Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Commercial Kitchen Hood Design Guide 1 031504

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

The Design Process

Design Guide 1
Improving Commercial Kitchen Ventilation System Performance
Selecting & Sizing Exhaust Hoods


This design guide provides informa-
tion that will help achieve optimum
performance and energy efficiency in
commercial kitchen ventilation sys-
tems by properly selecting and sizing
exhaust hoods. The information pre-
sented is applicable to new construc-
tion and, in many instances, retrofit
construction. The audience for this
guideline is kitchen designers, me-
chanical engineers, code officials,
food service operators, property man-
agers, and maintenance people. This
guide is intended to augment compre-
hensive design information published
in the Kitchen Ventilation Chapter in
the ASHRAE Handbook on HVAC
Applications, as well as Design Guide
2: Improving Commercial Kitchen
Ventilation System Performance
Optimizing Makeup Air (previously
published in 2002 by the California
Energy Commission under the title
Improving Commercial Kitchen Venti-
lation Performance).

This guide reviews the fundamentals
of kitchen exhaust, describes the de-
sign process from the perspective of
exhaust hood application and con-
cludes with real-world design exam-
ples illustrating the potential for en-
ergy efficient design.
Fundamentals of Kitchen Exhaust
Hot air rises! An exhaust fan in the ceiling could remove much of the
heat produced by cooking equipment. But mix in smoke, volatile organic
compounds, grease particles and vapor from cooking, and a means to capture
and contain the effluent becomes necessary to avoid health and fire hazards.
While an exhaust hood serves that purpose, the key question becomes: what is
the appropriate exhaust rate? The answer always depends on several factors: the
menu of food products and the type (and use) of the cooking equipment under
the hood, the style and geometry of the hood itself, and how the makeup air
(conditioned or otherwise) is introduced into the kitchen.

The Cooking Factor
Cooking appliances are categorized as light-, medium-, heavy-, and extra
heavy-duty, depending on the strength of the thermal plume and the quantity of
grease, smoke, heat, water vapor, and combustion products produced. The
strength of the thermal plume is a major factor in determining the exhaust rate.
By their nature, these thermal plumes rise by natural convection, but they are
turbulent and different cooking processes have different surge characteristics.
For example, the plume from hamburger cooking is strongest when flipping the
burgers. Ovens and pressure fryers may have very little plume until they are
opened to remove food product. Open flame, non-thermostatically controlled
appliances, such as underfired broilers and open top ranges, exhibit strong steady
plumes. Thermostatically controlled appliances, such as griddles and fryers have
weaker plumes that fluctuate in sequence with thermostat cycling (particularly
gas-fired equipment). As the plume rises, it should be captured by the hood and
removed by the suction of the exhaust fan. Air in the proximity of the appliances
and hood moves in to replace it. This replacement air, which must ultimately
originate as outside air, is referred to as makeup air.
Fundamentals of Kitchen Exhaust 1
The Cooking Factor 1
The Hood Factor 2
The Makeup Air Factor 6
The Design Process 7
QSR Design Example A-1
Casual Dining Example B-1

Building codes distinguish between cooking processes that create smoke
and grease (e.g., frying, griddling, or charbroiling) and those that produce only
Fundamentals of Kitchen Exhaust

Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 2
heat and moisture (e.g., dishwashing and some baking and steaming operations).
Cooking that produces smoke and grease requires liquid-tight construction with
a built-in fire suppression system (Type I hood), while operations that produce
only heat and moisture do not require liquid-tight construction or a fire sup-
pression system (Type II hood).
Building Codes
Historically the United States had three
organizations that drafted model building
codes which were adopted by local ju-
risdictions as law. These organizations
sponsored development of standardized
building codes, usually called model
building codes, to assure better code
uniformity within the three regions in
which they evolved. In the northeast US,
the Building Officials Council Association
sponsored the National Building Code.
In the southeast US, the Southern Build-
ing Code Council International, spon-
sored the Standard Building Code. In
western US, the International Council of
Building Code Officials sponsored the
Uniform Building Code. California juris-
dictions adopted the UBC, including the
Uniform Mechanical Code (UMC).

In 1994 these organizations formed the
International Code Council to unify their
codes. In 2000, the first full edition of the
International Building Code (IBC) was
published.

In 2000, the National Fire Protection
Association (NFPA) announced that it
would sponsor a complete building code
that would be an alternative to the IBC.
In 2002, NFPA published its first edition.

Mechanical code requirements for
kitchen ventilation are similar among
these model codes.

Unlisted Hoods must meet the prescrip-
tive materials and design requirements
of the local building and health codes. In
addition they must be operated at ex-
haust rates dictated by the local building
code.

Listed Hoods have been tested against
a recognized standard, such as Under-
writers Laboratories (UL) Standard 710.
Standard 710 dictates materials and
design requirements similar to those in
the building code and it has a perform-
ance test requirement for capture and
containment of the thermal plume.

Building codes also require Type I
hoods (liquid-tight construction with a
built-in fire suppression system) over
cooking operations which produce
smoke and grease. requires Cooking
operations that produce only heat and
moisture require a Type II hood (liquid-
tight construction and a fire suppression
system are not required).

