Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Is 731 1971

Download as pdf or txt
Download as pdf or txt
You are on page 1of 41

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.
!"#$%&# '(%)
!"# $ %& #' (")* &" +#,-.
Satyanarayan Gangaram Pitroda
Invent a New India Using Knowledge
/0)"1 &2 324 #' 5 *)6
Jawaharlal Nehru
Step Out From the Old to the New
7"#1 &" 8+9&"), 7:1 &" 8+9&")
Mazdoor Kisan Shakti Sangathan
The Right to Information, The Right to Live
!"# %& ;<" =7"#" > 72 &(: ?0)"@" #AB 7" <&*" A*
Bhart+hariN,ti-atakam
Knowledge is such a treasure which cannot be stolen
IS 731 (1971): Porcelain insulators for overhead power
lines with a nominal voltage greater than 1000 V [ETD 6:
Electrical Insulators and Accessories]
IS : 731 - 1971
Indian Standard
SPECIFICATION FOR PROCELAIN
INSULATORS FOR OVERHEAD POWER
LINES WITH A NOMINAL VOLTAGE
GREATER THAN 1 000 V
(Second Revision)
Ninth Reprint JANUARY 2006
( Incorporating Amendments No. 1 to 4 and
Including Amendments No. 5 and 6 )
UDC 621.315.62 : 665.5
Copyright 1981
BUREAU OF INDIAN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
Gr 7 June 1972


AMENDMENT NO. 7 JULY 2008
TO
IS 731 : 1971 SPECIFICATION FOR PORCELAIN
INSULATORS FOR OVERHEAD POWER
LINES WITH A NOMINAL VOLTAGE
GREATER THAN 1 000 V
( Second Revision )
[Page 13, clause 10.1.1(j)] Substitute 'Mechanical Performance Test
(10.9.1) and Thermal Mechanical Performance Test (only on string insulator
units) (10.9.2)' for '24 hours mechanical strength test (for string insulators only
when specified by the purchaser) (10. 9)'.
(Page 19, clause 10.9) Substitute ' Mechanical Performance Test and
Thermal Mechanical Performance Test' for 'Twenty-four Hours Mechanical
Test (for String Insul ator Units only when Specified by Purc ha s er) ' .
(Page 19, clause 10.9.1) Substitute the following for the existing text:
10.9.1 Mechanical Performance Test
This test has an initial stage of mechanical loading and unloading, and a
concluding stage of testing the insulator units to failure. The concluding stage is
identical to an ordinary electromechanical or mechanical failing load test.
During the initial stage of the test, the insulator units shall be subjected to a
tensile load equal to 60 percent of the specified electromechanical or mechanical
failing load (whichever is applicable). Unless otherwise agreed, the tensile load
shall be applied and immediately removed four times in succession. On the same
day, after loading and unloading, the insulator units shall be subjected
individually to an electromechanical or mechanical failing load test.
The performance of the insulator units will be determined by a comparison of
the failing load values and the fracture pattern obtained during the
electromechanical and mechanical failing load test and the same test carried out
as the final stage of the mechanical performance test defined here.
1
Amend No. 7 to IS 731 : 1971
NOTES
1 The test may be more decisive if the 60 percent load is applied and removed more than four
times in succession.
2 The insulator units may be coupled together in series and/or in parallel when subjected to
the 60 percent load. When parallel coupled, the insulator units must be equally loaded.
3 The test may not give information on the internally stressed zone If the failure occurs in a
metal part such as the socket or clevis of a cap or an insulator pin. In such cases, this test is
not suitable for a sample test, but by agreement it may be used as a design test or special
qualification test. It is possible to investigate the fundamental insulator design by using metal
parts suitably strengthened so that failure occurs in the internally stressed zone of the
insulator.
Precautions should be taken so that strengthening the metal parts does not affect the
fundamental stress relation.
4 Voltage may be applied to the insulator units (Type B only) whenever it is desired in the
course of the test to detect mechanical failure of the insulating part (puncture).
(Page 19, clause 10.9.1, last line) Insert the following and renumber
10.9.2 as 10.9.3:
10.9.2 Thermal-Mechanical Performance Test
During the initial stage of the test, the insulator units shall be subjected to four
24-hours cycles of cooling and heating, and a tensile load equal to 60 percent of
the specified electro-mechanical or mechanical falling load. The tensile load
shall be applied to the insulator units at room temperature before starting the
first thermal cycle.
Unless otherwise agreed, each 24-hour cycle shall comprise a cooling to 30
5C and a heating to + 40 5C. The temperature figure refers to the
surrounding air. The temperature sequence shall be first cooling, then heating.
The test equipment shall be such as to permit the minimum and maximum
temperatures each to be kept during atleast four consecutive hours of the
temperature cycle.
The tensile load shall be completely removed and re-applied towards the end of
each heating period and then last one accepted.
On completion of the fourth 24-hour cycle and cooling to room temperature, the
tensile load shall be removed. On the same day, after this load removal, the
2

Amend No. 7 to IS 731 : 1971
insulator unit shall be subjected individually to an electromechanical or
mechanical falling load test.
The performance of the insulator units will be determined by a comparison of
the failing load values and the fracture pattern obtained during the
electromechanical and mechanical failing load test and the same test carried out
as the final stage of the mechanical performance test defined here.
Further the tolerances on the temperatures of the hot and cold cycles shall be
respected in such a way so as to ensure a minimum difference of 70 degrees
between the recorded hot and cold temperatures.
NOTES
1 This thermal-mechanical performance test has reference to the fundamental insulator design
in respect of the internal stresses, and should not be repeated on types which differ in outward
form only, that is, the disc of the insulating part or the coupling ends of the metal fittings
Changes in internal design or in manufacturing processes are reasons for re-testing. The test
may not give information on the internally stressed zone if the failure occurs in a metal part
such as the socket or clevis of a cap or an insulator pin. In such cases, it is possible to
investigate the fundamental insulator design by using metal parts suitably strengthened so that
failure occurs in the internally stressed zone of the insulator.
Precautions should be taken so that strengthening the metal parts does not affect the
fundamental stress relation.
2 The insulator units may be coupled together in series and/or in parallel when subjected to
the thermal cycles and the 60 percent load. When parallel coupled, the insulator units must be
equally loaded.
3 Loose coupling pins, for example, those used with insulators of the long rod type, should
not be included in the mechanical test since they are not part of the internal design of the
insulator.
4 Voltage may be applied to the insulator units (Type B only) whenever desired in the course
of the test, but without altering the test cycle, in order to detect mechanical failure of the
insulating part (puncture).'
(Page 21, clause 10.14.2) Substitute '50 percent of the specified electro-
mechanical failing load' for '40 percent of the specified electro-mechanical
failing load'.
(ET 06)
3
Reprography Unit, BIS, New Delhi, India

AMENDMENT NO. 5 JULY 1987
TO
IS : 731-1971 SPECIFICATION FOR PORCELAIN
INSULATORS FOR OVERHEAD POWER LINES
WITH A NOMINAL VOLTAGE
GREATER THAN 1 000 V
( Second Revision )
[ This amendment takes into account the sequence of carrying out
acceptance tests and introduction of double plan of sampling procedure. ]
[ Page 14, Clause 10.1.2.2 (see also Amendment No. 3)] Substitute
the following for the existing clause:
'10.1.2.2 The insulators selected in accordance with 10.1.2.1 shall
be divided approximately into three parts and subjected to the applicable
acceptance tests in the following order:
Part(s) of
Samples
First and
Second Parts
Third Part
Tests on String Insulator
Units
Type A
10.5, 10.6,
10.9 ( when
specified ),
10.8 and
10.11
10.5, 10.6
and 10.12
Type B
10.5, 10.6,
10.9 ( when
specified ),
10.7 or 10.8
( whichever
is applicable )
and 10.11
10.5, 10.6,
10.10 and
10.12
Tests on Rigid
Insulator
Type A
10.5, 10.6,
10.8 and
10.11
10.5, 10.6
and 10.12
Type B
10.5, 10.6,
10.8 and
10.11
10.5, 10.6,
10.10 and
10.12
( Page 29, Appendix C ) Substitute the following for the existing
appendix:
A P P E N D I X C
( Clauses 10.1.2.1 and 10.1.23 )
SAMPLING PROCEDURE FOR INSULATORS FOR
OVERHEAD POWER LINES
C-1. SCALE OF SAMPLING
C-1.1 Lot In a consignment, all the insulators of the same type and
design manufactured from the same material in the same factory under
similar conditions of production shall be grouped together to constitute
a lot.
1
T
A
B
L
E

5

S
A
M
P
L
E

S
I
Z
E

A
N
D

A
C
C
E
P
T
A
N
C
E

N
U
M
B
E
R

(

C
l
a
u
s
e
s

C
-
1
.
2
,

C
-
2
.
1
,

C
-
2
.
2

a
n
d

C
-
2
.
3

)

