This document provides guidance on sizing bypass ducts for zoned HVAC systems. It includes charts listing recommended bypass duct sizes for different range of cooling capacities and airflow requirements. The key factors that influence bypass duct sizing are the total system airflow, airflow of the smallest zone, and whether branch or trunk dampers are used. The document also notes that bypass air is only used to eliminate noise from high static pressure and does not provide cooling.
This document provides guidance on sizing bypass ducts for zoned HVAC systems. It includes charts listing recommended bypass duct sizes for different range of cooling capacities and airflow requirements. The key factors that influence bypass duct sizing are the total system airflow, airflow of the smallest zone, and whether branch or trunk dampers are used. The document also notes that bypass air is only used to eliminate noise from high static pressure and does not provide cooling.
This document provides guidance on sizing bypass ducts for zoned HVAC systems. It includes charts listing recommended bypass duct sizes for different range of cooling capacities and airflow requirements. The key factors that influence bypass duct sizing are the total system airflow, airflow of the smallest zone, and whether branch or trunk dampers are used. The document also notes that bypass air is only used to eliminate noise from high static pressure and does not provide cooling.
This document provides guidance on sizing bypass ducts for zoned HVAC systems. It includes charts listing recommended bypass duct sizes for different range of cooling capacities and airflow requirements. The key factors that influence bypass duct sizing are the total system airflow, airflow of the smallest zone, and whether branch or trunk dampers are used. The document also notes that bypass air is only used to eliminate noise from high static pressure and does not provide cooling.
Download as XLS, PDF, TXT or read online from Scribd
Download as xls, pdf, or txt
You are on page 1of 6
At a glance
Powered by AI
The key takeaways are that bypass duct sizing is influenced by factors like duct style, equipment location, diffuser style, and size of the smallest zone. Maintaining a minimum of 3 outlets per ton of AC in each zone is also important. The bypass duct aims to eliminate air noise caused by high static pressure and velocity.
Factors that influence bypass sizing include duct style, equipment location, diffuser style, size of the smallest zone, location of the smallest zone, size of the smallest zone compared to its CFM output, blower performance, and flex duct applications. Variables like equipment size and number of outlets also affect sizing.
Branch dampering refers to dampers placed on individual branch runs, while trunk dampering refers to a damper placed on the main trunk or supply duct. Trunk dampering causes static pressures in open supply ducts to increase at a higher rate.
Leave blank if NO
Enter a "Y" if YES
Min-cfm Max-cfm Required Duct Size Amount Total cfm Total Small zone Bypass cfm Round Duct Rectangular Duct R-6 0 0 0 0 bypass not needed bypass not needed R-7 0 R-8 0 R-10 0 CFM ROUND R-12 0 Minimum Maximum R-14 0 200 300 6" R-16 0 300 500 7" 8" x 10" 0 400 700 8" 8" x 12" 0 550 1100 10" 8" x 16" 0 800 1600 12" 8" x 20" 0 1100 2100 14" 8" x 30" 0 1600 3000 16" Total 0 Copyright Arzel Zoning Technology, Inc. 2002 Rev- 2/25/03 jcr 8" X 20" or 10" X 16" 3.25" x 10" 3.25" x 12" 6" x 10" Arzel Zoning Technology Inc. Bypass Sizing calculator A/C Tons Trunk Dampering? capacity required See README File. This sizing calculation is only an estimate of bypass capacity needed, consideration of duct style, equipment location, diffuser style, etc, influences actual bypass Bypass Duct Size * If branch ducts are FlexDuct drop to next size smaller bypass 8" X 30", 10" X 20", 12" X 18" 8" X 10" or 6"x 14" 8" X 16" or 10" X 12" RECTANGLE Bypass Duct CFM Capacity Enter Capacity of Cooling Unit in Ton's (over 5 ton multiply by 1.2) Enter Number of and size of Branch runs in smallest zone Bypass Calculator will determine size of Bypass Duct needed Smallest Zone Size A/C Tonnage Adjusted CFM 5" Round 140 CFM 2 600 6" Round 200 CFM 2.5 750 7" Round 280 CFM 3 900 8" Round 340 CFM 3.5 1050 10" Round or 8" X 10" 550 CFM 4 1200 8" X 12" 600 CFM 5 1500 8" X 14" or 10" X 12" 700 CFM 5 ton w/ branch dampers 300 cfm / ton 12" Round or 8" X 16" 800 CFM Over 5 Ton 400 cfm / Ton 8" X 20" 1000 CFM Trunk Dampering 400 cfm / Ton 10" X 20" 1260 CFM (3) CFM @ Round 1500 to 2000 fpm Metal pipe 300 - 400 6" 400 - 550 7" 550 - 750 8" 750 - 1150 10" 1150 - 1600 12" 1600 - 2100 14" Dynamics of Air Flow and Zoning To maintain maximum heat transfer and peak effectivness with the