Menu items may produce more or less smoke and grease depending on
their fat content and how they are cooked. Higher fat content foods tend to re-
lease more smoke and grease regardless of the type of cooking process. Testing
under an ASHRAE sponsored research project at the University of Minnesota
confirmed that hamburger cooked on a charbroiler releases finer smoke parti-
cles and more grease vapor and particles than hamburger cooked on a griddle.
The percentage fat content of hamburger also contributes to differences in the
amount of grease and smoke released in cooking. Chicken breast, which has
less fat compared to hamburger, releases less particulate and less grease during
cooking on a charbroiler or on a griddle compared to hamburger.

The Hood Factor
The design exhaust rate also depends on the hood style and construc-
tion features. Wall-mounted canopy hoods, island (single or double) canopy
hoods, and proximity (backshelf, pass-over, or eyebrow) hoods all have differ-
ent capture areas and are mounted at different heights and horizontal positions
relative to the cooking equipment (see Figure 1). Generally, for the identical
(thermal plume) challenge, a single-island canopy hood requires more exhaust
than a wall-mounted canopy hood, and a wall-mounted canopy hood requires
more exhaust than a proximity (backshelf) hood. The performance of a double-
island canopy tends to emulate the performance of two back-to-back wall-
canopy hoods, although the lack of a physical barrier between the two hood
sections makes the configuration more susceptible to cross drafts.


Fundamentals of Kitchen Exhaust

Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 3

Wall Mounted Canopy Single Island Canopy
Double Island Canopy Eyebrow

Back Shelf Pass Over


Figure 1. Styles of Exhaust Hoods.
A note of caution: Although a well-engineered proximity hood can be
applied with success at very low exhaust rates (e.g., 150 cfm per linear foot over
medium-duty equipment), this same style of hood (if specified without per-
formance data and/or in accordance with maximum height and setback permit-
ted by code) may fail to effectively capture and contain the cooking effluent at
exhaust rates of 300 cfm/ft or more. Figure 2 illustrates relatively effective and
ineffective applications of proximity hoods.

Fundamentals of Kitchen Exhaust

Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 4





Figure 2. Proximity Hood Effective Design Ineffective Design
Building and/or health codes typically provide basic construction and
materials requirements for exhaust hoods, as well as prescriptive exhaust rates
based on appliance duty and length of the hood (cfm per linear ft.) or open face
area of the hood (cfm per ft
2
). Codes usually recognize exceptions for hoods
that have been tested against a recognized standard, such as Underwriters Labo-
ratories (UL) Standard 710. Part of the UL standard is a cooking smoke and
flair up test. This test is essentially a cooking effluent capture and containment
(C&C) test where no evidence of smoke or flame escaping outside the exhaust
hood must be observed. Hoods bearing a recognized laboratory mark are
called listed hoods, while those constructed to the prescriptive requirements of
the building code are called unlisted hoods. Generally, an off-the-shelf listed hood
can be operated at a lower exhaust rate than an unlisted hood of comparable style
and size over the same cook line. Lower exhaust rates may be proven by labora-
tory testing with specific hood(s) and appliance lineup using the test protocol
described in ASTM Standard F-1704, Test Method for Performance of Commercial
Kitchen Ventilation Systems. This process is sometimes referred to as custom-
engineering a hood.
Laboratory testing of different combinations of appliances has demon-
strated that minimum capture and containment rates vary significantly due to
appliance type and position under the hood. For example a heavy-duty appli-
ance at the end of a hood is more prone to spillage than the same appliance lo-
cated in the middle of the hood.


Fundamentals of Kitchen Exhaust

Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 5
Side Panels and Overhang
Side (or end) panels (as represented in Figure 3) permit a reduced ex-
haust rate in most cases, as all of the replacement air is drawn across the front
of the equipment, which improves containment of the effluent plume generated
by the hot equipment. They are a relatively inexpensive way to improve C&C
and reduce the total exhaust rate. Another benefit of end panels is to mitigate
the negative effect that cross drafts can have on hood performance. It is impor-
tant to know that partial side panels can provide almost the same benefit as full
panels. Although tending to defy its definition as an island canopy, end panels
can improve the performance of a double-island or single-island canopy hood.
An increase in overhang should improve the ability of a canopy hood
to capture because of the increased distance between the plume and hood
edges. This may be accomplished by pushing the appliances as far back under a
canopy hood as practical and/or by increasing the side length. Although this
improves C&C performance, for unlisted hoods under a local jurisdiction refer-
encing the Uniform Mechanical Code (UMC), this would require increase in the
code-required exhaust rate. Larger overhangs are recommended for appliances
that create plume surges, such as convection and combination ovens, steamers
and pressure fryers. This was the driving argument for converting the code-
specified exhaust rates from a cfm/ft2 to a cfm/linear ft. basis in the cur-
rent edition of the International Mechanical Code (IMC).
Figure 3. Illustration of
partial and full side
panels.

