Aqua Var
Aqua Var
Aqua Var
Models covered: All AV2 Model AQUAVAR II Controllers software revision 120
UL
IM131R01
Program Record
Please use the following to record the final values programmed into the AQUAVAR controller after installation. Required Value____________________ (select) Autostart ________________________ (on/off) Password ________________________ (value) Window ___________________________ (%) Ramp Hysteresis _____________________ (%) Ramp 1 _______________________ (seconds) Ramp 2 _______________________ (seconds) Ramp 3 _______________________ (seconds) Ramp 4 _______________________ (seconds) Max. Frequency _____________________ (Hz) Min. Frequency ______________________ (Hz) Config. F Min. __________ (F >0/F >F min.) Stop - Delay F Min._______________ (seconds) Sensor Adjust _______________ (out of range) Sensor Curve _____________ (linear/quadratic) Sensor Range - 20mA=362.6 __________ (PSI) Mode___________________________ (select) (actuator/controller/multicontroller/synch.) Regulation Mode _________________ (normal) Start Value _________________________ (PSI) Config. Second Value _________________ (off) Relay Config.__________________ (run motor) Offset Input ____________________________ Level 1 ____________________________ (%) Level 2____________________________ (%) Intensity 1 _________________________ (%) Intensity 2 _________________________ (%) Pressure Increase ___________________ (PSI) Pressure Decrease___________________ (PSI) Enable Sequence Control______________ (Hz) Switch Interval ___________________ (hours) Optional Value _________________________ Synchron Limit _____________________ (Hz) Sychron Window ____________________ (Hz) Pump Address _________________ (# or off) ADC Reference ___________________ (select) Freq. Lifting________________________ (Hz) Lift Intensity________________________ (%) Analog out ______________________ (select) Pressure Unit ____________________ (select) Test Run After__________________ (in hours) Test Frequency______________________ (Hz) Conveyor Limit _____________________ (PSI) Delay Time ____________________ (seconds) Error Reset ______________________ (on/off) Display Contrast_____________________ (%) Lock Function ____________________ (on/off)
Index
Index
!
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Materials Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1. Mounting the AQUAVAR II Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2. Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3. Pump Priming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 4. Run Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 1. The Main Menu - Setting One Pump Constant Pressure . . . . . . . . . . . . . . . . 31 2. Single Pump - Pump Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 To Set Run-Out Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 To Set Low/No Flow Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 3. Single Pump - System Curve Compensation . . . . . . . . . . . . . . . . . . . . . . . . 38 Entering Compensation Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Circulator Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 4. Single Pump Constant Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 5. Single Pump - Level Control Applications . . . . . . . . . . . . . . . . . . . . . . . . . . 43 6. Single Pump - Submersible . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 7. Setting a Second Required Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 8. Variable Second Required Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 9. Multiple Pump Constant Pressure and System Curve Compensation . . . . . . . 53 Synchronous Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 10. Multiple Pump - Pump Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 To Set Low/No Flow Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Operator Custom Features and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Jog Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Ramp Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Ramp Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Ramp 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Maximum Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 Minimum Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Config. F Min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Stop-Delay F Min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Sensor Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Sensor Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Start Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Config. Required Value 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Relay Config. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Submenu Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Regulation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Submenu Sequence Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Actual Value Increase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Index
Index (continued)
Operator Custom Features and Displays (continued) Actual Value Decrease . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Enable Sequence Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Switch Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Source Required Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Submenu Synchronous Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Synchronous Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Synchronous Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Pump Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Pump - Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 ADC Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Frequency Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Lift Intensity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Analog Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Pressure Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Submenu Test Run Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Submenu Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Clear Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Operating Hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Total Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Display Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Set Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Lock Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Heating On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Default Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Save ?? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Repair of Faults and Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Lack of Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Conveyor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Error 1-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Pressure Sensor Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Inverter Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 External Device Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Active Fault / Warning and Fault History Mode . . . . . . . . . . . . . . . . . . . . . . 70 Aquavar II Electrical Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Programming Flow Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Help Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Appendix A - Pressure Transducer Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Appendix B - AQUAVAR Controller Technical Data and Terminals . . . . . . . . . . . . . . . . .87 Appendix C - Interference Suppression Measures . . . . . . . . . . . . . . . . . . . . . . . . . .89
9 8 4 1 5
14
9 4
1 Pump with AQUAVAR controller 2 Diaphragm tank 3 Distribution panel 4 Gate valves 5 Check valves 6 Foot valves 8 Incoming pressure switch 9 Pressure gauges 10 Level switches 11 Supply tank 14 Pressure transmitter (Included with AQUAVAR) *
A diaphragm pressure tank is used on the discharge side of the pump or pumps to maintain pressure in the line when there is no demand. This will keep the pumps from continuing to run. With the AQUAVAR controller, it is not necessary to have a large tank for supply purposes. In selecting a tank, make sure it can withstand maximum system pressure. The tank should have a capacity of at least 10% of the maximum system flow rate in gpm. Pre-charge the tank to the following:
PSI Set Pressure PSI Tank Pre-charge 15 12 30 21 45 37 60 52 75 64 90 77 105 95 120 110 135 125 150 138
Note
Closed loop circulator systems may not require a pressure tank.
*Check with tank pressure limitations before precharge.
Safety Instructions
Important: Read all safety information prior to installation of the AQUAVAR controller.
Note
This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
DANGER WARNING
CAUTION
NOTICE
Warns of hazards that WILL cause serious personal injury, death, or major property damage. Warns of hazards that CAN cause serious personal injury, death, or major property damage. Warns of hazards that CAN cause personal injury or property damage. Indicates special instructions which are very important and must be followed.
1. This manual is intended to assist in the installation, operation, and repair of the AQUAVAR controller and must be kept with the AQUAVAR controller.
Note
All operating instructions must be read, understood, and followed by the operating personnel. Goulds Pumps accepts no liability for damages or operating disorders which are the result of non-compliance with the operating instructions. When in doubt, call for assistance. 2. To avoid serious or fatal personnel injury or major property damage, read and follow all safety instructions in this manual.
Note
Inspect AQUAVAR controller for any damage after unpacking from shipping crates. Report any damage immediately to the carrier or distributor/dealer immediately. 6. In addition to instructions contained in this manual, you must meet any local safety, electrical, or plumbing codes and requirements. Installation, maintenance, or repair work must only be carried out by trained, skilled, and qualified personnel, using proper protective gear and tools. 7. The AQUAVAR controller drive head must be disconnected from the main power supply before attempting any operation in the electrical or mechanical part of the system.
Note
When in operation, the motor can be stopped, but power remains at the drive head. The motor and pump could start unexpectedly and produce serious injury. When the AQUAVAR controller drive head is connected to the main power supply, the inverter power supply and master control unit are also connected to the power supply.
WARNING
WARNING!
FAILURE TO DISCONNECT ELECTRICAL POWER BEFORE ATTEMPTING ANY MAINTENANCE CAN CAUSE SHOCK, BURNS, OR DEATH.
Safety Instructions
Note
TOUCHING THESE COMPONENTS SERIOUSLY ENDANGERS LIFE! Voltages of up to 800 volts are possible (higher if there is a fault). Before removing the AQUAVAR controller drive top cover, the system must be disconnected from the main power supply. After switching off the power supply, you must wait at least 5 minutes before starting work on or inside the AQUAVAR controller drive head. This allows the capacitors in the circuit to be discharged by the discharge resistors. 8. The AQUAVAR controller has electronic safety devices which will stop the motor in the event of electrical or thermal faults. This does not remove power to the AQUAVAR controller.
WARNING
WARNING!
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
Note
Care must be taken when connecting external control wires and jumpers to avoid short circuit to neighboring components. 9. The system must be properly grounded before being put into operation. Use a common ground for the entire system. 10. High voltage tests of the AQUAVAR controller may damage the electronic components. Before carrying out such a test, bridge the incoming and outgoing terminals L1 - L2 - L3 - U - V W. Isolate the motor from the AQUAVAR controller drive to avoid incorrect capacitor metering inside the AQUAVAR controller.
Note
Repair of electrical faults can lead to the automatic restart of the motor and pump. You must remove all main line power to the AQUAVAR controller before attempting to correct a fault.
Installation Procedures
Step 1- Identify Materials
The following materials are provided with the AQUAVAR II controller. Please familiarize yourself with each prior to installation.
Part
1. AQUAVAR Controller 2. Pressure Transducer Assembly a. Pressure transducer - 25 bar b. Transducer adapter - (available as separate part only) See price book. c. 30 ft. transducer cord (standard) for AV II.
3.45
Quantity
1 1 1 /4 NPT 1 /4 NPT female threads & 3/8 B male thread per UNI ISO/228/1 (British Standard pipe threads)
14
NPT
1.07
34
HEX
2c
2a
2b
(If needed.)
Note
YOU MUST USE THE CABLE THAT IS PROVIDED WITH THE TRANSDUCER. DO NOT USE DIFFERENT CABLES OR OLDER STYLE CABLES.
WARNING
THE AQUAVAR CONTROLLER AND PUMP MUST BE TOTALLY DISCONNECTED FROM ALL POWER SUPPLY SOURCES BEFORE BEGINNING INSTALLATION OR REPAIR.
WARNING
WARNING!
FAILURE TO DISCONNECT ELECTRICAL POWER BEFORE ATTEMPTING ANY MAINTENANCE CAN CAUSE SHOCK, BURNS, OR DEATH.
Installation Procedures
Step 2 - Mounting the AQUAVAR II controller: AQUAVAR Controller
The AQUAVAR controller may be installed as a wall or panel mounted unit. The AQUAVAR controller may be mounted up to 60 feet away from the pump motor*. In addition, alternative motor enclosures may be selected such as ODP , explosion proof or wash down motors in addition to the TEFC enclosure required for on the pump mounting. Typical applications for the AQUAVAR Wall Mount controller include: 1. Hazardous environment applications including high heat, humidity or combustibility. 2. Installation to an existing pumping system with non-standard motors. 3. Installations where the operator desires all controls to be grouped together. Mounting of the AQUAVAR II Controller 1. An alternative mounting style is used in the AQUAVAR II controller configuration. In this style, the AQUAVAR II controller is supplied with a fan and mounting bracket already installed and can be mounted to a wall or panel. 2. 3. The mounting bolts for all units should be 14". The length of bolt and the strength of the mounting surface must be adequate to support the weight of the AQUAVAR II controller. The AQUAVAR II controller may be positioned up to 60 feet from the pump motor. The pump motor must be three phase. Unlike the standard AQUAVAR controller, the motor may be ODP , TEFC or explosion proof.* Mount the AQUAVAR controller to the panel, wall or frame using bolts at the points indicated on the following drawings. Be sure the unit is level and secured to the mounting surface before continuing. Ensure plenty of airflow for the AQUAVAR controller, when mounting.
4.
5.
*NOTE: If the AQUAVAR II controller is more than 60 feet wire length to motor, then the use of a load reactor (impedance coil) is required.
10
Installation Procedures
Step 2 - Mounting the AQUAVAR controller: (continued)
Diagram 3 HP Rating
1 10 (230 3) 1 5 (230 1) 1 20 (575) 15 20 (230 3) 712 10 (230 1) 25 40 (460) 25 40 (575) 25 75 (460) 25 75 (575)
A in (mm)
3.20 (81.28) 3.20 (81.28) 3.20 (81.28)
B in (mm)
7.88 (200.15) 7.88 (200.15) 7.88 (200.15)
C in (mm)
16.50 (419.10) 19.25 (488.95) 28.00 (711.20)
D in (mm)
9.32 (236.70) 11.44 (290.53) 12.68 (322.07)
E in (mm)
17.44 (442.98) 20.19 (512.83) 31.37 (796.80)
F in (mm)
12.08 (306.71) 13.51 (343.20) 14.00 (355.60)
G in (mm)
0.28 (7.11) 0.28 (7.11) 0.42 (10.67)
Note that the E-dimension in the 50-75 HP is maximum overall height to the conduit box rather than the bottom of the foot.