L
O
T

S
I
Z
E

F
O
R

D
I
M
E
N
S
I
O
N
S

A
N
D

T
E
M
P
E
R
A
T
U
R
E

C
Y
C
L
E

T
E
S
T

F
O
R

G
A
L
V
A
N
I
Z
I
N
G

A
N
D

P
U
N
C
T
U
R
E

T
E
S
T

F
O
R

M
E
C
H
A
N
I
C
A
L

E
L
E
C
T
R
O
-
M
E
C
H
A
N
I
C
A
L

A
N
D

P
O
R
O
S
I
T
Y

T
E
S
T

(
1
)

U
p

t
o

1
0
0
0

1

0
0
1

t
o

3

0
0
0

3

0
0
1

t
o

1
0

0
0
0

1
0

0
0
1

a
n
d

a
b
o
v
e

S
e
c
o
n
d

S
a
m
p
l
e

S
i
z
e

(
1
0
)

F
i
r
s
t

S
a
m
p
l
e

S
i
z
e

(
9
)

S
e
c
o
n
d

S
a
m
p
l
e

S
i
z
e

(
8
)

First
Sample
Size
(7)
S
e
c
o
n
d

R
e
j
e
c
t
i
o
n

N
u
m
b
e
r

(
r
2
)

(
6
)

F
i
r
s
t

R
e
j
e
c
t
i
o
n

N
u
m
b
e
r

(
5
)

A
c
c
e
p
-
t
a
n
c
e

N
u
m
b
e
r

(
a
)

(
4
)

S
e
c
o
n
d

S
a
m
p
l
e

S
i
z
e

(
i
t
)

(
3
)

F
i
r
s
t

S
a
m
p
l
e

S
i
z
e

(
2
)

3

3

5

5

2

2

0

8

8

5

5

8

8

2

2

0

1
3

1
3

7

1
2

7

1
2

1
3

2
0

1
3

2
0

2

4

2

3

0

1

2
0

3
2

2
0

3
2

2
C-1.2 The number of insulators to be selected from each lot shall depend
upon the size of the lot and shall be in accordance with col 1 and 2 of
Table 5 and procedure given in C-2.
C-1.2.1 These insulators shall be selected from the lot at random. In
order to ensure the randomness of selection, procedure given in
IS : 4905-1968 'Methods for random sampling' may be followed.
C-2. NUMBER OF TESTS AND CRITERIA FOR CONFORMITY
C-2.1 All the insulators selected at random according to col 1 and 2 of
Table 5 shall be subjected to dimensions and temperature cycle tests.
The insulators failing to satisfy either of the requirements shall be termed
as defectives. The lot shall be considered as conforming to these require-
ments if the number of defectives found in the sample is less than or
equal to corresponding acceptance number given in col 4 of Table 5.
The lot shall be rejected if the number of defectives in the same lot is
greater than or equal to the first rejection number (r
1
) given in col 5. If
the number of defectives is between the acceptance number and the first
rejection number, a second sample of the same size (see col 3 of Table 5)
shall be selected from the lot at random and subjected to these tests.
The number of defectives in the first sample and second sample shall
be combined. If the combined number of defectives is less than the
second rejection number(r
2
) given in col 6 of Table 5, the lot shall be
considered as conforming to these requirements. Otherwise the lot shall
be rejected without further testing.
C-2.2 The lot which has been found as conforming to the above require-
ments shall then be divided into two parts, as shown in col 7 and 9 of
Table 5. The number of insulators to be tested for mechanical, electro-
mechanical and porosity tests shall be in accordance with col 7 of
Table 5. The lot shall be considered as conforming to these requirements
if no defective is found in the sample and shall be rejected if there are
two or more defectives. If there is one defective, a second sample of
same size ( see col 8 of Table 5) shall be selected at random and sub-
jected to the tests. The lot shall be considered as conforming to these
requirements if no defective is found in the second sample; otherwise the
lot shall be rejected without further testing.
C-2.3 The lot which has been found as conforming to the requirements
of C-2.1 shall then be tested for galvanizing test and puncture test. For
this purpose, the sample size is given in col 9 of Table 5. The lot shall
be considered as conforming to these requirements if no defective is
found in the sample and shall be rejected if two or more defectives are
found in the sample. If there is one defective, a second sample of same
size ( see col 10 of Table 5 ) shall be selected at random and subected to
the tests. The lot shall be considered as conforming to these require-
ments if no defective is found in the second sample; otherwise the lot
shall be rejected without further testing.
C-2.4 The lot shall be considered as conforming to the requirements of
acceptance tests if conditions in C-2.1, C-2.2 and C-2.3 are satisfied.
( ETDC 3 )
3
Printed at New India Printing Press, Khurja, India

AMENDMENT NO. 6 JANUARY 1993
TO
IS 731 : 1971 SPECIFICATION FOR PORCELAIN
INSULATORS FOR OVERHEAD POWER LINES WITH
A NOMINAL VOLTAGE GREATER THAN 1 000 V
( Second Revision )
( Page 22, clause 10.15.5 ) Add the following sentence to the clause:
'Streamer pattern formed during routine electrical tests may be observable, but it
shall not disqualify the insulator for acceptance.'
( Page 29, Table 5 ) Add the following note to the table:
"NOTE Sample size for Type A insulators can be as per Table 3 of IS 2544 : 1973*."
( Page 29, foot-note ) Add the following foot-note:
"*Porcelain post insulators for systems with nominal voltage greater than 1 000 V (first revision)."
(ET 06)
Printed at New India Printing Press, Khurja, India