Hood Geometry
The ability of a hood to capture and contain cooking effluent can often
be enhanced by adding passive features (e.g., angles, flanges, or geometric flow
deflectors) or active features (e.g., low-flow, high-velocity jets) along the edges
of the hood or within the hood reservoir. Such design features can improve
hood performance dramatically over a basic box-style hood with the same
nominal dimensions.

Cross Drafts
Cross drafts can have a detrimental affect on all hood/appliance com-
binations. Cross-drafts affect island canopy hoods more than wall mounted
canopy hoods because they have more open area allowing drafts to push or pull
effluent from the hood. For example, a pedestal fan used by staff for additional
cooling can severely degrade hood performance, may make capture impossible,
Fundamentals of Kitchen Exhaust

Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 6
and may spill the plume into the kitchen. Location of delivery doors, service
doors, pass-through openings and drive-through windows may be sources of
cross drafts due to external and internal air pressure differences. Cross drafts
can also be developed when the makeup air system is not working correctly,
causing air to be pulled from open drive-through windows or doors.

The Makeup Factor
The layout of the heating, ventilating, and air-conditioning (HVAC) and
makeup air (MUA) supply air outlets or diffusers can affect hood performance.
These can be sources that disrupt thermal plumes and hinder C&C. Safety fac-
tors are typically applied to the design exhaust rate to compensate for the effect
that undesired air movement within the kitchen has on hood performance.
Air that is removed from the kitchen through an exhaust hood must be
replaced with an equal volume of outside replacement (makeup) air through one
or more of the following pathways:
1. Transfer air (e.g., from the dining room)
2. Displacement diffusers (floor or wall mounted)
3. Ceiling diffusers with louvers (2-way, 3-way, 4-way)
4. Slot diffusers (ceiling)
5. Ceiling diffusers with perforated face
6. Integrated hood plenum including (see Figure 4):
Short circuit (internal supply)
Air curtain supply
Front face supply
Perforated perimeter supply
Backwall supply (rear discharge)
Combinations of the above

Design issues related to replacement (makeup) air and its impact on
hood performance are the subject of Design Guide 2, Improving Commercial
Kitchen Ventilation Performance Optimizing Makeup Air (previously published by
the California Energy Commission under the title Improving Commercial Kitchen
Ventilation Performance).


Figure 4. Types of MUA
Supply Integrated with the
Hood.


Design Guide 1 Selecting and Sizing Exhaust Hoods 03.15.04 7
The Design Process
Successfully applying the fundamentals of commercial kitchen ventila-
tion (CKV) during the design process requires a good understanding of the local
building code requirements, the menu and appliance preferences, and the pro-
jects budget. Information about the kitchen equipment and ventilation re-
quirements may evolve over the course of the design phase. Data needed by
other members of the design team may require early estimates of certain pa-
rameters (e.g., the amount of exhaust and makeup air, motor horsepower, water
supply and wastewater flow rates). As more decisions are made, new informa-
tion may allow (or require) refinements to the design that affect exhaust and
makeup air requirements.
The fundamental steps in the design of a CKV system are:
1. Establish location and duty classifications of appliances including
menu effects. Determine (or coordinate with foodservice consult-
ant) preferred appliance layout for optimum exhaust ventilation.
2. Select hood type, style, and features.
3. Size exhaust airflow rate.
4. Select makeup air strategy; size airflow and layout diffusers.
Steps 1 through 3 are discussed in this Design Guide; Step 4 is the subject of
Design Guide 2, Improving Commercial Kitchen Ventilation Performance Optimizing
Makeup Air.
A good understanding of how building code requirements apply to
kitchen design is essential. Local or state building codes are usually based on
one of the model building codes promulgated by national code organizations
(see sidebar). Our discussion of the building codes will be limited to require-
ments that affect design exhaust and makeup air rates, which are usually found
in the mechanical code portion of the overall building code.
Historically, codes and test standards used temperature ratings for
classifying cooking equipment. Although these temperature ratings roughly cor-
related with the ventilation requirement of the appliances, there were many gray
areas. During development of ASHRAE Standard 154, Ventilation for Com-
mercial Cooking Appliances, it was recognized that plume strength, which takes
into account plume volume and surge characteristics, as well as plume tempera-
ture, would be a better measure for rating appliances for application in building
codes. Duty ratings were created for the majority of commercial cooking ap-
pliances under Standard 154, and these were recently adopted by the Interna-
The Design Process