Weight Pounds 24.0 24.0 24.0 24.0 24.0 24.0 28.0 28.0 Kilograms 10.9 10.9 10.9 10.9 10.9 10.9 12.7 12.7
11
Installation Procedures
Power Rating HP 25 30 40 50 60 75 Weight Pounds 52.0 52.0 60.0 107.0 107.0 107.0 Kilograms 23.6 23.6 27.2 48.6 48.6 48.6
Electrical Connections
WARNING
WARNING!
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
Note
Installation and maintenance must only be performed by properly trained and qualified personnel equipped with the proper tools.
WARNING
WARNING!
INSTALL, GROUND, AND WIRE ACCORDING TO LOCAL AND NATIONAL ELECTRICAL CODE REQUIREMENTS. INSTALL AN ALL LEG DISCONNECT SWITCH NEAR THE MOTOR. DISCONNECT AND LOCKOUT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING. ELECTRICAL SUPPLY MUST MATCH PUMPS AND AQUAVAR CONTROLLER NAME PLATE SPECIFICATIONS. INCORRECT VOLTAGE OR WIRING CAN CAUSE FIRE DAMAGE, AND VOIDS WARRANTY. MOTORS WITH AUTOMATIC THERMAL PROTECTION MAY OPEN THEIR ELECTRICAL CIRCUIT WHEN A THERMAL OVERLOAD EXISTS. THIS CAN CAUSE THE MOTOR TO START UNEXPECTEDLY AND WITHOUT WARNING. 12
Installation Procedures
Electrical Connections continued
CAUTION!
EQUIPMENT DAMAGE HAZARD - DO NOT OPERATE OR INSTALL ANY CONTROLLER THAT APPEARS DAMAGED. FAILURE TO OBSERVE THIS INSTRUCTION CAN RESULT IN INJURY OR EQUIPMENT DAMAGE.
13
Installation Procedures
Electrical Connections continued
14
Installation Procedures
Electrical Connections continued
Table 2: Required Dissipation for Models Entirely Inside an Enclosure
AQUAVAR Model AV2V2S010D 2S020D 2S030D 2S050D 2S075D 2S100D 20010D 20020D 20030D 20050D 20075D 20100D 20150D 20200D 40010D 40020D 40030D 40050D 40075D 40100D 40150D 40200D 40250D 40300D 40400D 40500D 40600D 40750D 50010D 50020D 50030D 50050D 50075D 50100D 50150D 50200D 50250D 50300D 50400D 50500D 50600D 50750D Switching Frequency Max. Switching Frequency for Watts Dissipated Watts Dissipated Watts Dissipated Rated Current (kHz) at 4 kHz at 7 kHz at 10 kHz 37 44 51 10 59 71 81 10 77 92 106 10 162 212 220 10 195 251 271 10 267 312 354 10 37 44 51 10 59 71 81 10 77 92 106 10 112 135 156 10 162 212 220 10 195 251 (1) 6 (2) (2) (2) (2) (2) (2) (2) (2) 33 43 53 10 52 69 84 10 68 90 110 10 99 131 161 10 112 144 174 10 139 180 217 10 170 210 255 (1) 9 200 245 7 280 383 7 335 371 (1) 5 398 (1) 2.5 600 670 (1) 5 710 (1) 4 720 (1) 2 40 52 64 10 62 83 101 10 82 108 132 10 85 115 155 10 91 131 172 10 112 160 8 164 282 (1) 9 218 277 (1) 6 286 364 (1) 6 343 388 (1) 5 417 4 700 4 720 (1) 3 745 (1) 2
15
Installation Procedures
Electrical Connections continued
Table 3: Required Dissipation When Fins are External to the Enclosure
AQUAVAR Model AV2V2S010D AV2V2S020D AV2V2S030D AV2V20010D AV2V20020D AV2V20030D AV2V20050D AV2V20070D AV2V20100D AV2V20150D AV2V20200D AV2V40010D AV2V40020D AV2V40030D AV2V40050D AV2V40070D AV2V40100D AV2V40150D AV2V40200D AV2V40250D AV2V40300D AV2V40400D AV2V40500D AV2V40600D AV2V40750D AV2V50010D AV2V50020D AV2V50030D AV2V50050D AV2V50070D AV2V50100D AV2V50150D AV2V50200D AV2V50250D AV2V50300D AV2V50400D AV2V50500D AV2V50600D AV2V50750D Watts Dissipated 19 20 27 19 20 27 29 36 34 68 73 20 21 27 30 36 40 46 50 75 76 80 134 145 150 20 21 27 30 33 39 43 44 73 78 82 135 143 152
16
Installation Procedures
Electrical Connections continued
Step 6 - Maintenance
Minimum Torque Values to Secure Cover
If you remove the cover of an IP55 AQUAVAR controller, it is imperative that the cover be closed and re-secured with sufficient tightness to maintain environmental integrity. The table below specifies the torque values for the bolts that secure the covers on the various models. AV2 Enclosure Type IP55 1-20 HP , 230 Vac input 1-20 HP , 460 and 575 Vac input 25-75 HP , 460 and 575 Vac input Torque Value English 12 in-lbs 18 in-lbs 12 in-lbs Metric 1.35 Nm 2.03 Nm 1.35 Nm
17
Installation Procedures
Electrical Connections continued
Use circuit breakers on the incoming power lines. Grounding must be in accordance with NEC and CEC. If multiple AQUAVAR controllers are installed near each other, each must be connected to ground. Take care to not form a ground loop. Maintain a common ground. Wire must be made of copper and rated 60 / 75C (unless otherwise specified in the table below). Refer to Tables 4, 5 and 6 for recommended wire gauges and temperature ratings.
(1) Use wire rated 90C in an environment where the ambient temperature is greater than 40C (122F).
18
Installation Procedures
Electrical Connections continued
Table 5: Recommended Wire Gauges (460 Vac Models)
Model Number AV2V40010D AV2V40020D AV2V40030D AV2V40050D AV2V40075D AV2V40100D AV2V40150D AV2V40200D AV2V40250D AV2V40300D AV2V40400D AV2V40500D AV2V40600D AV2V40750D Wire Size AWG 14 14 14 14 12 12 10 101 81 61 61 31 21 11 mm2 2.5 2.5 2.5 2.5 4.0 4.0 6.0 6.01 10.01 16.01 16.01 35.0 35.01 50.01
(1) Use wire rated 90C in an environment where the ambient temperature is greater than 40C (122F).
(1) Use wire rated 90C in an environment where the ambient temperature is greater than 40C (122F).
19
Installation Procedures
Electrical Connections continued
20
Installation Procedures
Electrical Connections continued Phase Imbalance
Phase voltage imbalance of the input AC source can cause unbalanced currents and excessive heat in the drives input rectifier diodes and DC bus capacitors. Phase imbalance can also damage motors running directly across the line.
CAUTION!
EQUIPMENT DAMAGE HAZARD - NEVER USE POWER-FACTOR CORRECTION CAPACITORS ON MOTOR TERMINALS T1/U, T2/V OR T3/W. DOING SO WILL DAMAGE THE SEMICONDUCTORS. FAILURE TO OBSERVE THIS INSTRUCTION CAN RESULT IN INJURY OR EQUIPMENT DAMAGE.
T3/W
GND
21
GND
T1/U
T2/V
L1/R
L2/S
L3/T
B + DB
Installation Procedures
Electrical Connections continued Typical Power Connections
Diagram 5 shows the terminal connections for line power and motor output. See Step 8 for input line requirements. Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V or T3/W) back to an input phase (L1/R, L2/S or L3/T). As shown in Diagram 5, it is necessary to provide fuses and a disconnect switch for the input AC line in accordance with all applicable electrical codes. The drive is able to withstand a 110% over load for 60 s. For maximum protection of the drive, use the fuses listed in Tables 9, 10 and 11 found below and on the next page. The recommended supplier is Bussman.
Disconnect Switch Three-Phase AC Power
AV2V Drive
GND L1/R
Fuses
Motor
22
Installation Procedures
Electrical Connections continued
Table 10: Recommended Fuses (460 Vac Models)
Model Number AV2V40010D AV2V40020D AV2V40030D AV2V40050D AV2V40075D AV2V40100D AV2V40150D AV2V40200D AV2V40250D AV2V40300D AV2V40400D AV2V40500D AV2V40600D AV2V40750D Fuse Size 380 Vac JJS/JJN1 6 6 10 15 20 20 40 50 60 70 80 90 110 150 Fuse Size 460 Vac JJS/JJN1 6 6 10 15 20 20 35 40 50 60 60 90 110 150
23
Installation Procedures
Electrical Connections continued
1. The wires routed from the terminal block U, V, W, and ground screw, should now be connected to the motor leads using the motor nameplate and Diagram 6 for reference. Always refer to motor wiring nameplate.
AQUAVAR
RS485 X5
X5 X2 X1
460 Volt
GROUND = PE GROUND = PE 2. Pressure Transducer Installation and Wiring Diagram 6 It is recommended that the transducer be mounted in the discharge piping. The location should be in a non-turbulent, straight piece of pipe. See layout on page 5. Locate the adapter for the pressure transducer, if needed.
4 3 2 1 4 3 2 1 6 5 4 3 2 1 14 13 + 5VDC GND RS-485 MultiSIO + pump SIO NO connected to drive CC Run Signal NC NO fault signal CC NC Digital Input Voltage Signal Input (0-10Vor 2-10V)
X2
1 2 3
7 5 8 4 9
X9
- 24 VDC + 24 VDC + 24 VDC FAULT RELAY
6 CONNECTED TO DRIVE 5 CONNECTED TO DRIVE JUMPER 4 CONNECTED TO DRIVE JUMPER 3 CONNECTED TO DRIVE 2 ANALOG OUT (PRESSURE) 1 RETURN SIGNAL
Transducer connection
BROWN 3 WHITE 2
12 Current Signal Input (4-20 mA) 11 Analog signal output (0-10V) connected to drive 10 9 Motor thermo or PTC * 8 7 low Water or jumper * 6 5 external on or jumper * 4 3 15 V Ub (max 100 mA) 2 IN (4-20 mA) actual value signal 1 shielding * NOTE: Jumpers are installed from the factory. Must remove to wire motor thermal, low water switch or external ON/OFF if used.
U V
2 3
8 9
5 6
Diagram 7
24
X1
Installation Procedures
Electrical Connections continued
3. Place the square gasket over the end of the transducer, plug the cable connector on, and tighten the screw. The transducer is supplied with 14 NPT threads for direct mounting in the discharge piping.