IS : 731 - 1971
Indian Standard
SPECIFICATION FOR PORCELAIN
INSULATORS FOR OVERHEAD POWER
LINES WITH A NOMINAL VOLTAGE
GREATER THAN 1 000 V
( Second Revision )
Electrical Insulators and Accessories Sectional Committee, ETDC 3
Chairman Representing
SHRI L. C.JAIN Central Water & Power Commission ( Power
Wing )
Members
DEPUTY DIRECTOR ( TRANSMISSION )
( Alternate to Shri L. C. Jain )
ADDITIONAL CHIEF ENGI NEER, Directorate General of Posts & Telegraphs
POSTS & TELEGRAPHS, JABALPUR ( Department of Communications ) , New
Delhi
DIRECTOR OF TELEGRAPHS ( L )
( Alternate )
DIVISIONAL ENGI NEER, TE L E -
G RAPH S ( C ) ( Alternate )
SHRI V. R. ANANTHANARAYANAN Bengal Potteries Limited, Calcutta
SHRI CHANDAR PARKASH ( Alternate )
SHRI MR ARUMUGAM Tamil Nadu Electricity Board, Madras
SHRI E. S. NARAYANAN ( Alternate )
DR A. S. BHADURI National Test House, Calcutta
SHRI S. K. MUKHERJEE ( Alternate )
SHRI D. S. CHABHL Directorate General of Technical Development,
New Delhi
SHRI B . C. DAW All India Pottery Manufacturers' Association.
Calcutta
SHRI B. C. BANERJEE ( Alternate )
SHRI A. N. DB B Damodar Valley Corporation, Calcutta
SHRI A. C. Boss ( Alternate )
DIRECTOR RESEARCH Maharashtra S u t e Electricity Board, Bombay
DIRECTOR (TRACTION AND Research, Designs & Standards Organisation
INSTALLATION ) ( Ministry of Railways ), Lucknow
DEPUTY DIRECTOR STANDARDS
( Alternate )
(Continued on page 2)
BUREAU OF I NDI AN STANDARDS
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
IS : 731 - 1971
(Continued from pagt 1)
Members Representing
SHRI R. K. DUTTA Bengal Porcelain Co Pvt Ltd, Calcutta
SHRI H. M. S. LINGAIAH Mysore State Electricity Board, Bangalore
SHRI A. S. NAGARKATI Inspection Wing, Directorate General of Supplies
& Disposals
SHRI G. R. BHATIA ( Alternate )
SHRI D. V. NARKE Heavy Electricals ( India ) Ltd, Bhopal
SHRI O. P. GUPTA ( Alternate )
SHRI K. B. PATWARDHAN Seshasayee Industries Ltd, South Arcot Dist
SHRI L. VENKATASUBBU ( Alternate )
SHRI P. S. RAMAN New Government Electric Factory, Bangalore
SHRI E. P. WLLFRED ( Alternate )
SHRI A. SAMBAMOORTHY Mysore Porcelains Ltd, Bangalore
SHRI K. N. JAYARAM ( Alternate )
SHRI P. S. SATNAM Punjab State Electricity Board, Patiala
SHRI M. S. SANDHU ( Alternate )
SHRI N. S. SETHURAMON W. S. Insulators of India Ltd, Madras
SHRI V. SRINIVASAN ( Alternate )
DR U. S. Singh High Tension Insulator Factory, Ranchi
SHRI A. D. DUA ( Alternate )
SHRI H. R. VARMA Indian Electrical Manufacturers' Association,
Calcutta
SHRI K. N. JAYARAM ( Al ternate )
SHRI Y. S. VENKATESWARAN, Director General, BIS ( Ex-officio Member )
Director ( Elec tech )
Secretary
SHRI R . C . J AI N
Assistant Director ( Elec tech ), BIS
2
IS : 731 - 1971
Indian Standard
SPECIFICATION FOR PORCELAIN
INSULATORS FOR OVERHEAD POWER
LINES WITH A NOMINAL VOLTAGE
GREATER THAN 1 000 V
( Second Revision )
0. F OREWORD
0.1 This Indian Standard ( Second Revision ) was adopted by the Indian
Standards Institution on 18 November 1971, after the draft finalized by the
Electrical Insulators and Accessories Sectional Committee had been
approved by the Electrotechnical Division Council.
0.2 This standard has been prepared to achieve the following objects:
a) To define the terms used;
b) To define insulator characteristics and to prescribe the conditions
' under which the specified values of these characteristics shall be
verified;
c) To prescribe test methods; and
d) To prescribe acceptance criteria.
0.3 This standard was originally issued as a tentative specification for
porcelain insulators in 1956. It was first revised in 1963 to make it more
comprehensive and up to date. This second revision has been under-
taken with a view to rationalizing the classification of tests. In this
revision, which includes all the amendments issued to date to the that
revision, the classification of the insulators according to their construc
tion has been incorporated and the requirements and methods of tests
have been modified to keep the standard in line with the latest develop-
ments taking place in insulator technology.
0.4 The fittings normally used with overhead porcelain insulators are
covered in IS : 2486 ( Part I )-1971* and IS:2486 ( Part II)-l 963.
*Specification for insulator fittings for overhead power lines of 3.3 kV and above
Part I General requirements and tests (first revision).
Specification for insulator fittings for overhead power lines of 3.3 kV and above
Part II Dimensional requirements.
3
IS : 731 - 1971
0.5 In the preparation of this standard, assistance has been derived from
the following publications:
IEC Pub 274 Tests on insulators of ceramic material or glass for
overhead lines with a nominal voltage greater than 1 000 V.
International Electrotechnical Commission.
BS 137 : Part I : 1970 Insulator of ceramic material or glass for
overhead lines with a nominal voltage greater than 1 000 V. Part I
Test. British Standards Institution.
Draft BS 137 : Part II : 1970 Insulators of ceramic material or glass
for overhead lines with a nominal voltage greater than 1 000 V.
Part II Requirements. British Standards Institution.
0.6 For the purpose of deciding whether a particular requirement of this
standard is complied with, the final value, observed or calculated,
expressing the result of a test, shall be rounded off in accordance with
IS : 2-1960*. The number of significant places retained in the rounded
off value should be the same as that of the specified value in this standard.
1. SCOPE
1.1 This standard applies to the porcelain insulators for ac overhead
power lines suitable for nominal system voltage greater than 1 000 volts
and a frequency not greater than 100 Hz.
NOTE 1 The specification applies to string insulator units, to insulator strings
consisting of one-string insulator unit or an assembly of such units, and to rigid over
head line insulators. The specification applies to insulators of the same type when
used in sub-stations. It does not apply to insulators forming part of electrical
apparatus or to parts used in their contruction.
NOTE 2 This specification applies to insulators for use on ac overhead lines
and may be regarded as a provisional specification for insulators for use on dc over-
head lines.
2. TERMINOLOGY
2.0 For the purpose of this standard, the following definitions shall apply.
2.1 Stri ng Insul ator Uni t An insulator consisting of a porcelain part
with the necessary interconnecting metal-work to enable it to be flexibly
attached to other string insulator units. Unless otherwise stated, for string
insulator unit with ball and socket couplings the term includes the locking
device (security clip) and for units with clevis and tonque coupling it
includes the pin and other parts necessary for coupling.
*Rules for rounding off numerical values ( revised ).
4
IS : 731 - 1971
2.2 Insul ator Stri ng One or more string insulator units intended to
give flexible support to an overhead line. The insulator string is
intended to be stressed only in tension.
2.2.1 Suspension Insulator Set One insulator string or two or more strings
suitably connected together, complete with fittings for flexible attachment
to a supporting structure and to carry a line conductor or conductors at
its lower end. The term 'set' includes all other metal parts and
accessories as required in service.
2.2.2 Tension Insulator Set One insulator string, or two or more strings
suitably connected together, complete with fittings for flexible attachment
to a supporting structure and to secure a line conductor or conductors in
tension. The term 'set' includes all other metal parts and accessories as
required in service.
2.3 Ri gi d Insul ator An insulator intended to give rigid support to an
overhead line and to be stressed mainly by bending and compressive
loads.
2.3.1 Pin Insulator A rigid insulator consisting of a single piece of
porcelain or of two or more porcelain components permanently connected
together, and intended to be mounted rigidly on a supporting structure
by an insulator pin passing up inside the insulator. Unless otherwise
stated, this term excludes the insulator pin.
2.3.2 Line Post Insulator A rigid insulator consisting of a porcelain
part permanently secured in a metal base and intended to be mounted
rigidly on a supporting structure by means of a stud attached to the base.
Unless otherwise Stated, this term includes the stud.
2.4 Shell A single insulating member without cement or other
connecting devices.
2.5 Lot All the insulators of the same type and design manufactured
under similar conditions of production, offered for acceptance; a lot may
consist of the whole or part of the quantity ordered.
2.6 Fl a shover A disruptive discharge external to the insulator, con-
necting those parts which normally have the operating voltages between
them.
2.7 Puncture A disruptive discharge passing through the solid
insulating parts of an insulator
NOTE A fragment breaking away from the rim of a ahed or damage to the
insulator due to the heat of a surface discharge is not considered a puncture.
2.8 Dry Impul se Wi thstand Vol tage The specified impulse voltage
which the insulator shall withstand, under the conditions specified in 10.3
without flashover or puncture.
5

IS : 731 - 1971
2.9 Fi fty-Percent Dry Impul se Fl ashover Vol tage The impulse
voltage which, under the conditions prescribed in 10.3 has a 50 percent
probability of producing a flashover on the insulator.
2.10 Wet Power-Frequency Wi thstand Vol tage The specified
power-frequency voltage which the insulator shall withstand ( wet ) under
the conditions prescribed in 10.4 for the specified time (one minute)
without flashover or puncture.
2.11 Wet Power-Frequency Fl ashover Vol tage The arithmetic
mean value of the measured power-frequency voltages which cause
flashover of the insulator under the conditions prescribed in 10.4.
2.12 El ectromechani cal Fai l i ng Load The maximum load which
can be reached when a string insulator unit is tested under the conditions
prescribed in 10.7.
2.13 Mechani cal Fai l i ng Load The maximum load which can be
reached when a string insulator unit or a rigid insulator is tested under
the conditions prescribed in 10.8.
2.14 Puncture Vol tage ( of a Stri ng Insul ator Uni t or a Ri gi d
Insul ator ) The voltage which, under the conditions prescribed
in 10.10, causes puncture.
2.15 Creepage Di stance ( of an Insul ator ) The shortest distance
or the sum of the shortest distances along the contours of the external
surfaces of the porcelain insulating parts of the insulator between those
parts which normally have the operating voltage between them. A distance
over a cement surface shall not be considered as forming part of the
creepage distance. If high-resistance coatings are applied to parts of the
insulator, such coatings shall be considered effective creepage surfaces and
the distance over them is included in the creepage distance ( see Fig. 1 ).
NOTE 1 The surface resistivity of such high-resistance coatings is usually about
10
3
ohms, but may bo as low as 10
4
ohms.
NOTE 2 If high-resistance coatings are applied to the whole surface of the
insulator ( the so-called stabilized insulator ), the questions of surface resistivity and
creepage distance should be subject to agreement between the user and the
manufacturer.
2.15.1 Protected Creepage Distance That part of the creepage distance
on the illuminated side of the insulator which would lie in shadow if light
were projected on to the insulator in a direction at 90 to the longitudinal
axis of the insulator ( see Fig. 1 ).
2.16 Hi ghest Vol tage of a Sy stem The highest rms line-to-line
voltage which can be sustained under normal operating conditions at any
time and at any point on the system. It excludes temporary voltage varia-
tions due to fault conditions and the sudden disconnection of large loads.
6
IS : 731 - 1971
N
O
T
E


T
h
e
s
e

s
t
r
u
c
h
e
r

a
r
e

o
n
l
y

i
l
l
u
s
t
r
a
t
i
o
n
s

f
o
r

t
o
t
a
l

c
r
e
e
p
a
g
e

a
n
d

p
r
o
t
e
c
t
e
d

c
r
e
e
p
a
g
e

d
i
s
t
a
n
c
e
s

a
n
d

t
h
e

s
a
m
e

s
h
o
u
l
d

n
o
t

b
e

m
i
s
t
a
k
e
n

f
o
r

s
t
a
n
d
a
r
d

c
o
n
f
i
g
u
r
a
t
i
o
n
.

