Power System Analysis
Power System Analysis
Homework 1
Reading: Chapters 1 and 2 of GS&O
Problem 1. With |V | = 100 V, the instantaneous power p(t) into a network N has a maximum value
1707 W and a minimum value of -293 W.
1. Find a possible series RL circuit equivalent to N.
Dene v(t) and i(t) of the network N as
v(t) =
2V cos(t +
V
),
i(t) =
2I cos(t +
I
).
Then, the instantaneous power into N is
p(t) = v(t)i(t) = 2V I cos(t +
V
) cos(t +
I
)
= V I [cos(
V
I
) + cos(2t +
V
+
I
)] .
The maximum value of p(t) occurs when cos(2t +
V
+
I
) = 1 and, similarly, the minimum value
of p(t) occurs when cos(2t +
V
+
I
) = 1. So we have the following 2 equations:
P
max
= V I cos(
V
I
) + V I = 1707 W
P
min
= V I cos(
V
I
) V I = 293 W
Subtracting one from the other, we get
2V I = 1707 + 293 = V I = 1000 W = I = 10 A,
and adding the two and substituting V I = 1000 in, we get
2V I cos(
V
I
) = 2000 cos(
V
I
) = 1414 =
V
I
= cos
1
1414
2000
= 45
.
An inductive load causes current to lag the voltage, so we get
V
I
= 45
.
Finally we obtain R = R(Z) = 7.07 and L = I(Z) = 7.07 = L = 0.0188 H.
2. Find S = P + jQ into N.
Using the voltage and current phasors from above, we get
S = V I
= (100
V
)(10
I
)
= (100
V
)(10(
I
)) = 1000(
V
I
) = 100045
.
So S = P + jQ, where P = R(S) = 707 W and Q = I(S) = 707 Var.
1
3. Find the maximum instantaneous power into L and compare with Q.
The instantaneous power into L is
p
L
(t) = v
L
(t)i(t) = L
di
dt
i(t) = L
2I sin(t +
I
)
2I cos(t +
I
)
= 2LI
2
sin(t +
I
) cos(t +
I
)
= LI
2
sin(2t + 2
I
).
The maximum value of p
L
(t) occurs when sin(2t + 2
I
) = 1, and at this point,
p
L,max
= LI
2
= 260(0.0188)(10
2
) = 707 W,
which is equal to Q.
Problem 2. A certain 1 load draws 5 MW at 0.7 power factor lagging. Determine the reactive power
required from a parallel capacitor to bring the power factor of the parallel combination up to 0.9.
With the current power factor of 0.7 lagging, we solve the following for the current Q:
tan(cos
1
(0.7)) =
Q
cur
P
=
Q
cur
5
= Q
cur
= 5.101 MVar
To reach a power factor of 0.9 lagging, we solve the following for the desired Q:
tan(cos
1
(0.9)) =
Q
des
P
=
Q
des
5
= Q
des
= 2.422 MVar
Therefore, the reactive power required from a parallel capacitor to bring the power factor to 0.9 is
Q
cap
= Q
cur
Q
des
= 5.101 2.422 = 2.679 MVar
Problem 3. A 3 load draws 200 kW at a PF of 0.707 lagging from a 440-V line. In parallel is a 3
capacitor bank that supplies 50 kVAr. Find the resultant power factor and current (magnitude) into the
parallel combination.
In each phase, the load draws 200/3 kW at a PF of 0.707 lagging. So we solve for the reactive power
that the load draws in each phase as follows:
tan(cos
1
(0.0707)) =
Q
load,1
P
load,1
=
Q
load,1
200/3
= Q
load,1
= 66.69 kVar.
With the capacitor bank in parallel, the combined reactive power drawn becomes
Q
combo,1
= Q
load,1
Q
cap,1
= 66.69 50/3 = 50.02 kVar.
So the power factor of the combination is
cos
tan
1
50.02
200/3
P
2
1
+ Q
2
combo,1
|V |
=
(200/3)
2
+ 50.02
2
440
= 189 A, per phase
Problem 4. A 1 load draws 10 kW from a 416-V line at a power factor of 0.9 lagging.
2
1. Find S = P + jQ.
At power factor 0.9 lagging, the complex power drawn is solved as
tan(cos
1
(0.9)) =
Q
P
=
Q
10
= Q = 4.84 kVar.
Then, S = 10 + j4.84 kVA.
2. Find |I|.
|I| =
|S|
|V |
=
10
2
+ 4.84
2
416
= 26.7 A
3. Assume that I = 0 and nd the instantaneous power p(t).
p(t) = v(t)i(t) =
2V cos(t +
V
)
2I cos(t)
= 2V I cos(t +
V
) cos(t)
= V I cos
V
+ V I cos(2t +
V
)
= P + V I [cos(2t) cos
V
sin(2t) sin
V
]
= P + V I cos
V
cos(2t) V I sin
V
sin(2t)
= P + P cos(2t) Qsin(2t)
= P(1 + cos(2t)) Qsin(2t)
= 10(1 + cos(2t)) 4.84 sin(2t) kW
Problem 5. A small manufacturing plant is located 2km down a transmission line, which has a series
reactance of 0.5 /km. The line resistance is negligible. The line voltage plant is 4800 V (rms), and
the plant consumes 120 kW at 0.85 power factor lagging. Determine the voltage and power factor at the
sending end of the transmission line by using:
1. A complex power approach.
The load draws 120 kW at 0.85 power factor lagging. We solve for the reactive power drawn by the
load as
tan(cos
1
(0.85)) =
Q
load
P
load
=
Q
l
oad
120
= Q
load
= 74.37 kVar.
Therefore, the complex power drawn by the load is S
load
= 120 + j74.37 kVA. We can now solve for
the current into the load as
I =
S
load
V
load
120 + j74.37
4800
= 294.1(31.79
) A.
The loss in the line can be computed as
S
line
= V
line
I
line
= Z
line
I
load
I
= j2(0.5)294.1
2
= j86.51 kVA.
Thus, the complex power supplied by the source is
S
source
= S
load
+ S
line
= 120 + j74.37 + j86.51 = 120 + j160.88 kVA = 200.753.28
kVA.
So the power factor at the sending end is cos(53.28
) = 0.598, lagging.
Finally, the voltage at the sending end is
V
source
=
S
source
I
=
200.753.28
294.131.79
= 682.421.5
V.
3
2. A circuit analysis approach.
Using KVL, we have
V
source
= Z
line
I + V
load
= j1(294.1(31.79
)) + 480 = 682.421.5
V.
And the power factor is cos(
V
I
) = cos(21.5
+31.79
) = 0.598, lagging.
4