Note
Cable connector will fit on one way only! Do not force on or damage may occur. 4. Now select one of the remaining ports in the AQUAVAR controller to route the transducer cable. Route the transducer cable through the strain relief, cut to length and connect to locations X1 #2 and #3 as shown in Diagram 7. (Note: Control board is mounted to the inside front cover of the drive enclosure.) The brown wire is connected to X1 #3 and the white wire to X1 #2. Tighten strain relief. 5. Terminals Found on the AV II Drive Control Board (Internal Drive) Description of the Control Terminals: Figure 8 shows the control terminals found on the I/O board of the AV II drive. (The actual control board cannot be accessed by the user.) These terminals are prewired by the factory with color coded wires below. Note that due to labeling constraints, the labels for some terminals start on the left (either on the side or top of the terminal block), are interrupted by the terminal screw, and then finish on the right (either on the side or top of the terminal block). For example, terminal A11 is labeled with A on the left side of the block and 11 to the right of the terminal screw on top of the block. Similarly, terminal NC2 is labeled with N to the left of the terminal screw on top of the block and then C2 on the Enhanced right side of the block. Keypad Port As is shown in the figure, the terminals are divided On side of On side of TB1 TB4 terminal block terminal block into four terminal blocks, Black Wire CM CM A0 A0 EN EN CM CM each of which pulls apart 10 D A1 A1 9 D CM CM for ease of field wiring: 8 D A 11 TB1 - analog input, 7 D 12 A 6 D + 10 analog output and Jumper Yellow Wire 5 D 21 A D digital output terminals. 4 CM CM 3 White Wire D CM CM TB2 - output relay 1 (R1). D Black Wire 2 CM CM Blue Wire 1 D D PQ TB3 - output relay 2 (R2). + 24 3 DQ DIP Switches 24 + DQ 2 Orange Wire TB4 - digital input 24 + DQ 1 Red Wire C2 R terminals. C1 R C2 N N C1 Table 12 starting on the N O2 C1 N next page describes the TB2 TB3 control terminals.
Diagram 8
25
Installation Procedures
Electrical Connections continued
Table 12: Description of AV II Drive Control Terminals (Internal Drive)
Terminal Description TB2 Terminal Block Common terminal for the first auxiliary relay. The function of the relay is set by parameter R1 Configure. The default setting is for the relay to activate when a fault is detected (Drv Flted). Normally-closed contact for the first auxiliary relay. It will open when the relay is activated. Normally-open contact for the first auxiliary relay. It will close when the relay is activated. TB3 Terminal Block (Drive Run Contacts) Common terminal for the second auxiliary relay. The function of the relay is set by parameter ROUT R2 Config. The default setting is for the relay to activate when the drive is running. The contact ratings are 115 VAC at 1 A or 230 VAC at 0.5 A. Normally-closed contact for the second auxiliary relay. It will open when the relay is activated. Normally-open contact for the second auxiliary relay. It will close when the relay is activated. TB4 Terminal Block Enable terminal. A jumper is placed between this terminal and the +2 terminal at the factory. You may replace this with a contact if desired. The circuit from EN to +24 must be closed for the drive to operate. Note that unlike all other terminals, this terminal cannot be configured for pull-down logic. That is, a high input to this terminal is always regarded as true and must be present if the drive is to operate. Digital inputs. The function of a digital input is configured by the parameter with the same name as the digital input in the DI Configure parameter group. Digital input. In 3-wire control, this must be a Stop input. In 2-wire control, it may be configured to another function with parameter D2 Configure. Digital input. This must be a Start or Run input.
RC2
NC2 NO2
EN
D3 to D10
D2 D1
26
Installation Procedures
6. For multi-pump systems: Use a three core shielded cable to connect terminals 1, 2, and 3 on X5 between the AQUAVAR controller units. These are the RS-485 interface connections. (See Diagram 11 and 13). Note: either RS485 port can be used. Connect pump one to pump two, two to three, and three to four (maximum is 4 pumps).
4 3 2 1 6 5 4 3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 4 3 2 1 6 5 4 3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 4 3 2 1 6 5 4 3 2 1 14 13 12 11 10 9 8 7 6 5 4 3 2 1
X5
X5
X2
X2
X1
X1
Diagram 9
7. External pressure switch or float switch- (if used) to check incoming pressure and low/no suction. Connect to terminal block X1 at the 6 and 7 location. Refer to Diagram 11. When using a suction pressure switch, set the cut off at the maximum NPSH required by the pump.
Note
If an external switch is NOT used, install a jumper wire between X1 Locations 4 and 5. 8. External on/off If used to turn the AQUAVAR controller on or off from an external panel or controller, connect to terminal block X1 at the 4 and 5 location (refer to Diagram 7, page 24). 9. Analog output of pressure A meter can be connected to X9 pins 2 and 1 for remote display of actual system pressure. The meter must be 0-10 VDC volt with no more than 2 mA. 10. Second Sensor Input The ground pin (X1-10) used for analog output can also be used to bridge a connection for a second sensor. This can be digital (on/off) such as a switch which would be connected between X1-10 and X1-14. Another choice is a sensor with a voltage signal of 0-10V or 2-10V which would be connected to X1-10 and X1-13. A final choice is a 4-20 mA current sensor which would be connected to pins X1-10 and X1-12.
Note
Power supplies using G.F.I. breakers will cause nuisance tripping which will result in the AQUAVAR controller displaying an undervoltage fault.
27
X1
X2
X5
Run Test
WARNING
DO NOT APPLY POWER TO THE AQUAVAR CONTROLLER OR PUMP UNTIL ELECTRICAL CONNECTIONS HAVE BEEN REVIEWED BY A QUALIFIED ELECTRICIAN AND MEET ALL APPLICABLE STATE AND LOCAL REQUIREMENTS.
Instructions
1. Check all wiring. All motors used with the AQUAVAR controller are three phase. You will need to check the direction of rotation of the motor shaft. If you have followed all of the previous steps carefully, you should now be ready to apply power to the AQUAVAR controller unit. 2. Close discharge valve. Make sure the discharge valve is closed. Apply power to the AQUAVAR controller. The first screen appears for 2 seconds and shows the software version and manufacture date. The next screen will appear automatically *If auto start is preprogrammed ON, pump will start immediately.
Screen
Date: 10/30/00
3. Check Power Light Check the AQUAVAR controller panel. The power on light should be illuminated and the display should say No Autostart - disable inverter. If either of these conditions is not present, turn off all power to the AQUAVAR controller and recheck all connections.
WARNING
WARNING!
FAILURE TO DISCONNECT AND LOCKOUT ELECTRICAL POWER AND WAIT FIVE MINUTES FOR CAPACITOR DISCHARGE BEFORE SERVICING AQUAVAR CONTROLLER CAN CAUSE SHOCK, BURNS, OR DEATH.
Note
To change the display language on the AQUAVAR controller, press the key and the up arrow key at the same time. A scrolling line will appear on the bottom of the screen and tell you which button to push for the language you want. After selecting the language, press the up arrow to return to the main display.
28
Installation Procedures
4. Check Display. * If these conditions exist, proceed. If NOT, check all wiring.
Screen
NO AUTOSTART - DISABLED INV.
5. Drive Component Keypad (Internal Drive) The AQUAVAR II units have an additional keypad inside the cabinet. You will need to use this keypad one time for initial system set up. Once set, all other functions are programmed with the main display on the front panel. Below are the instructions for initial programming of the internal keypad. This keypad provides access to a 2 Line by 16 Character Display comprehensive set of parameters that allow the AV II drive to meet the needs of almost any application. To make RUN WARNING FAULT PROG POWER customization as simple as possible, two levels of programming are available. Programming Mode
FWD STOP A. Programming mode is entered by REV PROG SHIFT ENTER pressing the PROG key. B. To program a parameters value, per form the following steps: C. Press PROG to initiate programming. Diagram 10 D. The Operate display will change to the list of parameters. An arrowhead indicates which one is selected. E. If the desired parameter is indicated by the arrowhead, press ENTER to select the parameter and display its current value. If the indicated parameter is not the one you want to program, use the up or down arrow keys to move the arrowhead to the desired parameter and then press ENTER to select the parameter and display its current value. F. After the ENTER key is pressed, the value for the parameter will be displayed. For example, parameter Motor voltage may range from 100V to 690 V and you may configure any value Sample display for Sample display for parameters assigned a value parameters assigned a function within that range Name of Parameter MIN FREQUENCY STOP TYPE V0301 160.05 Hz P0403 CST to Stp as shown on the Memory Data Units Memory motor Can Parameter Address Value Address Be Changed? nameplate.
P V Unlocked Yes. Locked No.
Diagram 11
29
RUN LIGHT ON
Programming
Programming of the AQUAVAR II controller is accomplished by using the three pressure sensitive buttons on the control panel along with the two line LCD display. The format of the program is a series of menus which can be scrolled through by using the select button. Each screen display is used to provide information about the operation of the system or to change one or more of the operating parameters. Changes are made by pushing the up or down arrows.
Diagram 12
Programming
31
Programming
Instructions
1. Check Power Light 2. Press the down arrowto advance the display to: 3. Press Select
Screen
NO AUTOSTART - DISABLE INVERTER
Note
If Inverter Locked is displayed, the external on/off switch is in the off position or contacts at X1:4 and 5 are not jumpered.
4. Enter the pressure you want the pump to maintain (constant pressure) for your system. Press the until the reading shows the value you want. Use the down arrow to back up if you have gone too far. For example: if you need a constant pressure of 50 PSI in your system at various demand rates, you would enter 50 as the value by using the . 5. Autostart setting Press to advance the display to: (This displays the autostart setting.) Push
Screen
REQUIRED VALUE - XXX PSI REQ. PRESS - XXX PSI
If the autostart function is on, the AQUAVAR II controller will automatically turn on and resume activity when power is restored after a failure. If autostart is off, the AQUAVAR II controller must be manually turned on by the operator after a power failure. Be sure the dis charge valve is closed to prevent pump start.
50
32
Programming
Note
If you have advanced past a window and want to return to it, press the same time to back up. 6. Press to advance the display to: This display shows the last recorded error or fault encountered by the AQUAVAR controller. 7. Press to advance the display to: This in the error which occurred before the last one. 8. Press to advance the display to: The error before error 2. 9. Press to advance the display to: The error before error 3.
and
at
* * * *
ERROR 1
ERROR 2
ERROR 3
ERROR 4
* 11. Press to advance the display to: * This is the total amount of run time of the
10. Press to advance the display to: The error before error 4. motor. It can be reset using a method described later.
at the same time until the display changes to: This will allow you to save the changes you have made in the microprocessor memory. 14. After about five seconds the display will automatically return to:
Push . The AQUAVAR II controller will begin to automatically maintain system pressure at the point you have selected and the display will show the pressure set point.
Note
If the AQUAVAR II controller is not maintaining the rating you selected, check the sensor adjustment procedures on page 60 or check rotation again.
33
SAVE ???
Programming
AQUAVAR II Controller Program Flow Chart Single Pump Constant Pressure
SW Ver. Date: Press long REQUIRED VALUE 50 PSI TOTAL RUN TIME 0000: 41
Auto-START ON
ERROR 1
ERROR 2
ERROR 3
ERROR 4
ERROR 5
SAVE ?? +v
Diagram 13
WARNING
FAILURE TO SAVE SETTINGS AFTER PROGRAMMING RESULTS IN LOSS OF PROGRAM VALUES WHEN POWER IS REMOVED!
Note
Low/no suction protection can be managed by the installation of a suction line pressure switch, or float switch for a tank. This switch is connected to the AQUAVAR II controller as described earlier in the Electrical Installation section. The cut off setting for this switch should be the maximum NPSH required by the pump.
