/240 V 380/415 V 440 V 500 V 525 V 660/690 V AC 50/60 Hz 220/240 V 380/415 V 440 V 500 V 525 V 660/690 V Mechanical Electrical 440 V 690 V In 40 C
PB103279-44
In/2 In In/2 In
Connections
Connection terminals Large Cu or Al cables Pitch Cross-section
A-10
Compact NSX
Characteristics and performance of Compact NSX circuit breakers from 100 to 630 A
With toggle With direct or extended rotary handle With remote control b b b b Plug-in base Chassis b b
Common characteristics
Control Manual Electrical Versions Fixed Withdrawable
NSX100
B
100 2 (3), 3, 4 40 25 20 15 85 36 35 25 22 8 90 50 50 36 35 10 90 50 50 36 35 10 100 70 65 50 35 10 100 70 65 50 35 10 120 100 90 65 40 15 120 100 90 65 40 15 150 150 130 70 50 20 150 150 130 70 50 20
NSX160
H S L B
160 2 (3), 3, 4 40 25 20 15 85 36 35 30 22 8 90 50 50 36 35 10 90 50 50 36 35 10 100 70 65 50 35 10 100 70 65 50 35 10 120 100 90 65 40 15 120 100 90 65 40 15 150 150 130 70 50 20 150 150 130 70 50 20
NSX250
H S L B
250 2 (3), 3, 4 40 25 20 15 85 36 35 30 22 8 90 50 50 36 35 10 90 50 50 36 35 10 100 70 65 50 35 10 100 70 65 50 35 10 120 100 90 65 40 15 120 100 90 65 40 15 150 150 130 70 50 20 150 150 130 70 50 20
NSX400
H S L F
400 3, 4 40 36 30 25 20 10 85 50 42 30 22 10 100 70 65 50 35 20 100 70 65 50 11 10 120 100 90 65 40 25 120 100 90 65 12 12 150 150 130 70 50 35 150 150 130 70 12 12
NSX630
S L F
630 3, 4 40 36 30 25 20 10 85 50 42 30 22 10 100 70 65 50 35 20 100 70 65 50 11 10 120 100 90 65 40 25 120 100 90 65 12 12 150 150 130 70 50 35 150 150 130 70 12 12
90 50 20 85 50 10
90 50 20 85 50 10
90 50 20 85 50 15
140 x 255 x 110 185 x 255 x 110 6.05 7.90 45/52.5 mm 45/70 mm 4 x 240
140 x 255 x 110 185 x 255 x 110 6.2 8.13 45/52.5 mm 45/70 mm 4 x 240
A-11
Compact NS
PB101050_33
Connections
Compact NS250H
Compact NS630N
Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 40 C 65 C Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 220/240 V 50/60 Hz 380/415 V 440 V 500 V 525 V 660/690 V Service breaking capacity (kA rms) lcs % Icu Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical 440 V In/2 In Electrical characteristics as per NEMA AB1 (H.I.C.) Breaking capacity (kA) 240 V 480 V 600 V Electrical characteristics as per UL508 Breaking capacity (kA) 240 V 480 V 600 V Protection Trip units Overload protection long time Ir (In x ) Short-circuit protection short time lsd (Ir x ) instantaneous Ii (In x ) Earth-fault protection lg (In x ) Zone selective interlocking ZSI Add-on earth-leakage protection add-on Vigi module combination with Vigirex relay Current measurements Additional measurement, indication and control auxiliaries Indication contacts MX shunt and MN undervoltage releases Voltage-presence indicator Current-transformer module and ammeter module Insulation-monitoring module Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons Dimensions (mm) W x H x D fixed, front connections 2-3P / 4P Weight (kg) fixed, front connections 3P / 4P Source changeover system (see section on source changeover systems) Manual, remote-operated and automatic source changeover systems
PB101044_42
(1) 2P in 3P case for type N only (2) specific trip units are available for operational voltages > 525 V (3) NS100N et U u 500 V: Ics = 50 % Icu (4) operational voltage y 500 V
A-12
Compact NS
NS125E
3, 4 b b b 125 750 8 500 E 25 16/10 10 6 50 % b A 10000 6000 6000 E 5 5 E non interchangeable 12.5 125 (A) b b b b -
NS100
2 (1), 3, 4 b b b b b b b b b 100 100 750 8 690 750 N SX 85 90 36 50 35 50 25 36 22 35 8 10 (3) 100 % b A 50000 50000 30000 N SX 85 90 35 50 8 20 N SX 85 85 25 50 10 10
NS160
2 (1), 3, 4 b b b b b b b b b 160 150 750 8 690 750 N 85 36 35 30 22 8 100 % b A 40000 40000 20000 N 85 35 20 N 85 35 10
NS250
2 (1), 3, 4 b b b b b b b b b 250 220 750 8 690 750 N 85 36 35 30 22 8 100 % b A 20000 20000 10000 N 85 35 20 N 85 35 18
NS400
3, 4 b b b b b b b b b 400 320 750 8 690 750 N 85 50 42 30 22 10 (2) 100 % b A 15000 12000 6000 N 85 42 20 N -
NS630
3, 4 b b b b b b b b b 630 500 750 8 690 750 N H 85 100 50 70 42 65 30 50 22 35 10 (2) 20 (2) (4) 100 % b A 15000 8000 4000 N H 85 100 42 65 20 35 N H -
H 100 70 65 50 35 10
SX 90 50 50 36 35 10
H 100 70 65 50 35 10
SX 90 50 50 36 35 10
H 100 70 65 50 35 10
H 100 70 65 50 35 20 (2)
H 100 65 35 H 85 65 10
L 200 130 50 L -
SX 90 50 20 SX 85 50 10
H 100 65 35 H 85 65 10
L 200 130 50 L -
SX 90 50 20 SX 85 50 18
H 100 65 35 H 85 65 18
L 200 130 50 L -
H 100 65 35 H -
L 200 130 50 L -
L 200 130 50 L -
TM (thermal-magnetic) b b b b b b b b b b b -
STR22 (electronic) b b b b b -
STR23 (electronic) b b b b b b b b b b
STR53 (electronic) b b b b b b b b
b b -
b b -
b b b b b
A-13
Compact NS
DB112530
Compact NS800L
E45178R_68
Compact NS2000H
front connection rear connection front connection with bare cables withdrawable (on chassis) front connection rear connection Electrical characteristics as per IEC 60947-2 and EN 60947-2 Rated current (A) In 50 C 65 C (1) Rated insulation voltage (V) Ui Rated impulse withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz Type of circuit breaker Ultimate breaking capacity (kA rms) lcu AC 220/240 V 50/60 Hz 380/415 V 440 V 500/525 V 660/690 V Service breaking capacity (kA rms) lcs Value or % Icu manual operation electrical operation Short-time withstand current (kA rms) lcw AC 50/60 Hz 1 s 3s Integrated instantaneous protection kA peak 10 % Suitability for isolation Utilisation category Durability (C-O cycles) mechanical electrical 440 V In/2 In 690 V In/2 In Pollution degree Electrical characteristics as per Nema AB1 Breaking capacity at 60 Hz (kA) 240 V 480 V 600 V Protection and measurements Interchangeable control units Overload protection long time Ir (In x ) Short-circuit protection short time Isd (Ir x ) instantaneous Ii (In x ) Earth-fault protection lg (In x ) Residual earth-leakage protection In Zone selective interlocking ZSI Protection of the fourth pole Current measurements Power measurements Advanced protection Remote communication by bus Device-status indication Device remote operation Transmission of settings Indication and identification of protection devices and alarms Transmission of measured current values Additional indication and control auxiliaries Indication contacts Voltage releases MX shunt release/MN undervoltage release Installation Accessories terminal extensions and spreaders terminal shields and interphase barriers escutcheons Dimensions fixed devices, front connections (mm) 3P HxWxD 4P Weight fixed devices, front connections (kg) 3P 4P Source changeover system (see section on "source changeover systems") Manual, remote-operated and automatic source changeover systems
(1) 65 C with vertical connections. See the temperature derating tables for other types of connections. (2) Ics: 100 % Icu for breaking capacity 440V/500V/660V Ics: 75 % Icu for breaking capacity 220V/380V. (3) Except 1600b-3200.
