Electric Heat Tracing: Installation Procedures
Electric Heat Tracing: Installation Procedures
Electric Heat Tracing: Installation Procedures
INSTALLATION PROCEDURES
Applications . . .
1. Electric heat tracing cables are used for freeze protection or temperature maintenance of piping, tanks and instrumentation. This set of instructions covers typical piping applications. For installation details on tanks and instrumentation, refer to the Installation Guides on our website www.thermon.com. 2. Heat tracing cables may be installed in ordinary (nonclassied) and hazardous (classied) locations depending on the specic cable options and approvals2. The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for electric heat tracing .
4 5
8 6 7
Initial Installation . . .
1. Locate the cable on the lower quadrant of the pipe at the 4 or 8 oclock position. If accessibility is a problem the cable may be installed at the 10 or 2 oclock position. Temperature sensor should be located at least 90 from all heating cables. Refer to Illustration B for Heating Cable vs. Sensor Location. 2. Begin temporary installation at the proposed end-of-circuit location and lay out heating circuit on the pipe, allowing extra cable for the power connection and for any splice locations3. Refer to Illustration C for temporary installation. 3. Make heating cable allowances for valves, anges, elbows and supports as per the applicable drawings and table on pages 3 and 4 of these installation procedures.
Temperature Sensor (Typical) 45 90 45 Pipe Wall
90
45
45
45
45
Pipe Support
Notes . . .
Cable Allowance for In-Line Heat Sinks Proposed Power Connection Location
1. Termination kits to fabricate a heat tracing circuit are not addressed in detail in these installation procedures. Refer to installation instructions included with cable termination kits or contact Thermon for specic instructions to fabricate heating cable. 2. For information on specic cable types and options, refer to Types of Heating Cables on page 1. 3. Heating cable minimum bend radius is 10mm (3/8) at -15C (5F). See product specication sheet for additional details.
Heating Cable
Heating Cable
3 Min. (8 cm)
3 Min. (8 cm)
Support Length
Note: Flange allowance will vary based on method of insulating ange and adjacent piping.
Heating Cable Attachment Tape (Typical) Heating Cable Serpentined on Valve Heating Cable Serpentined on Pump
Attachment Tape
Table 2: Attachment Tape (Value Represents Approximate Linear Pipe Length Allowance Per Roll)
Tape Length 36 yd 60 yd Pipe Diameter in Inches "-1" 130' 215' 1" 115' 195' 1" 110' 180' 2" 95' 160' 3" 75' 125' 4" 65' 105' 6" 50' 80' 8" 40' 65' 10" 35' 55' 12" 30' 50' 14" 26' 43' 16" 23' 38' 18" 21' 35' 20" 19' 31' 24" 16' 27' 30" 13' 22'
Thermal Insulation . . .
1. The need for properly installed and well-maintained thermal insulation cannot be overemphasized. Without insulation, heat losses are generally too high to be offset by a conventional heat tracing system. 2. In addition to piping and in-line equipment such as pumps and valves, all heat sinks must be properly insulated. This includes pipe supports, hangers, anges and, in most cases, valve bonnets. 3. Regardless of the type or thickness of insulation used, a protective barrier should be installed. This protects the insulation from moisture intrusion, physical damage and helps ensure the proper performance of the heat tracing system. Seal around all penetrations through the thermal insulation. 4. After the installation of the thermal insulation and weather barrier but BEFORE ENERGIZING THE HEATING CIRCUIT, the megohmmeter test should be repeated. This should call attention to any damage to the heating cable that may have occurred during the insulation installation. (Record 3 on Cable Testing Report)
Heater
NC
COM
5. Apply caution labels to insulation weather barrier at required intervals along pipe
1. It is recommended that the circuit be temporarily energized so that the volts, amps, pipe temperature and ambient temperature may be recorded. This information may be of value for future reference and should be maintained for the historical operating data log (Record 4 on Cable Testing Report). 2. Stabilized design can be used for self-regulating heating cables to assign a lower T-class through the use of the Thermon CompuTrace software or Thermon Engineering. 3. Stabilized design can be used for power-limiting and constant watt heating cables without a limiting device to determine the T-class through the use of the Thermon CompuTrace software or Thermon Engineering. 4. A sample historical operating data log form is included in the Electric Heat Tracing Maintenance and Troubleshooting Guide, Thermon Form TEP0066). The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for branch circuits supplying electric heat tracing.
COM
Thermostat Sensor
Heater
NOTE: To ensure the heating cable warranty is maintained through installation, the testing outlined on this sheet must be completed on the installed heating cables, and the test results recorded and mailed/faxed to: Thermon Customer Service 100 Thermon Drive San Marcos, Texas 78666 Fax: 512-754-2420
THERMON . . . The Heat Tracing Specialists 100 Thermon Dr. PO Box 609 San Marcos, TX 78667-0609 Phone: 512-396-5801 Facsimile: 512-396-3627 1-800-820-HEAT In Canada call 1-800-563-8461 Specications and information are subject to change without notice. Form PN50207-1111