F
I
G
.

1

I
N
S
U
L
A
T
O
R

C
R
E
E
P
A
G
E

D
I
S
T
A
N
C
E
S

(
C
R
E
E
P
A
Q
E

D
I
S
T
A
N
C
E

S
H
O
W
N

D
O
T
T
E
D

)

7
IS : 731 - 1971
2.17 Fa ctor of Ea rth i ng The factor of earthing at a selected location
of a three-phase system ( general l y the point of installation of an equip-
ment ) , for a given system layout, is the ratio, expressed as a percentage,
of the highest rms line-to-earth power-frequency voltage on a sound phase
at the selected location during a fault to earth ( affecting one or more
phases at any point ), to the line-to-line rms power-frequency voltage which
would be obtained at the selected location with the fault removed.
NOTE 1 This factor is a pure numerical ratio and characterizes in general terms
the earthing conditions of a system as viewed from the selected location, independently
of the actual operating values of the voltage at that location.
NOTE 2 The factors of earthing are calculated from the phase-sequence
impedance components of the system as viewed from the selected location, using for
the rotating machines the subtransient reactances. The practical rule given in the
Note under 2.18 1 results from such a calculation.
NOTE 3 This factor is used for the choice of the insulation level of the equip-
ment to be installed at a selected location, particularly in the case of systems in which
the highest voltage for equipment is 100 kV or more.
2.18 Ea rth ed Neutra l Sy st em A system in which the neutral is
connected to earth, either solidly, or through a resistance or reactance of
low enough value to reduce materially transient oscillations and to give a
current sufficient for selective earth fault protection.
2.18.1 A three-phase system with effectively earthed neutral at a given
location is a system characteriz ed by a factor of earthing at this point
which does not exceed 80 percent.
NOTE This condition is obtained approximately when, for all system configura-
tions, the ratio of zero-sequence reactance to the positive-sequence reactance is less
than three and the ratio of zero-sequence resistance to positive-sequence reactance is
less than one.
2.19 Ty p e Test s Tests carried out to prove conformity with the
specification. These are intended to prove the general qualities and
design of a given type of insul ator.
2.20 Accep ta nce Test s Tests carried out on samples tak en from the
lot for the purpose of acceptance of the lot.
2.21 Routi ne Test s Tests carried out on each insul ator to check
requirements which are likely to vary during production.
3. REFERENCE ATMOSPHERIC CONDITIONS
3.1 Reference atmospheric conditions at which insulator characteristics
shall be expressed for the purpose of comparison shall be as given below:
Ambient temperature 20C
Barometric pressure 1 013 mil l ibars
8
IS : 731 - 1971
Absolute humidity 11 g of water per cubic metre corres-
ponding to 63 percent relative humi-
dity at 20C.
NOTE 1 A pressure of 1 013 m bar is equivalent to a pressure of 760 mm of
mercury at 0C. If the height of the barometer is h mm Hg and the temperature of
the mercury if tC, the atmospheric pressure in millibars is:
NOTE 2 The Indian Standard reference temperature of 27C and corresponding
humidity have not been specified because of the non-availability of the test voltage
values and correction factors for these conditions. These conditions will replace those
specified above when the corresponding test voltage values and correction factors are
available.
3.2 Tests for the purpose of this standard shall preferably be carried out
under conditions of temperature and humidity specified in IS : 196-1966*
( that is, a temperature of 27 2C and relative humidity of 65 2 per-
cent ), and at the prevailing atmospheric pressure. When this is not
possible, test may be carried out under conditions natural l y obtaining at
the time of the test. The barometric pressure, air temperature and
humidity shall be recorded for the purpose of corrections. Corrections of
test voltages for atmospheric conditions is given in Appendix A.
4. GENERAL REQUIREMENTS
4.1 The porcelain shall be sound, free from defects, thoroughly vitrified
and smoothly glazed.
4.2 Unless otherwise specified, the glaze shall be brown in colour. The
glaze shall cover all the porcelain parts of the insulator except those areas
which serve as supports during firing or are left unglazed for the purpose
of assembly.
4.3 The design of the insulator shall be such that stresses due to expansion
and contraction in any part of the insulator shall not lead to deterioration.
The porcelain shall not engage directly with hard metal .
4.4 Cement used in the construction of the insulator shall not cause
fracture by expansion or loosening by contraction, and proper care shall
be taken to locate the individual parts correctly during cementing. The
cement shall not give rise to chemical reaction with metal fittings, and its
thickness shall be as uniform as possible.
5. CLASSIFICATION
5.1 Overhead line insulators are divided into two types according to their
construction:
Type A An insul ator or an insulator unit in which the length of
the shortest puncture pa t h through solid insulating material is at least
*Atmospheric conditions for testing.
9
IS : 731 - 1971
equal to half the length of the shortest flashover path through air outside
the insulator.
Type B - An insulator or an insulator unit in which the length of the
shortest puncture path through solid insulating material is less than half
the length of the shortest flashover path through air outside the insulator.
NOTE Type A insulator are of solid core type.
6. BASIC INSULATION LEVELS
6.1 The basic insulation levels of the insulators shall be as given in
Tabl e 1A and Tabl e 1B.
6.2 In this standard, power-frequency voltages are expressed as peak
values divided by and impulse voltages are expressed as peak values.
6.3 The withstand and flashover voltages are referred to the reference
atmospheric conditions.
7. MECHANICAL LOADS
7.1 The insulators shall be suitable for the minimum failing loads specified
in Tabl e 2. The loads shall be transverse in the case of pin and line post
insulators and axial in the case of string insulator units.
8. MARKING
8.1 Each insulator shall be legibly and indelibly marked to show the
following:
a) Name or trade-mark of the manufacturer,
b) Month and year of manufacture,
c) Minimum failing load in newtons, and
d) Country of manufacture.
8.1.1 Mark ings on porcelain shall be printed and shall be applied before
firing.
8.2 Insul ators may also be mark ed with the I SI Certification Mark .
NOTE The use of the Standard Mark is governed by the provisions of the
Bureau of Indian Standards Act, 1986 and the Rules and Regulations made there-
under. The Standard Mark on products covered by an Indian Standard conveys
the assurance that they have been produced to comply with the requirements of that
standard under a well defined system of inspection, testing and quality control
which is devised and supervised by BIS and operated by the producer. Standard
marked products are also continuously checked by BIS for conformity to that
standard as a further safeguard. Details of conditions under which a licence for
the use of the Standard Mark may be granted to manufacturers or producers may
be obtained from the Bureau of Indian Standards.
10

IS : 731 - 1971
TABLE 1A TEST VOLTAGES FOR ALL INSULATORS UP TO AND
INCLUDING 72.5 kV RATED VOLTAGE AND FOR INSULATORS
FOR NON-EFFECTIVELY EARTHED SYSTEMS ABOVE 72.5 kV
( Clauses 6.1 and 10.2 )
H I G H E S T
SYSTEM
VOLTAGE
(1)
k V ( rms )
3.6
7.2
12
24
36
72. 5
*123
145
245
VI SI BLE
DISCHARGE
TEST
(2)
kV ( rms )
3
5. 5
9
18
27
53
88
105
154
WET POWER-
FREQUENCY
WITHSTAND
TEST
(3)
kV ( rms )
21
27
35
55
75
140
230
275
460
Pin or Li ne
Pott
Insulators
(4)
k V ( rms )
78
90
105
140
180
310



