1:6
(2/12) (2/12)
With Without
Ceiling Ceiling
Residential (Part 9)
Commercial (Part 4)
Farm (Part 4)
0.5 (10) 0.15 (3)
0.5 (10) 0.25 (5)
0.5 (10) 0.20 (4)
0.34 (7) N/A
0.34 (7) 0.25 (5)
0.34 (7) 0.20 (4)
Note: The designer should check the suitability of these minimums for their applications.
This applies to trusses carrying flat roof (where roof portion with slope <1:6 exceeds
50% of building width).
3.3.2 Floor Dead Loads
1) The minimum dead loads specified below shall be used for all designs unless specified
otherwise by an authority having jurisdiction.
2) The minimum top chord dead load shall be 0.5 kPa (10 psf)
3) The minimum bottom chord dead load shall be 0.25 kPa (5 psf)
4) In areas of a building where partitions, other than permanent partitions shown on design
drawings, or, where partitions might be added in the future, allowance shall be made for
the weight of such partitions.
The partition weight allowance for the above shall be determined from the actual or
anticipated weight of the partitions placed in any probable position, but shall not be less
than 1.0 kPa (21 psf) over the area of floor being considered.
5) A non-bearing partition wall may be neglected in the design provided:
a) Live load of supporting truss system results from residential occupancy and is not
less than specified in 3.2.4.
(b) Floor trusses are not spaced over 610 mm o/c (24 in o/c)
(c) Top chord panel length of supporting truss system does not exceed 750 mm (30 in)
for lumber-on-flat trusses.
(d) Partition weight does not exceed 0.88 kN/m (60 plf)
(e) Partition wall is not to be parallel to the trusses.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 12
4. MEMBER DESIGN PROCEDURE
4.1 ANALOGUE
4.1.1 Analogue Joint Types
(a) Pitch Break J oint: A joint formed by the intersection of two non-parallel chords (see
Fig 4.1.2).
(b) Heel J oint: A pitch break joint consisting of a non-vertical top chord and non-vertical
bottom chord (see Fig 4.1.2).
(c) Splice J oint: A joint formed by two parallel and adjacent chords (see Fig 4.1.2.3).
(d) Lapped J oint: A joint formed by one end of a chord placed parallel and in contact with
the adjacent chord along one of its edges (see Fig 4.1.2.4).
(e) Web J oint: A joint formed by one or more webs along one edge of a given chord
(see Fig 4.1.2.5).
(f) Internal J oint: A joint formed by two web joints on opposite edges of a given chord
such that their contact lengths overlap along the axis of the chord (see Fig 4.1.2.6).
(g) Tail Bearing J oint: A joint consisting of a single member going to a support. (see Fig
4.1.2.7)
(h) Top Chord Bearing J oint: A joint consisting of two or more members connecting at
an exterior support. (see Fig 4.1.2.8)
(i) Bearing J oint: A joint where a bearing touches a chord. (see Fig 4.1.2)
4.1.2 Analogue Points
(a) Simple Analogue Point: An analogue point consisting of only one point formed by
two uniquely identifiable lines.
(b) Compound Analogue Point: Analogue formed by two or more joints located at the
same physical joint. (see Fig 4.1.2)
Except as in 4.1.3, analogue points shall be constructed as described in this section.
4.1.2.1 Heel Analogue: The heel analogue is a compound analogue consisting of three simple
analogue points and three fictitious members. (see Fig 4.1.2.1.A-G)
a) First analogue point shall be determined as follows: Construct a vertical line at the
end of TC or BC member whichever is shorter. (For Girder Heel, end of BC is always
used to construct this line. See Fig 4.1.2.1.B. The only exception to this rule is in the
case of a short cantilever. If the bearing occurs inside the point where the top chord
terminates then this line is constructed at the end of the top chord and is considered
the design span. See Appendix A.1 to A.4.) Find the intersection of the vertical line
with the centrelines of the TC and BC. First heel analogue point shall be the lower of
the two intersection points. This is the bearing point except as mentioned in (f) below.
b) The second heel analogue point shall be located at the intersection of the centreline
of BC and a vertical at 75% of scarf length from the first analogue point. This vertical
may not be more than 610mm (24) away from the first analogue point.
c) The third heel analogue point shall be located along the centreline of the top chord
directly above the second heel analogue point.
d) Where the second and the third points are closer to the first point than 2", remove the
second and third points and reduce the heel analogue to simple analogue.
e) In the case of a reinforcing wedge, the second heel analogue point shall be located
at the intersection of the centreline of the BC and, a vertical at 75% of the combined
BC and wedge scarf lengths, from the first analogue point. This vertical may not be
more than 610mm (24) away from the first analogue point.
f) In the case of a reinforcing member, a fourth point is required. The reinforcing
member acts as the fourth member. The fourth point is the intersection of the
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 13
centreline of the chord with a line perpendicular to the chord at a distance d/2
where d is the depth of the chord. (see Fig 4.1.2.1.C & D)
g) In the case of a reinforcing web, the analogue is similar to the reinforcing member
analogue with the following exceptions:
1. The fourth analogue point is the analogue point of the adjacent joint.
2. The fourth member is the reinforcing web.
3. The bearing point is the first analogue point only if all of the bearing surface falls
between the first and second analogue points inclusive. (see Fig 4.1.2.1.C & E)
Short cantilever and high heel rules apply. (see Appendix A)
4. If any part of the bearing surface falls past the second analogue point, the
bearing point is at the second analogue point or a new bearing joint is introduced
depending on the contact between the bearing surface and the scarf of the
reinforcing web. (see Fig 4.1.2.1F) Short cantilever and high heel rules do not
apply for this condition.
5. If the reinforcing web is not fully parallel and touching the chord, two separate
joints are constructed; a heel joint and a web joint. (see Fig 4.1.2.1G)
4.1.2.2 Pitch Break Analogue Point: The pitch break analogue point shall be located along a
plumb line through the outside edge intersection of the two chords. The analogue point
shall have the same X coordinate as the plumb location and Y coordinate equal to the
average Y coordinates formed by intersection points of the chord centrelines and the
plumb line. (see Fig 4.1.2.2)
In case of a mitre cut pitch break, the analogue point is the intersection of the centrelines
of the chords. (see Fig 4.1.2.2.A) For corner joints, the analogue point shall be the
intersection of the centreline of the chord and a line at the end of the chord. (see Fig
4.1.2.2.B)
4.1.2.3 Splice J oint Analogue Point: Analogue point shall be the point located at the halfway
point between the intersection points of the centrelines of the two chord members and
the splice line. (see Fig 4.1.2.3)
4.1.2.4 Lapped J oint Analogue Point: Analogue point shall be the point located at the halfway
point between the intersection points formed by the end cut and centrelines of the chord
members on the two sides of the joint. (see Fig 4.1.2.4)
4.1.2.5 Web J oint Analogue Point: Analogue point shall be the intersection of the centrelines of
chord and a line perpendicular to the chord passing through the centre of contact area
between the webs and the chord. (see Fig 4.1.2. and Fig 4.1.2.5)
4.1.2.6 Internal J oint Analogue Point: Analogue point shall be the intersection of the centreline
of chord and a perpendicular through the centre of common contact area, from both
sides, between the webs and the chord. (see Fig 4.1.2.6)
4.1.2.7 Tail Bearing J oint Analogue Point: Analogue point shall be at the intersection of the
centreline of the chord and a vertical through outside corner of support. For a vertical tail
bearing, use the horizontal through the outside corner of bearing instead of the vertical.
(see Fig 4.1.2.7)
4.1.2.8 Top Chord Bearing J oint: Except as in 4.1.2.9 the top chord bearing joint analogue is
compound and consists of two points. The first point is the bearing point and it is the
intersection of the centreline of the top chord with a vertical along the inside face of the
bearing. The second point is the intersection of the centreline of the top chord with a
vertical through the outside edge of any webs coming to the top chord at the bearing.
The maximum distance allowed between these points is 13mm (1/2). (see Fig 4.1.2.8
and Appendix D)
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 14
4.1.2.9 Top Chord Bearing J oint With End Vertical and Block: The analogue of this point is
compound and consists of three points and two ficitious members. The first joint is the
bearing point and it is the intersection of a vertical through centreline of the required
bearing size and surface of bearing. The second point is the intersection of a horizontal
through the first point and the outside edge of end vertical. The third point is intersection
of the centreline of the top chord and the outside edge of end vertical. (see Fig 4.1.2.9)
Top chord bearing joint guidelines in section 4.6.6 must be observed when using the
analogue described in the above sections (4.1.2.8 and 4.1.2.9)
4.1.3 Analogue Modifications
4.1.3.1 Analogue points shall be constructed using the following heirarchy: Pitch break joints,
then, most member to least member web joints. All other joints not mentioned here may
be constructed in any order.
4.1.3.2 Analogue points for joints connected by a vertical web to joints of higher hierarchy shall
be obtained as intersection of vertical through the higher hierarchy joint and the
centreline of chord.
4.1.3.3 Two analogue points closer to each other than 2" (unprojected) shall be reduced to one
joint located between the two original joints.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 15
Figure 4.1.2 Simple and Compound Analogue
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 16
Figure 4.1.2.1.A Standard Heel Analogue
Figure 4.1.2.1.B Girder Heel
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 17
Figure 4.1.2.1.C Raised Heels
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 18
Figure 4.1.2.1.D Short Cantilevered Heels
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 19
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 20
Figure 4.1.2.2 Pitch Break J oint
Figure 4.1.2.2.A Mitre Cut Pitch Break J oint
Figure 4.1.2.2.B Corner J oint
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 21
Figure 4.1.2.3 Splice J oint
Figure 4.1.2.4 Lapped J oint
Figure 4.1.2.5 Web J oints Figure 4.1.2.6 Internal J oint
Figure 4.1.2.7 Tail Bearing J oint
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 22
Figure 4.1.2.8 Top Chord Bearing Details
Figure 4.1.2.9 Top Chord Bearing with End Vertical and Block
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 23
4.2 ULTIMATE LIMIT STATES
4.2.1 Method of Analysis
Structural analysis shall be by stiffness or flexibility method utilizing pin-rigid
mathematical model.
1) Truss Model
(a) All chord members shall be rigidly connected through joints, including web joints and
lapped joints. All splices shall be considered pinned unless designed for moment.
Fictitious members representing top and bottom chords at the heel shall be pinned to
each other but rigidly connected at other end.
(b) Ends of members connecting to pitch break joints shall be considered pinned at the
joints.
(c) The fictitious vertical strut at heel shall be pinned to top and bottom chords.
(d) Properties of fictitious members shall be as follows:
A top chord fictitious member shall have the same properties as the adjacent top
chord. A bottom chord fictitious member shall have the same properties as the
adjacent bottom chord. Other fictitious members shall have the properties of 2x4
No.2 S.P.F. lumber.
(e) Fictitious members in top chord bearing conditions such as in detail 4.1.2.9 shall be
pinned at both ends and have properties of 2x4 No. 2 S.P.F. lumber.
(f) Overhangs shall be modelled such that they impose zero moment to the adjacent top
chord member.
2) Support Model
Except for the leftmost support, all supports shall be considered as horizontal or vertical
rollers. The leftmost support must be pinned. No support shall be considered to provide
rotational restraint unless such restraint is adequately specified on the drawing. At a heel
joint the support shall be located at the first analog point (the outermost joint). Except at
heel joints, a support is considered to be at a joint when there is an overlap between
contact surfaces of bearing and webs. A support is considered to be at the heel joint if
the heel condition is to be used with short cantilever rules. See Section 4.6.3
3) Member Forces and Moments
(a) Member force shall be the average of the member end forces. Member force for
connections shall be the actual member forces at the joint.
