PIN:
YVFA0259CS X50AAVBXXX SAKGXXXX41 54XDFXXV17 3W1SXSG2BT XCXRNOXXXX XXXFX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90
Electrical Data
Circuit 1 2 3 4
Compressor kW 118.5 98
Compressor RLA 210 176
Fan QTY/FLA (each) 8 / 3.7 6 / 3.7
Single Point
Min. Circuit Ampacity 495
Max. Fuse / CB Rating (A) 700
Unit Short Circuit Withstand (STD) 65 [kA]
Wires Per Phase 3
Wire Range (Lug Size) 3/0 - 400 kcmil
Operating Condition Electrical Data
Compressor kW 216.5
Total kW 236.4
Notes:
* 100% Free Cooling Ambient Temperature is provided for comparison purposes only. For maximum efficiency, energy optimization controls may
utilize mechanical cooling below this temperature.
Minimum and maximum evaporator flow information are for full load ratings with Ethylene Glycol.
Evaporator Passes: 2, Condenser Type: T, Fan Type: C
Total Pressure Drop includes evaporator and free cooling heat exchangers and is to be used for pump sizing.
Mechanical mode pressure drop includes the evaporator and factory provided pipework inside the chiller frame.
ASHRAE Standard 90.1-2010 and ASHRAE Standard 90.1-2013 & 2016 Compliant.
Note: Unit is equipped with Low Sound Kit (Level 1 Reduction) and Low Profile High Efficiency Fans with Variable Speed EC motor NOTE: SQ and
Additional Lead Time Required.
Measurement of sound pressure used to obtain the sound power data presented is based on AHRI-370.
Air-cooled chillers are rated in terms of sound power not sound pressure. Johnson Controls provides estimates of sound pressure, but this is not the
rating metric.
For an air-cooled chiller, sound pressure calculated from sound power varies depending on how the chiller is assumed to behave, i.e. the radiation
model. In other words, determining sound pressure from sound power requires making assumptions that result in different answers at a given
distance from the chiller. The environment also influences sound pressure in the field installation. Sound pressure estimation radiation models
pertaining to air-cooled chillers include the ‘traditional’ hemispherical model, parallelepiped model and equivalent hemispherical model.
Regarding sound power, Johnson Controls references tolerance limits based on ASHRAE guidelines. These are +/- 6dB in the 63Hz octave band,
+/- 4dB in all other octave bands and +/- 3dB for the overall dBA.
Tolerance limits are based on uncertainties associated with:
1. Measurement Test Procedure
2. Repeatability
3. Production / Manufacturing Variability
Standard deviation associated with air-cooled chiller sound data is a measure of spread i.e. it indicates the range of probability of sound levels.
Note that for operating conditions other than AHRI’s Standard Rating Condition, higher levels of uncertainty can be expected.
Lead times for factory performance testing depend on test laboratory availability. Please confirm with Johnson Controls Customer Service.