POWER-FREQUENCY PUNCTURE
WITHSTAND TEST
String
Insulator
Uni ts
(5)
k V ( rms )
1.3 times the
a c tua l dry
flashover
vol tage of
the unit
IMPULSE
VOLTAGE
WITHSTAND
TEST
(6)
kV ( peak )
45
60
75
125
170
325
550
650
1 050
*Even though the highest system vol tage of 123 kV is not a standard val ue in
IS : 585-1962 ' Vol tages and frequency for ac transmission and distribution systems' , a
nu mber of ol der power systems a re retaining the nominal system vol tage of 110 k V
which corresponds to the highest system vol tage of 123 k V. The test vol tages for this
highest system vol tage a re, therefore, given for the benefit of such power systems.
TABLE 1B TEST VOLTAGES FOR INSULATORS FOR USE ON
EFFECTIVELY EARTHED SYSTEMS ABOVE 72.5 kV
( Clauses 6.1 and 10.2 )
HIGHEST VISIBLE WET POWER- POWER-FREQUENCY IMPULSE
SYSTEM DISCHARGE FREQUENCY PUNCTURE WITHSTAND VOLTAGE
VOLTAGE TEST WITHSTAND TEST ON STRING WITHSTAND
TEST INSULATOR UNI TS TEST
(1) (2) (3) (4) (5)
kV ( rms ) kV ( rms ) kV ( rms ) kV ( rms ) kV ( peak )
*123 88 185 1.3 times the actual 450
145 105 230 dry flashover 550
243 154 395 vol tage of the unit 900
420 266 680 1 550
*Even though the highest system vol tage of 123 kV is not a s tandard val ue in IS : 586-
1962 ' Vol ta ges and frequency for ac transmission a nd dis tribution s ys tems ' , a nu mber of
ol der power systems a rc retaining the nominal system vol tage of 110 k V which corres-
ponds to t he highest system vol tage of 123 k V. The test vol tages for this highest system
vol tage a re, therefore, given for benefit of such power systems.
11
IS : 731 - 1971
TABLE 2 MINIMUM FAILING LOADS
(Clause 7.1)
PI N INSULATOR
(1)
kN
5
10




Failing
Load
(3)
kN
45
70
90
120
160
190
Recommended
Pin Ball Shank
Diameter
(4)
mm
11 or 16
16
16
16 or 20
20
24
STRING INSULATOR UNITS
NOTE 1 In the case of Type B string insulator units, the electromechanical
failing load shall be the minimum failing load given above.
NOTE 2 1 N = 0.101 972 kgf.
HIGHEST
SYSTEM
VOLTAGE
(1)
k V
3.6
7.2
12
24
36
72
123
145
245
420
TABLE 3 MINIMUM CREEPAGE DISTANCES
MODERATELY
POLLUTED
ATMOSPHERES
TOTAL
(2)
mm
75
130
230
430
580
1 100
1 850
2 250
3 800
6 480
Total
(3)
mm
130
230
320
560
840
1 700
2 800
3 400
5 600
9 660
Protected
(4)
mm
420
850
1 400
1 700
2 800
4 830
HEAVILY POLLUTED ATMOSPHERES
NOTE For insulator used in an approximately vertical position the values given
in col 2 or 3 and 4 shall apply. For insulators used in an approximately horizontal
position, the values given in col 2 shall apply, but the values in col 3 and 4 may be
reduced by as much as 20 percent.
12
LIKE POST
INSULATORS
(2)
kN
10





9. CREEPAGE DISTANCES
9.1 For moderatel y polluted atmospheres, the minimum creepage
distances shall be those given in Tabl e 3. Recommended minimum
creepage distance for insulators to be used with their axis approximatel y
vertical in heavily polluted atmospheres are given in col 3 and 4 of Tabl e 3;
protected creepage distances ( see also Fig. 1 ) being given for insulators of
highest systems voltage of 36 kV and above under those conditions.
No minimum creepage distances are specified for clean atmospheric
conditions.

IS : 731 - 1971
10. TESTS
10.1 Genera l
10.1.1 Type Test The following tests shall constitute the type tests:
a) Visual examination (10.13)
b) Verification of dimensions (10.5)
c) Visible discharge test (10.2)
d) Impulse voltage withstand test (10.3)
e) Wet power-frequency voltage withstand test (10.4)
f) Temperature cycle test (10.6)
g) Electro-mechanical failing load test ( for string insulator units,
Type B only ) (10.7)
h) Mechanical failing load test ( for string insulator units of Type A
and those of Type B to which electromechanical failing load test
(10.7) is not applicable and for rigid insulators only ) (10.8)
j) 24 hours mechanical strength test (for string insulators only when
specified by the purc ha s er) (10.9)
k) Puncture test ( for insulators, Type B only ) (10.10)
m) Porosity test (10.11)
n) Galvanizing test (10.12)
NOTE 1 A radio interference test is under consideration.
NOTE 2 Type tests are normally made once and unless otherwise agred to, test
certificate giving the results of type tests, made on not less than two insulators identical
in all essential details with those to be supplied, are regarded as evidence of
compliance. The tests should be carried out on two samples in the order mentioned
below:
a) Tests on boh insulators:
i) Visual examination (10.13)
ii) Verification of dimensions (10.5)
iii) Visible discharge test (10.2)
iv) Impulse voltage withstand test (10.3)
v) Wet power frequency withstand test (10.4)
vi) Temperature cycle test (10.6)
b) Tests on first insulator:
i) Twenty-four hour mechanical strength test ( for string insulators only
when specified by the purchaser ) (10.9)
ii) Electromechanical failing load test ( for string insulator units Type B
only ) (10.7)
iii) Mechanical failing load test ( for string insulator units Type A and for
rigid insulators only ) (10.8)
iv) Porosity test (10.11).
13
IS : 731 - 1971
c) Tests on second insulator :
i) Puncture test ( for insulator units, Type B only ) (10.10)
ii) Galvaninizing test (10.12).
NOTE 3 Type test shall be made and certified by the manufacturer or by an
agreed independent authority.
10.1.2 Acceptance Tests The test samples shall be subjected to the
following acceptance tests in the order indicated below:
a) Verification of dimensions (10.5)
b) Temperature cycle test (10.6)
c) Twenty four hours mechanical strength test ( for string insulator
units only when specified by the purchaser ) (10.9)
d) Electro-mechanical failing load test ( for string insulator units
Type B only ) (10.7)
e) Mechanical failing load test ( for string insulator units Type A
and for rigid insulators only ) (10.8)
f) Puncture test ( for string insulator units, Type B only ) (10.10)
g) Porosity test (10.11)
h) Galvanizing test (10.12).
10.1.2.1 For carrying out acceptance tests specified in this standard
the sampling procedure given in Appendix C shall be followed.
10.1.2.2 The insulators selected in accordance with 10.1.2.1 shall be
divided approximatel y into three parts and subjected to the applicable
tests in the following order:
First and Second Part
Third Part
10.1.2.3 The criterion of conformity to the requirements of the
acceptance tests shall be as given in Appendix C.
14
Type A
10.5, 10.6,
10.8, 10.11
and 10.9
( when spe-
cified )
10.5, 10.6
and 10.12
Type B
10.5, 10.6,
10.7 or 10.8
( whichever
is appl ica-
ble ) , 10.9
( when spe-
cified ) and
10.11
10.5, 10.6,
10.10 and
10.12
Type A
10.5, 10.6,
10.11
10.5, 10.6
and 10.12
Type B
10.5 10.6,
10.8 and
10.11
10.5, 10.6,
10.10 and
10.12
Part(s) of Samples Tests on String Insulator
Units
Tests on Rigid
Insulator