Instructions
1. Password The password protection prevents untrained personnel from accidentally changing the base settings. From the main menu, hold down the key for 2-3 seconds until the display changes to:
Screen
*
34
PASSWORD 0000
Programming
2. Press the key until you reach the number 66. You will now be able to access all of the alternate menus for all AQUAVAR controller optional controls. 3. Press to advance the display to the next window: The jog mode is very useful because it allows you to check on the actual outgoing frequency and system pressure. By pressing either or the controller changes to manual, and you can change the frequency to set any constant speed. The Aquavar returns to normal automatic operation when you leave the jog mode window. 4. Continue to briefly touch the key to scroll past all of the windows and submenus until you reach: 5. Hold the key down for 2-3 seconds until the display changes to: 6. Set the minimum pressure the system is allowed to maintain before shutting down. For example, if the set point for the system is 50 PSI, and the operator will allow anything above 41 PSI, then the conveyor limit would be set at 40 PSI. This function can also be turned off by pressing until disabled is shown.
0066
JOG MODE
SUBMENU ERRORS
35
Programming
Press the to enter the number of seconds. The pump will run after pressure begins to drop at pump run out or a suction switch activates.
8. Error Reset Turning this control on will enable the AQUAVAR II controller to retry its operation five times when a fault condition occurs. Turning the control to off means that the AQUAVAR II controller will shut down the first time a fault occurs. Select the mode you want by pushing the up or down arrow key.
Note
Fatal errors will always shut down the system the first time. Press
Press to set the time between attempted restarts or to disable this function
9. Clear error. The error memory can be deleted by entering a password supplied by your distributor.
SAVE ???
36
15 SEC
ERROR RESET
Screen
SUBMENU ERRORS
SW Ver. Date:
Press long
Auto-START ON
PASSWORD 0000 RAMP 1 4.0 Sec. RAMP 2 4.0 Sec. RAMP 3 70 Sec. RAMP 4 70 Sec.
JOG-MODE XX Hz XX PSI
WINDOW 5%
SUBMENU Offset
SAVE ?? +v
37
ADC REFERENCE Local CONVEYOR LIMIT disabled DELAY TIME 2 sec. TEST RUN Man. +v TEST FREQUENCY 30.0 Hz ENABLE SEQ. CTL. 58.0 Hz SWITCH INTERVAL 12 hours SOURCE REQ. VALUE ADR1 SUBMENU Synch. Control PUMP SEQUENCE Adrl disabled BUSARBIT DIAG. 0 INTENSITY 1 0.0% INTENSITY 2 0.0% SYNCHRON. LIMIT 0.0 Hz SYNCHRON WINDOW 2.5 Hz
DEFAULT EUROPE +v
DEFAULT USA +v
LEVEL 1 2.0%
LEVEL 2 0.0%
Diagram 14
f = 100%
%f WINDOW
%f
SET PRESSURE 4 3 2 1 0
Q 0 0
Diagram 15
38
Instructions
1. From the main menu, hold down the key for 2-3 seconds until the display changes to: Enter 66 by pressing the
Screen
2. Freq.- Lifting 30.0 hz This indicates the speed (flow rate) at which you want the pressure compensation to begin. On a 60 hz system, there is virtually no flow below 40 hz. Set this frequency with the up arrow. On a 50 hz system, the normal starting point would be 30 hz. Use the key to scroll through the menu screens until you reach: Change if required. 3. Use the
Use the to enter the percentage pressure increase calculated on page 37.
Increase values are recommended from 0 to 20%. If your friction loss increase is above 20% of your set pressure, please contact the AQUAVAR distributor or factory for application assistance. 0-99.9% actual.
Press both the arrows until the display indicates the save process is complete. The screen will automatically return to the main menu.
SAVE ???
39
SW Ver. Date:
Press long
Auto-START ON
PASSWORD 0000 RAMP 1 4.0 Sec. RAMP 2 4.0 Sec. RAMP 3 70 Sec. RAMP 4 70 Sec.
JOG-MODE XX Hz XX PSI
WINDOW 5%
SENSOR RANGE 20 mA 362.6 Bar REGULATION MODE Normal START VALUE Disabled CONFIG. REG. Val. 2 OFF
SUBMENU Offset
SUBMENU RS485 Interface DIMENSION UNIT PSI TEST RUN after 100 h. SUBMENU ERRORS
SAVE ?? +v
40
ADC REFERENCE Local CONVEYOR LIMIT disabled DELAY TIME 2 sec. TEST RUN Man. +v TEST FREQUENCY 30.0 Hz BOOST TEST-RUN 10.0% ENABLE SEQ. CTL. 58.0 Hz SWITCH INTERVAL 12 hours SOURCE REQ. VALUE ADR1 SUBMENU Synch. Control PUMP SEQUENCE Adrl disabled BUSARBIT DIAG. 0 INTENSITY 1 0.0% INTENSITY 2 0.0% SYNCHRON. LIMIT 0.0 Hz SYNCHRON WINDOW 2.5 Hz
DEFAULT EUROPE +v
DEFAULT USA +v
LEVEL 1 2.0%
LEVEL 2 0.0%
Diagram 16
Programming
Circulator applications
On circulator pumps, the system curve can be automatically tracked through the use of a differential pressure transducer. This pressure transducer reads the outgoing discharge pressure and the incoming return pressure and compensates for differences in pressure as demand and speed increase. Programming is the same as just covered for the single transducer version. Data on the differential pressure transducer can be found in Appendix A.
Instructions
In flow applications, you will want to change the sensor curve from linear or to quadratic and the units from PSI to %, when using to orifice/transducer assembly. To do this, hold down the key at the main menu until screen:
PASSWORD 0000
0066
1. Enter the number 66. 2. Briefly press the key to scroll through the displays until screen: 3. Use the to change to Quadratic. Note: If you are using a flow sensor rather than an orifice plate, leave the sensor curve at linear. 4. Briefly press the key to scroll through the displays until screen:
SENSOR CURVE
QUADRATIC
41
Programming
Single Pump Constant Flow continued
5. Use the to change the units to GPM if you are using a flow sensor or % if you are using the orifice plate. 6. Hold down the 7. Hold down the
8. Enter either 37 psi for orifice plate application or the maximum flow range of your flow sensor in gpm. 9. Hold down the
The display will automatically return to the main menu. 10. Advance to the screen: 11. Use either to enter the flow you want to maintain on the AQUAVAR II controller (see example). For orifice plate applications, use the table below to set the required %.
REQUIRED VALUE
Select orifice size from the following chart. Select the orifice by the maximum flow of the pump.
Orifice 1 2 3 4 5 Nominal Pipe Size 1" 1" 1 1/2" 1 1/2"
2 1/2"
Based on the maximum flow shown for the orifice selected, calculate the percent of maximum flow you want to maintain. For example, to maintain a flow of 20 GPM with a #1 orifice, select 57% (20 35).
* *
GPM
NORMALIZE 20 mA = 40 GPM
Screen
Orifice 6 7 8 9
3 3 3
42
Programming
V. Single Pump - Level Control Applications
For drainage applications using a surface pump, the transducer is typically needed to measure pressure on the suction line. As the catch basin or tank empties, the pressure will decrease, and the pump needs to slow down and eventually stop. This is the opposite way the AQUAVAR II controller would usually respond. To change to suction side measurement: 1. On the main menu, enter the PSI value of the liquid at the LOWEST level you want to maintain. For example, you may want to leave 3-4 feet of water in a tank which is equal to 2-3 PSI.
Screen
2. From the main menu, hold down the key for 2-3 seconds until the screen changes to: Enter 66 by pressing the 3. Use the
In operation, the pump will start wherever the suction side pressure is above the set point and slow down and stop when the suction pressure comes down to the set point and stays there.
Note
For discharge level control, the programming operation is the same as a constant discharge pressure system.
43
* Use the
key.
PASSWORD 2000
Programming
VI. Single Pump - Submersible Applications and Minimum Frequency
It is possible to use the wall mounted version of the AQUAVAR II controller with a submersible pump. *Never attempt to mount an AQUAVAR II controller on the pump itself in these applications since the AQUAVAR II controller is not designed to be submerged. The standard distance allowed between the pump and the AQUAVAR II controller is up to 60 feet. If you need a longer connection, be sure to contact your distributor for a drive applied filter or load reactor. The submersible pump will often use motor service factor and will overload the AQUAVAR II controller at maximum speed. To avoid this, select an AQUAVAR II controller based on the service factor amp rating of the motor and the maximum amps allowed by the AQUAVAR II. If you have questions about the requirements of the submersible pump and which AQUAVAR II controller to use, please contact the AQUAVAR II controller distributor or factory applications Goulds Pumps. The submersible pump can be set for either constant pressure or level control applications as described in programming section I and section V. Normally, the constant pressure application would use well pumps or turbines with a steady source of water. Drainage applications would normally use a sump, effluent or sewage pump. Minimum Frequency Many submersible well pumps have a required minimum frequency to keep motor bearings lubricated. To avoid running the motor at lower frequencies, you can program in a minimum frequency. For most Franklin submersible motors the minimum is 30 Hz, so a setting of 35 Hz is good.
NOTE
End suction centrifugal pumps may also be used in level control systems for draining or filling. Multiple pumps end suction or submersible systems may also be used in level control.
44
Programming
At the status window, hold the key until you reach the password screen. Enter the password. Use the
PASSWORD 0066 MINIMUM FREQUENCY 0 Hz MINIMUM FREQUENCY 35 Hz CONFIG. FMIN F -> FMIN
Use the and to change to the desired minimum frequency (Example 35 Hz). Use the
Use the andarrow keys to change to: This allows the AQUAVAR II to go down to the selected minimum frequency but not below it.
Note
In the setting f -> Fmin, the AQUAVAR II will only run between minimum frequency and maximum frequency. Automatic shut off is not possible, but manual shut off is possible with external on/off connected at X1/4 and X1/5. Use the
Use the andkeys to enter the number of seconds the AQUAVAR II will run at minimum speed before it shuts off when there is no demand. Advance to the same window and save all settings.
SAVE ???
45
Programming
VII. Setting A Second Fixed Required Value
The AQUAVAR II controller can also be used in applications where the required value changes. As an example, a single pump system might be used to supply both water supply and irrigation needs on a farm. When the irrigation system is used, the pressure which needs to be maintained is higher than the pressure for normal water supply. The AQUAVAR II gives you the ability to program in this higher set point and to automatically change to it when the irrigation system turns on, and change back when it turns off. Electrical Wiring for the switch to change between one set point and the other is shown below. This could be a normal switch or a timer for automatic operation. Wire the switch to X1-14 and X1-10 (ground). When the switch is open, set point 1 is used. Closing the switch activates set point 2.
14 13 12 11 10 9 8 7 6 5 4 3 2
Digital Input Voltage signal input 0..10V or 2..10V Current signal input 4..20mA Analogue signal output 0-10V Ground Motor thermoswitch or PTC
Low Water External on/off +15 VDC max. 100mA Actual value signal input 4-20mA Screen
X1
46
Programming
Enter the submenu by holding the Enter the password and press the Press the Use the
* * key.
key.
ITT INDUSTRIES 20 PSI PASSWORD 0066 CONFIG. 2ND REQUIRED VALUE OFF CONFIG. 2ND REQUIRED VALUE INT
Note
The other possibilities (Ext. ADC-1, Ext ADC-U 0-10V, Ext ADC-V 2-10V) involve variable second values controlled by a second sensor. These are discussed in the next section. Advance the display with the Hold the
SAVE ???
Press both buttons until the display changes to: Press the Use the
Close the switch connected to X1-10 and X1-14 to activate the second set point. The display changes INT to: Use the andarrows to set the second required value. Advance to the Save window and save all settings.
