Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Specifier's Guide: Line Installation and Protective Equipment Master Catalog 5 KV - 35 KV Electrical Distribution Systems

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Specifier's Guide

Specifier's
Guide
Line installation and protective
equipment master catalog
5 kV - 35 kV electrical
distribution systems

Choose Eaton's Cooper Power Systems for Your Complete Project Needs

Eaton and Cooper united.

Energizing a world

that demands more.

We deliver:

Electrical solutions that use less energy, improve power reliability and make the places
we live and work safer and more comfortable
Hydraulic and electrical solutions that enable machines to deliver more productivity
without wasting power

Aerospace solutions that make aircraft lighter, safer and less costly to operate, and
help airports operate more efficiently

Vehicle drivetrain and powertrain solutions that deliver more power to cars,
trucks and buses, while reducing fuel consumption and emissions

Discover todays Eaton.


Powering business worldwide
As a global power management company, we help
customers worldwide manage the power needed for
buildings, aircraft, trucks, cars, machinery and businesses.
Eatons innovative technologies help customers manage
electrical, hydraulic and mechanical power more reliably,
efficiently, safely and sustainably.

We provide integrated solutions that help make energy,


in all its forms, more practical and accessible.
With 2012 sales of $21.8 billion on a pro forma basis, Eaton
has approximately 102,000 employees around the world
and sells products in more than 175 countries.
Eaton.com

Specifiers Guide: Components Master Catalog

Table of Contents
Table of Contents

Page

Standard Interfaces For Separable Connectors and Components

Certified Tests and Performance

Conductor Sizing

AEIC Insulation Diameter Chart

ICEA Insulation Diameter Chart

200 A Loadbreak Connectors

10

200 A Deadbreak Connectors

14

200 A Stacking Dimensions

16

Clr 600 A Loadbreak Connectors

18

600/900 A Deadbreak Connectors

22

600/900 A Components and Replacement Parts

25

600/900 A Connector Systems

26

600 A Stacking Dimensions

28

Junction Bars/Cable Transition and Oil Stop Modules

30

Splices

36

Underground Surge Arresters

38

Tools & Maintenance

40

Bushings

44

Fusing

46

MagneX Single-Phase Interrupter

48

MagneX Three-Phase Interrupter

50

Faulted Circuit Indicators

52

Sectionalizing Cabinets

56

Part Number Index

58

Support Available When You Need It

61

Product Application Overhead and Underground Distribution Systems

62

Eaton's Cooper Power Systems

Standard Interfaces for Separable Connectors and Components


Standard
Interfaces
Separable
Connectors
and Components
Standard Interfaces
forfor
Separable
Connectors
and Components
The following diagram specifies the IEEE Std 386 standard
interfaces supplied by Cooper Power Systems for various
applications to ensure interchangeability of any mating
components.
Interface Description Per IEEE Std 386 2006 standard
Interface

Interface

200 A Loadbreak
8.3 kV/14.4 kV

200 A Bushing Well


8.3 kV and 15.2 kV
200 A 15 kV Bushing
Well Insert

200 A Bushing Well


15/25 kV

-.910 I
100

Transformer or
Switching
Apparatus

-2 3 .1 1

17

LE215

78

200 A Loadbreak
15 kV Connector
200 A Loadbreak
15.2 kV/26.3 kV
200 A 25 kV Bushing
Well Insert
200 A Loadbreak
25 kV Connector
200 A Loadbreak
Interface 1A
21.1 kV/36.6 kV
(Large Interface)

200 A Three-Phase Integral


35 kV Loadbreak Bushing

200 A Loadbreak
35 kV Connector
200 A Deadbreak
8.3/15.2 kV

200 A Deadbreak Connector


15 kV and 25 kV
BOL-T
15.2/26.3 kV
BT-TAP
8.3/14.4 kV and
15.2/26.3 kV
600 A Deadbreak
Connector
15 kV and 25 kV
(T-OP II Shown)

T-OP II
8.3/14.4 kV and
15.2/26.3 kV

BOL-T
21.1/36.6 kV
BT-TAP
21.1/36.6 kV
600 A Deadbreak
Connector 35 kV
(T-OP II Shown)

600 A Deadbreak
Bushing 15/25 kV

600 A Deadbreak
Bushing 35 kV

T-OP II
21.1/36.6 kV

Specifiers Guide: Components Master Catalog

Certified Tests and Performance


Certified
Tests
Performance
Certified
Tests
and and
Performance
Eaton's Cooper Power Systems Connectors,
Splices, Underground Surge Arresters, Tools,
Bushings, Fusing, Faulted Circuit Indicators and
Sectionalizing Equipment have been designed
and tested per applicable portions of Institute of
Electrical and Electronics Engineers, Inc. (IEEE),
American National Standards Institute (ANSI),
National Electrical Manufacturers Association
(NEMA) and other industry standards including:
Std 386 standard for Separable
Connectors
n IEEE Std 404 standard for Cable Joints and
Splices
n IEEE Std C62.11 standard for Metal Oxide
Surge Arresters
n IEEE Std C37.41 standard for Current-Limiting
Fuses
n IEEE Std 592 standard for Exposed
Semi-conducting Shields
n ANSI C119.4 Standard for Copper and
Aluminum Conductor Connectors
n AEIC CS5, CS6 and CS8 Standards for XLP
and EPR Insulated Cables
n ICEA S-94-649 Standard for XLP and EPR
Insulated Cables
n IEEE

Cooper Power Systems Separable Connectors


are rated for 15 kV, 25 kV and 35 kV systems in
accordance with the following ratings.
Splice Voltage Ratings in Accordance with IEEE Std
404 standard
Voltage Ratings and Characteristics
Description

Voltage

Standard Voltage Class (kV)

15

25

35

Maximum Rating Phase-to-Ground


(kV rms)