Design Guide 1 Exhaust Hood Selection and Sizing 03.15.04 8
tional Mechanical Code (IMC). The Kitchen Ventilation chapter of the
ASHRAE Applications Handbook (2003 edition) applied the same concept to
establish ranges of exhaust rates for listed hoods. The appended Design Exam-
ples in this Guide reference duty classifications for appliances. The duty classifi-
cations listed in the sidebar are from ASHRAE Standard 154-2003, Ventilation
for Commercial Cooking Operations.
Appliance Duty Classifications
From ASHRAE Standard 154
Light Duty
Gas and electric ovens (including
standard, bake, roasting, revolving,
retherm, convection, combination
convection/steamer, conveyor,
deck or deck-style pizza, and pas-
try)
Electric and gas steam-jacketed
kettles
Electric and gas compartment
steamers (both pressure and at-
mospheric)
Electric and gas cheesemelters
Electric and gas rethermalizers
Medium Duty
Electric discrete element ranges
(with or without oven)
Electric and gas hot-top ranges
Electric and gas griddles
Electric and gas double-sided grid-
dles
Electric and gas fryers (including
open deep-fat fryers, donut fryers,
kettle fryers, and pressure fryers)
Electric and gas pasta cookers
Electric and gas conveyor (pizza)
ovens
Electric and gas tilting skillets
/braising pans
Electric and gas rotisseries
Heavy Duty
Electric and gas underfired broilers
Electric and gas chain (conveyor)
broilers
Gas open-burner ranges (with or
without oven)
Electric and gas wok ranges
Electric and gas overfired (upright)
broilers
Salamanders
Extra Heavy Duty
Appliances using solid fuel such as
wood, charcoal, briquettes, and mes-
quite to provide all or part of the heat
source for cooking.
Calculation of Exhaust Rates Us-
ing Duty Ratings
The rule for unlisted hoods is to
apply the duty rating for the highest
duty appliance to the length of the
entire hood (or separate section of
hood served by an individual ex-
haust fan).
For listed hoods, the same rule may
be applied if little is known about
the expected cooking operations. If
details of the cooking operation are
known, rates for each appliance
may be applied and added up to
determine the total exhaust rate.
The IMC dictates exhaust rates based on hood type and appliance duty.
Table 1 states these exhaust rates in cfm per linear foot of hood (linear foot
in this case applies to the distance from edge to edge along the front face of the
hood). The Code requires that the exhaust rate for the highest duty-rated appli-
ance be applied to the entire hood. The Uniform Mechanical Code (UMC), used
in many California jurisdictions, requires calculating exhaust rates based on
square-footage of capture area (capture area is the open area defined by the
lower edges of the hood). The UMC uses temperature classifications for appli-
ances, as described above. Both the IMC and the UMC require a minimum 6-
inch hood overhang (front and sides) for canopy style hoods.

Table 1. Unlisted Hood Exhaust Flow Rates.
IMC MinimumExhaust FlowRate for Unlisted Hoods
(cfmper linear foot of hood)
Type of Hood
Light
Duty
Equipment
Medium
Duty
Equipment
Heavy
Duty
Equipment
Extra-Heavy
Duty
Equipment
Wall-mounted Canopy 200 300 400 550
Single Island Canopy 400 500 600 700
Double Island Canopy 250 300 400 550
Eye Brow 250 250 not allowed not allowed
Backshelf 250 300 400 not allowed
Passover 250 300 400 not allowed

The prescriptive mechanical code exhaust rate requirements must be
conservative because the AHJ (authority having jurisdiction) has no control
over the design of an exhaust hood or the positioning and diversity of appli-
ances placed beneath that hood. However, in cases where the CKV system de-
sign and appliance configuration has been optimized, the code-specified exhaust
rate may be significantly greater than what is required for effective capture and
containment of the cooking plume. The code-based safety factor (which may
be necessary for unlisted systems) can place an energy cost burden on the CKV
system through its demand for more heated and cooled makeup air.
The Design Process

Design Guide 1 Exhaust Hood Selection and Sizing 03.15.04 9
When the energy crisis of the 1970s occurred, kitchen ventilation sys-
tems became an obvious target. Industry responded with two methods of reduc-
ing the amount of replacement air that had to be cooled or heated: (1) short-
circuit hoods, and (2) listed hoods.
One strategy, called internal compensation, was to introduce the
makeup air directly into the hood reservoir. This is more commonly known as
short-circuit makeup air. Although short-circuit hoods have been installed
and operated with as much as 80% of replacement air being introduced inter-
nally, field and laboratory investigations have shown that these hoods fail to
capture and contain effluent adequately.
Short-Circuit Hoods

Generally, not more than 20% of the
replacement air can be introduced
internally without interfering with
proper capture and containment. The
net exhaust from the kitchen space is
the key factor in determining effective
capture. Specifying short-circuit hoods
is not a recommended strategy for
reducing the energy load of a CKV
system (see Design Guide 2 for more
information).
The second industry strategy was to test hoods under laboratory condi-
tions according to a test protocol specified by Underwriters Laboratories, Stan-
dard 710, Exhaust Hoods for Commercial Cooking Equipment. This UL Standard
covers materials and construction of exhaust hoods as well as C&C perform-
ance. The C&C performance is based on testing a single appliance under a rep-
resentative hood at one or more of three cooking temperature operating set
points (400F, 600F, or 700F). The UL listing reports the minimum C&C rate
determined under this laboratory test.
Safety Factors