Two required values are now stored in memory. The active required value is determined by the switch on X1/10 - X1/14. As noted earlier, this can be a manual or automatic (timer controlled) switch.
47
* key to:
Programming
VIII. Variable Second Required Value
In this section, we will cover the set up and programming of the AQUAVAR II for a second sensor input. This sensor can be either a 4-20mA or 0/2-10V device such as a pressure transducer, flow transducer, heat sensor, etc. When connected to the AQUAVAR II, the output of this second sensor becomes the new set point. As input from the second sensor changes, the set point will also change. Example: If the second sensor was a 150 psi 4-20mA pressure transducer and the input to the AQUAVAR was 10mA, the set point would become 62 psi. If the input dropped to 8mA, the set point would go to 94 psi. Keep in mind that this change only offsets the set point. Motor speed continues to be varied by the primary transducer reading of demand change. This function could be used for chlorine or fertilizer injection where a flow sensor in the main pipe would track system demand and adjust the pump flow set point to keep the mix percentage the same. Electrical Connect the second sensor as shown to X1/10 and either X1/12 for 4-20mA or X1/13 for 0/2-10V.
14 13 12 11 10 9 8 7 6 5 4 3 2
Digital Input Voltage signal input 0..10V or 2..10V Current signal input 4..20mA Analogue signal output 0-10V Ground Motor thermoswitch or PTC external current signal Switch
Low Water External on/off +15 VDC max. 100mA Actual value signal input 4-20mA Screen
X1
48
Programming
Enter the submenu by holding the Enter the password and press the Press the
* * key.
key.
ITT INDUSTRIES 20 PSI PASSWORD 0066 CONFIG. 2ND REQUIRED VALUE OFF CONFIG. 2ND REQUIRED VALUE EXT ADC-1
Use the andarrows to change the selection to: EXT ADC-1 for 4-20mA input EXT ADC-U 0-10V for 0-10V input EXT ADC-U 2-10V for 2-10V input Advance the display with the
Hold the
Use the arrow keys to change to: Hold the advance to:
SAVE ???
Press both buttons until the display change to: Press the key to advance to: Use the andarrows to set the first required value. Close the switch connected to X1/10 and X1/14 to activate the second set point. The display changes to:
Note
This display is now a read only window. The actual set point is coming from the external signal.
49
key to:
SUBMENU SEQUENCE CONTROL SOURCE REQUIRED VALUE OFF SOURCE REQUIRED VALUE ADR1 +
Offsets
It is also possible to use second sensor input as an offset for the primary required value. An example would be locating the second sensor in a supply tank or well and setting an offset so that when the water level got too low, the pump discharge pressure setting would be reduced until the tank or well had recovered. Another example would be the use of both a pressure sensor and flow sensor in the discharge line so that if the flow became too high for the pump, the offset could reduce the discharge pressure set point to keep the pump from cavitation.
Programming
To Implement the offset function, Enter the submenu by holding the Enter the password and press the Press the
* * key.
key.
key.
Use the and arrows to select the source of the second value: EXT ADC-1 for 4-20mA input EXT ADC-U 0-10V 0-10V input EXT ADC-U 2-10V 2-10V input
Refer to the following page to determine the offset variables and intensities to use for your application. Example for Offset: Sensor range: 20mA = 150 PSI
<
Level 1: 20% of the 2nd additional input Level 2: 80% of the 2nd additional input Intensity 1: -10% = -15 PSI (refer to the required value) Intensity 2: -20% = -30 PSI (refer to the required value)
< <
50
Programming
analogue value 1 Level 1 % Level 2 %
required value 75 PSI Intensity 1 - 10% 60 PSI Intensity 2 - 20% 45 PSI additional input 2 0%=4mA (0V/2V) 20% 80% 100%=20mA (10V)
At Level 1 and Level 2, you enter the required value in percent from the Second Additional input (20%) and (80%). Intensity one and two depend on the Sensor range of the external value signal. The Intensity 1 that you have entered is valid until you reach Level 1, after reaching Level 1 the Required Value has no offset. The Required Value is valid until you reach Level 2. After reaching Level 2, the new value, depending on the Intensity 2, is valid. Note that for most applications only one level and one intensity would be needed. Press the
Use the andarrow keys to enter the % of the additional input range where the first offset to the required value will occur. The chart on the previous page uses 20% as an example. Press the
Use the and arrow keys to enter the % of the additional input range where the second offset to the required value will occur (if needed) The chart on the previous page uses 80% as an example.
LEVEL 2 XX.X%
LEVEL 2 80.0%
51
Programming
Press
INTENSITY 1 +XX.X%
Use the and arrow keys to enter the % of the INTENSITY 1 required value you want to increase or decrease -10.0% when the second sensor input is below Level 1. The chart on the previous page uses -10% as an example. This represents an application where the second sensor is in a well or tank. When the pressure reading or the second sensor drops below an acceptable minimum, the discharge pressure set point automatically drops by 10% to give the tank or well time to recover. As soon as the pressure in the well reaches the minimum again, the set point returns to normal. Press the
INTENSITY 2 +XX.X%
Use the and arrow keys to enter the % of INTENSITY 2 required value you want to increase or decrease -20.0% when the second sensor input is above level 2. The chart on the previous page was -20% as an example. This represents an application where the second sensor is a flow transducer in the discharge line. When the flow reading on this second sensor goes higher than an acceptable maximum, the discharge pressure set point automatically drops by 20% until flow demand is reduced. As soon as flow is back below the maximum again, the set point returns to normal. Hold the Press the
SAVE ???
52
SUBMENU OFFSET +
Programming
IX. Multiple Pump Constant Pressure and System Curve Compensation
When two, three, or four AQUAVAR II controller controlled pumps are connected in a system, they can be programmed to work together to maintain system pressure up to the maximum flow rate of all pumps combined. As the first pump reaches its maximum speed and flow, the second pump will automatically turn on (and so on). In addition, the sequence of the pump that will run first (lead pump) can be automatically varied to reduce premature wear on any one pump in the system. 1. Refer to the section The Main Menu - Setting One Pump Constant Pressure. Follow steps 1 through 6, then continue with step 2 below.
Instructions
2. From the main menu, hold down on the key for 2-3 seconds until the display changes to:
Screen
PASSWORD 0000
Use
3. Mode: Multicontroller This setting allows the AQUAVAR II controller units to communicate with each other in a multi-pump system. Use the key to scroll through the screens to reach: Use the
Note
Other possibilities are Synchronous Controller described later in this section and Actuator which shuts off the internal controller and allows the AQUAVAR II to function as a standard VFD. This can be from external input (actuator) or manual control (actuator local). This is described further in operator custom features and displays.
SUBMENU SEQ CONTROL
0066
MODE CONTROLLER
MODE: MULTICONTROLLER
53
Programming
Multiple Pump Constant Pressure... continued
Generally, a slight pressure drop is allowed on the first pump before the next is started. This allows for brief system fluctuations without pump cycling. Once the next pump starts, however, you will want the system to resume its normal set pressure. 5. To do this, enter the amount of pressure drop you will allow before the next pump starts. Diagram 16 shows the pressure drop and increase.
5 P
4 P1 3 P1 + P2 P1 + P2 + P3
Q 0
Diagram 17
6. To increase the pressure even more to compensate for system losses at higher flow, enter the total of the system drop allowed before next pump starts and the increased pressure desired. For example, if the pressure drop allowed is 5 PSI before the next pumps starts, and the increased pressure needed to compensate for system losses is 3 PSI, you would enter 5 + 3, or 8 PSI to compensate for both system pressure drop and compensation requirements. Examples: Value Increase = Value Decrease > Pressure is constant Value Increase > Value Decrease > Pressure increases with each additional pump Value Increase < Value Decrease > Pressure decreases with each additional pump
Note
This value is cumulative. An extra 3 PSI will be added to the total system pressure with each additional pump which turns on. For example, if the initial system pressure was 50 PSI, pump two would create 53 PSI, pump three would create 56 PSI, and pump four would create 59 PSI system pressure. 7. Pressure Incr. 000 psi This setting tells the AQUAVAR controller how much to increase the pressure setting when the second pump turns on. Hold down the for 2-3 seconds until the display changes to:
54
Programming
Multiple Pump Constant Pressure... continued
Screen
8. Enter the value required.
ACTUAL VALUE INC. 0003 PSI
Press
Enter the PSI drop before the next pump starts. Use this value for each pump in the AQUAVAR controller system.
9. Enable Seq. Ctl. 60.0 hz This tells the next pump when the preceding pump has reached its maximum speed. Press
Screen
ENABLE SEQ. CTL. 60.0 HZ.
In most North American applications, this would be set for 58-60 hz. If you are using a 50 hz system, reset the display for 50 hz.
Note
The next pump will not start until both the system pressure drop and maximum first pump speed have been reached. If Enable Sequence Control is set higher than the maximum frequency, the next pump will not start. 10. Switch Interval This allows you to set the amount of time before the lead pump switches over to another pump in the system. This means that the first pump to turn on when the system starts up will change when the switch interval time is reached. A manual change over is also possible by using the in the first main menu display. Press
to set the time desired. Use the (If set over 100 hours, the function is disabled.)
55
SWITCH INTERVAL
Programming
Multiple Pump Constant Pressure... continued
Source Required Value The next screen refers to the use of a second input signal for changing the required value. This was discussed in Section VIII. If a second sensor or switch is used, you must tell SOURCE REQUIRED VALUE the AQUAVAR II which pump has the connection. Use ADR1 the andkeys to select. ADR1, ADR2, ADR3 or ADR4. If you are not using a second sensor, leave this set to off or disabled. Follow the other steps in Section VIII for using a second sensor with multiple pumps. 11. Synchronous Control: If you choose synchronous control, the second pump (and 3 or 4) will all try to regulate the pressure together by running at the same frequency (speed). In order to get the second pump to shut off, you need to set a minimum frequency. To choose synchronous control hold to enter the submenu.
The window can be set between 0-10 Hz. This number will be added to the synchronous limit. For example, if the synchronous window is set at 5 hz, pump four will turn off when all pumps go below 50 hz, and pump three will turn off when all pumps go below 45 hz.
Note
The synchronous option can only be used if all pumps are the same.
When synchronous limit appears use to set the frequency for pump #2 to shut off. For 60 Hz pumps, this would normally be 50 hz.
SYNCHRON LIMIT - 50 HZ
SYNCHRON WINDOW - 0 HZ
SYNCHRON WINDOW - 5 HZ
56
Programming
Multiple Pump Constant Pressure... continued
12. Pump Address In this section you will give the pump an address number. Generally, the first pump programmed will be number 1, the second will be number 2, and so on. The purpose of this is to help the AQUAVAR II controller sequence the start and stop activity of the pumps in the system including the selection of lead and lag pumps. Hold the Press
* again briefly to advance to: Press again for 2 seconds to display: * Use the to select the address number.
(1, 2, 3 or 4) 13. Hold the Press Press
* *
Set at 0% with
SAVE ???
Hold the for 2 seconds to return to the Main Menu. At the Main Menu, advance to the screen: Press at the same time until the display changes to:
SAVE ???
14. Repeat steps 1 through 12 for each pump in the system. Use a different address number for each pump.
57
Screen
for 2 seconds to return to: briefly to advance to: again to advance to:
FREQ. LIFTING
LIFT INTENSITY 0%
SW Ver. Date:
Press long
Auto-START ON
PASSWORD 0000 RAMP 1 4.0 Sec. RAMP 2 4.0 Sec. RAMP 3 70 Sec. RAMP 4 70 Sec.