IS : 731 - 1971
10.1.3 Routine Tests The following tests shall be carried out as routine
tests:
a) Visual examination ( 10.13 ),
b) Mechanical routine test ( for string insulator units only ) ( 10.14) ,
c) Electrical routine test ( for Type B string insulators and rigid
insulators ( 10.15 ).
NOTE Attention is drawn to the fact that ultrasonic tests may be used on
Type A insulator to detect internal flaws and cracks. Experience is necessary to
interpret results of ultrasonic tests and, therefore, precis forms of tests cannot yet
be adopted as standard.
10.2 Vi si bl e Di sch a rg e Test - The test room shall be darkened and a
period of five minutes shall be allowed for the observer to become accus-
tomed to darkness. A power-frequency test voltage of the specified value
given in Tabl e 1A or Tabl e 1B shall be applied in accordance with
Appendix B and maintained at this value for five minutes. During this
time, observations shall be made and there shall be no sign of visible
corona.
10.3 Imp ul se Vol ta g e Wi th sta nd Test
10.3.1 The insulator shall be tested dry under the conditions prescribed
in Appendix B.
10.3.2 The impulse generator shall be adjusted to produce a standard
1.2/50 impulse wave of peak value equal to the specified value of the
impulse withstand voltage corrected for atmospheric conditions in
accordance with Appendix A.
10.3.3 Five such impulse voltage waves shall be applied to the insula-
tor. If there is no flashover or puncture, the insulator shall be considered
to have passed the test. If during the application of these five waves
puncture occurs or if there is more than one flashover, the insulator shall
be considered to have failed to comply with the standard. If only one
flashover occurs, a new series of ten impulse waves shall be applied.
The insulator shall be considered to have passed this test only if during
this new series of tests there is no flashover or puncture.
10.3.4 The insulator shall be capable of passing the impulse voltage
withstand' test with voltages of both positive and negative polarity.
However, when it is evident which polarity will give the lower breakdown
voltage, it shall suffice to test with that polarity.
10.3.5 To provide information when specially requested, the 50 percent
impulse flashover voltage for positive and negative polarities may be
determined by a suitable procedure [ see IS : 2071 ( Part II )-l974* ].
*Methods of high voltage testing: Part II Test procedures (first revision).
15
IS : 731 - 1971
10.3.5.1 The impulse flashover voltages to be recorded shall be the
positive and negative 50 percent impulse flashover voltage as measured
above and corrected in accordance with Appendix A.
10.3.5.2 The insulator shall not be damaged by these tests, but slight
marks on the surface of the insulating parts or chipping of the cement or
other material used for assembly shall be permitted.
10.4 Wet Power-Frequency Voltage Wi thstand Test
10.4.1 The insulator shall be arranged as prescribed in Appendix B.
10.4.2 Before the commencement of the test, the insulator shall be
exposed to the artificial rain produced in accordance with 3.3 of IS : 2071
( Part I )-1974* for at least one minute before application of voltage and
then throughout the test.
10.4.3 The test voltage to be applied to the insulator shall be the
specified value of the wet power-frequency withstand voltage adjusted for
atmospheric conditions at the time of test (see Appendix A) .
10.4.4 A voltage of about 75 percent of the test voltage as determined
in 10.4.3 shall be applied and then increased gradually to reach the test
voltage in a time not less than five seconds. The test voltage shall be
maintained at this value for one minute [ see IS : 2071 ( Part II )-1974 ].
The insulator shall not flashover or puncture during the application
of the test voltage.
10.4.5 To provide information when specially requested, the wet
flashover voltage of the insulator may be determined by increasing the
voltage gradually from about 75 percent of the wet withstand voltage to
reach the flashover voltage in not less than five seconds. The flashover
voltage shall be the arithmetic mean of five consecutive readings and the
value after correction to standard atmospheric conditions ( see Appendix
A ) shall be recorded.
10.5 Verification of Di mensi ons It shall be verified that the
insulator unit is in accordance with the relevant drawings, particularly as
regards any dimensions to which special tolerances apply ( for example,
spacing ) and details affecting interchangeability ( for example, ball and
socket dimensions ).
Unless otherwise specified, a tolerance of:
( 0.04 d + 1.5 ) mm when d 300 mm
( 003 d + 6 ) mm when d > 300 mm
*Methods of high voltage testing: Part I General definitions and test requirements
(first revision).
Methods of high voltage testing: Part II Test procedures (fist revision).
16
IS : 731 - 1971
is allowed on all dimensions for which special tolerances do not apply ( d
being the dimension in millimetres ).
NOTE Pending the publication of Indian Standard covering the spacing of
string insulator units, the tolerance formula:
( 0.03 S + 0.3 ) mm
shall, unless otherwise specified, be applied to the spacing, where S is the spacing in
millimetres.
10.6 Temp era ture Cy cl e Test Insulators with their integral parts,
if any, shall be quickly and completely immersed, without being placed in
an intermediate container, in a water ba th maintained at a temperature
of 70C higher than that of the cold bath used in the rest of the test and
left submerged for 15 minutes. They shall then be withdrawn and
quickly and completely immersed, without being placed in an intermediate
container, in the cold water bath where they shall remain for 15 minutes.
This heating and cooling cycle shall be performed three times in succession.
The time taken to transfer from either bath to the other shall be as short
as possible and never exceed 30 seconds.
The quantity of water in the test tanks shall be sufficiently large
for the immersion of the insulators so as not to cause a temperature
variation of more than 5 C in the water.
On completion of the third cold cycle, the insulator shall be
examined to verify the that they have not crack ed. Type A insul ator
shall then be subjected to the mechanical test prescribed in 10.14. Type
B insulator shall be subjected for one minute to the power-frequency test
prescribed in 10.15.
The insulators shall withstand the appropriate test without cracking
or puncture or mechanical break age.
NOTE 1 For very large rigid insulators or string insulator units, the tests,
prescribed in 10.6 may be too severe and a test of reduced severity may then be
applied by agreement between manufacturer and purchaser. For this purpose, very
large rigid insulators or string insulator units shall be considered as those having one
of the following dimensions:
L greater than 120 cm L = length of insulator
D
2
L greater than 80 000 cm
2
D = greatest external diameter
greater than 2.5 cm = the greatest thickness defined by the
diameter of the greatest circle which
can be inscribed within the outline of
a section through the axis of the
hollow insulator
d greater than 9 cm d = core diameter for solid core insulator
NOTE 2 The restriction against using an intermediate container does not
exclude the use of a wire mesh basket having a low thermal capacity and giving free
access for the water.
NOTE 3 Also see IS : 5621-1970*.
*Specification for large hollow porcelains for use in electrical installation.
17
IS : 731 - 1971
10.7 El ectromechani cal Failing Load Test ( on Type B String
Insul ator Uni ts Only )
10.7.1 This test shall be applied to string insulator units of such types
where electrical discharge will serve to indicate mechanical failure. For
other types, the insulators shall be submitted to the mechanical failing
load test ( see 10.8 ).
10.7.2 The insulator units shall be subjected individually to a power-
frequency voltage and to a tensile load applied simultaneously between
the metal parts.
10.7.3 For insulators with ball and socket couplings, the coupling pieces
of the testing machine shall be in accordance with IS : 2486 ( Part II )-
1974*, as regards their essential dimensions.
10.7.4 The voltage shall be 50 percent to 60 percent of the specified wet
power-frequency withstand voltage of the string insulator unit, and it shall
be maintained at this value throughout the test.
10.7.5 The tensile load shall be. gradually increased from a value of 75
percent of the specified electromechanical failing load until the specified
electromechanical failing load is reached.
10.7.6 The insulator passes the test if the specified electromechanical
failing load is reached, without puncture.
10.7.7 To provide information when specially requested, the load may
be increased until the failing load as defined in 2.12 is reached and the
value recorded.
10.8 Mechani cal Failing Load Test
10.8.1 String Insulator Units
10.8.1.1 String insulator units of type A and those of type B to which
the electromechanical failing load test ( see 10.7 ) is not applicable shall
be subjected individually to a tensile load applied between the metal
parts.
10.8.1.2 For insulators with ball and socket couplings, the coupling
pieces of the testing machine shall be in accordance with IS : 2486 ( Part
II )-1974*, as regards their essential dimensions.
10.8.1.3 The load shall be gradually increased from a value of 75
percent of the specified mechanical failing load until the specified
mechanical failing load is reached.
10.8.1.4 The insulator passes the test if the specified mechanical
failing load is reached.
*Specification for insulator fittings for overhead power lines of 3 3 kV and above:
Part I I Dimensional requirements ( first revision ) .
18