Designers should apply a safety factor
to address dynamic conditions en-
countered in real kitchens. Although
manufacturers do not publish safety
factors to be applied to their minimum
listed cfm they will typically rec-
ommend increasing the exhaust rate
by 5% to 25% over the minimum list-
ing.
Another national standard, ASTM Standard F-1704-1999, Test Method
for Performance of Commercial Kitchen Ventilation Systems, covers exhaust hood cap-
ture and containment performance as well as heat gain from hooded appliances.
The current version of ASTM F-1704 also does not address dynamic condi-
tions, but there are amendments under consideration to add a dynamic test that
would quantify a safety factor. The capture and containment tests in UL 710
and ASTM F-1704 are similar.
While the exhaust rates shown in Table 1 are minimum mandatory
rates for unlisted hoods, the rates in Table 2 reflect the typical range in design
exhaust rates for listed hoods. The values in this table may be useful for estimat-
ing the cfm advantage offered by listed hoods over unlisted hoods for a given
project. But in the final stage of design, exhaust rates may be adjusted to ac-
count for:
1. Diversity of operations (how many of the appliances will be on at the
same time).
2. Position under the hood (appliances with strong thermal plumes, lo-
cated at the end of a hood, tend to spill effluent more easily than the
same appliance located in the middle of the hood).
The Design Process

Design Guide 1 Exhaust Hood Selection and Sizing 03.15.04 10
3. Hood overhang (in combination with appliance push-back). Positioning
a wall-mounted canopy hood over an appliance line with an 18-inch
overhang can dramatically reduce the required ventilation rate when
compared to the minimum overhang requirement of 6 inches. Some
manufacturers list their hoods for a minimum 12-inch overhang,
providing an immediate advantage over unlisted hoods.
4. Appliance operating temperature (e.g. a griddle used exclusively by a
multi-unit restaurant at 325F vs. 400F surface temperature) or other
specifics of appliance design (e.g. 18-inch vs. 24-inch deep griddle sur-
face).
5. Differences in effluent from menu selections, such as cooking ham-
burger on a griddle versus on a charboiler, or using a charbroiler to
cook chicken versus hamburger.
6. Operating experience of a multi-unit restaurant can be factored into the
equation. For example, the CKV system design exhaust rate (for the
next new restaurant) may be increased or decreased based on real-world
assessments of the CKV system in recently constructed facilities.

Table 2. Typical Exhaust Rates for Listed Hoods.
MinimumExhaust FlowRate for Listed Hoods
(cfmper linear foot of hood)
Type of Hood
Light
Duty
Equipment
Medium
Duty
Equipment
Heavy
Duty
Equipment
Extra-Heavy
Duty
Equipment
Wall-mounted Canopy 150-200 200-300 200-400 350+
Single Island Canopy 250-300 300-400 300-600 550+
Double Island Canopy 150-200 200-300 250-400 500+
Eye Brow 150-250 150-250
not recom-
mended
not recom-
mended
Backshelf/Passover 100-200 200-300 300-400
not recom-
mended
Source: ASHRAE 2003 Applications Handbook, Chapter 31, Kitchen Ventilation



Design Examples
CKV design examples, based on actual kitchen layouts, illustrate the design process and the potential for
optimization. Each example starts with a base case that specifies an unlisted hood. Design options for reducing
the exhaust (and makeup) airflow rates without compromising capture and containment are presented. Each ex-
ample concludes with a best case option that may be achieved through a rigorous custom-engineered effort.

Disclaimer: The design examples are representative cases for illustration of design concepts only. Application of the concepts to particu-
lar designs may result in savings that are lower or higher than those depicted in the examples. Close coordination with local code offi-
cials, hood and fan manufacturers, and construction contractors is recommended for all kitchen ventilation projects.


Design Guide 1 Example A 03.15.04 A-1

Design Example A: Quick Service Restaurant
A quick serve restaurant (QSR) has the appliances listed in Table A-1. As in most quick-service restaurants,
kitchen space is at a premium and the limited menu is prepared using a few primary appliances.
Table A-1. Duty Rating and Lengths of Appliances.
Appliances (left to right under hood)
Appliance
Rated Input
(kBtu/h)
Appliance Duty
Rating
(per IMC)
Active Cooking
Length (Ft)
Hood Front Face
Length (Ft)
Overhang (6-inches) 0.00 0.50
Two (2) Deep Fat Fryers (80 kBtu/h each) 160 Medium 2.50 2.50
Fryer Drip Station 0.00 1.25
4-foot Griddle 80 Medium 4.00 4.00
Half-Size Convection Oven 35 Light 2.50 2.50
Overhang (6-inches) 0.00 0.50
Total 275 9.00 11.25

Case 1 (Base Case) Unlisted Wall-Mounted Canopy Hood
Our base case design will place the cooking equipment under a 4-ft deep, wall-mounted, unlisted canopy
hood. The nominal active cooking surface length is 9 feet. In addition, there is a 1.25-foot fryer drip station between
the fryers and the griddle. Adding the code-required 6-inch hood overhang at each end of the hood, a hood length of
11.25 ft. is required (see Figure A-1).
Since both the fryers and the griddle have a medium-duty rating, the design exhaust rate is based on 300 cfm
per linear foot of hood (equivalent to 75 cfm/ft
2
for a 4-foot deep hood per the UMC) for a design exhaust flow rate
of 3375 cfm.