A-14
Compact NS
NS630b
3, 4 b b b (except LB) N H b b b b b b b b b b 630 630 800 8 690 N 50 50 50 40 30 100 % 75 % 19.2 40 b B 10000 6000 5000 4000 2000 3 N 50 35 25
NS800
NS1000
3, 4 b b b N b b b b b 1000 1000 800 8 690 N 50 50 50 40 30 100 % 75 % 19.2 40 b B 10000 6000 5000 4000 2000 3 N 50 35 25
NS1250
3, 4 b b b N b b b b b
NS1600
3, 4 b b b N b b b b 1600 1510 800 8 690 N 50 50 50 40 30 75 % 75 % 19.2 40 b B 10000 5000 2000 2000 1000 3 N 50 35 25
NS1600b
3, 4 b N b 1600 1550 800 8 690 N 85 70 65 65 65 100 % (2) 100 % (2) 32 130 b B 5000 3000 2000 2000 1000 3 N 85 65 50
NS2000
NS2500 NS3200
L b b b b 800 800
LB b b b
H b b b b b
L b b b b
H b b b b b
H b b b b
L 150 150 130 100 100 % 100 % A 4000 3000 3000 2000 L 125 100 -
LB 200 200 200 100 75 100 % A 4000 3000 3000 2000 LB 200 200 100
1250 1250 800 8 690 H L N 70 150 50 70 150 50 65 130 50 50 100 40 42 30 75 % 100 % 100 % 50 % 100 % 75 % 19.2 19.2 40 40 b B A B 10000 6000 4000 5000 5000 3000 4000 4000 3000 3000 2000 2000 2000 3 H L N 65 125 50 50 100 35 50 25
H 70 70 65 50 42 75 % 50 % 19.2 40 B
H 70 70 65 50 42 50 % 50 % 19.2 40 B
H 125 85 85 75 % 75 % 32 130 B
H 65 50 50
H 65 50 50
H 125 85 Micrologic 5.0 P (3) b b b b b b b b b b b b b Micrologic 6.0 P (3) b b b b b b b b b b b b b b Micrologic 7.0 P (3) b b b b b b b b b b b b b
Micrologic 5.0 b b b b b b -
Micrologic 2.0 A b b b b b b b b b b
Micrologic 5.0 A b b b b b b b b b b b b b
Micrologic 6.0 A b b b b b b b b b b b b b
Micrologic 7.0 A b b b b b b b b b b b b b b b
A-15
Number of poles
Service breaking capacity Rated making capacity Utilisation category Breaking time Suitability for isolation Pollution degree (as per IEC 60664-1) Protection against overcurrents (see on catalogue LVPED208006EN) Trip units Protection Durability (O/C cycles)
PB101048-20
Ics Icm
PB101055-27
Fixed
(1) Number of poles taking part in current interruption. Example. The NS100N circuit breaker exists in the following versions: - 1 pole with an Icu of 50 kA, for systems y 250 V - 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.
A-16
NS160
1 160 750 8 250 N 50 50 2 3/4
H 85 85 -
500 N 85 85 85 -
H 85 85 -
500 N 85 85 85 -
161 x 35 x 86 0.7 -
161 x 70 x 86 1.2 -
161 x 35 x 86 0.7 -
161 x 70 x 86 1.2 -
A-17
Masterpact NT and NW
PB100767-48
Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000 12 690/1000 3
Basic sweatchgear
Circuit breaker as per IEC 60947-2
Rated current (A) Rating of 4th pole (A) Sensor ratings (A) Type of circuit breaker Ultimate breaking capacity (kA rms) V AC 50/60 Hz In at 40 C/50 C (1)
Icu
Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 10 %) Rated making capacity (kA peak) V AC 50/60 Hz
Ics Icw
220/415 V 440 V 525 V 690 V 1000 V % Icu 0.5 s 1s 3s 220/415 V 440 V 525 V 690 V 1000 V
Icm
Break time (ms) between tripping order and arc extinction Closing time (ms)
Icw
Ultimate breaking capacity Icu (kA rms) with an external protection relay Maximum time delay: 350 ms Service life Mechanical C/O cycles x 1000 Type of circuit breaker Rated current C/O cycles x 1000 Electrical IEC 60947-2 without maintenance
440 V (4) 690 V 1000 V AC23A 440 V (4) 690V AC3 (5) 380/415 V (kW) 440 V (kW) 440 V (4) 690 V
(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the catalogue LVPED208008EN. (3) SELLIM system. (4) Available for 480 V NEMA. (5) Suitable for motor control (direct-on-line starting).
Type of circuit breaker or switch-disconnector Rated operationnal current Ie (A) C/O cycles x 1000 Electrical without maintenance IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operationnal current Ie (A) Motor power C/O cycles x 1000 Electrical IEC 60947-3 Annex M/IEC 60947-4-1 without maintenance
A-18
Masterpact NT and NW
Sensor selection
Sensor rating (A) 250 (1) Ir threshold setting(A) 100 to 250 (1) For circuit breaker NT02, please consult us. 400 160 to 400 630 250 to 630 800 320 to 800 1000 400 to 1000 1250 500 to 1250 1600 640 to 1600
NT06
630 630 400 to 630 H1 H2 42 50 42 50 42 42 42 42 100 % B B 42 36 42 36 24 20 90 88 105 88 105 88 88 88 88 25 25 < 50 42 42 42 50 50 42
NT08
800 800 400 to 800 L1 (2) 150 130 100 25 A 10 10 x In (3) 330 286 220 52 9
NT10
1000 1000 400 to 1000
NT12
1250 1250 630 to 1250 H1 H2 42 50 42 50 42 42 42 42 100 % B B 42 36 42 36 24 20 90 88 105 88 105 88 88 88 88 25 25 < 50 42 42 42 50 50 42
NT16
1600 1600 800 to 1600
150 100 25
HA 75 75 75 36 36 20 36
HA 75 75 75 36 36 20 36
12.5 H1 H2 630 6 6 3 3 H1/H2/HA 630 6 3 H1/H2/HA 500 y 250 y 300 6 L1 3 2 H1 800 6 3 800 6 3 630 250 to 335 300 to 400 H2 6 3 L1 3 2 H1 1000 6 3 1000 6 3 800 335 to 450 400 to 500 H2 6 3 L1 3 2 H1 1250 6 3 1250 6 3 1000 450 to 560 500 to 630 H2 6 3 H1 6 3 1600 6 3 1000 450 to 560 500 to 630 H2 6 3 -
A-19
Masterpact NT and NW
PB100768-38
Common characteristics
Number of poles Rated insulation voltage (V) Impulse withstand voltage (kV) Rated operational voltage (V AC 50/60 Hz) Suitability for isolation Degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000/1250 12 690/1150 4 (1000 V) / 3 (1250 V)
at 40 C / 50 C (1)
Icu
Rated service breaking capacity (kA rms) Utilisation category Rated short-time withstand current (kA rms) V AC 50/60 Hz Integrated instantaneous protection (kA peak 10 %) Rated making capacity (kA peak) V AC 50/60 Hz
Ics Icw
Icm
Break time (ms) between tripping order and arc extinction Closing time (ms)
Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4) Rated making capacity (kA peak) V AC 50/60 Hz Icm 220...690 V
440 V (5) 690 V 1150 V AC23A 440 V (5) 690 V AC3 (6) 380/415 V (kW) 440 V (5) (kW) 690 V (kW) 440/690 V (5)
(1) 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (2) See the current-limiting curves in the catalogue LVPED208008EN. (3) Equipped with a trip unit with a making current of 90 kA peak. (4) External protection must comply with permissible thermal constraints of the circuit breaker (please consult us). No fault-trip indication by the SDE or the reset button. (5) Available for 480 V NEMA. (6) Suitable for motor control (direct-on-line starting).
