01A Design Criteria For Towers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3
At a glance
Powered by AI
The document discusses the design criteria for a 400kV transmission line including specifications for towers, conductors, insulators, ground clearances, wind and temperature loadings etc.

The different types of towers mentioned are Suspension Tower DA, Angle Tower Type DB, Angle Tower Type DC, Dead End Tower Type DD.

The design wind pressure considered is 701 N/m2 as per Table 4 of IS 802 for Wind Zone 4.

1 Voltage Class : 400KV

2 Configuration of Conductors :
3 Number of Circuits :
4
5 Configuration of Earth wire :
6 Conductor :
Spacing of Sub-conductors 457mm
7 Earth wire : a. GSW (7/3.66mm)
b. 24 FIBER OPGW [Refer attached drawing sheet]
8 Classification of Towers
Suspension Tower DA :
Angle Tower Type DB :
Angle Tower Type DC :
Angle Tower Type DD :
Dead End Tower Type DD :
9 Extension to Towers : +1.5/+3/+4.5/+6/+7.5/+9m for all types of tower
+18m & 25m for DA & DD Towers only
10 Spans
Normal Span : 400 m
Wind Span : NC=400m; BWC=240m (for DA,DB,DC,DD)
NC=260m; BWC=156m (for DD dead end tower)
[Slack span considered as 15% of Normal Span]
Weight Span (max) : NC=600m; BWC=360m (for DA )
[Refer CBIP Manual] NC=600m; BWC=360m (for DB,DC,DD Angle Tower )
NC=600m; BWC=360m (for,DD Dead End Tower )
Weight Span (min) : NC=200m; BWC=100m (for DA )
[Refer CBIP Manual] NC=0m; BWC=-200m (for DB,DC Angle Tower )
NC=0m; BWC=-300m (for DD Angle Tower )
NC=0m; BWC=-300m (for DD Dead End Tower )
11 Temperature Range
Minimum Temperature : 0
0
C
Everyday Temperature : 32
0
C
Maximum Temperature : 85
0
C
12
Maximum Working Tension of
Earth wire or Conductor
100% of design wind pressure at 32
0
C, or, 36% of design wind
pressure at 0
0
C; whichever is more stringent
:
0
0
Dead End; Dead End with 0
0
-15
0
deviation both on line
side & slack span side
[Refer IS 802 (Part I /Sec 1) - 1995]
CLIENT
Essel Infraprojects Limited.
MUZAFFARPUR-DARBHANGA
400 KV D/C TL
DESIGN CRITERIA
2 nos of Earthwire per Tower
Vertical Formation
2
The towers shall be of Rectangular / Square base, self supporting lattice steel structure.
Hexagonal bolts & nuts with spring washers shall be used for connection of fabricated
tower members. The towers including stubs, cleats, bolts, nuts & washers shall be
galvanized.
Placement of Circuit on each
side of Tower
30
0
-60
0
deviation
:
(A) DESIGN CRITERIA FOR TOWERS
1
Triple "ACSR SNOWBIRD" (42/3.99+7/2.21)
15
0
-30
0
deviation (To be used as Section Tower)
0
0
-2
0
deviation
0
0
-15
0
deviation (To be used as Section Tower)
CLIENT
Essel Infraprojects Limited.
MUZAFFARPUR-DARBHANGA
400 KV D/C TL
DESIGN CRITERIA
(A) DESIGN CRITERIA FOR TOWERS
13 Minimum Ground Clearance 8840 mm (+150mm Sag Error) At maximum Sag
condition at maximum temperature & no wind
14 Insulator Strings
Composite Insulator Sets
Suspension Strings: :
Double "I" Suspension String
Tension Insulator Strings: :
Single Suspension:(Pilot) String :
Double Tension String :
15
(i) Suspension Insulator : 0
0
- 3050 mm
22
0
- 3050 mm
44
0
- 1860 mm
(ii) J umper : 0
0
- 3050 mm
20
0
- 3050 mm
40
0
- 1860 mm