Table A-2. Unlisted Hood Exhaust Flow Rates for Wall-Mounted Canopy Hood.
IMC rate for medium duty equipment under wall-mounted canopy hood 11.25 ft. x 300 cfm/ft. 3375 cfm
UMC rate for medium duty equipment under wall-mounted canopy hood 11.25 ft. x 4 ft. x 75 cfm/sf. 3375 cfm






Design Exampl e A: Quick Servi ce Restaurant

Design Guide 1 Example A 03.15.04 A-2

11.25 ft



Figure A-1. Base Case - Unlisted Wall-Mounted Canopy Hood.

Design Exampl e A: Quick Servi ce Restaurant

Design Guide 1 Example A 03.15.04 A-3
Case 2: Application of a Listed Canopy Hood
In this second design scenario, the unlisted canopy hood is replaced with a listed canopy hood that will per-
mit selecting an exhaust airflow rate below the prescriptive code value. In addition (following coordination with the
owner and operations manager), the fryer dump station is moved to the end of the line (partially under the hood),
while a full-size end panel is added to the oven-end of the hood. This reduces the hood length from 11.25 ft. to 9.5 ft.
For listed hoods, the exhaust rate is also established by the highest appliance duty, which in this case is set by either
the fryer and griddle as medium duty. Based on its own testing and experience with the selected hood and the pro-
posed cookline, the manufacturer recommends a design ventilation rate of 250 cfm per linear foot of hood. Note that
if the hood length were not reduced, the required exhaust rate would be about 440 cfm greater, or 2815 cfm.

Table A-4. Listed Wall-Mounted Canopy Hood Exhaust Flow Rates.
UL Listed Canopy hood @ 250 cfm/ft 9.5 ft x 250 cfm/ft 2375 cfm


9.5 ft



Figure A-2. Case 2 - Listed Wall-Mounted Canopy Hood with End Panel.
Design Exampl e A: Quick Servi ce Restaurant

Design Guide 1 Example A 03.15.04 A-4
Case 3: Optimized Design Using a Listed Backshelf and Canopy Hood
Capitalizing on the design practice of larger QSR operators, the canopy hood over the fryers and griddle is
replaced with a listed backshelf hood. Within its listing for this hood, the manufacturer recommends an exhaust rate
of 150 cfm per linear ft. for medium duty equipment. Since this backshelf hood incorporates integrated side panels (in
accordance with its listing), the fryer dump station can be moved completely outside of the hood footprint and the
hood length is reduced to 9 feet. A custom canopy hood with full side panels serves the convection oven, again at the
manufacturers recommended exhaust rate of 150 cfm per linear ft. The exhaust rates in this example would require
laboratory verification in accordance with ASTM F1704-99.


2.5



6.5
Figure A-3. Case 3 - Optimized Design with a Listed Backshelf Hood and a Listed Canopy Hood.

Table A-5. Listed Backshelf and Canopy Hood Exhaust Flow Rates.
Listed canopy hood w/full side panels 2.5 ft. x 150 cfm/ft. 375 cfm
Listed backshelf hood with side panels 6.5 ft. x 150 cfm/ft. 975 cfm
Total Exhaust Rate 1350 cfm

Design Exampl e A: Quick Servi ce Restaurant

Design Guide 1 Example A 03.15.04 A-5
Summary of Savings
A significant reduction in exhaust airflow may be achieved by appropriate arrangement of equipment and
hood style selection, as summarized in Table A-6 and Figure A-4. In the case of the custom-engineered design, the
dedicated makeup air unit was eliminated from the system.

Table A-6. Summary of Exhaust Rates
Hood Type and Arrangement Exhaust (cfm) %Reduction
Single Unlisted Canopy Hood 3375 cfm
Single Listed Canopy Hood 2375 cfm 30%
Custom-Engineered Backshelf /Canopy Hood Combination 1350 cfm 60%


1350
2375
3375
0 500 1000 1500 2000 2500 3000 3500 4000
Custom-Engineered
Backshelf /Canopy
Hood Combination
Single Listed Canopy
Hood
Single Unlisted
Canopy Hood
Exhaust Rate (cfm)
1000 cfm
savings
2025 cfm
savings

Figure A-4. Quick Service Restaurant Design Example Savings



Design Guide 1 Example B 03.15.04 B-1


Design Example B: Casual Dining Restaurant
A casual dining restaurant will have the appliances listed in Table B-1. Figure B-1 shows the proposed layout.

Table B-1. Duty Rating and Lengths of Appliances.
Appliances (left to right under hood)
Typical Rated Input
(kBtu/h)
Typical IMC Appli-
ance Duty Rating
Active Cooking
Length (Ft)
Front Face Length
(Ft)
Overhang (6-in over 1-ft Counter) 0.5
6-foot Griddle 120 Medium 6 6
3-foot Charbroiler 96 Heavy 3 3
Fryer Drip Station 1.25
Three (3) Fryers (80 kBtu/h each) 240 Medium 3.75 3.75
Prep Surface 1
4-burner Open Range Top 80 Heavy 2 2
Overhang (6-in) 0.5
Totals 536 14.75 18.0


18 ft



Figure B-1. Base Case Appliance Layout.
Design Exampl e B: Casual Dining Restaurant