Type of circuit breaker or switch-disconnector Rated operational current Ie (A) C/O cycles x 1000 Electrical without maintenance IEC 60947-3 Type of circuit breaker or switch-disconnector Rated operational current Ie (A) Motor power
without maintenance
A-20
Masterpact NT and NW
Sensor selection
250 (1) 400 100 160 to 250 to 400 (1) For circuit breaker NW02 , please consult us. Sensor rating (A) Ir threshold setting(A) 630 250 to 630 800 320 to 800 1000 400 to 1000 1250 500 to 1250 1600 630 to 1600 2000 800 to 2000 2500 1000 to 2500 3200 1250 to 3200 4000 1600 to 4000 5000 2000 to 5000 6300 2500 to 6300
NW20
2000 2000 1000 to 2000 H1 65 65 65 100 % B 65 36 143 143 143 25 < 70 65 65 H2 100 85 85 H3 150 130 100 L1 (2) 150 130 100 H10 50
50 50 105 25
50 50 105 25
50 50 105 25
65 65
100 85
150 100
100 85
150 100
150 100
100 85
150 100
150 100
HA 50 100 % 50 36 105
HF (3) 85 85 50 187
HA 50 100 % 50 36 105
HF (3) 85 85 75 187
HA 55 100 % 55 55 121
HF (3) 85 85 75 187
HA 85 100 % 85 85 187
NW08/NW10/NW12
NA 88 42 HA 105 50 36 HF 187 85 50 HA10 105 50 50
NW16
HA 105 50 36 HF 187 85 50 HA10 105 50 50
NW20
HA 105 50 36 HF 187 85 75 HA10 105 50 50
NW25/NW32/NW40 NW40b/NW50/NW63
HA 121 55 55 HF 187 85 75 HA10 105 50 50 HA 187 85 85 10 5 H1 H2 4000b/5000/6300 1.5 1.5 1.5 1.5 H1/H2/HA 4000b/5000/6300 1.5 1.5
25 12.5 N1/H1/H2 L1 800/1000/1250/1600 10 3 10 3 H1/H2/HA/HF 800/1000/1250/1600 10 10 H1/H2/HA/HF 800 1000 335 to 450 450 to 560 400 to 500 500 to 630 y 800 800 to 1000 6
H10 0.5
20 10 H1/H2 H3 L1 2000 8 2 3 6 2 3 H1/H2/H3/HA/HF 2000 8 6 H1/H2/H3/HA/HF 2000 900 to 1150 1000 to 1300 1600 to 2000
H10 0.5
H10 0.5
A-21
Masterpact NT and NW
All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management.
Dependability
Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor.
Accessories
Certain functions require the addition of Micrologic control unit accessories, described on catalogue LVPED208008EN. The rules governing the various possible combinations can be found in the documentation accessible via the Products and services menu of the www.schneider-electric.com web site.
Current protection
Micrologic 2: basic protection
Protection: long time + instantaneous
DB101116
2.0 A
X Y Z
X: type of protection b 2 for basic protection b 5 for selective protection b 6 for selective + earth-fault protection b 7 for selective + earth-leakage protection. Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement b A for ammeter b P for power meter b H for harmonic meter.
PB100772-32
A-22
Masterpact NT and NW
DB101121
DB101122
DB101123
DB101124
DB101123
DB101124
DB101124
7.0 A
7.0 P
7.0 H
DB101124
6.0 A
6.0 P
6.0 H
DB101122
5.0 A
DB101120
2.0 A
5.0 P
5.0 H
A-23
C or D (3 poles) E (4 poles) In Ui Uimp Ue L/R = 5 ms Icu (A) (V) (kV peak) (V DC) (kA) V DC 500 750 900 500 750 900 500 750 900
PB101129-34
L/R = 15 ms
Icu
L/R = 30 ms
Icu
NW10DC 4P.
Service breaking capacity Rated making capacity Short-time withstand current Utilisation category Breaking time Making time Suitability for isolation Pollution degree (as per IEC 60664-1) Protection against overcurrents (see catalogue LVPED208006EN) Trip units Protection Durability (O/C cycles)
Mechanical Electrical
500 V DC 900 V DC
A-24
NW20
b b 2000 1000 12 500/900 N 85 35 25 -
NW40
b b 4000 1000 12 500/900 N 85 35 25 -
H 100 85 85 85 50 35 50 50 25
H 100 85 85 85 50 35 50 50 25
H 100 85 85 85 50 35 50 50 25
85
50
85
50
85
2000 b b b HA 85 85 b b b b
5000 b b b
2000 b b b HA 85 85 b b b b
2000 b b b
1000 b b b HA 85 85 b b
b b b b
b b b b
b b
439 x 441 x 494 439 x 556 x 494 352 x 422 x 427 352 x 537 x 427 90 to 116 125 to 146 60 to 86 85 to 106
439 x 441 x 594 439 x 556 x 594 352 x 422 x 527 352 x 537 x 527
A-25
Interpact INS
Switch-disconnector selection
Interpact INS40 to 160
052164a-38
Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Interpact INS80 switch-disconnector.
Rated operational voltage AC20 and DC20 (V) Rated operational current (A) Ie
059203a-38
052168a-50
Icw
059202a-50
Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution
Upstream protection
See catalogue LVPED208015EN. (1) Suitable for 480 V NEMA.
A-26
Interpact INS
Switch-disconnector selection
Interpact INS40 to 160
INS40
3-4
INS63
3-4
INS80
3-4
INS100
3-4
INS125
3-4
INS160
3-4
AC23A 40 40 40 32 DC23A 40 40
AC23A 63 63 63 40 DC23A 63 63
AC23A 80 72 63 40 DC23A 80 80
100 100 750 8 690 250 750 AC22A 100 100 100 100 100 DC22A 100 100
125 125 750 8 690 250 750 AC22A 125 125 125 125 125 DC22A 125 125
160 160 750 8 690 250 750 AC22A 160 160 160 160 160 DC22A 160 160
11 7,5 20 22 22 18,5 b Class 120 - 60 % 15 75 3000 1730 670 550 b 20000 AC22A 1500 1500 1500 1500 DC22A 1500 b b 3 -
15 15 30 30 30 22 b Class 120 - 60 % 15 75 3000 1730 670 550 b 20000 AC22A 1500 1500 1500 1500 DC22A 1500 b b 3 -
22 15 37 37 30 22 b Class 120 - 60 % 15 75 3000 1730 670 550 b 20000 AC22A 1500 1500 1500 1500 DC22A 1500 b b 3 -
22 22 45 55 55 55 55 b Class 120 - 60 % 20 154 5500 3175 1230 1000 b 15000 AC22A 1500 1500 1500 1500 1500 DC22A 1500 b b 3 -
37 37 55 55 75 75 75 b Class 120 - 60 % 20 154 5500 3175 1230 1000 b 15000 AC22A 1500 1500 1500 1500 1500 DC22A 1500 b b 3 -
45 45 75 90 90 110 90 b Class 120 - 60 % 20 154 5500 3175 1230 1000 b 15000 AC22A 1500 1500 1500 1500 1500 DC22A 1500 b b 3 -
A-27
Interpact INS
Switch-disconnector selection
Interpact INS40 to 160
Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters
Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module
Locking Interlocking
Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)
A-28
Interpact INS
Switch-disconnector selection
Interpact INS40 to 160
INS40
b b b b -
INS63
b b b b -
INS80
b b b b -
INS100
b b b b b b b b b b b b b 1.4 < Nm < 2 b b b b 8 100 x 135 x 62.5 100 x 135 x 62.5 0.8 0.9 260 x 160 x 55
INS125
b b b b b b b b b b b b b 1.4 < Nm < 2 b b b b 8 100 x 135 x 62.5 100 x 135 x 62.5 0.8 0.9 260 x 160 x 55
INS160
b b b b b b b b b b b b b 1.4 < Nm < 2 b b b b 8 100 x 135 x 62.5 100 x 135 x 62.5 0.8 0.9 260 x 160 x 55
b
b b b b b b b 0.7 < Nm < 1.3 b b b b 8 85 x 90 x 62.5 85 x 90 x 62.5 0.5 0.6 190 x 115 x 55
b
b b b b b b b 0.7 < Nm < 1.3 b b b b 8 85 x 90 x 62.5 85 x 90 x 62.5 0.5 0.6 190 x 115 x 55
b
b b b b b b b 0.7 < Nm < 1.3 b b b b 8 85 x 90 x 62.5 85 x 90 x 62.5 0.5 0.6 190 x 115 x 55
A-29
Interpact INS
Switch-disconnector selection
Interpact INS250-100 to 630
056648a-41
Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V)
Rated operational voltage AC20 and DC20 (V) Rated operational current (A) Ie Interpact INS250 switch-disconnector.