(b) Panel moment shall be taken as the maximum moment within the panel. Panel point
moment shall be that at each individual panel end.
(c) Combined Stress index shall be calculated for the panel on the basis of CSI from
average member force combined with the greater of maximum panel moment or the
maximum panel point moment.
4.2.2 Ultimate Limit States Requirements
The design of truss members for ultimate limit states shall include:
(a) Establishing the value of the effect of the factored loads individually and with the load
combinations specified in Section 3; and
(b) Confirmation by rational means that for each load effect in item (a), the factored load
effect does not exceed the factored resistance as determined by appropriate clauses
of this standard.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 24
4.3 SPECIFIED STRENGTHS
4.3.1 Visually Stress-Graded Lumber
The specified strengths (MPa) for visually stress-graded structural joist and planks, light
framing, structural light framing and stud grade categories of lumber shall be those
presented in Table 5.3.1.A and Table 5.3.1.B of O86-09.
4.3.2 Machine Stress-Rated And Machine Evaluated Lumber
The specified strengths (MPa) for machine stress-rated lumber are given in Table 5.3.2
of O86-09. The specified strengths (MPa) for machine evaluated lumber are given in
Table 5.3.3 of O86-09. The specified strengths in shear are not grade dependent and
shall be taken from Table 5.3.1.A of O86-09 for the appropriate species.
4.3.3 Design Specified Strengths
The design specified strengths are the product of the basic specified strengths and the
appropriate strength modification factors as in Section 4.3.4.
4.3.4 Modification Factors
The strength modification factors are defined as follows:
1) Load Duration Factor, K
D
The specified strengths and resistances shall be multiplied by a load duration factor, K
D
,
in accordance with table 4.3.4.(1)
Table 4.3.4.(1) Load Duration Factor, K
D
Duration of Load K
D
Explanatory Notes
Short term 1.15 Short term loading means that condition of loading
where the duration of the specified loads is not
expected to last more than 7 days continuously or
cumulatively throughout the life of the structure.
Examples include wind loads, earthquake loads,
falsework, formwork, as well as impact loads.
Standard term 1.00 Standard term means that condition of loading where
the duration of specified loads exceeds that of short
term loading, but is less than long term loading.
Examples include snow loads, live loads due to
occupancy, wheel loads on bridges, and dead loads in
combination with of all of the above.
Long term 0.65 Long-term duration means the condition of loading
under which a member is subjected to more or less
continuous specified load. Examples include dead
loads or dead loads plus live loads of such character
that they are imposed on the member for as long a
period of time as the dead loads themselves. Such
loads include those usually occurring in tanks or bins
containing fluids or granular material, loads on retaining
walls subjected to lateral pressure such as earth, and
floor loads where the specified load can be expected to
be continuously applied, such as those in buildings for
storage of bulk materials. Loads due to fixed machinery
should be considered to be long term.
Note: Load duration requires professional judgement by the designer.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 25
1(a) Long term load factor
For Standard-term loads where the specified long-term load, P
L
, is greater than the
specified standard-term load P
S
, the long-term load factor may be used or the factor
may be calculated as follows:
K
D
=1.0 0.50log (P
L
/P
S
) 0.65
where: P
L
=specified long-term load
P
S
=specified standard term load based on S and L loads acting alone or in
combination
=S; L; (S +0.5L) ; OR (0.5S +L), determined using importance factors
equal to 1.0
2) Service Condition Factor, K
S
The specified strengths for sawn lumber shall be multiplied by the service condition factor
K
S
as indicated in Table 4.3.4.(2)
Table 4.3.4.(2) Service Condition Factors, K
S
K
S
Property Wet service Dry Service
K
Sb
K
Sv
K
Sc
K
Scp
K
St
K
SE
Bending at extreme fibre
Longitudinal shear
Compression parallel to grain
Compression perpendicular to grain
Tension parallel to grain
Modulus of elasticity
0.84
0.96
0.69
0.67
0.84
0.94
1.0
1.0
1.0
1.0
1.0
1.0
3) Treatment Factor, K
T
When lumber is treated with preservatives and retardants, the specified strengths,
including modulus of elasticity, shall be decreased by treatment factor K
T
as given in
Table 4.3.4.(3)
Table 4.3.4.(3) Treatment Factor K
T
Product Dry service
conditions
Wet service
conditions
Untreated Lumber 1.00 1.00
Preservative Lumber
(1)
1.00 1.00
Fire-retardant or other strength reducing
chemically Treated Lumber
See note 2 for effects of fire
retardant treatment
Notes:
1. Refers to unincised lumber only. Incised treated lumber is not permitted in trusses.
2. For lumber treated with fire-retardant or other strength reducing chemicals, strength
and stiffness capacities shall be based on the documented results of tests that shall
take into account the effects of time, temperature, and moisture content. Test
procedures shall meet the requirements of Clause 3.3.2. of O86-09.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 26
4) System Factor, K
H
Specified strengths for sawn lumber members in a light frame truss system consisting of
three or more essentially parallel members spaced not more than 610 mm apart and so
arranged that they mutually support the applied load may be multiplied by the system
factor given in Table 4.3.4.(4)
Table 4.3.4.(4) System Factor K
H
Symbol Property K
H
K
Hb
K
Hv
K
Hc
K
Hcp
k
Ht
K
HE
Bending
Longitudinal shear
Compression parallel to grain
Compression perpendicular to grain
Tension parallel to grain
Modulus of elasticity
1.10
1.10
1.10
1.00
1.10
1.00
Note: These system factor increases are also applicable when spacing does not
exceed 1220 mm for low human occupancy applications and for all girders consisting of
not less than 3 members.
5) Size Factor K
Z
Size factors presented in Table 4.3.4.(5) shall be used to increase basic specified
strength.
Table 4.3.4.(5) Size Factor, K
Z
For Visually Graded Lumber
Symbol Description Lumber Size (mm) 38 x
64 89 114 140 184 235 286
K
Zb
Bending 1.7 1.7 1.5 1.4 1.2 1.1 1.0
K
Zv
Longitudinal shear 1.7 1.7 1.5 1.4 1.2 1.1 1.0
K
Zc
Compression parallel to
grain
* * * * * * *
K
Zcp
Compression
perpendicular to grain
** ** ** ** ** ** **
K
Zt
Tension parallel to grain 1.5 1.5 1.4 1.3 1.2 1.1 1.0
K
ZE
Modulus of elasticity 1.0 1.0 1.0 1.0 1.0 1.0 1.0
* See Section 4.4.3.(3)
** See Section 4.4.4.(4)
6) Flat Roof Factor K
F
Roof trusses meeting the housing and small building requirements of Part 9 of the
NBCC10 and carrying flat roof (where roof portion with slope <1:6 exceeds 50% of
building width) shall be designed with a reduced factored resistance strength of lumber
by applying a flat roof factor K
F
=0.75.
K
F
=1.0 for all other cases.
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 27
4.4 STRENGTH AND RESISTANCE
4.4.1 Bending Moment Resistance
1) The factored bending moment resistance, M
r
of sawn members shall be taken as:
M
r
= |F
b
SK
Zb
K
L
K
F
where | = 0.9
F
b
= f
b
(K
D
K
Hb
K
Sb
K
T
)
f
b
= specified strength in bending, MPa
(Tables 5.3.1 to 5.3.3 of O86-09)
S = section modulus, mm
3
K
Zb
= size factor in bending
K
L
= lateral stability factor (Clause 4.4.1.(2))
K
F
= flat roof factor
2) Lateral Stability Factor, K
L
The lateral factor K
L
may be taken as unity when lateral support is provided at points of
bearing to prevent lateral displacement and rotation, and the following additional support
is provided:
Table 4.4.1.(1) Lateral Stability Factor, K
L
MEMBER SIZE SUPPORT CONDITION
38 x 64 (2x3)
38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)
No additional intermediate support is required.
38 x 184 (2x8) The member is held in line by purlins.
38 x 235 (2x10) The compressive edge is held in line by direct connection
of sheathing or purlins spaced not more than 610 mm (24
in) apart.
38 x 286 (2x12) The compressive edge is held in line by direct connection
of sheathing or purlins spaced not more than 610 mm (24
in) apart and adequate bridging or blocking is installed at
intervals not exceeding 2280 mm (90 in).
Note: Alternatively, K
L
may be calculated in accordance with Clause 6.5.6.4 of O86-09.
4.4.2 Shear Resistance
The factored shear resistance, V
r
for sawn members shall be taken as:
V
r
=| F
v
3
2A
n
K
Zv
K
F
where | = 0.9
F
v
= f
v
K
D
K
Hv
K
Sv
K
T
f
v
= specified strength in shear, MPa
(Tables 5.3.1A and 5.3.1B of O86-09)
K
Zv
= size factor in shear
A
n
= net area of cross-section, mm
2
K
F
= flat roof factor
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 28
4.4.3 Compressive Resistance Parallel To Grain
1) Effective Length
Unless noted otherwise, the effective length L
e
= K
e
L
p
shall be used in determining the
slenderness ratio of truss compression members.
where K
e
= 0.8 for buckling between adjacent panel points in the truss
K
e
= 1.0 for buckling between brace or purlin locations on the truss
L
p
= actual length of member between adjacent analogue panel points, or;
locations of braces or purlins restraining buckling (normally
perpendicular to the plane of the truss). For design of truss webs the
longest cutting length shall be used.
Other recommended effective length factors K
e
for compression members can be found
in Appendix A.5.5.6.1 of O86-09.
2) Simple Compression Members - Constant Rectangular Cross-Section
The slenderness ratio C
c
of simple compression members of constant rectangular
section must not exceed 50 and shall be taken as the greater of:
C
c
=
effective length associatied with width
member width
C
c
=
effective length associatied with depth
member depth
Note: The slenderness ratio C
c
of a simple tension member shall be limited to 80. K
e
for
a tension member should be taken as 0.8.
3) Factored Compressive Resistance Parallel To Grain
The factored compressive resistance parallel to grain, P
r
shall be taken as:
P
r
=| F
c
A K
Zc
K
c
K
F
where | = 0.8
F
C
= f
c
(K
D
K
Hc
K
Sc
K
T
)
f
c
= specified strength in compression parallel to grain, MPa
(Tables 5.3.1 to 5.3.3 of O86-09)
K
Zc
= 6.3(dL)
-0.13
s 1.3
K
F
= flat roof factor
where d = dimension in direction of buckling (depth or width), mm
L = length associated with member dimension, mm
Note: The member length L used to compute the factor K
ZC
shall be the greater of the
panel length or one-half the chord length between pitch breaks for chord design; and,
shall be the longest cutting length or the analogue length for web design.
4) Slenderness Factor, K
C
The slenderness factor, K
C
, shall be determined from:
K
C
= +
1.0
F K C
35E K K
c Zc C
3
05 SE T
1
where E
05
= 0.82E for MSR lumber
= 0.75E for MEL lumber
= as specified in Tables 5.3.1A and 5.3.1B of O86-09, for visually graded
lumber
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 29
4.4.4 Compressive Resistance Perpendicular To Grain (Bearing Resistance)
1) Effect Of All Applied Loads
The factored compressive resistance perpendicular to grain under the effect of all
factored loads shall be taken as Q
r
in the following formula:
Q
r
= | F
cp
A
b
K
B
K
Zcp
K
F
K
p
where | = 0.8
F
cp
= f
cp
(K
D
K
Scp
K
T
)
f
cp
= specified strength in compression perpendicular to grain, MPa
(Tables 5.3.1 to 5.3.3 of O86-09)
A
b
= bearing area, mm
2
K
B
= length of bearing factor, Clause 4.4.4.5
K
Zcp
= size factor for bearing, Clause 4.4.4.4
K
F
= flat roof factor
K
p
= bearing plate increase factor = 1.18 when truss plate, with minimum
width of 3, is located over bearing such that the lower edge of the plate
is flush with the lower edge of truss chord and the plate length covers
the entire bearing length.