smallest zone calling, we attempt to deliver 200% of design cfm. To deliver 200% of design cfm, we must increase static pressure by approximatley 400 to 500% . In most applications the smallest zone can deliver twice the design cfm without air noise issues. Arzel Zoning Technology, Inc. Bypass Sizing Chart What determines bypass need and size ? If the smallest zone moves less than 40% of the total cfm at design static, you might need a bypass duct If Equipment Size is larger than 5 tons , the blower has the capacity to deliver higher static pressure. (use 400 cfm/ton in step #1) If Location of smallest zone is very close to equipment and has minimal friction, next size larger bypass might be appropriate If the smallest zone is far from equipment and has significant friction, you might need to decrease bypass size If the Size of the smallest zone(sg ft) compared to cfm output at 200% increase is out of balance, it may require larger bypass Blower performance (cfm output) decreases up to 25% as the static pressure increases. Bypass air does not provide BTU exchange at equipment and is used soley to eliminate air noise caused by elevated static and velocity. Velocity incresaes at the open branch runs and decreases at the main trunk and equipment. Variables that influence Bypass Sizing When in doubt, call for application assistance 1-800-611-8312 / 216-831-6068 (1) Determine Total CFM @ max static pressure (2) Subtract CFM of smallest zone @ max static pressure Excessive cfm into a small area might cause overshooting of thermostat set-point When Trunk Dampering static pressures in open supply duct will increase at a higher rate ( use 400 cfm/ton for total in step #1) In Flex Duct Applications, it might require higher static to deliver max cfm to the small zone. (downsizing bypass might be appropriate) (3) Size Bypass per chart below Rectangle Metal duct 3.25" X 10" (3) Size bypass for remaining cfm per chart (1) Approx CFM @ max static pressure (2) Max CFM of smallest zone Subtract (2) from (1) to find required bypass CFM (3) 8" X 20" or 10" X 16" When bypassing over 2100 cfm, use two bypass ducts Copyright 2002 by Arzel Zoning Technology, Inc. 3.25" X 12" 8" X 6" 8" X 10" 8" X 16" or 10" X 12" Min-cfm Max-cfm Outlet Amount Total cfm Total Small zone Stnd- 5" OD 0 0 0 Slotted .5x8 0 Total 0 CFM Minimum Maximum 400 600 500 800 700 1000 Copyright Arzel Zoning Technology, Inc. 2002 Smallest Zone Size This sizing calculation is an estimate of required bypass, consideration of duct style, equipment location, diffuser style, etc, influences actual bypass required Unico's recommendation when zoning their system is to maintain a minimum of 3 outlets per ton of A/C in each zone Bypass Calculator will determine size of Bypass Duct needed Bypass Duct CFM Capacity Arzel Zoning Technology Inc. "High Velocity" Bypass Sizing calculator Enter Capacity of Cooling Unit in Ton's A/C Tons Enter Number of Outlets in smallest zone Required Bypass cfm 0 ROUND 6" 7" 8" Rev- 3/04/04 jcr Bypass Duct Size This sizing calculation is an estimate of required bypass, consideration of duct style, equipment location, diffuser style, etc, influences actual bypass required Round Duct bypass not needed Unico's recommendation when zoning their system is to maintain a minimum of 3 outlets per ton of A/C in each zone Bypass Calculator will determine size of Bypass Duct needed Bypass Duct CFM Capacity Arzel Zoning Technology Inc. "High Velocity" Bypass Sizing calculator Enter Capacity of Cooling Unit in Ton's Enter Number of Outlets in smallest zone A/C tonnage CFM DUCT SIZE CFM @ 1000fpm 5" Round 140 CFM 2 800 x.75 = 600 6" ROUND 200 CFM 2.5 1000 x.75 = 750 7" ROUND 280 CFM 3 1200 x.75 = 900 8" ROUND 340 CFM 3.5 1400 x.75 = 1050 10" ROUND & 8"X 10" 550 CFM 4 1600 x.75 = 1200 8" X 12" 600 CFM 4.5 1800 x.75 = 1350 8" X 14" - 10"x 12" 700 CFM 5 2000 x.75 = 1500 12" Round & 8" X 16" 800 CFM 8" X 20" 1000 CFM 10" X 20" 1260 CFM (3) CFM ROUND 1000-1500fpm Barometric 300 to 600 8" 500 to 800 10" 800 to 1200 12" 1100 to 1600 14" Arzel Zoning Technology Bypass (Barometric) Sizing Chart Subtract (CFM capacity of smallest zone(2)) from (total cfm x.75(1)) Size bypass for remaining cfm according to chart below (3) RECTANGLE Barometric 8" X 12" (1) Minimum CFM of System (2) CFM Capacity of smallest zone Subtract (2) from (1) for BYPASS SIZING (3) Over 5 Ton- Use 400 cfm/ton 400 cfm x .75 = 300 cfm/ton 8" X 12" to 10" x 12" 10" X 12" to 12" x 12" 8" X 20" to 12" X 20"
1054 Bypass sizing factors Branch dampering vs Trunk dampering Tonnage divided by total runs damperd Protect/Unprotect Password
Validation and Quality Control of an ICP‐MS Method for the Quantification and Discrimination of Trace Metals and Application in Paper Analysis-An Overview