056652a-41
Rated duties Interpact INS250 emergency-off switch-disconnector. Short-circuit making capacity (kA peak) Icm
059487a-54
Icw
Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution
Upstream protection
See catalogue LVPED208015EN. (1) Suitable for 480 V NEMA. (2) 550 A (DC).
059488a-54
A-30
Interpact INS
Switch-disconnector selection
Interpact INS250-100 to 630
INS320
3-4
INS400
3-4
INS500
3-4
INS630
3-4
100 100 750 8 690 250 750 AC22A 100 100 100 100 100 DC22A 100 100
160 160 750 8 690 250 750 AC23A AC22A 100 160 100 160 100 160 100 160 100 160 DC23A DC22A 100 160 100 160
200 200 750 8 690 250 750 AC23A AC22A 160 200 160 200 160 200 160 200 160 200 DC23A DC22A 160 200 160 200
250 250 750 8 690 250 750 AC23A AC22A 200 250 200 250 200 250 200 250 200 250 DC23A DC22A 200 250 200 250
320 320 750 8 690 250 750 AC23A AC22A 250 320 250 320 250 320 250 320 250 320 DC23A DC22A 250 320 250 320
400 400 750 8 690 250 750 AC23A AC22A 320 400 320 400 320 400 320 400 320 400 DC23A DC22A 320 400 320 400
500 500 750 8 690 250 750 AC23A AC22A 400 500 400 500 400 500 400 500 400 500 DC23A DC22A 400 500 400 500
630 630 (2) 750 8 690 250 750 AC23A AC22A 500 630 500 630 500 630 500 630 500 630 DC23A DC22A 500 550 500 550
AC23A 630 630 630 630 630 DC23A DC23B 550 630 550 630
22 22 45 55 55 55 55 b Class 120 - 60 % 30 330 8500 4900 2200 1800 b 15000 AC22A 1500 1500 1500 DC22A 1500 b b 3 -
110 110 200 220 220 250 400 b Class 120 - 60 % 50 330
132 150 250 250 250 355 500 b Class 120 - 60 % 50 330
200 200 315 400 375 400 560 b Class 120 - 60 % 50 330
8500 4900 2200 1800 b 15000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23A DC22A 1500 1500 b b 3 -
8500 4900 2200 1800 b 15000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23A DC22A 1500 1500 b b 3 -
8500 4900 2200 1800 b 15000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23A DC22A 1500 1500 b b 3 -
20000 11500 4900 4000 b 10000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23A DC23A 1500 1000 b b 3 -
20000 11500 4900 4000 b 10000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23B DC23A 1000 b b 3 -
20000 11500 4900 4000 b 10000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23B DC23A 1000 b b 3 -
20000 11500 4900 4000 b 10000 AC23A AC22A 1500 1500 1500 1500 1500 1500 DC23B DC23A 1000 b b 3 -
A-31
Interpact INS
Switch-disconnector selection
Interpact INS250-100 to 630
Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters
Flat-facing bars
Edgewise bars Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Control, locking and interlocking Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle Locking By keylock By padlocks Interlocking By keylock Mechanical Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)
A-32
Interpact INS
Switch-disconnector selection
Interpact INS250-100 to 630
INS320
b b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INS400
b b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INS500
b b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INS630
b b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
A-33
Interpact INS
Switch-disconnector selection
Interpact INS630b to 2500
PB100016a-55
Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V)
Rated operational voltage AC20 and DC20 (V) Rated operational current (A) Ie
380-415 V 440-480 V (1) 500-525 V 660-690 V Electrical DC 125 V (2P in series) 250 V (4P in series) Electrical AC 50/60 Hz 220-240 V 380-400 V 415 V 500-525 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) 0.5 s 0.8 s 1s 3s 20 s 30 s Mechanical Electrical AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V Electrical DC 125 V (2P) 250 V (4P)
PB100018a-55
Rated duties Interpact INS1600 emergency-off switch-disconnector. Short-circuit making capacity (kA peak)
PB100020a-65
Icm
Icw
Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution
Upstream protection
See catalogue LVPED208015EN. (1) Suitable for 480 V NEMA. (2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED208015EN.
A-34
Interpact INS
Switch-disconnector selection
Interpact INS630b to 2500
INS630b
3-4
INS800
3-4
INS1000
3-4
INS1250
3-4
INS1600
3-4
INS2000
3-4
INS2500
3-4
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A
1600 1450 1600 1450 1600 1250 1600 1250 1600 1250
1600 1450 1600 1450 1600 1250 1600 1250 1600 1250
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B
630/2 630/2 630/2 800/2 800/2 800/2 1000/2 1000/2 1000/2 1250/2 1250/2 1250/2 1600/2 1600/2 1600/2 2000/2 2000/2 630/4 630/4 630/4 800/4 800/4 800/4 1000/4 1000/4 1000/4 1250/4 1250/4 1250/4 1600/4 1600/4 1600/4 2000/4 2000/4 250 400 500 560 710 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 5000 250 400 500 560 710 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 315 560 630 710 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 400 710 800 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 400 710 800 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 b Class 120 - 60 % 105 330 50 50 50 30 13 11 b 3000
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A
100 500 100 500 100 500 100 500 100 500 500 500 b b 3 -
100 500 100 500 100 500 100 500 100 500 500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B
1000 1000 b b 3 -
1000 1000
1000 1000
500 500 b b 3 -
500 500
500 500
500 500 b b 3 -
500 500
500 500
500 500 b b 3 -
500 500
500 500
500 500
100 100 b 3 -
100 100
100 100 b 3 -
100 100
A-35
Interpact INS
Switch-disconnector selection
Interpact INS630b to 2500
Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters
Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module
Locking Interlocking
Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)
A-36
Interpact INS
Switch-disconnector selection
Interpact INS630b to 2500
INS630b
b b b b b b b b b b b b b 30 b b b b b 50
INS800
b b b b b b b b b b b b b 30 b b b b b 50
INS1000
b b b b b b b b b b b b b 30 b b b b b 50
INS1250
b b b b b b b b b b b b b 30 b b b b b 50
INS1600
b b b b b b b b b b b b b 30 b b b b b 50
INS2000
b b b b b b b b b b b 60 b b b b b 50
INS2500
b b b b b b b b b b b 60 b b b b b 50
A-37
Interpact INV
Switch-disconnector selection
Interpact INV100 to 630
056650a-41
Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V)
Rated operational voltage AC20 and DC20 (V) Rated operational current (A) Ie Interpact INV250 switch-disconnector.
056654a-41
059491a-54
Icw
Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution Interpact INV400 Std.
Upstream protection
See catalogue LVPED208015EN. (1) Suitable for 480 V NEMA. (2) 550 A (DC).