Design Guide 1 Example B 03.15.04 B-2
Base Case - Unlisted Wall-Mounted Canopy Hood
Our first design example will place all of these appliances under a single hood. Note that for ease of fabrica-
tion and installation, hood sections are usually shipped in lengths up no greater than 12 feet. To obtain our required
length for a single hood, two 9-ft sections are mounted end-to-end and the exhaust collars are ducted to a single ex-
haust fan.
We have a nominal active cooking surface length of 14.75 feet. We also have two 1-ft counter top sections
that are desired for convenience (prep) as shown in Figure B-1. A 6-inch hood overhang for active cooking appliances
is required by IMC and UBC codes. The active appliance on the left side is the griddle. Thus, one half of the 1-ft
counter top on the left end is under the hood. The total hood length is 18 feet.
Since we have at least one appliance in our proposed cook line with a heavy-duty rating, the required exhaust
rate is 400 cfm per linear foot of hood, or 7,200 cfm total for an 18-ft wall-mounted canopy hood. Under the UMC,
for canopy hoods with high temperature (roughly equivalent to heavy-duty) appliances, the rate for a wall-mounted
canopy hood is 100 cfm/sf, yielding the same exhaust rate of 7,200 cfm for a 4-ft by 18-ft capture area.
An alternative layout can be considered. Note that for our initial layout there is a heavy-duty appliance under
each 9-ft section of the hood. Using the code rule stated above, the exhaust rate for the highest duty appliance(s) is
applied to calculate the exhaust rate for the entire hood. If we treat the hood as two hoods by using separate exhaust
fans for each section, we can reduce the overall exhaust rate by placing the two heavy-duty appliances (charbroiler and
range top) under the same 9-ft section. The total exhaust required can be reduced by 900 cfm (i.e., from 7,200 to
6,300 cfm based on 400 cfm/lf for heavy-duty (9 x 400 = 3600 cfm) and 300 cfm/lf for medium-duty (9 x 300 = 2700
cfm) appliances).


18 ft



Figure B-2. Base Case Alternative Unlisted Hood Layout.
Design Exampl e B: Casual Dining Restaurant

Design Guide 1 Example B 03.15.04 B-3

Table B-2. Unlisted Wall-Mounted Canopy Hood Exhaust Flow Rates.
Base Case: Single Unlisted Wall-Mounted Canopy Hood
IMC, Heavy Duty Equipment: 18 ft. x 400 cfm/ft. 7,200 cfm
UMC, High Temperature Equipment: 18 ft. x 4 ft. x 100 cfm/ft
2
. 7,200 cfm
Alternative Layout Case: Two Unlisted Wall-Mounted Canopy Hood
IMC, Heavy Duty Equipment: 9 ft. x 400 cfm/ft. 3,600 cfm
IMC, Medium Duty Equipment: 9 ft. x 300 cfm/ft. 2,700 cfm
Total for Alternative Layout under the IMC: 6,300 cfm

UMC, High Temperature Equipment: 9 ft. x 4 ft. x 100 cfm/ft
2
.
3,600 cfm
UMC, Medium Temperature Equipment: 9 ft. x 4 ft. x 75 cfm/ft
2
.
2,700 cfm
Total for Alternative Layout under the UBC: 6,300 cfm

Case 2 - Listed Wall-Mounted Canopy Hoods
Another technique to reduce overall exhaust rates is to select listed hood lengths to match appliances
grouped by duty rating. In Case 1 with the alternative appliance layout, we used two 9-ft unlisted hoods with two ex-
haust fans. Note that non-cooking surfaces are under both hoods (such as the counter tops and the fryer drip station)
and two fryers (medium-duty appliances) are under the hood with the broiler and range top (heavy-duty appliances).
Non-cooking surfaces under the hood have required exhaust rates of zero. Grouping the heavy-duty appliances to-
gether and selecting the hood length to match (in this case, 5.5 feet including the 6-in. overhang), applies the largest
exhaust rate only where it is needed. Where possible, place work counters and other non-cooking surfaces (such as the
fryer drip station) at the ends of the hoods, or outside the hood envelope. Assuming that placing non-cooking sur-
faces at the ends of the hoods is acceptable for efficient operation (in some cases it may not be), we re-arrange the
cookline as in Figure B-3, which also shows the griddle placed next to the charbroiler again (an arrangement preferred
by many cooks). This reduces the left side hood to 10.25 ft.
For listed hoods, we apply the exhaust rates by appliance duty from Table 2. The hood model selected should
be rated for the highest duty (or temperature) rating required for any appliance in the line up. In our case, the char-
broiler and the range top are classified as heavy duty. The charbroiler produces a strong thermal plume under typical
operating conditions. However, the range top has a wide variation in plume strength because its input is adjustable
and it is often used for low input operations such as sauting or stockpot cooking.
Under the hood on the right side, the charbroiler (heavy duty) would require 400 cfm per linear ft (lf) and the
four-burner range top (heavy-duty, but used for stockpot cooking typically low input for extended periods), the low
end of the heavy-duty category (200 cfm/lf) could be applied. The high end of the heavy-duty category is appropriate
in this situation due to the predominance of the charbroiler plume.
Under the hood on the left side, the griddle (medium duty) would require 200 to 250 cfm/lf and assuming the
menu requires moderate deep-fat frying, the mid-range rate for the medium-duty category can be used for the fryers
(250 cfm/lf). Using the higher rates for each hood, the left hood requires 2,560 cfm and the right hood requires 2,220
cfm. Together, the two hoods exhaust 4,760 cfm, which is 2,540 cfm less than the base case unlisted hood. Each hood
should have its own fan to assure that the design exhaust rates are maintained. Re-arranging the cook line as shown in
Figure B-3 reduced the overall hood length to 15.75 feet and allows a further reduction in exhaust rates.
It would also be feasible to add end panels to this listed hood. This would allow reducing the hood length by
six inches on each end, saving 125 cfm on the left and 200 cfm on the right.
Design Exampl e B: Casual Dining Restaurant