Note: The requirements of 4.4.4.(1) may be met by providing adequate bearing
reinforcement against the effects of concentrated bearing loads acting near a support.
See Section 5.5.9
2) Effects Of Loads Applied Near A Support
The factored compressive resistance perpendicular to grain, under the effect of only
those loads applied within a distance from the centre of the support equal to the depth of
the member, shall be taken as Q'
r
in the following formula:
Q'
r
= (2/3) | F
cp
A'
b
K
B
K
Zcp
K
F
K
p
where | = 0.8
F
cp
= f
cp
(K
D
K
Scp
K
T
)
A'
b
= average bearing area (Clause 4.4.4.(3))
3) Unequal Bearing Areas On Opposite Surfaces Of A Member
Where unequal bearing areas are used on opposite surfaces of a member, the average
bearing area shall not exceed the following:
A'
b
= b
L L
but b L
b b
b
1 2
1
2
15
+
`
)
s , . ( )
where L
b1
= lesser bearing length, mm
L
b2
= larger bearing length, mm
b = average bearing width (perpendicular to grain), mm
4) Size Factor For Bearing, K
Zcp
For lumber used on flat, as opposed to on edge, the compression perpendicular to grain
may be multiplied by a size factor for bearing, K
Zcp
in accordance with Table 4.4.4.(4)
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 30
Table 4.4.4.(4) Size Factor For Bearing, K
Zcp
Ratio of Member Width To Member Depth* K
ZCP
1.0 or Less 1.00
2.0 or More 1.15
* Interpolation applies to intermediate ratios.
5) Length Of Bearing Factor, K
B
When lengths of bearing are less than 150 mm, specified strengths in compression
perpendicular to grain may be multiplied by a length of bearing factor in accordance with
Table 4.4.4.(5) provided that:
(a) no part of the bearing area is less than 75 mm from the end of the members; and
(b) bearing areas do not occur in positions of high bending stresses.
Table 4.4.4.(5) Length Of Bearing Factor, K
B
Bearing Length Measured Parallel To Grain (mm) Modification Factor, K
B
12.5 and Less 1.75
25.0 1.38
38.0 1.25
50.0 1.19
75.0 1.13
100.0 1.10
150.0 or More 1.00
4.4.5 Tensile Resistance Parallel To Grain
The factored tensile resistance, T
r
, parallel to grain shall be taken as:
T
r
= |F
t
A
n
K
Zt
K
F
where | = 0.9
F
t
= f
t
(K
D
K
Ht
K
St
K
T
)
f
t
= specified strength parallel to grain, MPa
(Tables 5.3.1 to 5.3.3 of O86-09)
A
n
= net area of cross-section, mm
2
K
Zt
= size factor in tension
K
F
= flat roof factor
4.4.6 Stress Index due to Bending
Members subject to factored bending moment, M
f
, shall be so proportioned that:
s
r
f
M
M
1.0
4.4.7 Stress Index due to Shear
Members subject to factored shear load, V
f
, shall be so proportioned that:
V
V
f
r
s 1.0
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 31
4.4.8 Stress Index due to Compression (Parallel to Grain)
Members subject to factored compressive axial load, P
f
, shall be so proportioned that;
P
P
f
r
s 1.0
4.4.9 Stress Index due to Compression (Perpendicular to Grain)
Members subject to factored compressive bearing load, Q
f
, shall be so proportioned
that;
Q
Q
f
r
s 1.0
4.4.10 Stress Index due to Tension
Members subject to factored tensile axial load, T
f
, shall be so proportioned that:
T
T
f
r
s 10 .
4.4.11 Combined Stress Index due to Tension and Bending
Members subject to both bending and axial tension shall be so proportioned that:
T
T
M
M
f
r
f
r
+ s 1.0
4.4.12 Combined Stress Index due to Compression and Bending
Except as permitted in Section 4.4.13, members subject to both bending and axial
compression shall be so proportioned that;
0 . 1
P P 1
1
M
M
P
P
e f r
f
2
r
f
s
|
|
.
|
\
|
+
|
|
.
|
\
|
where P
f
= factored compressive force parallel to grain
P
r
= factored compressive resistance parallel to grain, clause 4.4.3
M
f
= factored bending moment
M
r
= factored bending moment resistance, clause 4.4.1
P
E
= Euler buckling load in the plane of the applied moment
=
2
E
05
K
SE
K
T
I / L
e
2
where E
05
= modulus of elasticity for design compression members, MPa
I = moment of inertia in the plane of the applied moment, mm
4
L
e
= K
e
L
where K
e
= effective length factor given in clause 4.4.3.(1)
4.4.13 Combined Stress Index due to Compression and Bending
(Modified formula as per Section 5.5.13.5 O86-09)
Provided;
(a) the members form part of a fully triangulated, metal plate connected truss; and;
(b) the spacing of the truss does not exceed 610 mm (24 in) or the truss does not
support more than 610 mm (24 in) of uniform loading; and;
(c) clear spans between bearings does not exceed 12.20 m (40 ft) and, the design span
or overall length of the truss, not including overhangs, does not exceed 18.3 m (60
ft), and with no single cantilever length exceeding 25% of the adjacent clear span,
and;
TRUSS PLATE INSTITUTE OF CANADA (2011)
June 2011 32
(d) the top chord slope is not less than 1/6, which is meant to exclude flat roof trusses
but not flat top trusses forming part of hip roof systems;
Note: This clause is not for use with girder, bow string, semi-circular, attic, flat roof, or
floor trusses.
Members subject to both bending and axial compression shall be so proportioned that;
s +
|
|
.
|
\
|
r M
f
2
r
f
M K
M
P
P
1.0
1) Bending Capacity Modification Factor, K
M
The bending capacity modification factor, K
M
, shall be determined as shown in the
following:
(a) Compression chord members continuous over one or more panel points, and where;
1.0 <
M
M
1
2
s 3.0
K
M
= 131 012
1
2
1 6
. .
/
+
`
)
(
(
`
)
s
M
M
L
d
p
1.3
(b) Compression chord members continuous over one or more panel points, and where;
-1.0 s
M
M
1
2
s 1.0
K
M
= 220 053 064 041
1
2
1
2
2
1
2
3 1 6
. . . .
/
`
)
`
)
+
`
)
(
(
`
)
s
M
M
M
M
M
M
L
d
p
1.3
(c) All other compression chord members
K
M
= 1.67
L
d
p
`
)
s
1 6
13
/
.
where L
p
= actual length of the member between adjacent analogue panel
points,mm
d = depth of the member between adjacent analogue panel points, mm
*M
1
= maximum bending moment between analogue panel points, N-mm
M
2
= maximum of the two panel point bending moments, N-mm
Note: The sign of the bending moment, M
1
and M
2
are retained in determining K
M
. The
factored bending moment, M
f
, used in Section 4.4.13 is the larger of the absolute value of
M
1
and M
2
.
* Maximum of bending moment at points along a panel where the slope of the moment
curve changes sign. Where there are no such points along the panel, M
1
shall take the
value of the bending moment at mid panel.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 33 3
4.5 SERVICEABILITY LIMIT STATES
Design for serviceability Limit States shall include:
(a) establishing the value of the effect of the specified loads individually and with the
load combinations specified in Section 3; and
(b) confirming by rational means that for each load effect in item (a), the structural effect
falls within the limits specified in appropriate clauses contained herein.
4.5.1 Serviceability Requirements (Allowable Deflections)
1) Modulus of Elasticity
The modulus of elasticity for stiffness calculations, E
S,
shall be taken as:
E
S
= E(K
SE
K
T
)
where
E = specified modulus of elasticity
K
SE
= service condition factor
K
T
= treatment factor
2) J oint and member deflections shall be determined using the methods presented in
Section 4.2.1. Loadings used are as described in Section 3.0.
3) Maximum vertical truss deflection shall be the largest of deflections calculated at any
panel point, or within any bottom chord panel. Top chord members shall be checked for
their vertical panel deflections relative to their end points.
4) Maximum truss deflection and loadings to be considered in computing these deflections
are as shown in Table 4.5.1.(4). Lengths to be used in the limit ratios are shown in Figure
4.5.1.(4)
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 34 4
Table 4.5.1.(4) Truss Deflection Limitations
Application
Residential Commercial Farm Floor
Deflection Location Loading Used
1.33SL+0.5LL+DL VL+DL (SL+LL+WL)+DL VL+DL
Allowable Deflection Limits - Vertical
Top chord panel * PL/180 PL/180 PL/180 PL/180
Bottom chord panel * PL/240 PL/360 PL/240 PL/360
Cantilever CL/120 CL/120 CL/120 CL/120
Overhang OL/120 OL/120 OL/120 N/A
Bottom Chord Truss
J oint or Panel
(a) Plaster/Gypsum
ceiling
(b) Other ceiling
(c) No ceiling
See Below
L/360
L/240
L/180
L/180
L/360 (DL)
L/360 (VL)
L/240 (VL)
L/240 (VL)
L/180
L/360 (DL)
See Note: 3 (LL)
L/360 (LL)
L/240 (LL)
L/240 (LL)
L/180
L/360 (DL)
L/360 (VL)
L/360 (VL)
L/360 (VL)
Allowable Deflection Limit - Horizontal
At Roller Support 25 mm (1 in) 25 mm (1 in) 25 mm (1 in) 25 mm (1
in)
Note: 1. SL refers to Snow Load contribution. LL refers to Occupancy Load contribution. WL
refers to Wind Load contribution. DL refers to Dead Load contribution.
2. VL refers to variable load combinations of SL, LL and WL computed in accordance with
table 3.1.3.2 Load Combinations for Serviceability Limit States.
3. (SL+LL+WL) were considered as Live Load (LL) in NBCC95. See TPIC 1996 for
serviceability load combinations for Farm designs.
* Top and bottom chord panel deflection is local deflection measured relative to panel
ends.
4.5.2 Permanent Deformation
Structural members supporting continuously applied loads in excess of 50% of the total
specified load shall be designed to avoid excessive permanent deformation. An upper
limit of 1/360 of the span should be imposed on the deflection due to continuously
applied loads.
4.5.3 Ponding
The roof surface has to be provided with sufficient slope to allow drainage to prevent
accumulation of rain water.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 35 5
4.6 SPECIAL DESIGN CONSIDERATIONS
4.6.1 Overhangs
Top chord overhangs for all categories of trusses shall be treated as simple overhangs,
with no consideration of any support provided by the soffit return, except in cases where
the truss designer is able to ensure that such consideration is provided for in the design
and construction of the building.
4.6.2 Splices
Splice locations as permitted in section 4.6.2.(1) and 4.6.2.(2) with tolerances described
in 4.6.2.(3) are only intended for use in trusses where these locations are of low chord
moment. i.e. Chords of triangulated, uniformly loaded, statically determinate trusses. For
other cases where the splice is positioned at a location of substantial chord moment, it
must either be designed for in the connection, or, eliminated by describing the splice as a
pin joint in the analysis.
1) Top Chord Splices
(a) shall not be located at any joint and shall not be located in the panel adjacent to heel
joint.
(b) shall not be located at the quarter point adjacent to any perimeter break.
(c) may be located at either quarter point of interior panels except there shall be no more
than one splice per panel.