IS : 731 - 1971
10.8.1.5 To provide information when specially requested, the load
ma y be increased until the failing load as difined in 2. 13 is reached and
the value recorded.
10.8.2 Rigid Insulators
10.8.2.1 Rigid insulators shall be mounted on a rigidly fixed pin
capabl e of withstanding without appreciable deformation the loads to
which it will be subjected during the test; insulators provided with integral
metal fittings for mounting shall be mounted for test using these fittings.
The insulator shall be subjected to a load equal to 75 percent
of the specified mechanical failing load applied perpendicular to
the axis of the insulator in the plane of the side groove by means of a wire
rope encircling the side groove. The wire rope shall be such that
lacalized stresses in the side groove of the insulator are avoided. If the
insulator is provided with means of cl amping the conductor, the load
shall be applied to this cl amp. The load shall be gradual l y increased
until the specified mechanical failing load is reached.
10.8.2.2 The insulator passes the test if the specified mechanical
failing load is reached.
10.8.2.3 To provide information when specially requested, the load
may be increased until the failing load as defined in 2.13 is reached and
the val ue recorded.
10.9 Tw enty -four Hours Mech a ni ca l Test ( for Stri ng Insul a tor
Uni t s onl y w h en Sp eci fi ed by Purch a ser )
10.9.1 The insulator shall be subjected for 24 hours to a tensile l oad,
applied axially which shall be two-thirds of the specified minimum
failing l oad.
10.9.2 The insulator shall then pass the power-frequency routine test
given in 10.15.
10.10 Puncture Test ( for Insul a tors Ty p e B Onl y )
10.10.0 The puncture test may be either a power-frequency puncture
test or, by agreement between manufacturer and purchaser, an impulse
overvoltage test.
10.10.1 Power-Frequency Puncture Test
10.10.1.1 The insulators, after having been cleaned and dried, shall
be completely immersed in a tank containing a suitable insulating
medium to prevent surface discharges on them. If the tank is ma de of
meta l , its dimensions shall be such tha t the shortest distance between any
19
IS : 731 - 1971
part of the insulator and the side of the tank is not less than 1.5 times the
diameter of the largest insulator shed. The immersion medium shall be
at about room temperature.
10.10.1.2 The test voltage shall be applied between those parts which
normally have the operating voltage between them. During immersion
in the insulating medium, precautions shall be taken to avoid air pockets
under the sheds of the insulator.
10.10.1.3 The voltage shall be raised as rapidly as is consistent with
its value being indicated by the measuring instrument to the specified
puncture voltage. No puncture shall occur below the specified puncture
voltage.
10.10.1.4 To provide information when specially requested, the
voltage may then be raised until puncture occurs and the puncture
voltage is recorded.
NOTE It is not possible to define exactly the properties of the immersion
medium, but one desirable property is a slight conductivity ( resistivity of the order
of 10
???
10
???
m )
10.10.2 Impulse Overvoltage Test
10.10.2.1 If this test is required, the details shall be agreed to
between the purchaser and the manufacturer.
10.11 Porosity Test
10.11.1 Porcelain fragments from the insulators or, by agreement, from
representative pieces of porcelain fired adjacent to them shall be
immersed in a 1 percent alcohol solution of fuchsin ( 1 g fuchsin in 100 g
methylated spirit ) under a pressure of not less than 15 X 10
6
N/m
2
for a
time such that the products of the test duration in hours and the test
pressure in N/m
2
is not less than 180 X 10
6
.
10.11.2 The fragments shall then be removed from the solution, washed
dried and again broken.
10.11.3 Examination with the naked eye of the freshly broken surfaces
shall not reveal any dye penetration. Penetration into small cracks
formed during the initial breaking shall be neglected.
10.12 Galvanizing Test
10.12.1 This test comprises firstly verification of the uniformity of the
coating of zinc ( test by immersion in copper sulphate ) and secondly
verification of the weight of zinc per unit surface ( test by chemical
dissolution ). This second test is optional and shall be carried out only if
so agreed by the manufacturer and the purchaser.
10.12.2 The uniformity of zinc coating of galvanized metal fittings
shall satisfy the requirements given in IS : 2633-1972*.
*Methods of testing uniformity of coating on zinc coated articles (first revision).
20
IS : 731 - l 971
10.43 Vi sua l Exa mi na ti on Test
10.13.1 A visual examination shall be ma d e on each insulator. The
colour of the insulator shal l approximate to the colour specified on the
drawing. Some variation in the colour shade is permitted and shall not
justify rejection of the insulator. The insulator shall be free from physical
distortion of shape within tolerances specified.
The areas specified as glazed on the drawing shall be covered by a
smooth hard glaze free from cracks and other defects prejudicial to
satisfactory performance in service.
Ou t of those areas specified as glazed on the drawing, the total area
not covered by glaze shall not exceed:
Also the area of any single glaze defect shall not exceed:
where
D is the greatest diameter of the insulator, in centimetres.
F is the creepage distance of the insulator, in centimetres.
10.14 Mech a ni ca l Routi ne Test ( for Stri ng Insul a tor Uni te onl y )
10.14.1 Type A string insulator units shall be subjected for at least 1
minute to a tensile load equal to 60 percent of the specified mechanical
failing l oad.
10.14.2 Type B string insulator units shall be subjected for at least 10
seconds to a tensile l oad equal to 40 percent of the specified electro-
mechanical failing l oad.
10.14.3 Insulators which break or whose metal parts are fractured or
become detached during the test shall be rejected.
NOTE Mechanical routine tests on Type A rigid insulators shall be made only
by agreement between purchaser and manufacturer.
10.15 El ectri ca l Routi ne Test ( f or Ty p e B Insul a tors )
10.15.1 Type B string insulator units and rigid insulators shall be sub-
jected to a power-frequency voltage. For string insulator units, the voltage
shal l be appl ied between the metal parts, but the normal metal work of
interl ink ed insulators may be repl aced by other suitable fittings.
21
IS : 731 - 1971
10.15.2 Rigid insulators shall be placed head downwards in a tank con-
taining water to a depth sufficient to cover the side conductor grooves, and
the voltage shall be applied between the tank and water practically filling
the pin hole or cavity of each insulator. Alternatively, metal electrodes
may be used provided the electric stress in the porcelain is not reduced.
10.15.3 The test voltage shall be such as to produce frequent flashover
( every few seconds ).
10.15.4 The time of application of the test voltage shall be at least 5
consecutive minutes.
10.15.5 Insulators which puncture during the test shall be rejected.
NOTE 1 This test should preferably be carried out after the mechanical
routine test, in order to eliminate insulators which may have been partially damaged
in the mechanical test.
NOTE 2 For certain designs of rigid insulator Type B, it may not be possible to
apply the test described above. By agreement between the purchaser and the manu-
facturer, the test on the assembled insulator may then be replaced by a test on the
insulating parts before assembly.
AP P E NDI X A
( Clauses 3.2, 10.3.2, 10.3.5.1, 10.4.3 and 10.4.5 )
CORRECTION OF TEST VOLTAGES FOR ATMOSPHERIC
CONDITIONS
A-1. GENERAL
A-1.1 Variations in barometric pressure and in humidity of the atmosphere
cause variation in the electric strength of the air and hence also in the
withstand and flashover voltage of insulators exposed to the air; under-oil
flashover and puncture strength, however, are not significantly affected by
these changes.
A-2. CORRECTION FACTORS
A-2.1 When the atmospheric conditions in the neighbourhood of the
insulator during the test differ from the reference conditions, adjustments
should be made to certain of the test voltages by the application of the
following correction factors in accordance with Table 4:
a) Correction factor for air density d :
( where d lies between 0.95 to 1.05 )
22

IS : 731 - 1971
where
p = atmospheric pressure in millibars, and
t = temperature in degrees Celsius.
For a wider range of density and for higher accuracy, instead of d
the factor k shall be used as under. The values of k correspond-
ing to factor d are given below:
d k
0.70 0.72
0.75 0.77
0.80 0.82
0.85 0.86
0.90 0.91
0.95 0.95
1.00 1.00
1.05 1.05
1.10 1.09
1.15 1.13
TABLE 4 CORRECTION OF VOLTAGES FOR ATMOSPHERIC CONDITIONS
( Clause A-2.1 )
b) Correction factor for humidity (h): Fig. 2 gives the absolute
humidity values for wet and dry bulb temperatures ( when the
velocity of air over the wet bulb exceeds 3 m/s ) for the standard
atmospheric pressure of 1 013 millibars. For better accuracy, a
correction should be applied to absolute humidity value obtained
from Fig. 2 for any deviation of ambient atmospheric pressure
from the standard value of 1 013 millibars. This correction
should be obtained from Fig. 3 as follows.
23
(1)
10.2
10.3
10.3
10.4
10.4
10.10
TEST
(2)
Visible discharge test
Impulse voltage withstand test
Impulse voltage flashover test
Wet power-frequency voltage
withstand test
Wet power-frequency voltage
flashover test
Power-frequency puncture with-
stand test
ADJ US TME NT RE QUI RE D
(3)
Voltage applied shall be specified value
multiplied by k and divided by h.
Voltage applied shall be specified value
multiplied by k and divided by h
Measured voltage shall be divide by k
and multiplied by h
Voltage applied shall be the specified
values multiplied by k
Measured voltage shall be divided by k
No adjustment required

IS : 731 - 1971
FIG. 2 DETERMINATION OF ABSOLUTE HUMIDITY
Locate the point corresponding to the deviation of ambient
atmospheric pressure from 1 013 millibars on the left hand side
of Fig. 3B and join it with right hand side top corner by a
straight line. Then locate the point on the curve in Fig. 3A
corresponding to the observed value of the difference of dry and
wet bulb temperatures. Draw a vertical line through this point
to intersect the straight line drawn in Fig. 3B. Read the correc-
tion to be applied to humidity from the right hand side of Fig.
3B corresponding to the point of intersection. This correction is
positive for a positive deviation and negative for a negative
deviation, from the standard atmospheric pressure.
24
IS : 731 - 1971
FIG. 3 CORRECTION TO ABSOLUTE HUMIDITY FOR
VARIATION IN PRESSURE
For the corrected value of absolute humidity thus obtained, the
correction factor h shall be determined from Fig. 4.
25
IS : 731 - 1971
26
F
I
G
.