8.7

14.4

20.2

AC 60 Hz 1 Minute Withstand (kV rms)

35

52

69

DC 15 Minute Withstand (kV)

70

100

125

BIL and Full Wave Crest (kV peak)

110

150

200

Minimum Corona Voltage Level (kV)

13

22

31

Splice Current Ratings in Accordance with


IEEE Std 404 standard
Current Ratings and Characteristics
Description

Amperes

Continuous

Equal to the current rating of


the cable per
IEEE Std 404 standard

Short Time

Equal to the current rating of


the cable per
IEEE Std 404 standard

200 A Loadbreak Connector Ratings in Accordance with IEEE Std 386 standard
Voltage Ratings
Standard Voltage Class
Maximum Rating Phaseto-Phase
Maximum Rating Phaseto-Ground
AC 60 Hz 1 Minute
Withstand
DC 15 Minute Withstand
BIL and Full Wave Crest
Minimum Corona Voltage
Level
Current Ratings
Continuous
Switching

Fault
Closure

Short Time

15 kV
15

25 kV
25

35 kV
35

14.4

26.3

36.6

8.3

15.2

21.1

34

40

50

53
95
11

78
125
19

103
150
26

15 kV
200 A rms
10 make/break
operations at
200 A rms at
14.4 kV
10,000 A rms
sym. at 14.4 kV
for 0.17s after
10 switching
operations
10,000 A rms
sym. for 0.17s
3,500 A rms sym.
for 3.0s

25 kV
200 A rms
10 make/break
operations at
200 A rms at
26.3 kV
10,000 A rms
sym. at 26.3 kV
for 0.17s after
10 switching
operations
10,000 A rms
sym. for 0.17s
3,500 A rms sym.
for 3.0s

35 kV
200 A rms
10 make/break
operations at
200 A rms at
36.6 kV
10,000 A rms
sym. at 36.6 kV
for 0.17s after
10 switching
operations
10,000 A rms
sym. for 0.17s
3,500 A rms sym.
for 3.0s

600 A Deadbreak Connector Ratings in Accordance with IEEE Std. 386 standard
Voltage Ratings
Standard Voltage Class
Maximum Rating Phaseto-Ground
AC 60 Hz 1 Minute
Withstand
DC 15 Minute Withstand
BIL and Full Wave Crest
Minimum Corona Voltage
Level
Current Ratings
600 A Interface**
Continuous
24 Hour
Overload
Short Time

15 kV
25
15.2

25 kV
25
15.2

35 kV
35
21.1

40

40

50

78
125
19

78
125
19

103
150
26

15 kV

25 kV

35 kV

600 A rms
1,000 A rms

600 A rms
1,000 A rm

600 A rms
1,000 A rms

25,000 A rms
sym. for 0.17 s
10,000 A rms
sym. for 3.0 s

25,000 A rms
sym. for 0.17 s
10,000 A rms
sym. for 3.0 s

25,000 A rms
sym. for 0.17 s
10,000 A rms
sym. for 3.0 s

Plug (LRTP)*
200 A rms
10 make/break
operations at
200 A rms at
26.3 kV
10,000 A rms
sym. at 26.3 kV
for 0.17s after
10 switching
operations
10,000 A rms
sym. for 0.17 s
3,500 A rms sym.
for 3.0s

200 A rms
10 make/break
operations at
200 A rms at
36.6 kV
10,000 A rms
sym. at 36.6 kV
for 0.17s after
10 switching
operations
10,000 A rms
sym. for 0.17 s
3,500 A rms sym.
for 3.0s

200 A Interface On Loadbreak Reducing Tap


Continuous
200 A rms
Switching
10 make/break
operations at
200 A rms at
14.4 kV
Fault
10,000 A rms
Closure
sym. at 14.4 kV
for 0.17s after
10 switching
operations
Short Time
10,000 A rms
sym. for 0.17 s
3,500 A rms sym.
for 3.0s

Notes:
* System design and protection must recognize the ratings of 200 A interface.
** Optional 900 A rating is available. Refer to 600/900 A Deadbreak Connector section for more
detail.

Eaton's Cooper Power Systems

Conductor Sizing
Part Number Selection Process for Cable
Sensitive Products

EXAMPLE:
PROPER ELBOW PART NUMBER SELECTION

Eaton's Cooper Power Systems 200 A and 600 A connector


products are designed for applications on XLPE, EPR or other
solid dielectric insulated underground electrical cables. In
order to maintain a reliable termination, the cable accessories
must be sized correctly with the cable conductor size and
cable insulation diameter.

Select an Eaton's Cooper Power Systems 15 kV 200 A


Loadbreak Elbow with optional integral jacket seal and test
point for an AEIC standard tape-shielded 15 kV cable with
133% insulation and 1/0 compact stranded conductor with
an outer jacket diameter of 1.07".

The cable conductor size is used to determine the compression


connector used. Proper sizing is important to ensure reliable
current transfer from the underground cable conductor to
the elbow connector. Conductor diameters are dependent
on the conductor size in AWG or kcmil, and conductor type
(stranded, compressed, compact or solid).
The cable insulation diameter (the diameter over the insulation)
is critical because it is important to maintain a tightly sealed
fit between the cable insulation and the elbow housing at
the cable entrance. As the insulation thickness changes,
so must the range of the cable accessory. Cable insulation
diameter can be determined from the cable manufacturer's
specification, or by referring to pages 8 (for cable made to the
AEIC Standard including the 0.030 inch tolerance) or 9 (for
cable made to the ICEA Standard) for minimum and maximum
diameters.