2) Bottom Chord Splices
(a) shall not be located in the panel adjacent to heel joint and shall not be located at the
quarter point adjacent to any perimeter break.
(b) may be located between quarter points of interior panels.
(c) may be located at any interior joint except that the joint adjacent to heel joint may not
be spliced. Kingpost and Queenpost trusses may be spliced at the bottom chord
interior joint. See Figure 4.6.2.(2) for referenced truss configurations.
Figure 4.6.2.(2) Kingpost and Queenpost Truss Configurations
3) Maximum Tolerance in Splice Location
Maximum tolerance in splice location shall be +10% of panel length.
Kingpost
Queenpost
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 36 6
4.6.3 Short Cantilevers and Heel Cuts
Short cantilevers and high heel cuts shall be designed in accordance to procedures
presented in Appendix A.
4.6.4 Girder Trusses (Single and Multi-Ply)
1) Girder type heels are created by cutting the top chord onto a scarfed bottom chord. In
this scarfing, the resulting section of bottom chord directly over the inside face of the
bearing shall not be less than the greater of 50% of the original bottom chord section or
100 mm (4). Girder type heel design procedures are presented in Appendix F.
2) Truss-to-truss connection of multi-ply girder trusses carrying load that is not evenly
distributed to each ply shall be performed in accordance to Table B.1 to B.5, Appendix B.
Girders carrying this type of loading shall be limited to 5 plies maximum.
3) Truss-to-truss connection of multi-ply girder trusses, carrying load that is evenly
distributed to all plies, shall be performed using the minimum number of rows shown in
Table B.1., Appendix B and a spacing of 305 mm (12 in). Girders carrying this type of
loading shall be limited to 10 plies.
4.6.5 Truss Bracing
1) For instructions on installation of temporary and permanent truss bracing, refer to BCSI
brochure Building Component Safety Information.
Truss bracing location, as required in the design of the truss component, shall be
specified by the truss designer/engineer.
2) For HSB trusses, minimum fastening of braces shall be as per NBCC10 Section
9.23.14.11
19 x 89 (1x4) braces 2 - 63 mm (2-1/2) common wire nails
38 x 89 (2x4) braces 2 - 76 mm (3) common wire nails.
3) An alternate method for bracing compression webs and long tension webs is by applying
a member parallel to the web to form a T-section. See Table C.1.1, Appendix C.
4.6.6 Top Chord Bearing Guidelines
1) For lumber-on-edge top chord bearing trusses the recommended maximum factored
reactions for Spruce-Pine-Fir and D.Fir chords are as shown in Table D.1, Appendix D
for the various truss configurations. The recommended maximum gaps and minimum
chord coverage must be observed when using these values.
Reaction limits are based on gross reaction and load duration factor for standard term
loading. Values shall be adjusted downward for permanent loading and upward for short
term loading using appropriate duration of load factors for plating.
2) For lumber-on-flat top chord bearing trusses, the recommended maximum factored
reactions for Spruce-Pine-Fir and D.Fir chords are as shown in Table D.2 Appendix D for
the various truss configurations. The recommended maximum gaps and minimum chord
bites also shown must be observed when using these values.
Reaction limits are based on gross reaction and load duration factor for standard term
loading. Values shall be adjusted downward for permanent loading and upward for short
term loading using appropriate duration of load factors for plating.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 37 7
5. JOINT DESIGN PROCEDURES
5.1 GENERAL
The design requirements for truss plate joints, utilizing light gauge metal plates, shall be
in accordance with O86-09 Section 10.
1) These procedures do not apply to the following conditions:
(a) corrosive conditions
(b) galvanized truss plates used in lumber that has been treated with fire retardant and is
used in wet service conditions or in locations prone to condensation
NOTE:
For metal connector plates used in environmental conditions that fall within the scope of
(a) & (b) above, refer to Appendix E.
2) Design criteria for truss plates are based on the following conditions:
(a) the plate is prevented from deforming during installation;
(b) the teeth are normal to the surface of the lumber;
(c) the tooth penetration in joints is not less than that used in the tests to determine the
resistance values; and
(d) the lumber beneath the plate complies with Appendix G.
3) Thickness of members used in joints shall not be less than twice the tooth penetration.
4) Joint design shall be based on tight fitted joints with truss plates placed on opposing
faces in such a way that, at each joint, the plates on opposing faces are identical and are
placed directly opposite each other.
5) The lateral resistance value used to determine necessary plate area for any member
shall be the appropriate value considering direction of load relative to grain and direction
of load relative to primary axis of plate (see fig. 5.1.(5)). The resistance value is
determined using the test values in conjunction with the formulae contained in Clause
5.3.3.
6) The unit values of lateral resistance of teeth shall be expressed as per tooth, per rosette,
or per net area, whichever is appropriate or preferred. The design shall be based on net
area method using test values or on gross area method using 80 percent of the test
values and with areas defined in items (a) and (b) as follows:
(a) the gross area is defined as the total area of member covered by a truss plate:
(b) the net area is defined as the total area of a member covered by a truss plate less
the area within a given distance from the edge or end of member. For net area
calculation, the minimum end distance measured parallel to grain, shall be the
greater of 12 mm (1/2), or 1/2 the length of tooth; the minimum edge distance
measured perpendicular to grain, shall be the greater of 6 mm (1/4), or 1/4 the
length of the tooth.
Any joint in a truss may be designed by either net or gross area method of joint design
but not a combination of both within same joint.
7) Minimum Bite for Chords and Webs
At all joints, the connector plates are to be sized such that the minimum bites into all
chords and webs are as given in Table 5.1.(7):
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 38 8
Table 5.1.(7) Minimum Bite For Chords and Webs, mm (in)
Truss Length L, m ( ft )
Lumber Size 0 < L s 12.5
( 0 < L s 41 )
12.5 < L s 18.3
( 41 < L s 60 )
18.3 < L s 24.4
( 60 < L s 80 )
24.4 < L s 30.5
( 80 < L s100 )
38x64 (2x3) 38 (1.5) 45 (1.75) 51 (2.0) 57 (2.25)
38x89 (2x4) 38 (1.5) 45 (1.75) 51 (2.0) 57 (2.25)
38x114 (2x5) 38 (1.5) 45 (1.75) 51 (2.0) 57 (2.25)
38x140 (2x6) 38 (1.5) 51 (2.0) 57 (2.25) 64 (2.5)
38x184 (2x8) 51 (2.0) 57 (2.25) 64 (2.5) 76 (3.0)
38x235 (2x10) 64 (2.5) 70 (2.75) 76 (3.0) 83 (3.25)
38x286 (2x12) 76 (3.0) 76 (3.0) 83 (3.25) 89 (3.5)
Note: (1) Plates must be sized so that the min. bite into chords is as shown above:
(a) parallel to chord direction
(b) perpendicular to chord direction
(2) Plates must be sized so that the min. bite into webs is as shown above:
(a) parallel to chord direction
(b) perpendicular to chord direction
(c) along the centreline of the web
3) An exception to the 38mm (1.5 in) minimum is the case of a single web to through-chord
joint for 0 < L < 12.5m (0 < L < 41ft.) and for lumber sizes of 38x64 (2x3) to 38x140 (2x6)
where 25 mm (1.0 in) wide, minimum 76 mm (3.0 in) long plates may be used.
5.2 CONNECTOR PLATE EVALUATION
1) The metal connector plate design values (per tooth, nail, square mm, linear mm, or other
unit) shall be determined in accordance to procedures contained in S347-99 "Method of
Test for Evaluation of Truss Plates used in Lumber Joints" latest edition.
2) The tensile and shear values, for connector plates manufactured from a grade of steel
higher than that used in the plate testing program, may be adjusted by the ratio of the
ultimate tensile strength of the steel used in the manufacturing of the plate to that of the
steel used in the test plates. This adjustment does not apply to the gripping values; these
values may require adjustment , so should be verified by test.
3) Strength resistance values for plates and teeth are to be obtained from tests carried out
in accordance with S347-99, where the resistance values are
(a) the average, divided by 1.6, of the 3 lowest of 10 ultimate test values for lateral
resistance of the teeth;
(b) the average of the 2 lowest of 3 corrected test values for tensile strength of the plate;
and
(c) the average of the 2 lowest of 3 corrected test values for shear strength of the plate
at the angles specified;
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 3 39 9
4) Lateral slip resistance values are to be obtained from tests carried out in accordance with
S347-99, where the resistance values are the average of 10 test loads at 0.8 mm wood-
to-wood slip divided by 1.4.
5.3 STRENGTH LIMIT STATES
5.3.1 General
Truss plate joints shall be designed such that for the strength limit state, the effect of
factored load is less than or equal to;
(a) the factored ultimate lateral resistance of the teeth;
(b) the factored tensile resistance of the plates; and
(c) the factored shear resistance of the plates;
5.3.2 Modification Factors
1) Load Duration Factor, K
D
The load duration factor K
D
for truss plates is as previously given in Table 4.3.4.(1)
2) Service Condition Factor, K
SF
The service condition factor, K
SF
, for truss plates is given in Table 5.3.2.(2)
Table 5.3.2.(2) Service Condition Factor, K
SF
LUMBER CONDITION AT TIME OF MANUFACTURE
Seasoned (Moisture Content 15%) Unseasoned (Moisture Content > 15%)
LUMBER CONDITION IN SERVICE
DRY WET DRY WET
1.00 0.67 0.80 0.67
3) Treatment Factor, K
T
For connections containing wood-based members treated with fire-retardant or other
strength-reducing chemicals, strength capacities of connections shall be based on the
documented results of tests that shall shall take into account the effect of time,
temperature, and moisture content. Test procedures shall meet the requirements of
Clause 3.3.2 from O86-09.
Note: The effects of fire-retardant treatments can vary depending on manufacturing
materials and processes. See the Canadian Wood Council Commentary for additional
explaination.
4) Flat Roof Factor, K
F
Roof trusses meeting the housing and small building requirements of Part 9 of the
NBCC10 and carrying flat roof (where roof portion with slope < 1:6 exceeds 50% of
building width) shall be designed with a reduced factored resistance strength of plate by
applying a flat roof factor K
F
= 0.75.
K
F
= 1.0 for all other cases.
5.3.3 Ultimate Lateral Resistance
The ultimate lateral resistance of the teeth,n
u,
are calculated as follows:
(a) For loads parallel to the primary axis of the plate
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 40 0
n
p q
p q
u
u u
u u
sin cos
2 2
and
(b) For loads perpendicular to the primary axis of the plate
2 2
cos sin
u u
u u
u
q p
q p
n
where p
u
, q
u
, p
u
, q
u
are the ultimate lateral resistances obtained in accordance with
Clause 5.2.(3) (a) used with the following values of and :
p
u
0 0
: 0 0 ,
q
u
0 0
: 90 , 0
p' : 0 0
u
0 0
, 9
q
u
0 0
: 90 , 90
where and are defined in Figure 5.1(5)
When the primary axis of the plate is oriented at an angle other than parallel or
perpendicular to the direction of the load, the resistance value shall be determined by
linear interpolation between the values n
u
and n'
u
.
Figure 5.1.(5)
Truss Plate, Load and Grain Orientation
5.3.4 Tensile Resistance
Tensile resistance of the plate, t
p
, is determinded for both parallel to and perpendicular to
the direction of the plate primary axis in accordance with 5.2.(3) (b). For all other angles,
tensile resistance shall be determined by linear interpolation.