(iv) Conductor to Conductor
Vertical Clearance : 8000 mm
16 Earth wire Clearances
(ii) Angle of Protection : 20
0
(from the vertical)
(iii) Earth wire Sag :
17 (a) 22% of UTS at 32
0
C No Wind for Conductor
(b) 70% of UTS at 32
0
C Full Wind for Conductor & Earthwire
(c) 70% of UTS at 0
0
C 36% Wind
(d) 20% of UTS at 320C No Wind for Earthwire
18 Broken Wire Condition : Any One for Suspension Tower Type DA
Any Two for Light/Medium Angle Tower Type DB&DC
Any Three for Heavy Angle/Dead End Tower Type DD
19 Design Concept : Towers to be designed as per provisions of
Wind Pressure for Security Cond
n
: For Suspension Tower - 75%; For other towers - 100%
: 1.02 for NC & BWC - Strength Factor [as per IS 802 (Part I
/Sec 1) - 1995]
[Refer IS 802 (Part I /Sec 1) -
1995]
[Refer IS 802 (Part I /Sec 1) -
1995]
As per IS 802 (Part I/Sec 2): 1992
As per IS 802 (Part I/Sec 1): 1995
Allowable stresses in tower
members, bolts & nuts etc.
;
[Refer IS 5613 (Part 2 /Sec 1) -
1985]
;
Final Tension Limits for
Conductor & Earth wire
Factor Of Safety
9000 mm (Vertical distance between earth wire & Top
Power Conductor)
;
Loading on towers,
wires and insulator
:
For detailed dimensions with hardware
Refer attached drawing sheets
(i) Mid span clearance
between Earth wire and
Power Conductor
Minimum Electrical Clearances [for Line MSL upto 1000m]
Earth wire sag shall not be more than 90% of corresponding
sag of power conductor under still air conditions for entire
specified temperature range
As per CBIP Manual
CLIENT
Essel Infraprojects Limited.
MUZAFFARPUR-DARBHANGA
400 KV D/C TL
DESIGN CRITERIA
(A) DESIGN CRITERIA FOR TOWERS
20 Wind Zone : 4
21 Reliability Level : 1
22 Terrain Category : 2
23 Basic Wind Speed : 47 m/sec
24 Design Wind Pressure : 701 N/m
2
(As per Table 4, IS 802)
25 Narrow Front Wind :
26 Materials for towers
Mild Steel : As per IS 2062: 2011 Grade: E250
High Tensile Steel : As per IS 2062: 2011 Grade: E350
Angle Sections of Steel As per IS 808
Bolts & nuts : As per IS 12427 Grade: 5.6
Stresses in Bolts as per Clause 5.4 IS: 802
(Part 1/Sec 2) 1992
Shear Stress in Bolts : 310 Mpa
Bearing Stress
Of Bolts =2 x 310 = 620 Mpa
Of Members (MS) =2 x 250 = 500 Mpa
Of Members (HT) =2 x 350 = 700 Mpa
27 Effective Slenderness Ratio (Kl/r)
Leg Members, Ground Wire Peak and Cross arm chord members 120
Bracing and other members 200
Redundant Members 250
Tension - only members 400
Redundant members shall be checked for axial compressive load of 2.5% of ultimate
load of member to which it connects [as per IS 802 (Part I /Sec 2) - 1992]
28 Minimum Thickness of Members
Main Tower Legs, peak & lower members of cross arm 5 mm
Other Members 4 mm
Gusset Plates 5 mm
Suspension tower shall be checked for narrow front wind
with a wind speed of 1.5 times basic wind speed.
As per IS 802 (Part
I/Sec 2): 1992
Note: All aforesaid details have been filled up as per details available in the Technical
Specification of the subject project. Values / Guidelines not available in the specification has been
selected from the Standard Indian code and/or manufacturer's data sheets (mentioned therein).
As per IS 802 (Part
I/Sec 2): 1992