Step 1 Base Part Number Selection


Select base part number of LEJ215 from page 11 for 15 kV
voltage class. Note that on page 11 reference is also made to
tables CR1 and CC1.
Step 2 Determine Insulation Outside Diameter Range
Since cable is made to AEIC Standards, refer to page 8.
133% 15 kV cable corresponds to 220 mil insulation wall
thickness. The AEIC table gives a range of 0.805" to 0.865"
for 1/0 compact 220 mil cable.
Step 3 Elbow Cable Range Selection
Refer to CR1 Table on page 13 and select a cable range
code of "AB" with a range of 0.610" to 0.970" to cover
0.805" to 0.865".
LEJ215

CABLE RANGE
CODE (CR1)

Step 4 Elbow Connector Selection


Refer to CC1 Table on page 13 and select a conductor
code of "05" which applies to the specified 1/0 compact
conductor.
LEJ215

AB

CONDUCTOR
CODE (CC1)

Step 5 Optional Test Point Selection


In accordance with Note 1 on page 11, for an elbow with test
point, add a "T" after the cable range and conductor code.
LEJ215

AB

05

Step 6 Optional Ground Strap


Tape-shielded cable requires a ground strap and bleeder wire
to terminate. Add "GS" after test point option.
LE215

AB

05

TGS

Step 7 Ordering
Therefore, order Eaton's Cooper Power Systems part number
LEJ215AB05TGS

Specifiers Guide: Components Master Catalog

CR

CABLE
INSULATION
DIAMETER

INSULATION
WALL
THICKNESS
CONCENTRIC
STRANDED

COMPACT
STRANDED

COMPRESSED
STRANDED

Types of Stranded Conductor


Cable insulation
METAL NEUTRAL
OR SHIELD
OUTER JACKET

INSULATION
SHIELD

DIAMETER OVER
INSULATION (CR)
CONDUCTOR

INSULATION

CONDUCTOR
SHIELD

Illustration showing typical construction of medium voltage underground cable.

Cable Conductor Reference


Conductor
Size
AWG or kcmil
14
12
10
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
600
700
750
800
900
1000

No. of Strands
and their Nom.
Strand Dia. (in.)
7 x 0.0242
7 x 0.0305
7 x 0.0385
7 x 0.0486
7 x 0.0612
7 x 0.0772
7 x 0.0974
19 x 0.0664
19 x 0.0745
19 x 0.0837
19 x 0.0940
19 x 0.1055
37 x 0.0822
37 x 0.0973
37 x 0.1162
61 x 0.0992
61 x 0.1071
61 x 0.1109
61 x 0.1145
61 x 0.1215
61 x 0.1280

Cross-sectional Area
Square
Inches
0.0032
0.0051
0.0082
0.0130
0.0206
0.0328
0.0521
0.0657
0.0829
0.1045
0.1318
0.1662
0.1964
0.2749
0.3927
0.4712
0.5498
0.5891
0.6283
0.7069
0.7854

Eaton's Cooper Power Systems

mm2
Conversion
2.08
3.31
5.26
8.37
13.30
21.15
33.62
42.41
53.49
67.43
85.01
107.2
127
177
253
304
355
380
405
456
507

Stranded
Conductors
(inches)
0.073
0.092
0.116
0.146
0.184
0.232
0.292
0.332
0.373
0.418
0.470
0.528
0.575
0.681
0.813
0.893
0.964
0.998
1.031
1.094
1.152

Compressed
Conductors
(inches)
0.283
0.322
0.362
0.405
0.456
0.512
0.558
0.661
0.789
0.866
0.935
0.968
1.000
1.061
1.117

Compact
Conductors
(inches)
0.268
0.299
0.336
0.376
0.423
0.475
0.520
0.616
0.736
0.813
0.877
0.908
0.938
0.999
1.060

Solid
Conductors
(inches)
0.064
0.081
0.102
0.129
0.162
0.204
0.258
0.289
0.325
-

AEIC Insulation Diameter Chart


AEIC Insulation Diameter Chart
Cable Insulation Diameters for Standard AEIC Cables with 175, 220, 260, and 345 mil Insulation Wall Thickness
Concentric
Stranded
Insulation
AWG or
kcmil

Wall
Thickness*
(Inches)