5.3.5 Shear Resistance
Shear resistance of the plate, v
p
, is determinded for specified angles of plate primary axis
to load direction in accordance with 5.2.(3) (c). For all other angles, shear resistance
shall be determined by linear interpolation.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 41 1
5.3.6 Factored Resistance of Truss Plates
For the strength limit state the factored resistances of truss plates shall be determined as
follows:
(a) The factored lateral resistance of the teeth, N
r
, shall be expressed in terms of
the surface area of the plates.
N
r
= |N
u
J
H
K
F
where | = 0.9
N
u
= n
u
(K
D
K
SF
K
T
)
J
H
= moment factor for heel connection (Clause 5.5.7.(1) or (2))
K
F
= flat roof factor
(b) The factored tensile resistance of the plates, T
r
, shall be expressed in terms of the
dimension of the plate measured perpendicular to the line of action of the applied
forces.
T
r =
| t
p
K
F
where | = 0.6
t
p
= tensile resistance of the plate (Clause 5.3.4)
K
F
= flat roof factor
(c) The factored shear resistance of the plates, V
r
, shall be expressed in terms of the
dimension of the plate measured along the line of action of the shear forces.
V
r
= | V
p
K
F
where |
= 0.6
V
p
= shear resistance of the plate. (Clause 5.3.5)
K
F
= flat roof factor
5.4 SERVICEABILITY LIMIT STATES
Truss plate joints shall be designed such that for the serviceability limit state the effect of
specified loads is less than or equal to the lateral slip resistance of the teeth.
1) Lateral Slip Resistance
The lateral slip resistance of the teeth, n
s
, shall be calculated as follows:
(a) For loads parallel to the primary axis of the plate
u u
2 2
cos sin
s s
s s
s
q p
q p
n
+
=
and
(b) For loads perpendicular to the primary axis of the plate
u u
2 2
cos sin
s s
s s
s
q p
q p
n
' + '
' '
= '
where p
s
, q
s
, p'
s
, q'
s
are the lateral slip resistances obtained in accordance with Clause
5.2.(4) used with the following values of u and :
p : 0 0
s
0 0
u = = ,
q : 90 , 0
s
0 0
u = =
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 42 2
' = = p : 0 , 90
s
0 0
u
' = q : =90 , 90
s
0 0
u
where and u are defined in Figure 5.1.(5)
When the primary axis of the plate is oriented at an angle other than parallel or
perpendicular to the direction of the load, the resistance value shall be determined by
linear interpolation between the values n
s
and n'
s
.
2) For the serviceability limit state, the lateral slip resistance of the teeth, N
rs
, shall be
determined as follows:
N
rs
= n
s
K
SF
Where K
SF
is the same as for strength limit state Table 5.3.2.(2)
5.5 MEMBER JOINT CONNECTIONS
5.5.1 Connection of Tension Members
1) The factored lateral resistance, N
r
, in each tension member must be a minimum of 100%
of the factored axial load in the member.
2) There must be sufficient factored tensile resistance, T
r
, in the connector plates to transmit
the full factored axial load in each tension member, considering the appropriate planes of
action.
5.5.2 Connection of Compression Members
1) Metal connector plates resisting factored compressive axial loads shall be sized to
provide factored lateral resistance, N
r
, equal to the vectorial sum of no less than 50% of
the component factored loads normal to the wood member interface, and 100% of the
component factored loads parallel to the wood member interface.
2) Truss plates shall not be considered to transfer compression loads at joints.
5.5.3 Connection of Members for Shear
1) There must be sufficient factored lateral resistance of the teeth, N
r
, in webs and chords to
transmit the factored shear loads at a joint.
2) There must be sufficient factored shear resistance, V
r
, in the truss plates to transmit the
factored shear loads at a joint.
5.5.4 Combined Shear-Tension Resistance
The combined factored shear and tension resistance,C
ST
, of the metal connector plate in
the contact area of webs and chords, shall be determined as follows:
( ) C ST L ST L
ST L1 1 L2 2
= +
where;
ST
L1
- combined factored shear/tension resistance of the pair of metal connector
plates through the line of contact L1. (see Figure 5.5.4)
L
1
- length of effective steel at the horizontal edge of the member under
consideration.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 43 3
ST
L2
- combined factored shear/tension resistance of the pair of metal connector
plates through line of contact L2.
L
2
- length of effective steel at the vertical edge of the member under consideration.
ST
L1
= ( ) V
90
T V
rL1
1
rL1 rL1
+
|
\
|
.
|
u
ST
L2 = ( ) T
90
V T
rL2
1
rL2 rL2
+
|
\
|
.
|
u
Figure 5.5.4
Shear-Tension Lengths and Angles
V
r
L
1
- factored shear resistance parallel to the line of action, L1
V
r
L
2
- factored shear resistance parallel to the line of action, L2
T
r
L
1
- factored tensile resistance perpendicular to the line of action, L1
T
r
L
2
- factored tensile resistance perpendicular to the line of action, L2
P
TW
- factored tensile force in web
C
ST
(L1 and L2 shown in figure 5.5.4) > P
TW
NOTE: Where the truss plate extends significantly past any chord and/or web
member, additional blocking is recommended.
5.5.5 Net Section Lumber Check (h')
At all joints, members shall have metal connector plates sized and/or positioned so that
the axial stress index of the member is not exceeded on the reduced net section resulting
from the coverage of the plate (See Figure 5.5.5)
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 44 4
h
'
h'
b
h
'
b
h
'
b
h'
Fig. 5.5.5 (a) Fig. 5.5.5 (b)
Fig. 5.5.5 (c)
Figure 5.5.5
Typical h Dimensions
5.5.6 Tension Perpendicular-To-Grain Considerations
Any joint which carries a factored concentrated load that is perpendicular to the chord or
has a component that is perdendicular to the chord and/or has a shear component that is
perpendicular to the chord and exceeds 2.5 kN (562 lbs) must be reinforced for tension
perpendicular-to-grain with a minimum chord bite as follows:
Min. Bite (mm) =
P 2500
0041
.
.
For Spruce-Pine-Fir
Min. Bite (mm) =
P 2500
0055
.
.
For Douglas-Fir-Larch
where P = Factored Concentrated Load, kN
The calculated minimum bite requirement need not exceed 3/4 of the depth of the
lumber.
5.5.7 Heel Joint Considerations
1) To allow for moment effects at the heel joint of pitched trusses, the heel joint moment
factor J
H
shall be as given in Table 5.5.7.(1)
Table 5.5.7.(1) Heel Joint Moment Factors, J
H
Slope of top chord J
H
Under 1/4 slope 0.85
1/4 to less than 1/3 slope 0.80
1/3 to less than 1/2.4 slope 0.75
1/2.4 to 1/2.2 inclusive 0.70
over 1/2.2 slope 0.65
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 45 5
2) In lieu of the values from the table above, the following formula can be used in
determining the Heel Joint Moment Factor:
J
H
= 0.85 - 0.05 (12 tanu - 2.0)
where 0.65 s J
H
s 0.85
u = the angle between the top and bottom chord
3) Where the vertical reaction results in factored shear loads that exceed the factored
shear resistance of the lumber, the heel joint lumber may be reinforced by additional
plating. For the design of the additional plating for girder type heels, refer to Appendix F.
4) The heel joint of a chord extended rafter shall be plated as an ordinary heel joint with the
appropriate heel joint moment factor applied. Consideration should be given to prevent
splitting due to tension perpendicular-to-grain and longitudinal shear by supplementary
plating on the continuous rafter.
5.5.8 Chord Member Splice Considerations
5.5.8.1 General
For all chord splices the plate width shall be at least 65% of the width of the chord
member.
5.5.8.2 Tension Splices
1) When determining the factored tensile resistance of the metal connector plate, the
maximum extension of the metal connector plate for an unblocked chord splice is 13 mm
(1/2).
2) In the case of blocked tension splices, the total plate effectiveness shall be modified by
the factor K as defined by the following equation:
K = 0.97e
-0.001(3.937 + 0.0186(88.9-h))X
where: h = Actual width of wood member, mm.
X = Extension of plate above member. Maximum X allowed in this
calculation is 89 mm (3.5).
Note: (1) For an un-blocked tension splice with an extension of 13mm (1/2) or less, K
is equal to 1.00
(2) In the case of a splice occurring at the panel joint, webs framing into joint
shall be considered as blocking.
(3) Maximum plate width to be applied with effectiveness factor K cannot be in
excess of the member actual width h, plus the maximum extension, X.
5.5.8.3 Compression Splices
1) Compression splice plates shall be designed so that the factored ultimate lateral
resistance in each member will be at least equal to 65% of the factored compressive
axial load.
2) In plumb cut compression joints the metal connector plates resisting factored
compressive axial loads shall be sized to provide factored ultimate lateral resistance,
equal to the vectorial sum of no less than 65% of the component factored loads normal to
the wood member interface and 100% of the component factored loads parallel to the
wood member interface.
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 46 6
5.5.8.4 Moment Considerations
When in line members terminate at a splice,where chord moment should be considered,
the splice plates must have sufficient resistance to transfer this factored bending moment
in addition to the factored axial load. This resistance is in both plate steel section clause
5.5.8.4.1 and plate tooth gripping clause 5.5.8.4.2. See also clause 4.6.2
5.5.8.4.1 Design of Steel Section for Effect of Moment
The factored moment resistance in combination with tension M
Tr,
of a pair of connector
plates at a splice joint shall be taken as:
M
Tr
= 0.27 t
p
(0.5w
br
+ y)
2
+ 0.18 b C(0.5d y)
2
F
f
K
T
y
0.5bC t
t 0.5w
K
T
1.85 0.25bdC
y
p
p br
F
f
+
+
=
where: t
p
= corrected tensile resistance of the connector plates, N/mm
w
br
= effective plate width for steel section calculations, mm (clause 5.5.8.2)
y = distance from the chord centreline to neutral axis of wood/steel
combination , mm (y can be positive or negative but the moment formula
is invalid if y lies outside the plate)
b = chord thickness, mm
C = F
c
, MPa
F
c
= f
c
(K
D
K
Sc
K
T
K
Zc
)
d = chord depth, mm
T
f
= factored tension force in chord at the splice (set equal to zero for
compression), N
K
F
= flat roof factor
The stress ratio for moment in combination with axial tension shall be taken as the
following:
1.0
M
K
M
Tr
F
f
s
where M
f
= factored bending moment in the chord at the splice, Nmm
The stress ratio for the axial tension shall be taken as the following:
1.0
w T
T
br r
f
s
where T
r
= factored tension-only resistance of the connector plate N/mm,
(including K
F
)
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 47 7
5.5.8.4.2 Design of Plate Lateral Resistance for Effect of Moment
The moment applied at the splice joint shall not exceed the moment capacity in lateral
resistance in any orientation, nor the combined capacity for moment and non-moment
loads defined as follows:
'
s
LRmin M
V V and,
'
s +
LR p M
V V V
( ) D A 4M V
ef f M
=
2 2
ef
h /h) (A D + =
where:
V
M
= tooth holding stress due to the factored moment on a pair of
plates,Mpa
V
P
= tooth holding stress resultant of factored shear and axial loads in
wood on a pair of plates, Mpa , equal to the vector addition of the
factored shear + axial loads in wood, divided by A
ef
V
LR
' = allowable tooth holding stress for a pair of plates for the orientation
of V
P
per section 5.5.3 with modification factors of 5.3.2, Mpa
(including K
F
)
V
LRmin
' = minimum allowable tooth holding value for any angle of load at the
joint for a pair of plates determined from section 5.5.3 with
modification factors of 5.3.2, Mpa (including K
F
)
A
ef
= effective plate area on one face of each wood member at the splice
joint, mm
2
D = diagonal of rectangle equivalent to A
ef
, mm
h = height of equivalent rectangle, equal to the greatest dimension
across A
ef
, perpendicular to the longest side of A
ef
, mm
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 48 8
5.5.9 Compression Perpendicular-To-Grain
Any joint which carries a factored concentrated compressive load that subjects the
member to compression perpendicular to grain stresses through the depth of the
member (example: the bottom chord on a bottom chord bearing flat truss) such that a
reduction of bearing strength as described in section 4.4.4.(2) applies, may be reinforced
with connector plates so that the increased bearing strength of section 4.4.4.(1) may be
used. This bearing reinforcement consists of applying connector plates at the joint of a
size that permit coverage of the chord member to within 6 mm () of the edge making
contact with the bearing. When using this reinforcement to reduce bearing size, the web
member contact on the opposite surface to the bearing, must be at least equal to that of
the bearing. See figure 5.5.9.
