2011 May 2011 Advanced Training BOGE KOMPRESSOREN 1
BOGE air. The air to work. Focus Controller 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 2 Focus Controller Overview of Capabilities Focus Hardware Focus Interface Parameters Faults Base Load Switching Leak Detection Software Updates Modules 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 3 Focus Basics General Capabilities All Ratio Capabilities, Plus: Control of 1-4 Compressors via Integrated ModBus Control of VFD Setpoint in SF Machines Efficiency Display Leak Detection Mode Clock/Sequencer Function More User-Friendly Interface Two Remote-Switchable Pressure Profiles Multiple Add-On Modules to Expand Capabilities Further 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 4 Focus Basics Focus Hardware Focus TAN Display Module 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 5 Focus Basics Focus Hardware Focus Base Module 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 6 Focus Basics Focus Hardware Additional Modules 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 7 Focus Controller Focus Interface Net/Line Pressure Compressor Status Air End Temperature Press Right Arrow for Next Screen 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 8 Focus Controller Focus Interface Net/Line Pressure Press Right Arrow for Next Screen Sump/System Pressure Compressor Status 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 9 Focus Controller Focus Interface Press Right Arrow for Next Screen Hours Until Motor Servicing Due Hours Until Compressor Servicing Due Load Cycles Until Separator Servicing Due Battery Voltage >2.8v is Normal 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 10 Focus Controller Focus Interface Right Arrow for Next Screen Total Hours Idle Hours Efficiency Load Cycles Up Arrow for Leakage Monitor 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 11 Focus Controller Focus Interface Press Right Arrow for Next Screen ModBus Status Key Switch Status Release Type Auto Restart After Power Loss Delay 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 12 Focus Controller Focus Interface Press Right Arrow for Next Screen Pressure Range Net Pressure Timer Status Sequencer Status 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 13 Focus Controller Focus Interface Press Right Arrow for Next Screen Hold Enter to Change Date/Time 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 14 Focus Controller Focus Interface Software Version Press Right Arrow for Main Screen Press Enter for Code Entry 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 15 Focus Controller Focus Interface Use Navi Keys to Enter Access Code Press Enter 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 16 Focus Controller Focus Interface Parameter Access 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 17 Focus Controller Focus Interface Parameter Access 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 18 Focus Controller Focus Parameters Parameter List in Functional Description 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 19 Focus Controller Focus Faults Fault Table 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 20 FOCUS base load switch (BLS) FOCUS base load switch - Integrated BLS for up to 4 machines (via RS485 / optional relay module) - Modular expendability (max. 5 additional modules) 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 21 Focus Controller Base Load Switching RS485 RS485 RS485 BLS is Intended to Sequence/Cycle 4 Machines of the Same or Similar Size 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 22 Focus Controller Base Load Switching 51 GND 52 RS485 + 53 RS485 - 120ohm Termination Resistor Jumper Wiring 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 23 Base load switch only by RS 485 FOCUS Bus address 0 MASTER FOCUS Bus address 2 SLAVE Bus address 3 SLAVE Bus address 4 SLAVE + RS485 Interface RATIO + RS485 Interface RATIO 3 3 3 FOCUS base load switch (BLS) 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 24 Contact Base load switch only by contact (Relay module) FOCUS + 3x Relay module RATIO BASIC Relay address 2 SLAVE Relay address 3 SLAVE Relay address 4 SLAVE Output release Output release Output release 22 2 FOCUS base load switch (BLS) Other brand 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 25 22 3 Base load switch with combination of contact and RS 485 Contact Bus address 0 MASTER FOCUS + 2x Relay module FOCUS RS 485 Bus address 2 SLAVE Relay address 3 SLAVE Relay address 4 SLAVE FOCUS base load switch (BLS) Autotronic Output release Other brand Output release 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 26 - A differential pressure between pressure transducers of machines and BLS must be - considered during adjustment of machine pressure settings 9.0 bar 8.0 bar - The cut in and cut off pressures of the compressors must be above the values of the BLS Pressure switch points compressors Pressure switch points BLS 8.3 bar 9.5 bar C 3 C 3 8.5 bar 9.6 bar C 2 C 2 8.7 bar 9.7 bar C 1 C 1 - The machine switching points of the machines should be cascaded Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 27 8.0 bar 9.0 bar Cut in and cut off characteristic of the BLS