#2

Compressed
Stranded

Compact
Stranded

Solid

Voltage
Class kV

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

.175
.220
.260
.345

15
15
25
35

0.670
0.760

0.730
0.820

0.665
0.775

0.725
0.815

0.650
0.740

0.710
0.800

0.640
0.730

0.700
0.790

#1

.175
.220
.260
.345

15
15
25
35

0.710
0.800
0.880

0.770
0.860
0.940

0.700
0.790
0.870

0.760
0.850
0.930

0.680
0.770
0.850

0.740
0.830
0.910

0.670
0.760
0.840

0.730
0.820
0.900

1/0

.175
.220
.260
.345

15
15
25
35

0.755
0.845
0.925
1.095

0.815
0.905
0.985
1.155

0.740
0.830
0.910
1.080

0.800
0.890
0.970
1.140

0.715
0.805
0.885
1.055

0.775
0.865
0.945
1.115

0.705
0.795
0.875
1.045

0.765
0.855
0.935
1.105

2/0

.175
.220
.260
.345

15
15
25
35

0.800
0.890
0.970
1.140

0.860
0.950
1.030
1.200

0.785
0.875
0.955
1.125

0.845
0.935
1.015
1.185

0.755
0.845
0.925
1.095

0.815
0.905
0.985
1.155

0.805
0.835
0.915
1.085

0.905
0.895
0.975
1.145

3/0

.175
.220
.260
.345

15
15
25
35

0.850
0.940
1.020
1.190

0.910
1.000
1.080
1.250

0.835
0.925
1.005
1.175

0.895
0.985
1.065
1.235

0.805
0.895
0.975
1.145

0.865
0.955
1.035
1.205

0.850
0.880
0.960
1.130

0.940
0.940
1.020
1.190

4/0

.175
.220
.260
.345

15
15
25
35

0.910
1.000
1.080
1.250

0.970
1.060
1.140
1.310

0.890
0.980
1.060
1.230

0.950
1.040
1.120
1.290

0.855
0.945
1.025
1.195

0.915
1.005
1.085
1.255

0.900
0.930
1.010
1.180

0.990
0.990
1.070
1.240

250

.175
.220
.260
.345

15
15
25
35

0.965
1.055
1.145
1.320

1.025
1.115
1.205
1.380

0.950
1.040
1.130
1.305

1.010
1.100
1.190
1.365

0.910
1.000
1.095
1.265

0.970
1.060
1.150
1.325

350

.175
.220
.260
.345

15
15
25
35

1.070
1.160
1.250
1.425

1.130
1.220
1.310
1.485

1.050
1.140
1.230
1.405

1.110
1.200
1.290
1.465

1.005
1.095
1.185
1.360

1.065
1.155
1.245
1.420

500

.175
.220
.260
.345

15
15
25
35

1.205
1.295
1.385
1.560

1.265
1.355
1.445
1.620

1.180
1.270
1.360
1.535

1.240
1.330
1.420
1.595

1.125
1.215
1.305
1.480

1.185
1.275
1.365
1.540

600

.175
.220
.260
.345

15
15
25
35

1.295
1.385
1.475
1.650

1.355
1.445
1.535
1.710

1.265
1.355
1.445
1.625

1.325
1.415
1.505
1.680

1.215
1.305
1.395
1.570

1.275
1.365
1.455
1.630

700

.175
.220
.260
.345

15
15
25
35

1.365
1.455
1.545
1.720

1.425
1.515
1.605
1.780

1.335
1.425
1.515
1.690

1.395
1.485
1.575
1.750

1.275
1.365
1.455
1.630

1.335
1.425
1.515
1.690

750

.175
.220
.260
.345

15
15
25
35

1.400
1.490
1.580
1.755

1.460
1.550
1.640
1.815

1.370
1.460
1.550
1.725

1.430
1.520
1.610
1.785

1.310
1.400
1.490
1.665

1.370
1.460
1.550
1.725

800

.175
.220
.260
.345

15
15
25
35

1.430
1.520
1.610
1.785

1.490
1.580
1.670
1.845

1.400
1.490
1.580
1.755

1.460
1.550
1.640
1.815

1.340
1.430
1.520
1.695

1.400
1.490
1.580
1.755

900

.175
.220
.260
.345

15
15
25
35

1.495
1.585
1.675
1.850

1.555
1.645
1.735
1.910

1.460
1.550
1.640
1.815

1.520
1.610
1.700
1.875

1.400
1.490
1.580
1.755

1.460
1.550
1.640
1.815

1000

.175
.220
.260
.345

15
15
25
35

1.550
1.640
1.730
1.850

1.610
1.700
1.790
1.955

1.515
1.605
1.695
1.815

1.575
1.665
1.755
1.920

1.460
1.550
1.640
1.760

1.520
1.610
1.700
1.865

* See table below for standard insulation thickness.


175
220
260
345
345

mil
mil
mil
mil
mil

is
is
is
is
is

100%
133%
100%
133%
100%

insulated
insulated
insulated
insulated
insulated

cable
cable
cable
cable
cable

at
at
at
at
at

15
15
25
25
35

kV.
kV.
kV.
kV.
kV.

Specifiers Guide: Components Master Catalog

ICEA Insulation Diameter Chart


ICEA
Insulation
Diameter
Chart
ICEA Insulation
Diameter
Chart
Cable Insulation Diameters for Standard ICEA Cables with 175, 220, 260, and 345 mil Insulation Wall Thickness
Concentric
Stranded

Compressed
Stranded

Compact
Stranded

Solid

AWG
or
kcmil

Insulation
Wall
Thickness*
(Inches)

Voltage
Class
kV

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

Min.
Dia.
(inches)

Max.
Dia.
(inches)