Design Guide 1 Example B 03.15.04 B-4

5.5 ft 10.25 ft


Figure B-3. Revised Layout with Two Listed Hoods.

Table B-4. Revised Layout with Listed Wall-Mounted Canopy Hood Exhaust Flow Rates.
Hood over griddle & fryers: 10.25 ft. x 250 cfm/ft. 2,560 cfm
Hood over broiler & range: 5.5 ft. x 400 cfm/ft. 2,200 cfm
Total Exhaust Rate: 4,760 cfm

Case 3 Optimized Design - Combination Backshelf/Canopy
The lower ranges of exhaust rates for each hood type in Table 3 can be achieved using custom-engineered,
listed hoods. These hoods have features that enhance capture and containment, such as end panels (partial or full) and
active or passive features at the capture edges that turn the thermal plume back into the reservoir.
Backshelf or passover style hoods are often used over griddles and fryers. We can group the appliances so
that our medium-duty appliances, the griddle and the 3-vat fryer (with fryer drip station), are under one 11-ft back-
shelf hood and our heavy-duty appliances, the charbroiler and the open burner range, are under a 5.5-ft wall-mounted
canopy hood. Assuming we have well-engineered hood features, such as interior capture-edge angles and partial side
panels on the wall-mounted canopy hood, that allow us to achieve the lowest rates for listed hoods, we can achieve
additional savings. As shown in Figure B-4, this example assumes that we have moved the counter area at the left end
outside of the capture envelope. The fryer drip station is also shown inside the capture envelope in this design, al-
though it is not required under code. Note that the entire hood length has been reduced by 1.5 ft compared to original
unlisted hood, which allows additional exhaust and makeup air savings without impairing hood capture effectiveness.
The exhaust rates used in this example would require laboratory verification in accordance with ASTM F1704-99.

Design Exampl e B: Casual Dining Restaurant

Design Guide 1 Example B 03.15.04 B-5

5.5 ft



11 ft
Figure B-4. Optimized Design with a Listed Backshelf Hood and a Listed Canopy Hood.

Table B-5. CustomCombination Backshelf/Canopy Hood Exhaust Flow Rates.
Custom backshelf hood over griddle & fryers: 11 ft. x 150 cfm/ft. 1,650 cfm
Custom canopy hood with full side panels over broiler & range: 5.5 ft. x 300 cfm/ft. 1,650 cfm
Total Exhaust Rates: 3,300 cfm

Summary of Savings
Significant savings may be achieved by appropriate arrangement of equipment and hood style selection, as
summarized in Table B-7.
Table B-7. Summary of Savings Based on Improved Design Examples.
Hood Type and Arrangement
Hood(s)
Exhaust Rate
SavingsCompared
Base Case
%Savings
One Unlisted Hood 7,200 cfm 0 cfm
Two Unlisted Hood Sections (with rearranged line) 6,300 cfm 900 cfm 13%
Two Listed Hood Sections (with rearranged line) 4,760 cfm 2,440 cfm 34%
Combo Backshelf/Canopy 3,300 cfm 3,900 cfm 54%



Design Guide 1 Acknowledgements 03.15.04 C-1


Notes and Acknowledgments


Funding
Southern California Edison
P.O. Box 6400
Rancho Cucamonga, CA 91729
(800) 990-7788
www.sce.com/showcasing-energy-efficiency
This Guide is funded by California utility cus-
tomers and administered by Southern California
Edison under the auspices of the California
Public Utilities Commission



Research Team
Architectural Energy Corporation
2540 Frontier Ave, Suite 201
Boulder, CO 80301
(800) 450-4454
www.archenergy.com

Fisher Nickel, inc.
12949 Alcosta Boulevard, Suite 101
San Ramon, CA 94583
(925) 838-7561
www.fishnick.com


Research Labs
Commercial Kitchen Ventilation Laboratory
955 North Lively Blvd.
Wood Dale, IL 60191
(630) 860-1439
www.archenergy.com/ckv

Food Service Technology Center
12949 Alcosta Boulevard, Suite 101
San Ramon, CA 94583
(925) 866-2864
www.pge.com/fstc










2004 by Southern California Edison. Permission is granted to reproduce this document in its entirely provided that this
copyright notice is included.

You might also like