Refrigeration Test Rig
Refrigeration Test Rig
Refrigeration Test Rig
Roll No. 37
Date: 23/08/2014
Academic Year: 2014 - 2015
possible to transfer heat from an area of low temperature (in this case evaporator) to an
area of high temperature (the surroundings).
The compressor pumps the low-pressure refrigerant from the evaporator through
the accumulator, increases its pressure, and discharges the high-pressure gas to the
condenser. The accumulator prevents liquid refrigerant entering the compressor. In the
condenser, the refrigerant rejects its heat to the surroundings by passing air over it. At
that pressure, the refrigerant loses its latent heat and liquefies. Then the refrigerant
passes through the drier/filter where any residual moisture or foreign particles present,
these are plugged. The flow of refrigerant into the evaporator is controlled by expansion
device where its pressure and consequently temperature is lowered to the saturation
temperature at the corresponding pressure. The low temperature refrigerant enters the
evaporator where it absorbs heat from the surrounding medium and evaporates. The
compressor sucks the cold vapours and the cycle repeats.
The required instrumentation is provided to measure the various parameters at
different points. This includes pressure gauges, temperature indicators and controller,
energy-meters, heater for applying load and flow meter to measure the refrigerant flow.
TECHNICAL SPECIFICATIONS OF REFRIGERATION TEST RIG
CAPACITY
REFRIGERANT
COMPRESSOR
CONDENSER
R-134 a
HERMETICALLY SEALED
FORCED CONVECTION AIR COOLED
INDUCTION TYPE
DRYALL MAKE
CAPILLARY TUBE
ROTAMETER
MEASURMENT
HP/LP CUTOUT
PRESSURE INDICATION
ENERGY METER
TEMPERATURE
CONTROL
PROVIDED
PRESSURE GAUGES, 2NOS PROVIDED
L&T MAKE,
AUTOMATIC BY TEMPERATURE CONTROLLER
OF THE CALORIMETER
EVAPORATOR
FOR
CAPACITY
REFRIGERATION TEST RIG
TEMPERATURE INDICATION
INSULATION
FOR
WATER
COIL.
DIGITAL LED
PUF
TANK
SUPPLY
CONSTRUCTION
PROCEDURE:
Put the machine in the proper position where its level is horizontal and it is well
ventilated. The machine must have at least 1.5 meters clearances from all sides.
Give 230 volts, 50Hz, and 1 phase supply to the unit.
Incoming cable should be adequate size (at least 4 sq. mm) to prevent overheating of
it.
The electrical point should have a MCB of 16 Amps rating.
Ensure proper earthing.
Fill the water tank with clean water.
Start the compressor by putting the switch ON.
Also switch on the heater; it will start automatically at set point.
Control the water flow to heat exchanger around 3 LPM.
Record all the readings as per the observation table.
Calculate the results as per the procedure mentioned. At various points.
PRECAUTIONS:
The plant should not be left with water in the tank when not in use.
Do-not tamper with the temperature as well as the pressure settings.
=
=
=
=
=
C
1 Ton of Refrigeration effect
=
=
=
1.1 kg/m3
3600 kJ
14.5 psig
1 kWHr (kilowatt-hour)
1 bar
REFRIGERATION
=
=
M Cp dT
0.086x4.18x4
==
1.45 KW
COMPRESSOR WORK W
= 10x3600/(tx3200) t is in
sec
= 0.34 KW
ACTUAL COEFFICIENT OF
PERFORMANCE
== ACTUAL REFRIGERATION
EFFECT/ ACTUAL COMPRESSOR
WORK
== 1.45/0.34 = 4.26
= 9 + 1 = 10 bar
ACCORDINGLY,
ENTHALPIES OF REFRIGERANT AT SALIENT POINTS ARE
H1=ENTHALPY OF REFRIGERANT AT INLET OF COMPRESSOR= 400 KJ/ KG
H2= ENTHALPY OF REFRIGERANT AT OUTLET OF COMPRESSOR= 450 KJ/KG
H3=ENTHAPLY OF REFRIGERANT AFTER CONDENSATION= 242 KJ/KG
H4=ENTHALPY OF REFRIGERANT AFTER EXPANSION = H3= 242 KJ/KG
THERORITICAL REFRIGERATION EFFECT = N= H1-H4= 158 KJ/KG
THERORITICAL COMPRESSOR WORK = W = H2-H1 = 50 KJ/KG
COEFFICIENT OF PERFORMANCE = C.O.P= N /W = 3.16
RESULTS
CAPACITY
OF
THE
== 1450
WATTS
SYSTEM
0.413 TONS
ACTUAL C.O.P.
=
= 4.26
THEORETICAL C.O.P.
=
= 3.16
OBSERVATION TABLE:
TIME
Water
REFRIGERANT TEMP.
Flow
(0C)
Water
Temp
Rate
PRESSUR
E
Psig
S
uctio
O n
D
isch
arge
R
EFRI
ergy
GERA
Meter
NT
Readin
FLOW
LPH
10
ut
Sec
Kg/s
After
After
Comp. Cond.
T1 oC
T2
After
After
Expn.
Eva.
C T3
T5
T6
C T4 oC
En
for
Pulses
P1
P2
Vr
sec
27.5
0.036
74
31
-2
14
1.5
33
11.5
0.086
71
30
-5
10
1.5
33
0.1
72
29
-7
-7
-7
8.5
34