JOG-MODE XX Hz XX PSI MIN. FREQUENCY 0.0 Hz CONFIG. FMIN F -> 0 STOP DELAY FMIN 0 Sec.
WINDOW 5%
SENSOR RANGE 20 mA 362.6 Bar REGULATION MODE Normal START VALUE Disabled CONFIG. REG. Val. 2 OFF
SUBMENU Offset
SUBMENU RS485 Interface DIMENSION UNIT PSI TEST RUN after 100 h. SUBMENU ERRORS
SAVE ?? +v
58
ADC REFERENCE Local CONVEYOR LIMIT disabled DELAY TIME 2 sec. TEST RUN Man. +v TEST FREQUENCY 30.0 Hz ENABLE SEQ. CTL. 58.0 Hz SWITCH INTERVAL 12 hours SOURCE REQ. VALUE ADR1 SUBMENU Synch. Control PUMP SEQUENCE Adrl disabled BUSARBIT DIAG. 0 INTENSITY 1 0.0% INTENSITY 2 0.0% SYNCHRON. LIMIT 0.0 Hz SYNCHRON WINDOW 2.5 Hz
DEFAULT EUROPE +v
DEFAULT USA +v
LEVEL 1 2.0%
LEVEL 2 0.0%
Diagram 18
Note
Low/no suction protection depends on the installation of a suction line pressure switch or float switch for a tank. This switch is connected to the AQUAVAR II controller as described earlier in the electrical installation section. The cut out setting for a suction pressure switch should be greater than the maximum NPSH required by the pump.
Instructions
1. Press the key for 2 seconds and advance to the: Use
Screen
PASSWORD 0000
Use and to set a low discharge pressure shut off value. 2. Press the key for 2 seconds to display: Set the minimum pressure the system is allowed to maintain before shutting down. For example, if the set point for the system is 60 PSI and the operator will allow anything above 55 PSI, then the conveyor limit would be set at 54 PSI. Press
Enter the amount of time the pump is allowed to run after the suction pressure switch or float switch has activated. This is also used to set the amount of time the pump can run at maximum frequency after the pressure drops below the conveyor limit.
Note
When using this feature, each pump in the system can have its own switch or a junction box must be used for multiple pump operation with one switch, in series.
to enter 66.
0066
SUBMENU ERRORS
59
Programming
Multiple Pump Pump Protection... continued
Instructions
3. Error Reset Turning this control on will enable the AQUAVAR II controller to retry its operation five times when a fault condition occurs. Turning the control to off means that the AQUAVAR II controller will shut down the first time a fault occurs. Press
Screen
ERROR RESET
Use the
Note
Fatal errors will always shut down the system the first time.
SUBMENU ERRORS
SAVE ???
5. Save the new settings by pressing the at the same time until the display changes to:
After a moment, the screen will automatically return to the main menu start position.
6. Repeat steps 1 through 5 above for each of the other pumps in the system which have suction switches or float switches.
60
Operator Custom Features and Displays Operator Custom Features and Displays
Refer to the overall Program Flow Chart for the location of the following operator custom features. To access a particular feature: Enter the password (66) at the Main Menu. Scroll to the selected feature by using the key. Other features have already been discussed in the application set-up instructions described earlier.
Note
Custom features are pre-programmed to default settings. These settings are the same for all horsepower sizes and may require adjustments to meet the particular pump system and horsepower requirements. Jog-Mode This display shows the actual frequency, in Hz, the pump is running and the signal being read by the pumps transducer. The frequency (speed) can also be manually changed by using the up or down arrow keys. When leaving the Jog Mode, the pump will automatically return to normal operating speed unless you have set 0.0 Hz for the frequency setting (this sets the AQUAVAR II controller to off). Window The AQUAVAR II controller regulates motor speed in very small increments, allowing the pressure to rise and fall within a range around the set point. This range is called the window. The size of this window can be set as a percentage of the set pressure. For example, if the set pressure is 100 PSI and the window is set at 10%, the swing in pressure would be 10 PSI (5 PSI above the set pressure and 5 PSI below the set pressure) during operation. This large a swing would probably become noticeable as motor cycling or surging. This setting should be adjusted according to the required value. Lower required values should use about 10% and higher required values should use about 5%. Adjustments may be needed for different systems. Ramp Hysteresis This setting tells the AQUAVAR II controller what portion of the operating window should be set aside for electrical fluctuations in the system (Hysteresis). Part of this built-in inaccuracy is due to the pressure transducer and part is due to the inverter drive. Typically, this would be set at 50%. In a 4 PSI window, 2 PSI would be the expected hysteresis error. This is also the point at which the AQUAVAR II changes over to the long slow ramps. Ramp Settings The next four displays relate to the time it takes for the AQUAVAR II controller to speed up and slow down the motor when pressure or flow requirements change. In normal operation, these should not be changed. Please carefully read the descriptions for the ramp speeds.
61
R1
R1: SPEED RAMP FAST INCREASE R2: SPEED RAMP FAST DECREASE R3: SPEED RAMP SLOW INCREASE R4: SPEED RAMP SLOW DECREASE
Diagram 19
Maximum Frequency This setting should match the requirements of the motor being used. If the motor being used is a 60 Hz motor, the setting should be 60 Hz. If the motor is 50 Hz, change this setting to 50 Hz.
Note
It is possible to set this frequency up to 70 Hz. This is not recommended for standard pumps. A 10% increase in frequency causes 33% more power draw. Pump and motor warranty will be void if operated above 60 Hz. Check with pump and motor manufacturer first!
62
Note
If Out of Range is displayed, the system is still under pressure and the transducer cannot be calibrated. The second sensor adjustment, Sensor Curve, allows control of linear and quadratic sensors. Use the linear setting for pressure, differential pressure, level, temperature and flow transmitters. Use the quadratic setting only for constant flow control with orifice plates and differential pressure transmitters. The third sensor adjustment, Normalize or Sensor Range, allows the maximum pressure or flow rating to be set for the sensor being used. Refer to the specification sheet for the sensor you are using to determine the maximum rating at 20mA. Use the up or down arrow to advance to the correct setting. The standard transducer supplied with the AQUAVAR II controller is 25 bar (362.6 PSI). Mode This setting is used to tell the AQUAVAR II controller the type of input which will be used to control the system. Controller - Used for a single AQUAVAR II controlled pump Multicontroller - Used where several AQUAVAR II pumps are connected via RS485
63
Sensor Fault
Frequency (Hz)
Manual - When this is used, the required value window in the main menu will change to manual control and the actual frequency and actual value will be displayed (similar to the Jog Mode). The and keys can then be used to set a specific frequency. If saved, this will become the set point after power loss. Start Value This allows the operator to set a pressure drop from the required value at which the AQUAVAR II will begin to ramp up, when there is demand. For example, if the required value is 50 psi and the start value is set at 45 PSI, the AQUAVAR II will start when system pressure drops to 45 psi. This is useful when small leaks in the system are causing pressure drops, that cannot be repaired. Config. Required Value 2 This allows you to select the types of second input value in use in a two value system. Refer to Section VII. Relay Config. This is used to select the function of the output relay for either motor running or slave pump. See Section IX. Submenu Offset A discussion of the various windows and functions of this submenu can be found in Section VIII. Regulation Mode The Normal setting increases the output speed with falling signal (discharge control). The Inverse setting decreases the output speed with falling signals (suction control).
64
65
66
Note
This will only work when the Auto Start function on the main menu is on. If you do not want to use the automatic test run function, you can turn it off by selecting 100 hours, and then pressing the up and down arrows at the same time until the display changes to deactivated. Submenu Test Run Manual To conduct a manual test run of the pump, enter this submenu by holding down on the S key. The first display in the submenu is the activation display for the test run. To start the test, press the up and down arrow keys at the same time. If you want the test to be conducted at some other frequency than 30 hz, use the next display in the submenu: Test Frequency. This can be set from 6-60 hz. When finished, hold down on the button until the display returns to the Submenu display.
Submenu Errors Two of the functions in this submenu have been covered: Conveyor Limit (used to set system shut off when maximum flow is exceeded) and Delay Time (used to set pump shut off in conjunction with conveyor limit and a suction side pressure switch or float). The remaining displays in this submenu are used to show the cause of failure in the last three instances where a pump or system failure caused the AQUAVAR II controller to turn the pump off. Within the Error Submenu, the Error Reset display allows the operator to tell the AQUAVAR II controller to re-try pumping after a non-fatal fault. When turned on, the AQUAVAR II controller will retry up to five times before shutting the unit off. If Error Reset is off, the AQUAVAR II controller will shut down the system the first time a fault occurs. In both cases, the AQUAVAR II controller can be
67
NOTE
YOUR GOULDS DISTRIBUTOR OR APPLICATION ENGINEER WILL NOT BE ABLE TO HELP YOU WITH PROGRAMMING PROBLEMS IF YOU HAVE CHANGED THE PASSWORD AND LOST IT! Lock Function This allows the operator to lock all of the settings on the main menu except On/Off. When the lock function is off, main menu settings may be changed normally. On pre-packaged systems, the lock function will assure that package settings remain as selected at the factory. Default Values Default values can be set for either US or Europe base data. The US default is PSI, 60 Hz, etc. To return all settings to the pre-programmed factory settings: press the up and down arrow keys at the same time and hold them as a count down timer counts back from 5 to 0. When complete, the display will return to the main menu and show Inverter - Stop/Default. All settings can be entered again following the directions given in the Programming Section. After loading default values, the screen will flash until values are saved. Save ?? This display allows any program changes to be saved and return to the main menu. Remember that all program changes will be cancelled when the system is turned off unless these are saved.
68
69
Diagram 20
Once the active fault display is shown, you must correct the condition causing the fault and then reset the drive to return to the Operate mode. However, if all three active fault displays only show warnings, you may return to the Operate mode by pressing SHIFT + ENTER. In addition to the active faults, the drive maintains a history of faults. The three most-recent faults are kept in the fault history log. The log is accessed by pressing SHIFT + ENTER. As shown in Diagram 20, the display is the same as for active faults, except that an H is shown in the upper left corner. (See Table 13 for a description of fault codes.) After viewing the fault history log, return to the Operate mode by pressing PROG twice.
03
Current Calibr
70
05
DC Volt Calibr
06
IOC Trip
07 09
11
Ground Fault
12 13
14
Under Voltage
71
18
19
20 21
22
72
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
EE Ref Checksum Parameter restoring error due to interference fault or component failure. EE Par Checksum Parameter restoring error due to interference fault or component failure. EEPROM Parameter restoring error due Checksum to interference fault or component failure. Outpt Phase Loss Current measurement detected a motor phase with no current. Precharge Fault Consult factory. TRIN Flt (ASIC) Consult factory. Satur Flt (ASIC) Consult factory. Empty Trp (ASIC) Consult factory. Appl Change Consult factory. High Unbal Curr Consult factory. MCP Software Consult factory. Loss of Ref The drive detected the loss of (Fault) the reference signal. Loss of Ref The drive detected the loss of (Warning) the reference signal. Broken Wire Trip The drive detected a broken (Fault) wire to Analog Input 1. Broken Wire Trip The drive detected a broken (Warning) wire to Analog Input 1.