059493a-52
A-38
Interpact INV
Switch-disconnector selection
Interpact INV100 to 630
INV100
3-4
INV160
3-4
INV200
3-4
INV250
3-4
INV320
3-4
INV400
3-4
INV500
3-4
INV630
3-4
100 100 750 8 690 250 750 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
160 160 750 8 690 250 750 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160 160
200 200 750 8 690 250 750 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
250 250 750 8 690 250 750 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 200 200 200 200
320 320 750 8 690 250 750 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320
400 400 750 8 690 250 750 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400
500 500 750 8 690 250 750 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
630 630 (2) 750 8 690 250 750 630 630 630 630 630 550 550 630 630 630 630 550 550 550 630/630 630/630 630/630 500/630 500/630 550/630 550/630
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/ AC23B
DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/ DC23B
55 55 90 110 110 132 160 b Class 120 - 60 % 30 330 8500 4900 2200 1800 b 15000
AC22A AC23A
75 75 132 150 150 132 160 b Class 120 - 60 % 30 330 8500 4900 2200 1800 b 15000
AC22A AC23A
90 90 160 185 185 220 250 b Class 120 - 60 % 50 330 20000 11500 4900 4000 b 10000
110 110 200 220 220 250 400 b Class 120 - 60 % 50 330 20000 11500 4900 4000 b 10000
132 150 250 250 250 355 500 b Class 120 - 60 % 50 330 20000 11500 4900 4000 b 10000
200 200 315 400 375 400 560 b Class 120 - 60 % 50 330 20000 11500 4900 4000 b 10000
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/ AC23B
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/ DC23B
1500 b b b 3 -
1500
1500 b b b 3 -
1500
1500 b b b 3 -
1500
1500 b b b 3 -
1500
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000/200 b b b b b b b b b b b b 3 3 3 3 -
A-39
Interpact INV
Switch-disconnector selection
Interpact INV100 to 630
Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters
Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module
Locking Interlocking
Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)
A-40
Interpact INV
Switch-disconnector selection
Interpact INV100 to 630
INV100
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6.2 b b b b b b b b b 15 136 x 140 x 96 136 x 140 x 96 2 2.2 400 x 300 x 200
INV160
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6.2 b b b b b b b b b 15 136 x 140 x 96 136 x 140 x 96 2 2.2 400 x 300 x 200
INV200
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6.2 b b b b b b b b b 15 136 x 140 x 96 136 x 140 x 96 2 2.2 400 x 300 x 200
INV250
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6.2 b b b b b b b b b 15 136 x 140 x 96 136 x 140 x 96 2 2.2 400 x 300 x 200
INV320
b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INV400
b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INV500
b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
INV630
b b b b b b b b b b b b b b b b b b b 13.5 < Nm < 16.5 b b b b b b b b b 50 205 x 185 x 130 205 x 185 x 130 4.6 4.9 600 x 400 x 200
A-41
Interpact INV
Switch-disconnector selection
Interpact INV630b to 2500
PB100017a-55
Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V)
Rated operational voltage AC20 and DC20 (V) Rated operational current (A) Ie
380-415 V 440-480 V (1) 500-525 V 660-690 V Electrical DC 125 V (2P in series) 250 V (4P in series) Electrical AC 50/60 Hz 220-240 V 380-400 V 415 V 500-525 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) 0.5 s 0.8 s 1s 3s 20 s 30 s Mechanical Electrical AC 50/60 Hz 220-240 V 380-415 V 440-480 V (1) 500-525 V 660-690 V Electrical DC 125 V (2P) 250 V (4P)
PB100019a-55
Rated duties Interpact INV1600 emergency-off switch-disconnector. Short-circuit making capacity (kA peak) Icm
PB100021a-65
Icw
Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution
Upstream protection
See catalogue LVPED208015EN. (1) Suitable for 480 V NEMA. (2) For vertical connection busbars only. For horizontal connection busbars, see catalogue LVPED208015EN..
A-42
Interpact INV
Switch-disconnector selection
Interpact INV630b to 2500
INV630b
3-4
INV800
3-4
INV1000
3-4
INV1250
3-4
INV1600
3-4
INV2000
3-4
INV2500
3-4
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A
1600 1450 1600 1450 1600 1250 1600 1250 1600 1250
1600 1450 1600 1450 1600 1250 1600 1250 1600 1250
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B
630/2 630/2 630/2 800/2 800/2 800/2 1000/2 1000/2 1000/2 1250/2 1250/2 1250/2 1600/2 1600/2 1600/2 2000/2 2000/2 630/4 630/4 630/4 800/4 800/4 800/4 1000/4 1000/4 1000/4 1250/4 1250/4 1250/4 1600/4 1600/4 1600/4 2000/4 2000/4 250 400 500 560 710 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 5000 250 400 500 560 710 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 315 560 630 710 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 400 710 800 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 400 710 800 900 b Class 120 - 60 % 75 330 50 42 35 20 10 8 b 3000 b Class 120 - 60 % 105 330 50 50 50 30 13 11 b 3000
AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A
100 500 100 500 100 500 100 500 100 500 500 500 b b b 3 -
100 500 100 500 100 500 100 500 100 500 500 500
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B
1000 1000 b b b 3 -
1000 1000
1000 1000
500 500 b b b 3 -
500 500
500 500
500 500 b b b 3 -
500 500
500 500
500 500 b b b 3 -
500 500
500 500
500 500
100 100 b b 3 -
100 100
100 100 b b 3 -
100 100
A-43
Interpact INV
Switch-disconnector selection
Interpact INV630b to 2500
Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters
Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module
Locking Interlocking
Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)
A-44
Interpact INV
Switch-disconnector selection
Interpact INV630b to 2500
INV630b
b b b b b b b b b b b b b 30 b b b b b 50
INV800
b b b b b b b b b b b b b 30 b b b b b 50
INV1000
b b b b b b b b b b b b b 30 b b b b b 50
INV1250
b b b b b b b b b b b b b 30 b b b b b 50
INV1600
b b b b b b b b b b b b b 30 b b b b b 50
INV2000
b b b b b b b b b b b 60 b b b b b 50
INV2500
b b b b b b b b b b b 60 b b b b b 50
A-45
Overview of solutions
Interpact
INS40 to INS80 INS100 to INS160 40 to 160 Switch-disconnectors with extended handles INS250 to INS630 INV250 to INV630 100 to 630 Switch-disconnectors
Compact
NS100 to NS250 NS400 to NS630 100 to 630 N/H/L circuit breakers NA switch-disconnectors
2 devices side-by-side
3 devices side-by-side
ON I
ON I O OFF
2 devices side-by-side
O OFF
2 devices side-by-side
2 devices side-by-side
A-46
Overview of solutions
Compact
NS630b to NS1600 630 to 1600 N/H/L circuit breakers NA switch-disconnectors
Masterpact
NT06 to NT16 630 to 1600 H1/L1 circuit breakers HA switch-disconnectors NW08 to NW63 800 to 6300 N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switchdisconnectors
2 devices side-by-side
O OFF
push
I ON
discharged
O OFF
push
O OFF
push
I ON
discharged
O OFF
FFO hsup
NO h
sup
FFO
O
degr ahcs id
FFO hsup
NO h sup
FFO
O
degr ahcs id
(1)
2 or 3 devices side-by-side
(2)
(1) Implemented with NS630b to NS1600 electrically-operated devices only. (2) For source-changeover systems using cables, always respect the installation conditions specified on catalogue LVPED208007EN.
A-47
Overview of solutions
Range
Models Rating (A) Type of device
Compact
NS100 to NS630 100 to 630 N/H/L circuit breakers NA switch-disconnectors NS630b to NS1600 630 to 1600 N/H/L circuit breakers NA switch-disconnectors
O
sup NO h sup
FFO
O
degr ahcs id
FFO
O
hsup NO h sup
FFO
O
degr ahcs id
2 electrically-operated devices one above the other combined with an electrical interlocking system
2 electrically-operated devices one above the other combined with an electrical interlocking system
DB101776
DB101776
BA controller
A-48
Overview of solutions
Masterpact
NT06 to NT16 630 to 1600 H1/L1 circuit breakers HA switch-disconnectors NW08 to NW63 800 to 6300 N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switch-disconnectors
2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1)
DB101775
DB101776
BA controller
(1) Three devices with Masterpact NW only. (2) For source-changeover systems using cables, always respect the installation conditions specified on catalogue LVPED208007EN. For other cases, please consult us.
A-49
Fupact
059000
Switch-disconnector fuses
Number of poles / type of fuse-link 3 poles / 3 fuse-links 4 poles / 3 fuse-links + switched neutral 4 poles / 4 fuse-links Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3 Conventional thermal current (A) In free air Ith at 40 C Maximum fuse power dissipation (W) In enclosure Ithe at 40 C Maximum fuse power dissipation (W) Rated insulation voltage (V) Ui AC 50/60 Hz / DC Rated impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational voltage AC20 and DC20 (V) Ue Rated operational current (A) Ie AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500/525 V 660/690 V DC/poles in serie 125 V/nbr of pole 250 V/nbr of pole 500 V/nbr of pole 750 V/nbr of pole Rated operational power (kW) (3) AC 220/240 V (motor power given for direct on-line starting) 380/400 V 415 V 500/525 V 660/690 V Rated duties Uninterrupted duty Intermittent duty Rated short-circuit making capacity (kA peak) Icm 415 V Switch-disconnector without fuse (refer to 500 V single- phase fuse limitation curves) 690 V Rated short-circuit breaking capacity (kA rms) / Icn / Icm 415 V (BS) Rated short-circuit making capacity (kA peak) (4) 500 V (DIN) 690 V (DIN) Rated short-time withstand current (A rms) Icw 1s 3s 20 s 30 s Endurance (category A) (CO cycles) Mechanical Electrical AC AC22A 500 V AC22A 690 V AC23A 500 V AC23A 690 V Suitability for isolation Positive contact indication Pollution degree Control Direct front rotary handle Extended front rotary handle Extended lateral rotary handle Locking by padlocks Operating torque (typical for 3 poles switch-disconnector fuses) (Nm) Indication auxiliaries Auxiliary contacts Blown-fuse indicator Fuse monitor Auxiliary contact test position (1) Suitable for 480 V NEMA. (2) AC23B. (3) Some fuse-links limit these values. Motor starting current must be considered separately. (4) Switch-disconnector combined with fuses. (5) Only for NFC fuse-links.