4

H
U
M
I
D
I
T
Y

C
O
R
R
E
C
T
I
O
N

F
A
C
T
O
R

IS : 731 - 1971
APPENDI X B
(Clauses 10.2, 10.3.1 and 10.4.1)
HIGH VOLTAGE TESTS
B 1. CONDITION OF THE INSULATORS
B-1.1 Before commencing the tests, the sample insulators shall be clean
and dry and in thermal equilibrium with its surroundings ( ambient
medium ).
B-2. METHODS OF SUPPORT
B-2.1 Stri ng Insul ator Uni t and Insul ator Stri ng
B-2.1.1 The string insulator unit or insulator string shall be suspended
vertically by means of an earthed wire rope or other suitable conductor
from a supporting structure. The distance between the uppermost Point
of the insulator metal work and the supporting structure shall be not
less than 1 metre. No other object shall be nearer to the insulator than
1 metre or 1.5 times the length of the insulator string, whichever is the
greater. A length of conductor in the form of a straight smooth metal
rod or tube shall be attached to the lower integral fitting of the string
insulator unit or insulator string so that it lies in a horizontal plane, and
the distance from the lowest shed of a porcelain part to the upper surface
of the conductor shall be as short as possible but greater than 0.5 times
the diameter of the lowest insulator.
B-2.1.2 The diameter of the conductor shall be about 1.5 percent of
the length of the string insulator unit or insulator string with a minimum
of 25 mm.
B-2.1.3 The length of the conductor shall be at least 1.5 times that
of the string insulator unit or insulator string, and it shall extend at
least 1 metre on each side of the vertical axis.
B-2.1.4 Precautions shall be taken to avoid flashover from the ends of
the conductor.
B-2.1.5 The test voltage shall be applied between the conductor and
earth.
B-2.2 Ri gi d Insul ator
B-2.2.1 The insulator shall be mounted on an earthed metallic vertical
pin, with a smooth surface and a diameter not less than 16 mm. The
pin shall be sufficiently long to ensure that the lowest edge of the
insulator is at least 1 metre above the ground. No other object shall be
nearer to the insulator than 1 metre or l.5 times the height of the
insulator, whichever is the greater.
27
IS : 731 - 1971
B-2.2.2 A conductor not less than 5 mm diameter and extending in both
directions at least twice the insulator height beyond the top shed shall be
secured as nearly as possible horizontally in the side groove of the
insulator by means of a metallic wire of about 1 mm diameter wrapped
round the conductor for a distance approximately twice the diameter of
the top shed and extending equally on each side of the insulator.
B-2.2.3 If the rigid insulator is provided with means of clamping,
conductor shall be placed in the clamp.
B-2.2.4 The test voltage shall be applied between the conductor and
earth.
NOTE When to agreed, tests may also be made under conditions reproducing
service conditions as closely as possible, taking account of all factors which may
influence flathover voltage. Under these conditions, the characteristics may differ
from the values measured using the standard methods of mounting.
B-3. TIME INTERVALS BETWEEN FLASHOVERS
B-3.1 The time intervals between consecutive flashovers shall be
sufficient to avoid effects from the previous application of voltage in
flashover or withstand tests.
B - 4 . MPULSE TESTS
B-4.1 The impulse tests shall be made in accordance with
IS : 2071 ( Parts I and II )-1974*.
B-4.2 The standard 1.2/50 impulse wave shall be used.
B-5. POWER-FREQUENCY TESTS
B-5.1 The power-frequency tests shall be made in accordance with
IS : 2071 ( Parts I and II )-1974*.
B-5.2 The test circuit shall be such that when the test object is short-
circuited at the test voltage, the current is not less t han 0.1 A if dry tests
are to be made, and not less than 0.5 A if wet tests are to be made.
B-6. EXCESSIVE HUMIDITY
B-6.1 Precautions shall be taken to avoid condensation on t he surface of
the insulator, especially when the relative humidity is high. For example,
the insulator shall be maintained at the ambient temperature of the test
location for sufficient time for equilibrium to be reached before the test
commences. Except by agreement between the manufacturer and the
purchaser, tests shall not be made if the relative humidity exceeds
85 percent.
*Methods of high voltage testing :
Part I General definitions and test requirements (first revision).
Part II Test procedures ( first revision ).
28

IS : 731-1971
A P P E N D I X C
(Clauses 10.1.2.1 and 10.1.2.3)
SAMPLING PROCEDURE
C-1. S AMPLE SIZE
C-1.1 The number of insulators to be selected at random from the lot
shall be in accordance with col 1 and 2 of Table 5. If required( see C-2 )
additional insulators as given in col 3 of Table 5 shall also be selected at
random.
LOT SI ZE
(1)
N
101 to 500
501 800
801 1300
1 301 3 200
3 201 8 000
8 001 and above
FI RST
SAMPLE
SIZE
(2)
n
1
5
7
10
15
25
35
SECOND
SAMPLE
SIZE
(3)
n
2
10
14
20
30
50
70
ACCEPTANCE
NUMBER
(4)
c
1
0
0
0
1
2
2
REJECTION
NUMBER
(5)
c
2
2
3
3
4
5
7
TABLE 5 SAMPLE SIZE AND CRITERION OF CONFORMITY
C-1.2 All the insulators selected as in C-1.1 shall be subjected to the
appropriate acceptance tests.
C-2. CRITERION OF CONFORMITY
C-2.1 The lot shall be considered as conforming to the requirements of
the acceptance tests if the number of failures found in the first sample n
1
is less than or equal to c
1
. If the number of failures is greater than or
equal to c
2
, the lot shall be considered as not conforming to the
requirements of the acceptance tests and shall be rejected. If the
number of failures is between c
1
and c
2
, and a second sample of n
2
insulators shall be selected and subjected to acceptance tests. If the
number of failures in the two samples combined is less than c
2
, the lot
shall be considered as conforming to the requirements of acceptance tests
otherwise it shall be considered to have failed.
29
BUREAU OF INDIAN STANDARDS
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, NEW DELHI 110002
Telephones : 23230131, 23233375, 23239402 Fax : 91+011 23239399, 23239382
E-Mail : info@bis.org.in Website : http://www.bis.org.in
Central Laboratory: Telephone
Plot No. 20/9, Site IV, Sahibabad Industrial Area, SAHIBABAD 201010 277 0032
Regional Offices:
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg, NEW DELHI 110002 2323 7617
*Eastern : 1/14 CIT Scheme VII M, V.I.P. Road, Kankurgachi, KOLKATA 700054 2337 8662
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022 260 3843
Southern: C.I.T. Campus, IV Cross Road, CHENNAI 600113 2254 1984
Western : Manakalaya, E9, MIDC, Behind Marol Telephone Exchange, 2832 9295
Andheri (East), MUMBAI 400093
Branch Offices:
'Pushpak', Nurmohamed Shaikh Marg, Khanpur, AHMEDABAD 380001 2560 1348
Peenya Industrial Area, 1
st
Stage, Bangalore-Tumkur Road, BANGALORE 560058 2839 4955
Commercial-cum-Office Complex, Opp. Dushera Maidan, E-5 Arera Colony, 242 3452
Bittan Market, BHOPAL 462016
62-63, Ganga Nagar, Unit VI, BHUBANESHWAR 751001 240 3139
5
th
Floor, Kovai Towers, 44 Bala Sundaram Road, COIMBATORE 641018 221 0141
SCO 21, Sector 12, FARIDABAD 121007 229 2175
Savitri Complex, 116 G. T. Road, GHAZIABAD 201001 286 1498
53/5 Ward No. 29, R. G. Barua Road, 5
th
By-lane, Apurba Sinha Path, 245 6508
GUWAHATI 781003
5-8-56C, L. N. Gupta Marg, Nampally Station Road, HYDERABAD 500001 2320 1084
E-52, Chitaranjan Marg, C-Scheme, JAIPUR 302001 237 3879
117/418 B, Sarvodaya Nagar, KANPUR 208005 223 3012
'Sethi Bhawan', 2
nd
Floor, Behind Leela Cinema, Naval Kishore Road, 261 8923
LUCKNOW 226001
NIT Building, Second Floor, Gokulpat Market, NAGPUR 440010 256 5171
Plot No. A-20-21, Institutional Area, Sector 62, Gautam Budh Nagar, NOIDA 201307 240 2206
H. No. 15, Sector 3, PARWANOO 173220 23 5436
Patliputra Industrial Estate, PATNA 800013 226 2808
First Floor, Plot Nos 657-660, Market Yard, Gultekdi, PUNE 411037 2426 1096
'Sahajanand House', 3
rd
Floor, Bhaktinagar Circle, 80 Feet Road, RAJKOT 360002 237 8251
T.C. No. 14/1421, University P.O. Palayam, THIRUVANANTHAPURAM 695034 233 9174
1
st
Floor, Udyog Bhavan, VUDA, Siripuram Junction, VISHAKHAPATNAM-03 271 2833
*Sales Office is at 5 Chowringhee Approach, P. O. Princep Street, KOLKATA 700072 2212 6215
Printed at New India Printing Press, Khurja, India

You might also like