Priority 1
Priority 2
Priority 3
Priority 4 Priority 1
Priority 4
Priority 2
Priority 3
Example parameters for base load switch
03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 28 FOCUS FOCUS + RS485 Interface RATIO + RS485 Interface RATIO - The RATIO controller must be equipped with the RS 485 BUS Interface RS485 - The machines need to be connected from controller to controller - Connection sequence in any direction is possible - the Bus address defines the Compressor - At great cable length a resistor (120 ) must be set on both ends of the line Example with only bus-compatible controllers 3 3 3 Example parameters for base load switch - The pressure control must be active on all Slave-Machines (Bridge on X2:18/19) 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 29 BLS (Priority change based on hours) by only RS485 connection with FOCUS Requirements: - 4 Machines connected (2x FOCUS and 2x RATIO) - all machines on the same or similar size - 7 hours changeover Example parameters for base load switch - Pressure range of installation 8bar - 9bar 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 30 Number of connected machines base-change cycle in hours P070 4 P071 7hrs RS485 P050 0 P051 9600 P052 8E1 FOCUS Cut off pressure Operating range of Cut in pressure base load switch Parameter settings of FOCUS Master machine MASTER SLAVE SLAVE SLAVE RATIO +Interface RATIO +Interface FOCUS 33 3 Example parameters for base load switch P012 9.0bar P013 8.0bar Modbus address MASTER = 0 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 31 RS485 FOCUS P063 2 P050 2 P051 9600 P052 8E1 P012 9.3bar P013 8.3bar Cut off pressure Operating range for Cut in pressure failure of BLS Modbus address SLAVE = 2 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE External release via Bus MASTER controls SLAVE Parameter settings of FOCUS Slave machine SLAVE RATIO +Interface RATIO +Interface FOCUS 33 3 Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 32 CODE 2 210 CODE 3 830 96 8E1 Cut off pressure Operating range for Cut in pressure failure of BLS Parameter settings of RATIO Slave machine Modbus address SLAVE = 3 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE External release via Bus MASTER controls SLAVE SLAVE RS485 FOCUS FOCUS RATIO +Interface RATIO + RS485 Interface RATIO 3 3 3 Example parameters for base load switch CODE 9.5bar 360 8.5bar 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 33 CODE 2 210 CODE 4 830 96 8E1 Cut off pressure Operating range for Cut in pressure failure of BLS SLAVE Parameter settings of RATIO Slave machine RS485 RATIO +Interface FOCUS FOCUS RATIO + RS485 Interface RATIO Modbus address SLAVE = 4 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE External release via Bus MASTER controls SLAVE 3 3 3 Example parameters for base load switch CODE 9.7bar 360 8.7bar 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 34 Code 360 9.5bar / 8.5bar Code 830 3 / 96 / 8E1 Code 210 2 P012 9.3bar P013 8.3bar P050 2 P051 9600 P052 8E1 P063 2 P012 9.0bar P013 8.0bar P050 0 P051 9600 P052 8E1 P070 4 P071 7hrs FOCUS FOCUS + RS485 Interface RATIO + RS485 Interface RATIO Code 360 9.7bar / 8.7bar Code 830 4 / 96 / 8E1 Code 210 2 RS485 33 3 Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 35 - all machines on the same or similar size - 23 hours changeover - Pressure range of installation 8bar - 9bar - 4 machines connected (1x FOCUS, 1x RATIO, 1x BASIC and 1x Other brand controller) Example parameters for base load switch BLS (Priority change based on hours) by only relay module connection with FOCUS Requirements: 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 36 Contact FOCUS + 3x Relay module RATIO BASIC Other brand Output release Output release - The FOCUS Master machine must be equipped with the relay modules for the - connected compressors Output release Signal line - Every single relay module has to be connected to the output release of the machines - Every single relay module must be configured with its own rotary switch - The cable length should not be longer then 50m 22 2 Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 37 MASTER Parameter settings of FOCUS Master machine FOCUS RATIO Other brand BASIC 22 2 Contact Example parameters for base load switch P012 9.0bar P013 8.0bar Cut off pressure Operating range of