INFB32.
056502
INFC63.
056503
INFD160.
A-50
Fupact
INFp32
NFC-BS NFC-BS NFC 32 3.5 32 3.5 750 8 750 250 690 AC22A 32 32 32 32 32 DC22A 32/2 32/4 8 14 15 18 25 b
INFD40
DIN DIN 40 4.5 40 4.5 750 8 750 250 690 AC22A 40 40 40 40 40 DC22A 40/2 40/4 11 18.5 18.5 22 30 b
INFp63
NFC-DIN-BS NFC-DIN-BS NFC-DIN 63 7.5 63 7.5 750 8 750 250 690 AC22A 63 63 63 63 63 DC22A 63/3 63/3 18.5 30 30 37 60 b
INFB100
BS BS 100 12 100 12 750 8 750 500 690 AC22A 100 100 100 100 100 DC22A 100/2 100/2 100/4 30 45 55 60 90 b
INFC125
NFC NFC NFC 125 12 125 12 750 8 750 500 690 AC22A 125 125 125 125 125 DC22A 125/2 125/2 100/4 37 60 60 80 110 b
INFp160
DIN-BS DIN-BS DIN 160 12 160 10 750 8 750 500 690 AC22A 160 160 160 160 160 DC22A 160/2 160/2 100/4 45 80 90 110 132 b
135 12
AC23A 100 100 100 100 100 (2) DC23A 100/2 100/2 100/4 -
AC23A 125 125 125 125 125 (2) DC23A 125/2 125/2 100/4 -
AC23A 160 160 160 160 160 (2) DC23A 160/2 160/2 100/4 -
class 120-60 % 9 7.5 6 80/176 100/220 50/105 1000 570 220 180 10000 1500 1500 1500 1500 b b 3 b b b b 3 b b (5) b b (standard)
class 120-60 % 9 7.5 6 80/176 100/220 50/105 1000 570 220 180 10000 1500 1500 1500 1500 b b 3 b b b b 3 b b b (standard)
class 120-60 % 17 17 13 80/176 100/220 50/105 2500 1440 560 460 10000 1500 1500 1500 1500 b b 3 b b b b 4 b b (5) b b (standard)
class 120-60 % 22 22 15 80/176 100/220 50/105 5000 2900 1150 950 10000 1500 1500 1500 1500 b b 3 b b b b 8 b b b (standard)
class 120-60 % 22 22 15 80/176 100/220 50/105 5000 2900 1150 950 10000 1500 1500 1500 1500 b b 3 b b b b 8 b b b b (standard)
class 120-60 % 22 22 15 80/176 100/220 50/105 5000 2900 1150 950 10000 1500 1500 1500 1500 b b 3 b b b b 8 b b b (standard)
A-51
Fupact
Switch-disconnector fuses
Type of fuse-link NFC 10 x 38 14 x 51 22 x 58 NH000 NH00 A1 (44.5) F1 A2 (73.0) A3 (73.0) A4 (93.7)
056502
INFC63.
Installation and connection Fixed front connection Terminal tightening torque (Nm) Fuse-link bolts tightening torque (Nm) Installation and connection accessories Bare-cable connectors Terminals Neutral link Terminal shields Dimensions and weight Overall dimensions H x W x D (mm) Approximate weight without fuses (kg) Enclosure dimensions for Ithe
3P 4P 3P 4P H x W x D (mm)
056503
Ith (A)
40 C 45 C 50 C 55 C 60 C 65 C 70 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
(1) Maximum fuse body diameter : 32 mm. (2) A: fuse-link with centre bolted tags. (3) Derating data is based on: - the maximum rating for fuse-links intended for the device, - maximum heat loss. (4) For installation on a ceiling, derate an additional 10 %.
A-52
Fupact
INFD40
b b 2 2 b (standard) b b 97 x 106 x 133 97 x 142 x 133 0.7 0.9
INFp63
b b b b b b b 3.5 2 b (standard) b b 100 x 143 x 128 100 x 188 x 128 1.3 1.6
INFB100
b b b (1) b M8: 15-22 M5: 3.5 b (optional) b b b 140 x 180 x 130 140 x 215 x 130 1.5 1.8 M8: 5
INFC125
b b M8: 15-22 b (optional) b b b 140 x 180 x 130 140 x 215 x 130 1.5 1.8
INFp160
b b b b b b (1) b M8: 15-22 M5: 3.5 b (optional) b b b 140 x 180 x 130 140 x 215 x 130 1.5 1.8 M8: 5
DIN 40 38 36 34 32 30 28 38 36 34 32 30 28 26 24
BS 100 95 90 85 80 75 70 96 92 87 83 78 74 69 65
NFC 125 119 113 106 100 94 88 121 115 109 103 97 92 86 81
DIN-BS 160 152 144 136 128 120 112 156 148 140 133 126 118 111 103
A-53
Fupact
PB104224
Switch-disconnector fuses
Number of poles / type of fuse-link 3 poles / 3 fuse-links 4 poles / 3 fuse-links + switched neutral 4 poles / 4 fuse-links Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3 Conventional thermal current (A) In free air Ith at 40 C Maximum fuse power dissipation (W) In enclosure Ithe at 40 C Maximum fuse power dissipation (W) Rated insulation voltage (V) Ui AC 50/60 Hz / DC Rated impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational voltage AC20 and DC20 (V) Ue Rated operational current (A) Ie AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500/525 V 660/690 V DC/poles in serie 125 V/nbr of pole 250 V/nbr of pole 500 V/nbr of pole 750 V/nbr of pole Rated operational power (kW) (2) AC 220/240 V (motor power given for direct on-line starting) 380/400 V 415 V 500/525 V 660/690 V Rated duties Uninterrupted duty Intermittent duty Rated short-circuit making capacity (kA peak) Icm 415 V Switch-disconnector without fuse (refer to single500 V phase fuse limitation curves) 690 V Rated short-circuit breaking capacity (kA rms) / Icn / Icm 415 V (BS) Rated short-circuit making capacity (kA peak) (3) 500 V (DIN) 690 V (DIN) Rated short-time withstand current (A rms) Icw 1s 3s 20 s 30 s Endurance (category A) (CO cycles) Mechanical Electrical AC AC22A 500 V AC22A 690 V AC23A 500 V AC23A 690 V Suitability for isolation Positive contact indication Pollution degree Control Direct front rotary handle Extended front rotary handle Extended lateral rotary handle Locking by padlocks Operating torque (typical for 3 poles switch-disconnector fuses) (Nm) Indication auxiliaries Auxiliary contacts Blown-fuse indicator Fuse monitor Auxiliary contact test position (1) Suitable for 480 V NEMA. (2) Some fuse-links limit these values. Motor starting current must be considered separately. (3) Switch-disconnector combined with fuses. (4) Category B (5) Only for DIN fuse-links.
INFD200.