#2

.175
.220
.260
.345

15
15
25
35

0.645
0.735

0.730
0.825

0.635
0.725

0.720
0.815

0.620
0.710

0.705
0.800

0.610
0.700

0.695
0.790

#1

.175
.220
.260
.345

15
15
25
35

0.685
0.775
0.845

0.770
0.865
0.935

0.675
0.765
0.835

0.760
0.855
0.925

0.655
0.745
0.815

0.735
0.830
0.905

0.645
0.735
0.805

0.725
0.820
0.895

1/0

.175
.220
.260
.345

15
15
25
35

0.725
0.815
0.885
1.055

0.810
0.905
0.980
1.155

0.715
0.805
0.875
1.045

0.800
0.895
0.965
1.145

0.690
0.780
0.850
1.020

0.775
0.865
0.940
1.120

0.680
0.770
0.835
1.010

0.760
0.855
0.925
1.110

2/0

.175
.220
.260
.345

15
15
25
35

0.775
0.865
0.935
1.105

0.855
0.950
1.025
1.200

0.760
0.850
0.920
1.090

0.845
0.935
1.010
1.190

0.730
0.820
0.890
1.060

0.815
0.905
0.980
1.160

0.715
0.805
0.875
1.045

0.800
0.895
0.965
1.145

3/0

.175
.220
.260
.345

15
15
25
35

0.825
0.915
0.985
1.155

0.905
1.000
1.075
1.255

0.810
0.900
0.970
1.140

0.895
0.985
1.060
1.240

0.775
0.865
0.935
1.105

0.860
0.955
1.030
1.205

0.765
0.855
0.925
1.095

0.845
0.940
1.015
1.195

4/0

.175
.220
.260
.345

15
15
25
35

0.880
0.970
1.040
1.210

0.965
1.060
1.135
1.310

0.865
0.955
1.025
1.195

0.950
1.045
1.115
1.295

0.830
0.920
0.990
1.160

0.910
1.005
1.080
1.260

0.815
0.905
0.975
1.145

0.895
0.990
1.065
1.245

250

.175
.220
.260
.345

15
15
25
35

0.935
1.025
1.095
1.265

1.020
1.115
1.190
1.370

0.920
1.010
1.080
1.250

1.005
1.100
1.175
1.350

0.880
0.970
1.040
1.210

0.965
1.060
1.135
1.315

350

.175
.220
.260
.345

15
15
25
35

1.045
1.135
1.205
1.375

1.130
1.220
1.295
1.475

1.025
1.115
1.185
1.355

1.110
1.200
1.275
1.455

0.980
1.070
1.140
1.310

1.065
1.155
1.230
1.410

500

.175
.220
.260
.345

15
15
25
35

1.175
1.265
1.335
1.505

1.260
1.355
1.430
1.605

1.150
1.240
1.310
1.480

1.235
1.330
1.405
1.580

1.100
1.190
1.260
1.430

1.185
1.275
1.350
1.530

600

.175
.220
.260
.345

15
15
25
35

1.265
1.355
1.425
1.595

1.350
1.445
1.520
1.695

1.235
1.325
1.395
1.565

1.325
1.415
1.490
1.670

1.185
1.275
1.345
1.515

1.270
1.365
1.440
1.615

700

.175
.220
.260
.345

15
15
25
35

1.335
1.425
1.495
1.665

1.420
1.515
1.590
1.765

1.305
1.395
1.465
1.635

1.390
1.485
1.560
1.740

1.245
1.335
1.405
1.575

1.335
1.430
1.500
1.680

750

.175
.220
.260
.345

15
15
25
35

1.370
1.460
1.530
1.700

1.455
1.550
1.625
1.800

1.340
1.430
1.500
1.670

1.425
1.520
1.595
1.770

1.280
1.370
1.440
1.610

1.365
1.460
1.535
1.710

800

.175
.220
.260
.345

15
15
25
35

1.400
1.490
1.560
1.730

1.490
1.580
1.655
1.835

1.370
1.460
1.530
1.700

1.455
1.550
1.625
1.805

1.310
1.400
1.470
1.640

1.395
1.490
1.565
1.740

900

.175
.220
.260
.345

15
15
25
35

1.465
1.555
1.625
1.795

1.550
1.645
1.720
1.895

1.430
1.520
1.590
1.760

1.520
1.610
1.685
1.865

1.370
1.460
1.530
1.700

1.455
1.550
1.625
1.800

.175
.220
.260
.345

15
15
25
35

1.520
1.610
1.680
1.850

1.610
1.705
1.775
1.955

1.485
1.575
1.645
1.815

1.575
1.670
1.740
1.920

1.430
1.520
1.590
1.760

1.515
1.610
1.685
1.865

1000

* See table below for standard insulation thickness.


175
220
260
345
345

mil
mil
mil
mil
mil

is
is
is
is
is

100%
133%
100%
133%
100%

insulated
insulated
insulated
insulated
insulated

cable
cable
cable
cable
cable

at
at
at
at
at

15
15
25
25
35

kV.
kV.
kV.
kV.
kV.

Eaton's Cooper Power Systems

200
Loadbreak
Connectors
200 AALoadbreak
Connectors
Our 200 A 15, 25, and 35 kV Loadbreak Elbow
Connectors and Accessories are submersible, fullyshielded and insulated plug-in terminations, ideal for
connecting underground cable to transformers,
switchgear, sectionalizing cabinets and junctions.
These connectors are molded using high-quality,
peroxide-cured EPDM insulation for reliable field
performance.
15 kV and 25 kV loadbreak elbows are available
with an integral jacket seal for use with concentric
neutral and other types of shielded cables.
All 200 A loadbreak connectors meet the electrical,
mechanical, and dimensional requirements of IEEE
Std 386 standard and are designed to be fully
interchangeable with other major manufacturers
currently complying with IEEE Std 386 standard.

25 kV POSI-BREAK Elbow and Cap


Our POSI-BREAK Elbow and Cap is an engineered
solution that increases strike distance and improves
reliability. The added features solve problems, such as:
n

Partial Vacuum Flashovers Under certain


conditions during 25 kV switching, a partial
vacuum can decrease the dielectric strength of the
air inside the elbow/bushing or cap/bushing. This
increases the possibility of a flashover from the
elbow or caps probe along the bushing interface
to the grounded collar on the mating bushing
product. The POSI-BREAK design eliminates
the possibility of partial vacuum flashovers
during switching because of the increased strike
distance.
n Contamination The field-proven interface seal
prevents the ingress of moisture or contaminants.
However, contamination introduced during installation or switching operations can reduce the
strike distance along the interface. The increased
insulation of the POSI-BREAK design counteracts
the effect of contamination, increasing system
reliability.

35 kV Large Interface Elbow Bushing System*


Our 35 kV 200 A Large Interface Elbow Bushing System is a reliable,
field proven design. This system has over 25 years of field experience
while being used on large 35 kV distribution systems. Features of the
Large Interface System include:
n Increased strike distance to provide greater reliability and
overall performance.
n Reliable loadbreak switching and fault closure capability.
n Full line of large interface accessory products.
*

Refer to bushing section on page 44 for more information on the bushing.

35 kV Elbow and Accessories Specification Information


To capitalize on the benefits of our 35 kV Large Interface Elbow include the
following information in your specification:
n The

200 A Elbows and Accessories shall be 21.1 kV/36.6 kV three-phase


rated, meeting the requirements of IEEE Std 386 standard interface
No.1A (large 35 kV class interface).