FIGURE 5.5.9 Bearing Reinforcement With Connector Plates
T TR RU US SS S P PL LA AT TE E I IN NS ST TI IT TU UT TE E O OF F C CA AN NA AD DA A ( (2 20 01 11 1) )
J Ju un ne e 2 20 01 11 1 4 49 9
6. MANUFACTURING AND MATERIAL VARIANCES
Minimum quality manufacturing criteria including tollerances to allow for manufacturing
variances can be found in Appendix G.
7. TRUSS DESIGN DRAWING
In addition to the truss drawing itself, minimum design information to be included on the
truss design drawing can be found in Appendix H.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 50
A.1 SHORT CANTILEVERS: DETAIL WITHOUT REINFORCING
Standard Heel
Girder Type Heel
MAXIMUM CANTILEVER C CALCULATION
C(mm) =S(mm) - (L
b
(mm) +13 mm)
C(in) =S(in) - (L
b
(in) +1/2 in)
C
DESIGN SPAN
DESIGN SPAN
H.C.
L
b
13mm (1/2 in) Min
L
b
13mm (1/2 in) Min
S
C
H.C.
S
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 51
A.2 SHORT CANTILEVERS: DETAIL WITH WEDGE REINFORCING
Standard Heel
Girder Type Heel
MAXIMUM CANTILEVER C CALCULATION
C(mm) =S
1
(mm) +89 mm
C(in) =S
1
(in) +3 1/2 in
Notes: 1. Minimum value for S
2
(mm) =L
b
(mm) +102mm
S
2
(in) =L
b
(in) +4 in
2. Maximum value for S
2
in determining analogue distance S is that calculated for a
wedge depth equaling the bottom chord depth.
S
1
C
DESIGN SPAN
C
DESIGN SPAN
H.C.
13mm (1/2 in) Min
H.C.
13mm (1/2 in) Min
S
1
S
2
L
b
S
2
S
L
b
S
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 52
A.3 SHORT CANTILEVERS: DETAIL WITH PARTIAL TOP CHORD REINFORCING MEMBER
(PARTIAL TOP CHORD SLIDER)
Standard Heel
Girder-Type Heel
MAXIMUM CANTILEVER C CALCULATION
C(mm) =S
1
(mm) +S
2
(mm) - (L
b
(mm) +13 mm)
C(in) = S
1
(in) +S
2
(in) - (L
b
(in)+1/2 in)
Notes: 1. Maximum value of S
2
is limited by maximum reinforcing member size
38x184 (2x8)
2. LT =Minimum of one half the length of top chord panel
3. Y =Minimum of 25 mm (1 in)
S
S
1
S
2
C L
b
13mm (1/2 in) Min.
S
S
1
S
2
C
DESIGN SPAN
L
b
DESIGN SPAN
13 mm (1/2 in) Min
LT
Y
H.C.
LT
Y
H.C.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 53
A. 4 SHORT CANTILEVERS: DETAIL WITH PARTIAL BOTTOM CHORD REINFORCING
MEMBER (PARTIAL BOTTOM CHORD SLIDER)
STANDARD HEEL
MAXIMUM CANTILEVER C CALCULATION
C(mm) =S
1
(mm) +S
2
(mm) - (L
b
(mm) +13 mm)
C(in) =S(in) +S
2
(in) - (L
b
(in)+1/2 in)
Notes: 1. Maximum value of S
2
is limited by maximum reinforcing member size
38x184 (2x8)
2. LB =Minimum of two thirds the length of bottom chord panel
3. Y =Minimum of 25 mm (1 in)
S
S
2
S
1
LB
Y
C
L
b
DESIGN SPAN
S
S
1
S
2
LB
Y
C
L
b
DESIGN SPAN
H.C.
13 mm (1/2 in) Min
13 mm (1/2 in) Min
H.C.
Girder-Type Heel
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 54
A. 5 HEEL CUTS
DETAIL-A
DESIGN SPAN
DESIGN SPAN
DESIGN SPAN
H.C.
DETAIL-B
H.C.
DETAIL-C
MAXIMUM 1/2 DEPTH
38X184 (2X8) MAXIMUM
REINFORCING MEMBER
MINIMUM OF 2/3 OF BOTTOM
CHORD PANEL
Heel cut less than or equal to
1/2 depth of bottom chord
Heel cut up to full depth of
bottom chord
Heel cut greater than depth of
bottom chord
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix A
June 2011 55
A.6 SUPPLEMENTARY NOTES FOR DESIGN OF SHORT CANTILEVERS AND HEEL CUTS
1. GENERAL
a. Design span is always out to out of bottom chord for standard details.
b. The sum of cantilever lengths shall not exceed 25% of span between bearings.
c. Maximum cantilever shall not exceed 1372 mm (4-6").
d. The TPIC standard procedures for plating heel joints shall apply. i.e. Reduction of grip value with
slope increase.
e. Partial reinforcing members used with short cantilevers and heel cuts are limited in scope to
trusses designed under Section 4.4.13. The reinforcing members shall be designed for top or
bottom chord forces as applicable. For all other applications these cantilevers and heel cuts
must be accomplished by full length reinforcement of the appropriate chord and limitations of
cantilever length, reinforcement size, species, grade and, plating to be determined by analysis.
2. SHORT CANTILEVER
a. All details:
Maximum values of C must be calculated for specific slope and heel cut as shown on the
details.
b. Detail without reinforcing.
Plate heel for actual chord force. Tie plate is recommended for long scarf cuts.
c. Detail with wedge reinforcing.
Plate heel for actual forces. Tie plates are always required with the wedge. Total area of tie
plates on chords shall be 20% of required area of heel plate on corresponding chord.
d. Detail with chord reinforcing:
i. Plates joining reinforcing member to parallel chord shall provide sufficient grip and shear
length to transfer full chord force to reinforcing member. Where only one plate is used, it
shall be designed for 1.20 times chord force.
ii. Heel shall be designed as per standard heel procedures. Reinforcing member may be
considered as top or bottom chord as applicable. There shall be a minimum of 25 mm (1 in)
overlap as shown in sketches.
iii. Where plating and scarf permit, the reinforcing member may form part of the heel cut.
iv. Tie plates are recommended for long scarfs.
3. HEEL CUTS
a. Detail A.
Heel cut less than or equal to 6mm (1/4 in.) may be considered as zero heel cut. Plate for full
chord forces.
b. Detail B.
Plate heel to resist full chord forces at 1/2 bottom chord depth with linear interpolation to twice the
full chord forces up to the full depth of bottom chord.
c. Detail C.
Plate heel for full chord forces. Plate design for connecting reinforcing member to parallel chord
shall be as per 2d.i. above.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix B
June 2011 56
B. 1 TRUSS-TO-TRUSS CONNECTION
Minimum nail length 76 mm (3.00")
Minimum nail diameter 3.66 mm (0.144")
Lumber Grade Spruce-Pine-Fir
Minimum nail spacing parallel to grain (a) 64 mm (2.50")
Minimum nail spacing from End distance 45 mm (1.75")
parallel to grain (b)
Minimum nail spacing perpendicular to grain (c) 32 mm (1.25")
Minimum nail spacing from edge distance 19 mm (0.75")
perpendicular to grain (d)
Maximum kN/m (PLF) apply only to nails as defined in CSA B111.
MEMBER
DEPTH
mm (inches)
MAXIMUM
NO. OF ROWS
MINIMUM *
NO. OF ROWS
64 (2.5)
89 (3.5)
114 (4.5)
140 (5.5)
184 (7.25)
235 (9.25)
286 (11.25)
1
2
2
3
4
5
6
1
1
1
2
2
3
3
* For web nailing, use minimum number of rows stated in table and
a surface nail spacing of 150 mm (6") o.c.
Table B.1.1 Nail Spacing and Maximum Number of Rows.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix B
June 2011 57
TABLE B.1.2 MAXIMUM kN/m (PLF) FOR 2 PLY GIRDER
WITH 3 NAILS AND S-P-F LUMBER
NUMBER
OF ROWS
SURFACE NAIL SPACING, mm (inches)
305 (12) 152 (6) 102 (4)
1 4.64 (318) 9.28 (636) 13.92 (954)
2 9.28 (636) 18.56 (1272) 27.84 (1908)
3 13.92 (954) 27.84 (1908) 41.77 (2862)
4 18.56 (1272) 37.13 (2544) 55.69 (3816)
5 23.20 (1590) 46.41 (3180) 69.61 (4770)
6 27.84 (1908) 55.69 (3816) 83.53 (5724)
NOTE: 1) Load duration factor for Standard Term loading has been used in the
computation of data in the table.
2) If 3-inch power driven nails (0.120 dia) are to be substituted for 3-inch common wire
nails then reduce the maximum kN/m (or PLF) to be transferred by a factor of 0.71.
3) These tables are based on seasoned untreated lumber.
Figure B.1.2 Nailing Pattern for 2-Ply Girder
SURFACE NAIL SPACING
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix B
June 2011 58
TABLE B.1.3 MAXIMUM kN/m (PLF) FOR 3 PLY GIRDER
WITH 3 NAILS AND S-P-F LUMBER
NUMBER
OF ROWS
SURFACE NAIL SPACING, mm (inches)
305 (12) 152 (6) 127 (5) *
1 3.48 (239) 6.96 (477) 8.35 (572)
2 6.96 (477) 13.92 (954) 16.71 (1145)
3 10.44 (716) 20.88 (1431) 25.06 (1717)
4 13.92 (954) 27.84 (1908) 33.41 (2290)
5 17.40 (1193) 34.81 (2385) 41.77 (2862)
6 20.88 (1431) 41.77 (2862) 50.12 (3434)
* Inner ply rows should be offset for spacing
NOTE: 1) Load duration factor for Standard Term loading has been used in the
computation of data in the table.
2) If 3-inch power driven nails (0.120 dia) are to be substituted for 3-inch common wire
nails then reduce the maximum kN/m (or PLF) to be transferred by a factor of 0.71.
3) These tables are based on seasoned untreated lumber.
Figure B.1.3 Nailing Pattern for 3-Ply Girder
SURFACE NAIL SPACING
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix B
June 2011 59
TABLE B.1.4 MAXIMUM kN/m (PLF) FOR 4 PLY GIRDER
WITH 3" NAILS AND S-P-F LUMBER
NUMBER
OF ROWS
SURFACE NAIL SPACING, mm (inches)
305 (12) 152 (6) 127 (5) *
1 3.09 (212) 6.19 (424) 7.43 (509)
2 6.19 (424) 12.38 (848) 14.85 (1018)
3 9.28 (636) 18.56 (1272) 22.28 (1526)
4 12.38 (848) 24.75 (1696) 29.70 (2035)
5 15.47 (1060) 30.94 (2120) 37.13 (2544)
6 18.56 (1272) 37.13 (2544) 44.55 (3053)
* Inner ply rows should be offset for spacing
NOTE: 1) Load duration factor for Standard Term loading has been used in the
computation of data in the table.