A-54
Fupact
INFp200
DIN-BS DIN-BS DIN 200 17 200 15 1000 12 750 750 690 AC22A 200 200 200 200 200 DC22A 200/1 200/2 200/3 180/4 60 110 110 140 200 b class 120-60 % 28 34 22 80/176 100/220 80/176 8000 4600 1800 1450 10000 1000 1000 1000 1000 b 3 b b b b 7 b b (5) b b
INFp250
DIN-BS DIN-BS DIN 250 23 250 20 1000 12 750 750 690 AC22A 250 250 250 250 250 DC22A 250/1 250/2 250/3 230/4 75 140 145 180 250 b class 120-60 % 38 35 25 80/176 100/220 80/176 8000 4600 1800 1450 10000 1000 1000 1000 1000 b b 3 b b b b 7 b b (5) b b (optional)
INFp400
DIN-BS DIN-BS DIN 400 45 400 34 1000 12 750 750 690 AC22A 400 400 400 400 400 DC22A 400/2 400/3 (4) 400/4 (4) 400/4 (4) 130 220 230 300 400 b class 120-60 % 53 56 37 80/176 100/220 80/176 14000 8000 3100 2500 8000 1000 1000 1000 1000 b b 3 b b b 19 b b (5) b b (optional)
INFp630
DIN-BS DIN-BS DIN 630 60 570 50 1000 12 750 750 690 AC22A 630 630 630 630 630 DC22A 630/2 630/3 630/4 630/4 200 355 355 480 630 b class 120-60 % 78 83 63 80/176 100/220 80/176 16000 9200 3600 2900 5000 1000 1000 1000 1000 b b 3 b b b 38 b b (5) b b (optional)
INFp800
DIN-BS DIN-BS DIN 800 65 720 55 1000 12 750 750 690 AC22A 800 800 800 800 800 DC22A 800/2 800/3 800/4 800/4 250 450 450 590 710 b class 120-60 % 78 83 63 80/176 100/220 80/176 16000 9200 3600 2900 5000 500 500 500 500 b b 3 b b b 38 b b (5) b b (optional)
180 18
230 27
360 37
AC23A 200 200 200 200 200 DC23A 200/1 200/2 200/3 180/4
AC23A 250 250 250 250 250 DC23A 250/1 250/2 250/3 230/4
AC23A 400 400 400 400 400 DC23A 400/2 400/3 (4) 400/4 (4) 400/4 (4)
AC23A 630 630 630 630 630 DC23A 630/2 630/3 630/4 630/4
AC23A 800 800 800 800 800 DC23A 800/2 800/3 800/4 800/4
A-55
Fupact
PB104224
Switch-disconnector fuses
Number of poles / type of fuse-link 3 poles / 3 fuse-links 4 poles / 3 fuse-links + switched neutral 4 poles / 4 fuse-links Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3 Conventional thermal current (A) In free air Ith at 40 C Maximum fuse power dissipation (W) In enclosure Ithe at 40 C Maximum fuse power dissipation (W) Rated insulation voltage (V) Ui AC 50/60 Hz / DC Rated impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational voltage AC20 and DC20 (V) Ue Rated operational current (A) Ie AC 50/60 Hz 220/240 V 380/415 V 440/480 V (1) 500/525 V 660/690 V DC/poles in serie 125 V/nbr of pole 250 V/nbr of pole 500 V/nbr of pole 750 V/nbr of pole Rated operational power (kW) (2) AC 220/240 V (motor power given for direct on-line starting) 380/400 V 415 V 500/525 V 660/690 V Rated duties Uninterrupted duty Intermittent duty Rated short-circuit making capacity (kA peak) Icm 415 V Switch-disconnector without fuse (refer to single500 V phase fuse limitation curves) 690 V Rated short-circuit breaking capacity (kA rms) / Icn / Icm 415 V (BS) Rated short-circuit making capacity (kA peak) (3) 500 V (DIN) 690 V (DIN) Rated short-time withstand current (A rms) Icw 1s 3s 20 s 30 s Endurance (category A) (CO cycles) Mechanical Electrical AC AC22A 500 V AC22A 690 V AC23A 500 V AC23A 690 V Suitability for isolation Positive contact indication Pollution degree Control Direct front rotary handle Extended front rotary handle Extended lateral rotary handle Locking by padlocks Operating torque (typical for 3 poles switch-disconnector fuses) (Nm) Indication auxiliaries Auxiliary contacts Blown-fuse indicator Fuse monitor Auxiliary contact test position (1) Suitable for 480 V NEMA. (2) Some fuse-links limit these values. Motor starting current must be considered separately. (3) Switch-disconnector combined with fuses. (4) Category B (5) Only for DIN fuse-links.
INFD200.
A-56
Fupact
INFp200
DIN-BS DIN-BS DIN 200 17 200 15 1000 12 750 750 690 AC22A 200 200 200 200 200 DC22A 200/1 200/2 200/3 180/4 60 110 110 140 200 b class 120-60 % 28 34 22 80/176 100/220 80/176 8000 4600 1800 1450 10000 1000 1000 1000 1000 b 3 b b b b 7 b b (5) b b
INFp250
DIN-BS DIN-BS DIN 250 23 250 20 1000 12 750 750 690 AC22A 250 250 250 250 250 DC22A 250/1 250/2 250/3 230/4 75 140 145 180 250 b class 120-60 % 38 35 25 80/176 100/220 80/176 8000 4600 1800 1450 10000 1000 1000 1000 1000 b b 3 b b b b 7 b b (5) b b (optional)
INFp400
DIN-BS DIN-BS DIN 400 45 400 34 1000 12 750 750 690 AC22A 400 400 400 400 400 DC22A 400/2 400/3 (4) 400/4 (4) 400/4 (4) 130 220 230 300 400 b class 120-60 % 53 56 37 80/176 100/220 80/176 14000 8000 3100 2500 8000 1000 1000 1000 1000 b b 3 b b b 19 b b (5) b b (optional)
INFp630
DIN-BS DIN-BS DIN 630 60 570 50 1000 12 750 750 690 AC22A 630 630 630 630 630 DC22A 630/2 630/3 630/4 630/4 200 355 355 480 630 b class 120-60 % 78 83 63 80/176 100/220 80/176 16000 9200 3600 2900 5000 1000 1000 1000 1000 b b 3 b b b 38 b b (5) b b (optional)
INFp800
DIN-BS DIN-BS DIN 800 65 720 55 1000 12 750 750 690 AC22A 800 800 800 800 800 DC22A 800/2 800/3 800/4 800/4 250 450 450 590 710 b class 120-60 % 78 83 63 80/176 100/220 80/176 16000 9200 3600 2900 5000 500 500 500 500 b b 3 b b b 38 b b (5) b b (optional)
180 18
230 27
360 37
AC23A 200 200 200 200 200 DC23A 200/1 200/2 200/3 180/4
AC23A 250 250 250 250 250 DC23A 250/1 250/2 250/3 230/4
AC23A 400 400 400 400 400 DC23A 400/2 400/3 (4) 400/4 (4) 400/4 (4)
AC23A 630 630 630 630 630 DC23A 630/2 630/3 630/4 630/4
AC23A 800 800 800 800 800 DC23A 800/2 800/3 800/4 800/4
A-57
Fupact
PB104311
ISFT100N.
62193A_SE
ISFT100.
62194A_SE
ISFT160.
62195A_SE
Number of poles / type of fuse-link IEC60 269-2-1 Section 1 Electrical characteristics as defined by IEC 60947-1 / IEC 60947-3 and EN 60947-1 / EN 60947-3 Conventional thermal current (A) In free air Ith at 40 C Maximum fuse power dissipation (W) In enclosure Ithe at 40 C Maximum fuse power dissipation (W) Rated insulation voltage (V) Ui AC 50/60 Hz / DC Rated impulse-withstand voltage (kV) Uimp Rated operational voltage (V) Ue AC 50/60 Hz DC Rated operational voltage AC20 and DC20 (V) Ue Rated operational current (A) Ie AC 50/60 Hz 220/240 V 380/415 V 440/480 V (2) 500 V 660/690 V DC/poles in series 125 V /nbr of poles 220 V /nbr of poles 440 V /nbr of poles Rated duties Uninterrupted duty Rated short-circuit breaking capacity (kA rms)/Rated Icn/Icm/In 415 V short-circuit making capacity (kA peak)/In fuse-link (A) (3) 500 V 690 V Endurance (category B) (CO cycles) Mechanical Electrical AC AC22B 415 V AC23B 415 V AC21B 690 V Suitability for isolation Visible break Pollution degree Control Direct front rotary handle (operator-dependent opening and closing) Locking Padlocks Lead seal Indication auxiliary Auxiliary contacts Fuse monitor Blown-fuse indicator Installation and connection accessories Mounting position possible Horizontal Vertical Bare-cable connectors Other connectors For bare Cu/Al cables For flexible bars Distribution connector Lugs for copper cables Comb busbars Insulated comb covers Incoming connector for comb busbars Terminal shields Dimensions and weight Overall dimension H x W x D (mm) 3P Approximate weight without fuse-links (kg) 3P (1) With 95 mm2 connector. (2) Suitable for 480 V NEMA. (3) Fuse-switch disconnectors with fuse-links.
ISFT630.