25 kV POSI-BREAK Elbow and Cap


Specification Information
To capitalize on the benefits of the
POSI-BREAK Elbow and Cap, include
the following information for both
the 25 kV 200 A Loadbreak Elbow
and Insulated Protective Cap in your
specification:
elbow and cap must fully
comply with IEEE Std 386
standard.

Shield
Adapter

Loadbreak
Elbow with
Fused
Optional
Loadbreak Integral Loadbreak
Elbow
Jacket
Elbow Connector
Connector Seal
with Test Point
TPR FCI
Loadbreak
Protective
Cap

Jacket
Seal

Bushing Well Insert w/


Latch Indicator Ring

Bushing
Well
Rotatable
Feedthru Insert

Transformer
or Switching
Apparatus

Bushing Well Plug

n Both

n Strike

distance from energized


component to ground shall be
at least 5.6" at 1/2" interface
separation.

n Both

elbow and cap shall have an


insulated probe and conductive
Faraday Cage for relief of electrical
stress and prevention of partial
discharge.

n Semi-conductive

insert shall be
completely surrounded with EPDM
insulating rubber.

One-Piece
Bushing
(35 kV only)

CR & LVR
FCI

ER FCI

Sectionalizing
Cabinets
Loadbreak
Junction
Elbow
Bar
Connector

M.O.V.E.
Elbow
Arrester

Grounding
Elbow

TPR FCI

Standoff
Bushing

Parking
Stand Arrester

FCI
Loadbreak
Elbow Connector

Junction
Bar

EZ II Splice

10

Parking
Stand
Bracket

Portable Feedthru

Loadbreak
Junction

SD Cable Loadbreak
Elbow Connector
Cable Transition Module

Loadbreak
Junction

Bushing
Opening

Catalog Section

Description
Loadbreak Elbow

kV Class
15 kV

Loadbreak Elbow with


Integral Jacket Seal

15 kV

Base Part Number


LE215 CR1 CC1

Notes
1, 2, 4, 5

LEJ215CR1 CC1

1, 2, 3, 5

(see CR1 & CC1 Tables Pg. 13)

-.910 I
100

-2 3 .1 1

17

LE215

78

500-10-7
(see CR1 & CC1 Tables Pg. 13)

200 A
Loadbreak &
Deadbreak
Connectors
1. For an elbow with test point, add
a T after the conductor code (CC1).

500-10-7
Loadbreak Elbow

25 kV

Loadbreak Elbow with


Integral Jacket Seal

25 kV

LE225 CR1 CC1

1, 4, 5

LEJ225CR1 CC1

1, 3, 4, 5

(see CR1 & CC1 Tables Pg. 13)

500-28-7
(see CR1 & CC1 Tables Pg. 13)

500-28-7
POSI-BREAK
Loadbreak Elbow

25 kV

PLE225 CR1 CC1

(see CR1 & CC1 Tables Pg. 13)

1, 4, 5

500-29-7
PLEJ225CR1 CC1

1, 3, 5

15 kV

LFEP215TFEC CR3 CC2 AT

16

25 kV

LFEP225TFEC CR3 CC2 AT

16

POSI-BREAK
Loadbreak Elbow with
Integral Jacket Seal

25 kV

Fused Loadbreak
Elbow Connector

Fused Loadbreak
Elbow Connector

(see CR1 & CC1 Tables Pg. 13)

500-29-7
(see CR3 and CC2 Tables on
page 13
(see Table 500-110 on page 13
for Fuse Ratings and Catalog
Numbers)

500-110

500-111

(see CR3 and CC2 Tables on


page 13
(see Table 500-110 on page 13
for Fuse Ratings and Catalog
Numbers)

LE235 CR2 CC1

1, 4, 5

15 kV

LBI215

Loadbreak Bushing
Insert

25 kV

LBI225

5, 6

Loadbreak
Feedthru Insert

15 kV
25 kV

LFI215
LFI225

Loadbreak Portable
Feedthru

15 kV
horizontal
vertical
universal
25 kV
horizontal
vertical
universal
35 kV
horizontal
vertical

LPF235H
LPF235V

Loadbreak
Junction

15 kV
25 kV
35 kV

LJ215C
LJ225C
LJ235C

Insulated Bushing
Well Plug

15/25 kV

IBWP225

Loadbreak
Protective Cap

15 kV

LPC215

Loadbreak Elbow

35 kV

Loadbreak Bushing
Insert

(see CR2 & CC1 Tables Pg. 13)

500-41

500-12
500-26
500-13
500-30

500-14
Loadbreak Portable
Feedthru
500-31
Loadbreak Portable
Feedthru
500-49
500-15
500-32
500-51
500-20
500-38
500-21

Eaton's Cooper Power Systems

2. For an elbow kit with a hold down


bail assembly included, insert a B
after the test point option code. 15
kV only.
3. For optional braided ground strap/
bleeder wire for termination tape and
wire shielded cable, insert "GS" after
test point and/or bail option code.
4. For individually packaged product
in a corrugated cardboard box,
insert an X as the last character
in the part number.
5. To include the SA Series Cold
Shrinkable Metallic Shield Adapters
Kit or CS Series Cold Shrink Cable
Sealing Kit, add the appropriate
suffix "SA1", "SA2", "SA3", "SA4"
or "CS1", "CS2", or "CS3" to the
end of the loadbreak elbow catalog
number. Refer to Tables CJ1 and
CJ2 on Page 13.
6. To order the long version (extended) of the bushing insert, put in an
L as the seventh character in the
part number.
7. Specify the number of interfaces
by inserting a 2, 3, or 4
directly after the base part number.
8. To add a stainless steel bracket,
insert a B as the last character in
the part number, or to add
U-straps, insert a U as the last
character in the part number.
9. To substitute a stainless steel
bracket, insert a S as the last
character in the part number.
10. Each CS Series Cold Shrink Cable
Sealing Kit includes:
(1) Cold Shrinkable Sleeve
(2) Mastic Sealing Strips
(1) Installation Instructions
For use on Concentric Neutral
Cable.
11. For use with tape shield, drain wire,
linear corrugated and Unishield
cable.