Ensure that the total load on the +10 terminal does not exceed 20 mAdc. Check for correct connection of devices to the +10 terminal. Check for short circuits associated with devices connected to the +10 terminal. Consult factory. Reset the fault and attempt a restart. If fault persists, contact the factory. Reset the fault and attempt a restart. If fault persists, contact the factory. Reset the fault and attempt a restart. If fault persists, contact the factory. Check motor cables. Consult factory. Consult factory. Consult factory. Consult factory. Consult factory. Consult factory. Consult factory. Restore the reference signal. Restore the reference signal. Check the control wiring for a broken wire and replace. Check the control wiring for a broken wire and replace.
73
51
52
53 54 55
56
57
58
DI Logic Changed Consult factory. Fan Fault The cooling fan on the drives enclosure is drawing too much current, which may indicate that the fan is jammed or has failed. Fan Warning The cooling fan on the drives enclosure is drawing excessive current, but not enough to generate a fault. This may indicate that the fan is jammed. Motor Over Temp The drives motor temperature (Warning) model detected motor overheating, but not severe enough to generate a fault. Motor Stall The motors stall protection (Warning) sensed a stall, but not severe enough to cause a fault. Motor Underload The load on the motor is (Warning) insufficient, but not so low that a fault occurs. DeviceNet No DeviceNet communication Timeout (Fault) has occurred in the specified amount of time, and a fault occurs. DeviceNet No DeviceNet communication Timeout has occurred in the specified (Warning) amount of time, and a warning occurs. Network Ext Fault The external communication network delivered a command to the drive that is forcing a system-wide error. Ser Lnk TimeOut The programmed value of (Warning) parameter Comm Timeout was exceeded.
Decrease motor loading. If the motor is not overheated, check the temperature model parameters. Check the motor. Check the motor and load. Reset and restore DeviceNet communication. See the DeviceNet manual for further information. Reset and restore DeviceNet communication. See the DeviceNet manual for further information. Reset and restore DeviceNet communication. Reset and restore serial link communications.
74
SW Ver. Date:
Press long
Auto-START ON
PASSWORD 0000 RAMP 1 4.0 Sec. RAMP 2 4.0 Sec. RAMP 3 70 Sec. RAMP 4 70 Sec.
JOG-MODE XX Hz XX PSI
WINDOW 5%
SUBMENU Offset
SUBMENU RS485 Interface DIMENSION UNIT PSI TEST RUN after 100 h. SUBMENU ERRORS
SAVE ?? +v
75
ADC REFERENCE Local CONVEYOR LIMIT disabled DELAY TIME 2 sec. TEST RUN Man. +v TEST FREQUENCY 30.0 Hz ENABLE SEQ. CTL. 58.0 Hz SWITCH INTERVAL 12 hours SOURCE REQ. VALUE ADR1 SUBMENU Synch. Control PUMP SEQUENCE Adrl disabled BUSARBIT DIAG. 0 INTENSITY 1 0.0% INTENSITY 2 0.0% SYNCHRON. LIMIT 0.0 Hz SYNCHRON WINDOW 2.5 Hz
DEFAULT EUROPE +v
DEFAULT USA +v
LEVEL 1 2.0%
LEVEL 2 0.0%
Diagram 21
You can access a help display at any time by pressing the and keys at the same time. This will change the second line of the window to a running text which provides more information about the window function. The following list shows the normal window text and the available help text. (NOTE: You can access this help text in any program window, hold and keys!)
Window text
No Autostart Disable Inverter Required Value X.XX PSI Auto-Start Off (Default) Error 1 Error 2 Error 3 Error 4 Error 5 Total Run Time 0000:00 Save ??? Inc + Dec Password 0000 Jog Mode 0.0Hz XX.XX PSI ITT Industries X.XX PSI
Help Text
Spanish > Inc.; English > Dec; French > Select, to change language, see page 28 Note. Input Required Pressure / Flow for Value #1 or Value #2. ON > Autostart enable; Off Autostart disable. Default is ON, allows auto operation of AV II. Last Error the unit has experienced. 4th recorded error. 3rd recorded error. 2nd recorded error. 1st recorded error. Total motor run time hh:mm. Press INC + DEC to save parameter values. Always save changes to programming. Enter Password. Default is 0066. Jog Mode: frequency controlled by Inc or Dec. Displays the motor frequency and pressure for manual control of motor, press the up arrow or down arrow.
76
? Help Windows
Help Windows
Window text
Window 5% Ramp Hysteresis 50% Ramp 1 4.0 Sec Ramp 2 4.0 Sec. Ramp 3 50 Sec. Ramp 4 50 Sec. Max. Frequency 60.0 Hz Min. Frequency 0.0 Hz Config. F Min f->0 or f->F Min Stop-Delay Time 0 Sec. Sensor Adjust? Out of Range Sensor Curve (Linear or Quadratic) Sensor Range 20mA = 25.0 bar (367.6 PSI) Mode: Controller
Help Text
Pressure window, percentage above and below set pressure. See pages 61 and 62. Hysteresis, part of the window. See pages 61 and 62. Ramp 1: fast acceleration time. (Ramp up speed.) See page 62. Set higher for larger HP motors. Ramp 2: fast deceleration time. (Ramp down speed.) See page 62. Set higher for larger HP motors. Ramp 3: slow acceleration time. See page 62. Ramp 4: slow deceleration time. See page 62. Maximum output frequency range: 6 - 70 Hz, see page 62. Minimum output frequency (range: 0 - max. frequency). See pages 43 and 63. Configuration behavior at minimum frequency, see page 63. Delay for pump stop when f->0 is chosen, see page 63. Sensor zero adjustment (press inc + dec). See page 63. Sensor characteristic curve (linear is default). See page 63. Normalize to maximum sensor value, adjust to sensors maximum value. See page 63. Mode: controller > pressure control; Actuator > frequency set point as ADC Value Multicontroller > control of up to 4 pumps. Synchronous > All motors synchronized for same speed operation. See page 64.
77
Help Windows
Window text
Regulation Mode (Normal Default) Start Value PSI or Selected Units Config. 2nd Required Value Off (Default) Relay Configuration Run Motor (Default) Submenu Offset Offset Input Off (Default) Level 1 XX.X % Level 2 XX.X% Intensity 1 XX.X% Intensity 2 XX.X% Submenu Seq. Control Pressure Incr. 4 PSI Pressure Dec. 4 PSI Enable Seq. Ctl. 58 Hz (Default) Switch Interval 12h (Default)
Help Text
Pumping regulation mode, normal or inverse. See page 64. Start value, allows pressure to drop in system before unit starts. (Disabled is default) See page 64. Configuration of a second value from another sensor. See page 64. Relay configuration. See page 64. Submenu offset: to enter push for at least two seconds.
key
Selection of offset input, if required. See page 49. Start level for offset 1. See page 50. Start level for offset 2. See page 50. Intensity of offset 1. See page 51. Intensity of offset 2. See page 51. Submenu seq. control; to enter push key for at least two seconds. See pages 52 and 53.
Pressure increment at switching of additional pumps in multicontroller mode. See pages 52 and 53. Pressure decrement for consecutive pumps. See pages 52 and 53. Frequency limit enable sequence control. Starts second pump in multicontroller. See page 55, step 9. Time interval pump sequence change. Allows multiple pumps to lead/lag in system, based on switch interval time. See page 55, step 10.
78
Help Windows
Window text
Submenu Synch. Control Synchron Limit 35.0 Hz Synchron Window 5.0 Hz Pump Sequence Adr 1 Hold P1 BUSARBIT DIAG 0 SUBMENU RS485 Interface Pump Address Off ADC Reference Local (Default) Frequency Lifting 30.0 Hz Lift Intensity 0.0% Analog Out Actual Value Dimension Unit PSI Test Run After 24 h Submenu Test Run Man.
Help Text
Submenu: synchronous regulation; to enter push select at least one second. See page 56. Frequency limit to enable the synchronous regulation. See page 56, step 11. Frequency offset for the frequency limit which activates the synchronous regulation. See page 56. Diagnostics: Pump sequence and status. Identifies address numbers and pump numbers in multicontroller mode and synchronous mode. Diagnostics: Bus arbitration (this pump). Diagnostics only, do not adjust. Submenu: Serial Interface; to enter push for at least two seconds.
key
SIO address of the pump, for addressing each AV II in multicontroller mode. Pressure or frequency reference enabled by local ADC or by SIO. Frequency limit for pressure lift. Max. lift in % of pressure set point at max. frequency. Meter output: frequency; pressure. Displayed dimension unit. Time interval for test run 10 - 100 hr. or deactivated (inc+ dec). Submenu pump test manual; to enter push select at least one second.
79
Help Windows
Window text
Test Run Man. (Inc + Dec) Test Frequency 30.0 Hz Submenu Errors Conveyor Limit Delay Seconds Disabled (Default) Error Reset On Clear Errors 0000 Operating Hours xxxxh Disp. Contrast 100%, 50% Default Set Password 0000 Lock Function Off Submenu Default Values Default USA/Europe Press up and down arrows (if needed). Save ??? Inc + dec
Help Text
Start test run with up and down arrows simultaneously. Test frequency. Frequency at when motor will run in test mode. Submenu: errors; to enter push for at least two seconds.
key
Value at which pump system shall be deactivated, due to lack of NPSH or system pressure. Enter a time the pump is allowed to run after a suction line sensor has activated, or conveyor limit has been reached. Automatic error reset measured in seconds. The AV II will restart 5 times. If error is still present, the AV II will stay off on faults. Clear error history, enter 0726 and press the key. Total AQUAVAR controller operating time (reset counters: press the up and down arrows). Display contrast, 0-100% contrast. Modify password enables the user to set a new password. On > keypad locked: off > changes allowed. Submenu load default parameters to enter push select at least 1 second. Reset to default parameters for US or European settings. Press Inc + Dec to save entered values
80
Appendix A
Type
Output-Signal: Supply: Linearity: Stability: Total Error: Operating Temperature: Material: Body and diaphragm: 17-4 PH
Sealed gauge:
4-20mA; 2 wire 7-35 VDC 0.5% FS 0.2% FS max. 2% FS -22F to 260 F
3.45
14
NPT
1.07
34
HEX
Diagram 22
81
Appendix A
P60 26
P+
= 95
Diagram 23
Specifications
Measuring Range (FS): Over-Pressure (PMAX): Class of protection: 0,4 bar 16 bar IP 65 4 bar 16 bar IP 65 10 bar 16 bar Differential (other ranges upon request) Single-sided
Type
Output-Signal: Supply: Load resistance: Linearity: Stability: Operating Temperature: Storage Temperature:
Sealed gauge:
4-20mA; 2 wire 8-28 VDC max. 50 at supply voltage = 10VDC 0.2% FS; max 0.5% FS 0.1% FS; max 0.2% FS -20 to +80 C -40 to +120 C
82
Appendix A
1 2 3 4 5
P1 Pressure high (+) P2 Pressure low (-) gaskets ceramic component ventplug
Diagram 24
OUT
2 1 3
2-wire
IN + supply
Diagram 25
Diagram 26
83
Technical Characteristics
Interpreting Model Numbers The model number of the AQUAVAR appears on the shipping carton label and on the technical data label affixed to the model. The information provided by the model number is shown below: AV2 V 20 010 AV Series Torque C = Constant Torque V = Variable Torque Input Voltage 2S = 230 Vac, single-phase 20 = 230 Vac, three-phase 40 = 460 Vac, three-phase 50 = 575 Vac, three-phase Horsepower Rating For example, 010 = 1 HP Enclosure D = NEMA 12 / IP55, with keypad N = NEMA 4 or NEMA 3R Power and Current Ratings Motor Power Model Number AV2V2S010D AV2V2S020D AV2V2S030D AV2V2S050D AV2V2S075D AV2V2S100D AV2V20010D AV2V20020D AV2V20030D AV2V20050D AV2V20075D AV2V20100D HP 1.0 2.0 3.0 5.0 7.5 10.0 1.0 2.0 3.0 5.0 7.5 10.0 kW 0.7 1.5 2.2 3.7 5.5 7.5 0.7 1.5 2.2 3.7 5.5 7.5 Input Maximum Load Output Output Current (A) Maximum Current (A) Voltage Voltage 200/380 230/460/ (Vac) 200/380 230/460/ (Vac) Vac 575 Vac Vac 575 Vac Single-phase 200 to 230 15% 5.6 9.0 12.7 20.2 29.2 37.2 8.9 16.2 23.1 32.9 47.5 62.8 4.8 7.8 11.0 17.5 25.3 32.2 4.8 7.8 11.0 17.5 25.3 32.2 4.8 7.8 11.0 17.5 25.3 32.2 4.2 6.8 9.6 15.2 22.0 28.0 4.2 6.8 9.6 15.2 22.0 28.0 D
0 to 230
0 to 230
84
Technical Characteristics
Power and Current Ratings (continued) Motor Power Model Number AV2V20150D AV2V20200D AV2V40010D AV2V40020D AV2V40030D AV2V40050D AV2V40075D AV2V40100D AV2V40150D AV2V40200D AV2V40250D AV2V40300D AV2V40400D AV2C40500D AV2C40600D AV2C40750D AV2V40500D AV2V40600D AV2V40750D AV2V50010D AV2V50020D AV2V50030D AV2V50050D AV2V50075D AV2V50100D AV2V50150D AV2V50200D AV2V50250D AV2V50300D AV2V50400D AV2C50500D AV2C50600D AV2C50750D
(1) Consult factory.