2) If 3-inch power driven nails (0.120 dia) are to be substituted for 3-inch common wire
nails then reduce the maximum kN/m (or PLF) to be transferred by a factor of 0.71.
3) These tables are based on seasoned untreated lumber.
Figure B.1.4 Nailing Pattern for 4-Ply Girder
Supplementary Notes:
In addition to nailing, all chords of 4 and 5 ply girders must be bolted together with 13 mm (0.5") ASTM A307
Grade A bolts and washers, 1 bolt per panel.
SURFACE NAIL SPACING
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix B
June 2011 60
TABLE B.1.5 MAXIMUM kN/m (PLF) FOR 5 PLY GIRDER
WITH 3" NAILS AND S-P-F LUMBER
NUMBER
OF ROWS
SURFACE NAIL SPACING, mm (inches)
305 (12) 152 (6) 127 (5) *
1 2.90 (199) 5.80 (398) 6.96 (477)
2 5.80 (398) 11.60 (795) 13.92 (954)
3 8.70 (596) 17.40 (1193) 20.88 (1431)
4 11.60 (795) 23.20 (1590) 27.84 (1908)
5 14.50 (994) 29.00 (1988) 34.81 (2385)
6 17.40 (1193) 34.81 (2385) 41.77 (2862)
* Inner ply rows should be offset for spacing
NOTE: 1) Load duration factor for Standard Term loading has been used in the
computation of data in the table.
2) If 3-inch power driven nails (0.120 dia) are to be substituted for 3-inch common wire
nails then reduce the maximum kN/m (or PLF) to be transferred by a factor of 0.71.
3) These tables are based on seasoned untreated lumber.
Figure B.1.5 Nailing Pattern for 5-Ply Girder
Supplementary Notes:
In addition to nailing, all chords of 4 and 5 ply girders must be bolted together with 13 mm (0.5") ASTM A307
Grade A bolts and washers, 1 bolt per panel.
SURFACE NAIL SPACING
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix C
June 2011 61
TABLE C.1 MAXIMUM WEB FORCE IN COMPRESSION KN (lbs) WITH ONE
T-BRACE
T-BRACE
Web
Web
Length
mm (inch)
38 X 89 (2 X 4)
38 x 64
(2 x 3)
38 x 89
(2 x 4)
38 x 114
(2 x 5)
38 x 140
(2 x 6)
915 (36) 27.75 (6240) 37.99 (8542) 47.83 (10750) 57.31 (12880)
1220 (48) 23.61 (5309) 31.61 (7107) 39.00 (8768) 45.89 (10320)
1525 (60) 18.95 (4260) 24.75 (5565) 29.90 (6723) 34.55 (7767)
1830 (72) 14.63 (3291) 18.70 (4205) 22.18 (4987) 25.24 (5674)
2135 (84) 11.11 (2498) 13.94 (3135) 16.30 (3666) 18.34 (4124)
2440 (96) 8.41 (1891) 10.41 (2342) 12.05 (2711) 13.45 (3024)
2745 (108) 6.41 (1442) 7.86 (1768) 9.03 (2031) 10.02 (2253)
3050 (120) 4.94 (1112) 6.02 (1354) 6.88 (1547) 7.59 (1708)
Supplementary Notes:
Web and T-brace material to be S-P-F No. 2 or better.
Load duration factor for Standard Term loading has been included in the computation of data in the
table.
Load sharing has been included as well.
Figure C.1.1 Nailing Pattern for T-Bracing on Single Ply Web
T-BRACE
Typical
150mm (6.0)
Nailing - 76mm (3) Common Wire Nails @ 150mm (6.0) O.C.
WEB
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix D
June 2011 62
TABLE D.1 TOP CHORD BEARING JOINT GUIDELINES FOR LUMBER ON EDGE
BEARING
DETAIL
SEE
FIGURE
TOP CHORD
SIZE
DIAGONAL
SIZE MIN
MAXIMUM
FACTORED
ALLOWABLE
REACTION
MAX ALLOWABLE GAP
mm (in)
D.4.6.6.1 mm (in) mm (in) kN (lbs) A B C
Detail 1 38 x 89 (2x4) N/A 14.10 (3170) 13 (1/2) 13 (1/2) 3 (1/8)
Detail 2 38 x 89 (2x4) N/A 14.10 (3170) N/A 13 (1/2) 13 (1/2)
Detail 3,4 38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)*
38 x 89 (2x4)
38 x 89 (2x4)
38 x 89 (2x4)
11.98 (2694)
14.80 (3328)
17.62 (3962)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
38 (1-1/2)
50 (2)
3 (1/8)
3 (1/8)
3 (1/8)
Detail 5 38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)*
38 x 89 (2x4)
38 x 89 (2x4)
38 x 89 (2x4)
16.92 (3804)
19.03 (4279)
21.15 (4755)
13 (1/2)
13 (1/2)
13 (1/2)
N/A
N/A
N/A
6 (1/4)
6 (1/4)
6 (1/4)
Detail 6,7 38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)*
38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)
38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)
38 x 89 (2x4)
38 x 114 (2x5)
38 x 140 (2x6)
16.92 (3804)
19.74 (4438)
22.56 (5072)
17.27 (3883)
21.32 (4794)
25.38 (5706)
17.62 (3962)
22.91 (5151)
28.20 (6340)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
13 (1/2)
13 (1/2)
13 (1/2)
38 (1-1/2)
38 (1-1/2)
38 (1-1/2)
50 (2)
50 (2)
50 (2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
13 (1/2)
* Or Greater
Note: Maximum factored reactions are for Spruce-Pine-Fir and D. Fir Chords.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix D
June 2011 63
FIGURE D.1 TYPICAL TOP CHORD BEARING JOINT GUIDELINES FOR LUMBER ON
EDGE
DETAIL 1
DETAIL 2
DETAIL 3
DETAIL 4
DETAIL 5
DETAIL 6
DETAIL 7
C
B
A
C
B
A
50mm (2in) minimum
C
B
C B
C
B
A
C
B
C
A
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix D
June 2011 64
TABLE D.2 TOP CHORD BEARING JOINT GUIDELINES FOR LUMBER ON FLAT
TOP CHORD BEARING
TYPE AS SHOWN IN FIGURE D.4.6.6.2
MAXIMUM
FACTORED
ALLOWABLE
REACTION
MAX ALLOWABLE GAP mm (in)
kN (lbs) A B C
Single Top
Chord
4 x 2
Detail 1,2
Detail 3
Detail 4
4.23 (951)
11.28 (2536)
4.23 (951)
13 (1/2)
N/A
13 (1/2)
3 (1/8)
3 (1/8)
3 (1/8)
3 (1/8)
13 (1/2)
3 (1/8)
Double Top
Chord
4 x 2
Detail 5, 7, 8
Detail 6
Detail 5, 6 (at B.C)
11.28 (2536)
11.28 (2536)
13 (1/2)
N/A
N/A
3 (1/8)
3 (1/8)
3 (1/8)
3 (1/8)
13 (1/2)
3 (1/8)
Double Top
Chord
3 x 2
Detail 7, 8 8.06 (1811) 13 (1/2) 3 (1/8) 3 (1/8)
Double Top
Chord
4 x 2
Detail 9,10 28.20 (6340) N/A 3 (1/8) 13 (1/2)
Note: Maximum factored reactions are for Spruce-Pine-Fir and D. Fir Chords
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix D
June 2011 65
FIGURE D.2 TYPICAL TOP CHORD BEARING JOINT GUIDELINES FOR LUMBER ON
FLAT
DETAIL 1
DETAIL 2
DETAIL 3
DETAIL 4
DETAIL 5
DETAIL 6
DETAIL 7
DETAIL 8
B
A
B
C
B
C
A
C
B
A
C
C
B
B
C
B
A
C
B
A
C
B
C
B
C
B
A
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix D
June 2011 66
FIGURE D.2 TYPICAL TOP CHORD BEARING JOINT GUIDELINES FOR LUMBER ON
FLAT
DETAIL 9
DETAIL 10
C
B
C
B
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix E
June 2011
67
E.1 CORROSION PROTECTION FOR METAL CONNECTOR PLATES
1. For metal connector plates used in unusual environmental conditions, or exposed to the weather,
additional corrosion resistant protection for the metal connector plates shall be installed when such
conditions are identified by the building designer/engineer.
2. Galvanized G 90 metal connector plates subject to environments described above shall be painted with
one coat of one of the following combinations:
a) Epoxy-Polyamide Primer (SSPC-Paint22)
b) Coal-Tar Epoxy-Polyamide Black or Dark Red Paint (SSPC-Paint 16)
c) Basic Zinc Chromate-Vinyl Butyral Wash Primer (SSPC-Paint 27) and cold applied Asphaltic Mastic
(Extra Thick Film) Paint (SSPC-Paint 12)
d) Any other coating or treatment acceptable to the building designer/engineer
3. All coatings shall be brush applied to the embedded metal connector plates at the jobsite during or after
truss installation. Embedded metal connector plates shall be free of dirt and oil prior to coating
application. In addition, all of the Manufacturers recommendations for application of products used must
be followed implicitly.
Note: To the best of industry knowledge these products will extend the serviceable life of the truss connector
plate under conditions described in 1. above.
No warranty or guarantee, other than that offered by the manufacturers of these products is expressed or
implied. Severe corrosive conditions may require maintenance of these protective coatings as part of the
standard building maintenance program.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix F
June 2011 68
F.1 SHEAR PLATE DESIGN FOR GIRDER TYPE HEEL JOINT
Truss Point - the intersection of the centreline of top chord and the centreline of bottom chord.
Projection Point - the intersection of the forty five degree line from the inside edge of the bearing and the
centreline of bottom chord.
Top Chord Point - the beginning point of the top chord scarf.
Shear Plate Requirements:
A shear check is required when the projection point is closer to the end of the truss than the truss point.
If P
A
P
W
, then shear plates are required.
Where
P
A
= The factored shear load at the girder heel, N (lbs)
P
A
=
15 . '
'
RL
D
R = Reaction N (lbs)
L = Distance between projection point and truss point, mm (in)
D = Lumber depth at projection point, mm (in)
P
W
= The factored shear resistance of the lumber without plate, N (lbs)
P
W
= F
V
tnL
= 0.9
F
v
= f
v
K
D
K
Hv
K
Sv
K
T
K
Zv
t = Lumber thickness per ply, mm (in)
f
v
= specified strength in shear, MPa (Psi)
n = Number of plies
K
D
= Load duration factor
K
Hv
= Load sharing factor for shear
K
sv
= Service condition factor for shear
K
T
= Treatment factor
K
zv
= Size factor for shear
PROJ ECTION POINT
TRUSS POINT
TOP CHORD POINT
PRIMARY
PLATE
SHEAR PLATE
D
L
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix F
June 2011 69
Shear Plate Design:
The shear plate must be sized and placed about the centreline of bottom chord to cover the distance L such that:
i) Area of the shear plate above or below the centreline of bottom chord must be capable of resisting the net
shear force at the girder heel.
Net Shear Force =
P
A
P
W
n
ii) The length of the shear plate along the centreline of bottom chord must be such that the shear capacity of the
plate, along the centreline of bottom chord, is greater than or equal to the net shear force at the girder heel.
The shear length as calculated must not be less than L.
Notes:
1. Where the primary plate interferes with the placement of the secondary shear plate then the primary plate
must be specified long enough to provide the required grip and metal shear capacity due to the net shear
force.