LPF215H
LPF215V
LPF215U

12. Each SA Series Kit includes:


(1) Cold Shrinkable Sleeve
(1) Tinned Copper Ground Strap
with attached elbow drain wire
(1) Constant Force Spring
(1) Semi-Conductive Tape
(3) Mastic Sealing Strips
(1) Installation Instructions

LPF225H
LPF225V
LPF225U

7, 8
7, 8
7, 8

13. Probe kit includes probe,


installation tool, silicone lubricant
and installation instructions.
14. For 200 A loadbreak inserts only.
15. 5 kV cable for luse in 15 kV and 25
kV "CC" size elbow only.

5
(continued next page)

16. Fuses sold separately. See Table


500-110 on page 13. Reference Cat.
240-97.

11

200
AA
Loadbreak
&&
Deadbreak
Connectors
200
Loadbreak
Deadbreak
Connectors
200 A
Loadbreak &
Deadbreak
Connectors
1. For an elbow with test point, add
a T after the conductor code (CC1).
2. For an elbow kit with a hold down
bail assembly included, insert
a B after the test point option
code. 15 kV only.
3. For optional braided ground strap/
bleeder wire for termination tape
and wire shielded cable, insert
"GS" after test point and/or bail
option code.
4. To include the SA Series Cold
Shrinkable Metallic Shield
Adapters Kit or CS Series Cold
Shrink Cable Sealing Kit, add the
appropriate suffix "SA1", "SA2",
"SA3", "SA4" or "CS1", "CS2", or
"CS3" to the end of the loadbreak
elbow catalog number. Refer to
Tables CJ1 and CJ2 on Page 13.
5. For individually packaged
product in a corrugated cardboard
box, insert an X as the last
character in the part number.
6. To order the long version
(extended) of the bushing insert,
put in an L as the seventh
character in the part number.
7. Specify the number of interfaces
by inserting a 2, 3, or 4
directly after the base part number.
8. To add a stainless steel bracket,
insert a B as the last character in
the part number, or to add
U-straps, insert a U as the last
character in the part number.
9. To substitute a stainless steel
bracket, insert a S as the last
character in the part number.
10. Each CS Series Cold Shrink
Cable Sealing Kit includes:
(1) Cold Shrinkable Sleeve
(2) Mastic Sealing Strips
(1) Installation Instructions
For use on Concentric Neutral
Cable.
11. For use with tape shield, drain wire,
linear corrugated and Unishield
cable.
12. Each SA Series Kit includes:
(1) Cold Shrinkable Sleeve
(1) Tinned Copper Ground Strap
with attached elbow drain wire
(1) Constant Force Spring
(1) Semi-Conductive Tape
(3) Mastic Sealing Strips
(1) Installation Instructions

(continued from previous page)

Catalog Section

Description
Loadbreak
Protective Cap

kV Class
25 kV

Base Part Number


LPC225

Notes
5

POSI-BREAK
Loadbreak
Protective Cap

25 kV

PLPC225

Loadbreak
Protective Cap

35 kV

LPC235

Insulated
Standoff Bushing

15 kV

ISB215

Insulated
Standoff Bushing

25 kV

ISB225

Insulated
Standoff Bushing

35 kV

ISB235

SA Series Cold
Shrinkable Metallic
Shield Adapter Kit

15/25/35 kV

SA CJ2

4, 11, 12

CS Series Cold Shrink


Cable Seal Kit

15/25/35 kV

CS CJ1

4, 10

Coppertop Connector
200 A, 2.88" Long
Bi-Metal

15/25/35 kV

200 A Loadbreak
Probe Kit

15 kV
25 kV

500-39

500-37
500-65

500-22

500-40
500-66

500-10-7
500-28-7
500-29-7
500-41
500-10-7
500-28-7
500-29-7
500-41
500-10-7
500-28-7
500-29-7
500-41
Catalog Section
500-12
500-10-7
500-15
500-32
500-51
500-15
500-32
500-51
500-15
500-32
500-51
500-15
500-32
500-51

Silicone Lubricant
Cooper 117

35 kV
15/25/35 kV

(for Elbows and Splices)

Description
Installation and
Torque Tool
Cable Adapter, 5 kV
0.495" - 0.585"
0.575" - 0.685"
U-Strap Kit with
Hardware (1 strap)
for Loadbreak Junction
2-way Stainless Steel
Bracket Assembly for
Loadbreak Junction
3-way Stainless Steel
Bracket Assembly for
Loadbreak Junction
4-way Stainless Steel
Bracket Assembly for
Loadbreak Junction

(see CJ2 Table Pg. 13)

(see CJ1 Table Pg. 13)

CC2C CC1 T

(see CC1 Table Pg. 13)

PK215
PK225
PKPB225 (POSI-BREAK)
PK235
2603393A03

13
13
13
13

(0.175 oz., 5 g packet)

2605670A02M

(5.25 oz., 150 g tube)

kV Class
15/25 kV
15/25 kV
15
25
35
15
25
35
15
25
35
15
25
35

kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV

Base Part Number


LBITOOL

Notes
14

CA225A
CA225B
2625439A16B
2625439A17B
2637570A01B
2637172B01BS
2637160B01BS
2604688B01B
2637172B02BS
2637160B02BS
2604688B02B
2637172B03BS
2637160B03BS
2604688B03B

15
15

13. Probe kit includes probe,


installation tool, silicone lubricant
and installation instructions.
14. For 200 A loadbreak inserts only.
15. 5 kV cable for use in 15 kV and 25
kV CC size elbow only.