HP 15.0 20.0 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 50.0 60.0 75.0 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0
kW 11.0 15.0 0.7 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.6 22.0 30.0 37.0 45.0 55.0 37.3 44.7 56.0 0.7 1.5 2.2 3.7 5.5 7.5 10.0 15.0 18.6 22.0 30.0 37.0 45.0 55.0
Input Maximum Load Output Current (A) Output Maximum Current (A) Voltage Voltage 200/380 230/460/ (Vac) 200/380 230/460/ (Vac) Vac 575 Vac Vac 575 Vac Three-phase 200 52.1 to 230 15% 53.9 3.4 5.2 7.2 12.0 15.0 19.7 30.9 Three-phase 40.0 380 to 460 49.2 15% 57.5 62.3 71.0 86.0 105.0 69.0 82.0 98.3 Three-phase 575 15% 46.4 47.4 2.4 3.9 5.6 8.8 12.8 16.3 25.8 33.3 40.0 47.8 53.3 65.0 77.0 96.0 58.0 68.8 82.2 2.0 3.6 5.0 7.6 10.4 14.1 20.8 27.8 33.4 39.1 52.0 52.0 62.0 77.0 0 to 230 48.3 62.1 2.4 3.8 5.7 8.9 12.0 15.6 23.0 31.0 37.0 43.0 61.0 71.0 86.0 105.0 73.0 87.0 105.0 42.0 54.0 2.1 3.4 4.8 7.6 11.0 14.0 21.0 27.0 34.0 40.0 52.0 65.0 77.0 96.0 65.0 77.0 96.0 1.7 2.7 3.9 6.1 9.0 11.0 17.0 22.0 27.0 32.0 41.0 52.0 62.0 77.0
0 to 460
0 to 575
85
Technical Characteristics
Power and Current Ratings (continued) Specifications Environmental MAXIMUM HEATSINK TEMP. = 100 C (212 F) Operating temperature 0C to +40C (32F to 104F) * Storage temperature -20C to +65C (-4F to 149F) Humidity 0% to 95% non-condensing Altitude 1000 m (3300 ft) without derating * Acoustic noise 80 dBA sound power at 1 m (3 ft) Electrical Voltage input
Input Line frequency Overvoltage trip Undervoltage trip Output voltage Overload capacity Rated output frequency Timed overload Agency listing Control Features Protective features and circuits
AV2C2x models: 200 to 230 Vac, 15% AV2C4x models: 380 to 460 Vac, 15% AV2C5x models: 575 Vac, 15% 50 / 60 Hz 2 Hz 407 Vdc 814 Vdc 1017 Vdc (DC BUS Voltage) 202 Vdc 404 Vdc 505 Vdc (DC BUS Voltage) 0 to 100% of line voltage, 3 Phase 110% of rated rms for 60 seconds 50/60 Hz 5% Adjustable time trip set for 110% of rated motor current UL and CUL Listed, CE marked
Overcurrent, overvoltage, phase loss, motor overtemperature, overtemperature, ground fault, undervoltage, short circuit, sensor fault.
* For high ambient temperatures, derate HP of drive. Altitudes above 3300 ft. of sea level, derate 2% of HP for every 1000 ft. above 3300 ft. Consult factory for assistance.
86
Appendix B
AQUAVAR Controller Drive Head Technical Data and Terminals
Terminals: There is a terminal strip inside the AQUAVAR controller which will allow the connection of a wide range of external devices for display or control. When using these terminals, shielded wires need to be used. Unshielded wires may produce signal interference which will affect the inverter. Ground connection Actual value input 4- 20 mA, 50 ohm load resistance. Used to connect external pressure transducer, flow meter, etc. Can also be used as input source from another device signalling actual speed when actuator is selected in controller mode. Power source for external transducer 15 V DC, max. 25 mA Ground connection for external on/off External on/off connection, 10 kOhm resistance, 5 VDC gold plated contact. Note that the external device must have a switch suitable for < 10 V. If no outside panel or control is used, a jumper wire is installed on contacts 4 and 5. Ground connection for low water switch. Low water switch connection, 10 kOhm resistance, 5 VDC. This contact is where an external level switch, float switch or pressure switch from the suction line would be installed. If no suction pressure devices are used, a jumper wire is installed on contacts 6 and 7. 5 V power source for the Klixon thermoswitch mounted in the motor conduit box. 10 kOhm resistance. A jumper wire is installed on contacts 8 and 9. Thermoswitch return connection. Ground connection for analog output Analog output connection 0 - 10 V, maximum 2 mA. Can be used to connect an outside meter or display panel to display actual pump running frequency or pressure as selected on the Analog Out part of the program. Current signal input 4-20mA Voltage signal input 0-10V or 2-10V Digital input Fault signal relay connection. This relay turns on the fault light on the control panel if a fault occurs. This relay may also be connected to an outside panel or display through connections 1, 2, and 3. Each is a maximum 250VAC connection with 1 Amp free of inductivity. Common connection for fault signal relay. 250 VAC with 1 Amp free inductivity. Commonly open connection for fault signal relay. 250 VAC with 1 Amp free inductivity. Connection 3 is commonly closed.
X1
1 2
3 4 5
6 7
8 9 10 11 12 13 14 X2 1
2 3
87
Appendix B
4 ** Pump operation signal relay connection. This relay turns on the run light on the control panel when the pump is operating. This relay may also be connected to an outside panel or display through connections 4, 5 and 6. Each is a maximum of 250 VAC with 1 Amp of free inductivity. Connection 6 is commonly closed. Four, 5 and 6 are fault relays connected to internal drive. ** Connected to internal drive. (For fault relay, use internal drive connection.) ** Connected to internal drive. (RC2, NC2, NO2, Diagram 8, page 25) RS-485 interface connection. SIO - (low) for connection of the AQUAVAR controller to other AQUAVAR controller units in a set, or to an outside controller. RS-485 interface connection. SIO + (high) for connection of the AQUAVAR controller to other AQUAVAR controller units in a set, or to an outside controller. RS-485 interface connection. Common ground. RS-485 interface connection. +5 VAC output signal. Maximum 20 mAmp output.
5 6 X5/6 1 2 3 4
Note
When using the RS-485 connection for multiple pump connection, connections X5 1, 2 and 3, must be connected with three core shielded wire to like connections on each AQUAVAR controller drive head. X9 6 5* 4* 3 2 1 24 VDC supply, connected to drive, control board supply Connected to drive, +24 VDC power to control board +24 VDC (jumper wire) connected to drive Connected to drive (fault relay) Analog out signal, 0-10 VDC (pressure reference) Return signal for analog out
* Jumper wire installed at factory, do not remove. ** X2, 4, 5 and 6 contacts are connected to the internal drive for a run light relay. (Pump run) For an external run relay, use internal drive connections on TB3, RC2, NC2, NO2, located in Diagram 8, page 25. TB3 terminal block specifications, located on page 26.
88
Diagram 27
Take care not to damage the shield cross section when connecting it to the continuing lines. This raises the RF resistance of the shield and radiates rather than discharges the RF energy traveling on the shield. Shields, particularly those on control cables, must not be routed through pin contacts (plug connectors). When shielded cables must pass through a plug connection, use the metallic hand guard of the plug for the continuation of the shield. It is strongly recommended that the shield be uninterrupted whenever possible.
89
Appendix C
Use a shielded motor cable which is grounded over a large surface area at both ends. The shield on this cable should be uninterrupted. If a shielded motor cable cannot be used, the unshielded motor line should be laid in a metal conduit or duct which is uninterrupted and grounded at both ends. When selecting shielded cable for use as motor leads, it is important to select a cable which is designed for operation at the frequencies and power levels involved. Improper selection of motor cable can cause high potential to exist on the shield. This could cause damage to the inverter and other equipment and could pose a safety hazard. The following cables are acceptable for this purpose: OLFlex Series 150CY, 110CY, 110CS, 100CY, 100CS and 540CP . Siemens CordaflexSM is also acceptable. Some of these cables are VDE-approved only; others carry VDE, UL, CSA and combinations of these ratings. Be sure to confirm that the cable you are using meets the certification of the agency required. OLFlex cables are available from OLFlex Wire & Cable, 30 Plymouth Street, Fairfield, NJ 07004, 1-800-774-3539. Cordaflex cables are available from Siemens Energy and Automation, Inc., Power Cables, 3333 State Bridge Road, Atlanta, GA 30202, 1-800-777-3539. If the installation requires the use of an output reactor, the reactor, like the line filter, should be placed a close as possible to the inverter. Control wires longer than 3 feet (1 meter) must be run in shielded cable and the shield must be terminated at common (CM) on the inverter. Note that connection to CM, the circuit common, rather than earth ground, is allowed because X2C inverters have isolated control inputs. If the signal run exceeds 30 feet (9 meters), a 0-2- mA or 4-20 mA signal should be used, as it will have better noise immunity than a low level voltage. Other loads connected to the power source may produce voltage transients (spikes) that may interfere with or damage the inverter. Line reactors or filters can be used on the input power to protect the inverter from such transients. If the inverter is operated from switchgear devices or is in close proximity to switchgear devices (in a common cabinet), the following procedures are recommended as a precaution to prevent these devices from interfering with the inverters operation: Wire the coils of DC devices with freewheeling diodes. The diodes should be placed as close as possible to the physical coil of the device. Wire the coils of AC devices with RC type snubber networks. Place the snubbers as close as possible to the physical coil of the device. Use shielded cables on all control and monitoring signals. Route distribution cables (for example, power and contactor circuits) separately and as far away from control and monitoring signal cables as possible.
90