Cut in pressure base load switch P070 4 P071 23hrs Number of connected machines base-change cycle in hours 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 38 FOCUS SLAVE Parameter settings of RATIO Slave machine RATIO BASIC The Relay module in the switch cabinet of the master machine, has to be configured to 2. CODE 9.3bar 360 8.3bar Cut off pressure Operating range for Cut in pressure failure of BLS CODE 1 210 External release via contact MASTER controls SLAVE 22 2 Contact Example parameters for base load switch Other brand 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 39 The Relay module in the switch cabinet of the master machine, has to be configured to 3. Parameter settings of BASIC Slave machine SLAVE RATIO FOCUS BASIC 2 2 2 Contact Example parameters for base load switch CODE 1 210 External release via contact MASTER controls SLAVE CODE 9.5bar 360 8.5bar Cut off pressure Operating range for Cut in pressure failure of BLS Other brand 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 40 The Relay module in the switch cabinet of the master machine, has to be configured to 4. 9.7bar 8.7bar Cut off pressure Operating range for Cut in pressure failure of BLS External release via contact MASTER controls SLAVE SLAVE Parameter settings of other brand Slave machine RATIO FOCUS BASIC Other brand 2 2 2 Contact Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 41 FOCUS + 3x Relay module RATIO BASIC Other brand Signal line Code 360: 9.5bar / 8.5bar Code 210: 1 Code 360: 9.3bar / 8.3bar Code 210: 1 P012 9.0bar P013 8.0bar P070 4 P071 23hrs Pressure settings: 9.7bar / 8.7bar Output release: active 22 2 Contact Example parameters for base load switch Output release Output release Output release 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 42 FOCUS + 3x Relay module RATIO BASIC Other brand 22 2 Contact Example parameters for base load switch Output release Output release Output release Settings of rotary switches of relay modules 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 43 BLS (Clock switch based priority change) by combination of contact and RS485 with FOCUS Requirements: - 4 machines connected ( 1x FOCUS 55 kW, 1x FOCUS 37 kW, - 1x Autotronic 22 kW und 1x other brand 37 kW - Working time: 6.00Uhr to 19.30Uhr Example parameters for base load switch 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 44 - Pressure range of installation 10.5bar - 11.5bar - The 55 kW machine is frequency controlled - The 55 kW compressor is base load machine - Both 37 kW compressors are peak load machines - The 22 kW compressor is a reserve machine Example parameters for base load switch BLS (Clock switch based priority change) by combination of contact and RS485 with FOCUS 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 45 RS485 - The FOCUS must be equipped with two relay modules FOCUS + 2x Relay module FOCUS - The FOCUS machines are connected from controller to controller - On great cable length resistor terminator (120 ) has to be set on the end of the bus - Every single relay module must be configured with its own rotary switch - Every single relay module has to be connected to the output release of the machines - The cable length should not be longer then 50m from relay module to machine controller 22 3 Contact Example parameters for base load switch Autotronic Output release Other brand Output release - The pressure control must be active on all Slave-Machines (Bridge on X2:18/19) 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 46 RS485 MASTER FOCUS Parameter settings of FOCUS Master machine BASIC Auto- tronic Other brand FOCUS FOCUS 22 3 Contact Example parameters for base load switch Number of connected machines base-change cycle = 0 deactivates BLS based on hours P070 4 P071 0hrs P050 0 P051 9600 P052 8E1 Cut off pressure Operating range of Cut in pressure base load switch P012 11.5bar P013 10,5bar Modbus address MASTER = 0 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 47
Canal A MO 6:00 1243 Canal B MO 19:30 3241 Channel A MO 6:00 1243 Channel B MO 19:30 3241 Canal D DI 19:30 3421 Canal C DI 6:00 1423 Channel C TU 6:00 1423 Channel D TU 19:30 3421 Canal I FR 6:00 1423 Channel I FR 6:00 1423 Canal J FR 11:00 1243 Channel J FR 11:00 1243 Clock switch settings of FOCUS Master machine RS485 MASTER FOCUS BASIC Auto- tronic Other brand FOCUS FOCUS 22 3 Contact Example parameters for base load switch Canal K FR 16:00 3241 Channel K FR 16:00 3241 Canal K FR 16:00 0000 Channel K FR 16:00 0000 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 48 SLAVE Parameter settings of FOCUS Slave machine FOCUS BASIC Auto- tronic Other brand RS485 FOCUS 22 3 Contact Example parameters for base load switch External release via bus MASTER controls SLAVE P063 2 P050 2 P051 