2. The tapered depth of the bottom chord at the inside edge of bearing should not be less than half the bottom
chord size or 100mm (4 in), whichever is greater.
3. An additional moment check should be carried out due to extension of the bottom chord past the top chord.
The moment to be used for this check is the overall span reaction times the distance from the inside edge of
the bearing to the top chord point.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 70
G MANUFACTURING AND MATERIAL VARIANCES
G.1 SCOPE
The purpose of this appendix is to establish minimum allowances to be used with the TPIC 2011
design procedures to account for material defects and variances in workmanship. It is the
responsibility of the manufacturer to adjust these allowances for trusses that cannot be
manufactured within the limits described in this appendix.
G.2 TRUSS SHOP DRAWING
The truss shop drawings are the drawings provided to the plant personnel for the fabrication of each
truss. They include enlarged joint details, tooth count requirements, cutting list, truss layout and/or
jig location details.
G.3 MATERIALS
G.3.1 Lumber
G.3.1.1 The lumber shall meet the criteria as described in TPIC Section 2.1 and be the size, species and
grade (or better) specified on the Truss Shop Drawings.
G.3.1.2 Splits in any wood member caused by the manufacturing process shall not exceed those permitted
in the grade and species of lumber used.
G.3.2 Metal Connector Plates
G.3.2.1 Metal connector plates shall meet the criteria as described in TPIC Section 2.2 and be of the gauge,
type, manufacturer, width and length as specified on the Truss Shop Drawing.
G.4 PLATING
Section 5.1 in the TPIC design procedures describes the conditions for which the design criterion for
truss plates is based. To allow for minimum manufacturing and material variances the plate design
criteria shall be adjusted to allow for plate misplacement and ineffective teeth. This section provides
the procedure to adjust the design criteria to match that which is generally achievable in the
manufacturing process.
G.4.1 Tooth Effectiveness
G.4.1.1 Effective Teeth
Effective teeth are teeth fully embedded normal to the surface of the lumber and into quality wood of
the member.
G.4.1.2 Ineffective Teeth
Ineffective teeth are teeth that are improperly embedded and cannot resist loading. Examples
include teeth located over wane, knot holes, loose or decayed knots, pitch pockets, unsound wood,
holes and joint gaps or teeth that have been flattened before or during the pressing, or that have a
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 71
tooth embedment gap of 1.6 mm (1/16) or greater. Teeth located within the 13 mm () end and 6
mm () edge distances of the lumber are considered to be ineffective when the design is based
upon the net area method.
G.4.1.3 Partially Effective Teeth
Teeth not completely embedded and can resist loading may be considered to be partially
effective.
When a metal connector plate is installed in the connection area of lumber which contains tooth
holes from a previously installed plate and where the wood is otherwise undamaged, metal
connector plate teeth shall be considered 50% effective.
G.4.1.4 Minimum Effective Teeth
a. Lumber on Edge (Wide face plating)
The truss designer shall provide a minimum 10% reserve capacity in grip for each member to allow
for ineffective teeth. This requirement may be met by limiting the grip JSI to 0.90 in each member.
The required number of effective teeth in each member shown on truss shop drawings or in lists
shall be calculated according to TPIC Section 5.1. This means that in the manufacturing process,
the average number of effective teeth for both sides of the joint in any member shall never be less
than the required number of teeth specified on the shop drawing. When averaging the effective teeth
on both sides no one side shall have less than 85% of the specified effective teeth required.
b. Lumber on Flat (narrow face plating)
The truss designer shall provide a minimum 5% reserve capacity in grip for each member to allow
for ineffective teeth. This requirement may be met by limiting the grip JSI to 0.95 in each member.
The required number of effective teeth in each member shown on truss shop drawings or in lists
shall be calculated according to TPIC Section 5.1. This means that in the manufacturing process,
the average number of effective teeth for both sides of the joint in any member shall never be less
than the required number of teeth specified on the shop drawing. When averaging the effective teeth
on both sides no one side shall have less than 85% of the specified effective teeth required.
Joint Stress Index: The Joint Stress Index (JSI) is the ratio of the calculated force in a member to
the lateral resistance of the teeth in that member. Example: If a member has a design force of 4.0
kN (900 lbs) in it and the teeth of the connector plate has a lateral resistance of 4.45 kN (1000 lbs),
the JSI = 0.90.
G.4.1.5 Tooth Flattening
After pressing, teeth are considered flattened and ineffective if or greater of the tooth is visible
within the tooth slot. A tooth shall also be considered flattened if the surface of the wood has raised
(i.e., wood lifted up beyond its normal surface plane) within the tooth-slot opening of the metal
connector plate.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 72
Sketch Showing Flattened Teeth
Both teeth are considered ineffective within a tooth slot.
G.4.1.6 Tooth Embedment Gap
After pressing, all teeth of each connector plate shall be completely embedded in each wood
member. Teeth with an embedment gap of less than .8 mm (1/32) shall be considered effective.
Teeth with a gap equal to or greater than 1.6 mm (1/16) shall be considered ineffective. Teeth with
a gap between .8 mm (1/32) and 1.6 mm (1/16) shall be considered to be 60% effective.
Tooth Effectiveness Table Embedment Gap
Tooth Embedment Gap (G) Tooth Effectiveness
0 mm < G < .8 mm
(0 < G < 1/32)
100%
.8 mm G < 1.6 mm
(1/32 G < 1/16)
60%
G 1.6 mm
( G 1/16)
0%
of tooth length visible
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 73
G.4.2 Plate Placement Tolerances
a. Lumber on Edge
During the truss manufacturing process, plates shall be positioned according to the Truss Shop
Drawing and should be placed within the 6 mm () plate placement translation tolerance and within
the plus and minus five degree (5) plate rotation tolerance. In no case shall the positioning
decrease the number of effective teeth in any member to less than the minimum number required for
that member.
b. Lumber on Flat
During the truss manufacturing process, plates shall be positioned according to the Truss Shop
Drawing and should be placed within the 3 mm (1/8) plate placement translation tolerance. In no
case shall the positioning decrease the number of effective teeth in any member to less than the
minimum number required for that member. Due to relative ease of locating plates parallel to and
near the edge of lumber, no allowance for rotational misplacement is required.
G.4.2.1 Translation
a. Lumber on Edge
The truss designer shall use a minimum plate placement translation tolerance of 6 mm () parallel
and perpendicular to the plate axis. The designer shall select a plate size and placement for each
joint that resists the lateral forces in each member. The plate shall then be shifted by 6 mm () up,
down, left, right, up and to the left, up and to the right, down and to the left, and down and to the
right, and shall be checked to verify that a JSI of 0.90 is not exceeded in any member.
b. Lumber on Flat
The truss designer shall use a minimum plate placement translation tolerance of 3 mm (1/8) parallel
and perpendicular to the plate axis. The designer shall select a plate size and placement for each
joint that resists the lateral forces in each member. The plate shall then be shifted by 3 mm (1/8) up,
down, left, right, up and to the left, up and to the right, down and to the left, and down and to the
right, and shall be checked to verify that a JSI of 0.95 is not exceeded in any member.
G.4.2.2 Rotation
a. Lumber on Edge
The truss designer shall also use a minimum plate placement rotation tolerance of plus and minus
five degrees (5) about the centre of the connector plate. The designer shall select a plate size and
placement for each joint that resists the lateral forces in each member. The plate shall then be
rotated 5clockwise and checked to verify that a JSI of 0.90 is not exceeded in any member. The
plate shall then be rotated 5counterclockwise from its original position and checked to verify that a
JSI of 0.90 is not exceeded in any member. If the plate does not resist the force in any member, the
plate size is increased and checked again for the two rotated (+ 5and -5) positions.
b. Lumber on Flat
Due to relative ease of locating plates parallel to and near the edge of lumber, no allowance for
rotational misplacement is required.
Note: In both the shifting and rotational checks these misplacements are limited to the outer
boundaries of the truss. Translation and Rotation checks are done independent of each other.
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 74
G.4.2.3 Metal Effectiveness
The truss designer shall ensure the sum of the length or width of metal across each side of a joint
shall adequately resist the shear or tension forces at the joint. This check also applies to each
shifted location and rotated location using the appropriate shear and breaking values for these
locations and actual length or width of metal across the joint.
All supplemental blocking such as wedges and splice blocks must be installed as per the Truss
Shop Drawing.
G.5 TRUSS ASSEMBLY
G.5.1 Member to Member Gaps
Members at each joint should have wood to wood bearing at each interface. Gaps in joints after
pressing shall not exceed 1.6 mm (1/16 inch) for compression splices including pitch breaks and 3
mm (1/8 inch) for all other joints.
a)
b)
Gap between Top and Bottom Chords in heel
joints shall not exceed 3 mm (1/8)
Gap between Top Chords in a Peak joint shall
not exceed 1.6 mm (1/16)
Effective metal
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix G
June 2011 75
c)
d)
e)
G.5.2 Overall Truss Dimensions
The dimensions of a completed truss if different from those as specified on the Truss Shop Drawing
shall not exceed the differences shown in the following table:
Maximum Difference
Truss Dimensions between specified and
measured dimensions
Length 9144 mm (30 feet) 6 mm (1/4")
Length > 9144 mm (30 feet) 13 mm (1/2")
Overall Height 1200 mm (4 feet) 3 mm (1/8")
Overall Height > 1200 mm (4 feet) 6 mm (1/4")
Left Heel/Stub Height 3 mm (1/8")
Right Heel/Stub Height 3 mm (1/8")
Left Overhang 3 mm (1/8")
Right Overhang 3 mm (1/8")
Gaps in Compression Splices shall not exceed
1.6 mm (1/16)
Gaps in interior webs shall not exceed
3 mm (1/8)
Gaps in Tension Splices shall not exceed
3 mm (1/8)
TRUSS PLATE INSTITUTE OF CANADA (2011)
Appendix H
June 2011 76
H.1 MINIMUM INFORMATION ON TRUSS DESIGN DRAWING
Truss Design Drawings shall include, but not limited to, the information specified below:
1. Building code, CSA and TPIC Standard to which the drawing complies to.
2. Slope or depth, span and spacing.
3. Location of all joints and support locations.
4. Input and required bearing widths.
5. Software version number.
6. Specified loads, as applicable, shall include:
a. Top chord variable loads (including snow, live loads).
b. Top chord dead load.
c. Bottom chord live load due to limited accessibility.
d. Bottom chord dead load.
e. Wind loads
f. Other lateral loads, including drag strut loads.
g. Statement of whether special loading requirements have been checked including but not limited to
unbalanced loading, minimum concentrated loads, etc.
h. All additional loads and their points of application as applicable.
7. Adjustments to wood member and metal connector plate design value for conditions of use.
8. Adjustments made to material strength due to load sharing.
9. Connection requirements for truss ply to ply.
10. Maximum factored reaction force and direction, including maximum factored uplift reaction forces where
applicable.
11. Maximum CSI on top chord, bottom chord and webs.
12. Maximum un-factored reaction force and direction for each load type.
13. Metal connector plate type, manufacturer, size, and thickness or gauge, and the dimensioned location of
each metal connector plate except where symmetrically located relative to the joint interface.
14. Size, species and grade for each wood member.
15. Calculated maximum vertical and horizontal deflection for variable load and total load as applicable.
16. Maximum axial tension and compression forces in the Truss members.
17. Fabrication Tolerance used per Appendix G.
18. Required Permanent Individual Truss Member Restraint location shall be shown for lateral bracing.
Fastening of the lateral brace, T/I-brace, scab brace, L-brace shall be specified.
19. Drawing identification.
20. Design equation used for combined bending and compression member design.
21. Output error messages when design exceeds limits.