A-58
Fupact
ISFT100N
3P/DIN (NH) 100 7.5 100 7.5 1000 6 690 440 690 AC21B AC23B 100 100 100 100 100 100 100 DC21B DC22B 100/3 100/3 100/3 100/3 100/3 100/3 b 80 / 176 / 100 50 / 105 / 100 50 / 105 / 100 2000 300 300 300 b b 3 b b b b b b b 216 x 53 x 82 0.54
ISFT100
3P/DIN (NH) 160 (1) 9 160 (1) 9 690 6 690 440 690 AC21B AC22B 160 160 160 160 100 100 100 DC21B DC22B 100/1 100/1 100/1 b 80 / 176 / 100 50 / 105 / 100 50 / 105 / 100 2000 300 300 b b 3 b b b b b b b b b b 141 x 89 x 71 0.46
ISFT160
3P/DIN (NH) 160 12 160 12 800 8 690 440 800 AC21B AC22B 160 160 160 160 160 160 100 DC21B DC22B 160/1 160/1 160/2 b 50 / 105 / 160 50 / 105 / 160 50 / 105 / 100 1600 200 200 b b 3 b b b b b b b b b b b b b 163 x 107 x 80 0.64
ISFT250
3P/DIN (NH) 250 23 250 23 800 8 690 440 800 AC21B AC22B 250 250 250 250 250 250 250 DC21B DC22B 250/1 250/1 250/2 b 50 / 105 / 250 50 / 105 / 250 50 / 105 / 200 1600 200 200 b b 3 b b b b b b b b b b 246 x 186 x 110 2.06
ISFT400
3P/DIN (NH) 400 34 400 34 800 8 690 440 800 AC21B AC22B 400 400 400 400 400 400 400 DC21B DC22B 400/1 400/1 400/2 b 50 / 105 / 400 50 / 105 / 400 50 / 105 / 315 1000 200 200 b b 3 b b b b b b b b b b 271 x 210 x 127 2.96
ISFT630
3P/DIN (NH) 630 48 630 48 800 8 690 440 800 AC21B AC22B 630 630 630 630 630 630 630 DC21B DC22B 630/1 630/1 630/2 b 50 / 105 / 630 50 / 105 / 630 50 / 105 / 500 1000 200 200 b b 3 b b b b b b b b b b 271 x 250 x 132 4.00
A-59
Fupact
PB104311
Fuse-switch disconnectors
Type of fuse-link DIN NH000 DIN NH00 DIN NH1 DIN NH2 DIN NH3 Installation and connection Symmetrical rail Direct connection on backplate Push-on connection to 60 mm busbars Hook-on connection to 60 mm busbars Hook-on connection to 100 mm busbars Tightening torque (Nm) Temperature derating (with gG fuse-link) (1) (2) Vertical mounting fuse-links in vertical position
ISFT100N.
62193A_SE
Ith (A)
Ith (A)
40 C 45 C 50 C 55 C 60 C 65 C 70 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
ISFT100.
62194A_SE
(1) Derating data is based on: - the maximum rating for fuse-links intended for the device, - maximum heat loss. (2) For installation on a ceiling, derate an additional 10 %. (3) With 100/160 A fuse-link.
ISFT160.
62195A_SE
ISFT630.
A-60
Fupact
ISFT100N
b -
ISFT100
b -
ISFT160
b b b b b -
ISFT250
b b b b b
ISFT400
b b b b
ISFT630
b
b b b b b see catalogue LVPED208014EN 100 95 90 85 80 75 70 100 95 90 85 80 75 70 100/160 (3) 95/152 90/144 85/136 80/128 75/120 70/112 100/160 (3) 95/152 90/144 85/136 80/128 75/120 70/112
b b b
160 152 144 136 128 120 112 160 152 144 136 128 120 112
250 238 225 213 200 188 175 250 238 225 213 200 188 175
400 380 360 340 320 300 280 400 380 360 340 320 300 280
630 599 567 536 504 473 441 630 599 567 536 504 473 441
A-61
Fupact
62196
ISFL160.
62197
ISFL250.
A-62
Fupact
ISFL160
3P/DIN (NH) 160 12 160 12 800 8 690 440 800 AC21B 160 160 160 160 100 DC21B b 50 / 105 / 160 50 / 105 / 160 50 / 105 / 100 1600 200 200 b b 3 b b b b (3) b b b b b b b 456 x 50 x 159 1.35
ISFL250
3P/DIN (NH) 250 23 250 23 800 8 690 440 800 AC21B 250 250 250 250 250 DC21B b 100 / 220 / 250 50 / 105 / 250 50 / 105 / 200 1600 200 200 b b 3 b b b b b b b b 755 x 100 x 192 6.35
ISFL400
3P/DIN (NH) 400 34 400 34 800 8 690 440 800 AC21B 400 400 400 400 400 DC22B b 100 / 220 / 400 50 / 105 / 400 50 / 105 / 315 1000 200 200 b b 3 b b b b b b b b 755 x 100 x 192 6.35
ISFL630
3P/DIN (NH) 630 48 630 48 800 8 690 440 800 AC21B 630 630 630 630 630 DC22B b 100 / 220 / 630 50 / 105 / 630 50 / 105 / 500 1000 200 200 b b 3 b b b b b b b b 755 x 100 x 192 6.35
A-63
Fupact
62196
Type of fuse-link DIN NH000 DIN NH00 DIN NH1 DIN NH2 DIN NH3 Installation and connection Hook-on connection to 60 mm busbars Direct connection to 100 mm busbars Direct connection to 185 mm busbars To 60 mm busbars using single-device conversion kit To 185 mm busbars using single or double device conversion kit Tightening torque (Nm) Temperature derating (with gG fuse-link) (1) Vertical mounting fuse-links in vertical position ISFL160.
Ith (A)
62197
Ith (A)
40 C 45 C 50 C 55 C 60 C 65 C 70 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
(1) Derating data is based on: - the maximum rating for fuse-links intended for the device - maximum heat loss.
ISFL250.
A-64
Fupact
ISFL160
b b b b b b see catalogue LVPED208014EN 160 152 144 136 128 120 112 160 152 144 136 128 120 112
ISFL250
b b -
ISFL400
b b -
ISFL630
b b -
A-65
Vigirex
Selection guide
DB107087
DB107092
DB107089
Functions
Protection Local indications Remote indications (hard-wired) Remote indications (via communication) Display of measurements b b b b b b b b 1 fixed instantaneous threshold choose from 0.03 A to 1 A b b b b b b b b 2 user-selectable thresholds 0.03 A or 0.3 A -
Wiring
Optimum continuity of service Optimum safety (failsafe)
Mounting
DIN rail Front-panel mount
Thresholds
Fault (IDn)
Alarm
Pre-alarm
Time delays
Fault Instantaneous Instantaneous for IDn = 0.03 A 1 user-selectable time delay instantaneous or 0.06 s for IDn = 0.3 A -
Alarm
Pre-alarm
Communication
Suitable for supervision (internal bus)
Characteristics
Sensors
b Merlin Gerin A, OA, E toroids (7) up to 630 A b Merlin Gerin rectangular sensors up to 3200 A (1) Type A relay up to IDn = 5 A. (2) Relay with output contact requiring local, manual reset after fault clearance. (3) Relay with output contact that automatically resets after fault clearance. b b (4) Mandatory with an RMH (multiplexing for the 12 toroids). (5) Mandatory with an RM12T (multiplexing for the 12 toroids).
A-66
DB107091
Vigirex
Selection guide
PB100429-18
PB100432-20
DB107088
DB107090
DB107086
DB107093
059484R_
(4)
b b b b except RHUs b b b b b 1 adjustable threshold from 0.03 A to 30 A 1 adjustable threshold from 0.015 A to 30 A -
b b b b b b -
b b b b b -
b b b b b -
b b b -
b b
b b
b b
b b (8) On a bargraph (9) No voltage presence relay. (10) With actuation of contacts only.
b b
(6) Depending on the type of wiring (optimum continuity of service or optimum safety). (7) See catalogue LVPED208009EN.
A-67
Notes
A-68
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper . Design: Schneider Electric Photos: Schneider Electric Printed: Centre impression - made in France 12-2008
http://www.schneider-electric.com
http://www.schneider-electric.co
LVPED208013EN