9600 P052 8E1 Modbus address MASTER = 2 Modbus baud rate MASTER = SLAVE Modbus communication parameter MASTER = SLAVE P012 11.5bar P013 10,5bar Cut off pressure Operating range for Cut in pressure failure of BLS 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 49 Contact to pressure switch External release via Contact MASTER controls SLAVE SLAVE Parameter settings of Autotronic Slave machine FOCUS FOCUS Other brand RS485 Auto- tronic 2 2 3 Contact Example parameters for base load switch The Relay module in the switch cabinet of the master machine, has to be configured to 3. PS- 12bar set. 11bar Cut off pressure Operating range for Cut in pressure failure of BLS 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 50 FOCUS External release via Contact MASTER controls SLAVE SLAVE Parameter settings of other brand Slave machine BASIC Auto- tronic FOCUS RS485 Other brand 2 2 3 Contact Example parameters for base load switch The Relay module in the switch cabinet of the master machine, has to be configured to 4. 12.2bar 11.2bar Cut off pressure Operating range for Cut in pressure failure of BLS 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 51 Autotronic Output release Pressure settings: 12.2bar / 11.2bar Output release: active Pressure switch 12bar / 11bar Contact to pressure switch P012 11.8bar P013 10.8bar P050 2 P051 9600 P052 8E1 P063 2 P012 11.5bar P013 10.5bar P050 0 P051 9600 P052 8E1 P070 4 P071 0hrs Contact RS485 FOCUS + 2x Relay module FOCUS 22 3 Example parameters for base load switch Other brand Output release 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 52 Example parameters for base load switch Contact RS485 FOCUS + 2x Relay module FOCUS Autotronic Output release Settings of rotary switches of relay modules 22 3 Other brand Output release 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 53 Focus Controller Leak Detection (>v1.15 Only) Single Measurement Continuous Measurement Hours of Run Time Used Only for Leaks 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 54 Focus Controller Leak Detection (v1.15 Only) Conditions: All Plant Usage Must be Off Compressors Must be Enabled / Green These conditions must remain for 6 hours 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 55 Focus Controller Leak Detection (v1.15 Only) Starting a Test: 1. Navigate to the Leak Detection Screen 2. Hold Enter for 2 secs, until Le starts flashing, then release Enter 3. Hold Enter for another 2 secs to initiate a 6hr test 4. After 6 hours, values will appear showing calculated wasted run hours 5. The system will monitor in 6hr intervals, and will update the values if a lower load period is detected 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 56 Focus Controller Leak Detection (v1.15 Only) Faults: 9999 = Power Failure 9990 = Loss of Ready Status 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 57 Focus Controller Software Updates Potential Damage to Focus Controller and PC Follow Directions Exactly NEVER Disconnect Flashing Cables With the Focus Energized 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 58 Focus Controller Software Updates Focus Flashing Device and Serial Cable Boge P/Ns: 659003101 & 681004805 CS Manager + Laptop w/ Serial Port 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 59 Focus Controller Software Updates Remove Power from the Focus the Screen Must Turn Off Breaker 4F is Sufficient Main Panel Disconnect is Safest The E-Stop Will Not Power Down the Focus 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 60 Focus Controller Software Updates Connect Flash Device Ground to Term 32 Connect the Flash Device Cable to the Software Update Port and the Serial Cable to your PC Disconnect the Digital Outputs 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 61 Focus Controller Software Updates Disconnect the Transformer Ground Power On the Focus Controller 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 62 Focus Controller 1 2 3 4 5 1. Restrict Selection 2. Identify 3. Ensure Type Turns Green Indicates Comm 4. Select Correct Program and Version 5. Write to Flash 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 63 Focus Controller Red Indicates a Comm Problem Check Cables, Port Settings, and Power 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 64 Focus Controller Software Updates Wait for Flashing to Finish Ignore Any Faults De-energize the Focus Wait 10 Seconds 03.11.2011 May 2011 Advanced Training BOGE KOMPRESSOREN 65 Focus Controller Software Updates After Waiting 10 Seconds: 1. Disconnect the Flash Cable from the Focus Base 2. Connect the Flash Cable to the Focus TAN 3. Energize the Focus and Repeat the CSM+ Process 4. De-Energize 5. Wait 10 Seconds 6. Disconnect All Flash Cables, Reconnect Transformer Ground