12

Specifiers Guide: Components Master Catalog

TABLE CJ1
Use for
Base Number Jacketed Concentric Neutral Cable

TABLE CR1
Use for
Base Number Cable Diameter (Insulation) Range

LE215
LEJ215
LE225
LEJ225
PLE225
PLEJ225

Cable Diameter Range


Inches
Millimeters
0.495-0.585
12.6-14.9
0.575-0.685
14.6-17.4
0.610-0.970
15.5-24.6
0.750-1.080
19.1-27.4
0.890-1.220
22.6-30.0

CABLE RANGE
CODE
CCA*
CCB*
AB
CC
DD

* Uses 5 kV cable adapter. (For use with "CC" range elbow only.)

TABLE CR2
Use for
Base Number Cable Diameter (Insulation) Range
Cable Diameter Range

LE235

CS

Millimeters

CABLE
RANGE CODE

0.825-1.000

21.00-25.40

0.995-1.180

25.20-30.00

1.180-1.340

30.00-34.00

Maximum
Installed
Diameter
(Inches)
1.94
2.67
3.50

CODE
1
2
3

TABLE CJ2
Use for
Base Number Cable Jacket (Outside Diameter) Range

SA

Inches

Minimum Seal
Diameter
Inches
0.950
1.28
1.60

Cable Jacket OD
(Inches)
0.590-1.050
0.830-1.640
1.270-2.170
1.600-2.600

JACKET
CODE
1
2
3
4

TABLE CR3

Use for
Cable Diameter (Insulation) Range for Fused
Base Number Loadbreak Elbow
LFEP215
LFEP225

Cable Diameter Range


Inches
Millimeters
0.610-0.820
15.5-20.8
0.740-0.980
18.8-24.9
0.910-1.180
23.10-29.9

CABLE
RANGE CODE
A
B
C

TABLE CC1
Use for
Base Number Conductor Size and Type

LE215
LEJ215
LE225
LEJ225
PLE225
PLEJ225
LE235
CC2C

Concentric or
Compact or
Compressed
Solid
AWG
mm2
AWG
mm2
No Connector
#6
16
#4
#4
#3
25
#3
25
#2
35
#2
35
#1
#1
1/0
50
1/0
50
2/0
70
2/0
50
3/0
3/0
4/0
95
4/0
95
250
120
250*
120
300
-

CONDUCTOR
CODE
00
01
02
03
04
05
06
07
08
09
10

TABLE CC2

Conductor Size and Type for Fused


Use for
Base Number Loadbreak Elbow

LFEP215
LFEP225
FECC

Class B
Stranded or
Compact or
Compressed
Solid
AWG
mm2
AWG
mm2
No Connector
#2
35
#2
35
#1
#1
1/0
50
1/0
50
2/0
70
2/0
70
3/0
3/0
4/0
95
4/0
95
250*
120
-

CONDUCTOR
CODE
00
03
04
05
06
07
08
09
10

* Compressed stranded only.


Note: Coppertop compression connector may be used on
both alunimum and copper cable conductors.

* Compressed stranding only.

Table 500-110
Fused Loadbreak Elbow Connector Fuse Electrical Ratings and Catalog Numbers
Nominal
System Voltage
Class - kV

15.5

25

Nominal
Nominal Fuse
Fuse Voltage Current rating
Rating kV
in Amperes
6
8
10
12
8.3
18
20
25
30
40
6
8
10
15.5
12
18
20

Fuse Catalog
Number
FEF083A006
FEF083A008
FEF083A010
FEF083A012
FEF083A018
FEF083A020
FEF083A025
FEF083A030
FEF083A040
FEF155A006
FEF155A008
FEF155A010
FEF155A012
FEF155A018
FEF155A020

Maximum Continuous Current


25 C
8.9
12.1
15.0
16.6
21.9
25.5
34.5
40.1
45.5
8.3
11.3
13.9
15.5
20.4
23.7

40 C
8.5
11.7
14.4
16.0
21.1
24.6
33.2
38.7
43.8
8.5
11.7
14.4
16.0
21.1
24.6

65 C
8.0
10.9
13.5
15.0
19.7
23.0
31.1
36.2
41.0
8.0
10.9
13.5
15.0
19.7
23.0

Minimum
Melt It (As)
710
1,000
1,200
1,200
1,500
2,425
4,500
6,000
9,700
710
1,000
1,200
1,200
1,500
2,425

Note: Peak arc voltage levels found during testing were within the values specified for Distribution-Class Current-Limiting Fuses in
ANSI C37.47 Standard - latest edition.

Eaton's Cooper Power Systems

Maximum
Total It (As)
3,800
5,425
5,825
5,825
8,000
12,000
20,500
26,200
39,750
3,800
5,435
5,500
5,500
7,800
12,000

13

200 A Loadbreak & Deadbreak Connectors


200 A LOADBREAK CONNECTORS
1. Bail assembly included in kit.
2. Bail assembly is ordered
separately.
3. See following for appropriate
junction strap. For DJ250-2 order
quantity 2 of 2639524B01. For
DJ250-T2, order quantity 1 of
2638617C01.

Catalog Section

Description

kV Class

Base Part Number

Notes

Deadbreak Elbow

15/25 kV

DE225 CR4 CC3 T

Deadbreak
Straight

15/25 kV

DS225 CR4 CC3 T

Deadbreak
Junction

15/25 kV

DJ250-T2

2, 3

15/25 kV

DJ250-2

2, 3

Insulated
Deadend Plug

15/25 kV

DPD250

Insulated Standoff
Bushing

15/25 kV

DPS250

15/25 kV

DPE250

I550-13

Grounded
Standoff
Bushing

15/25 kV

DRC250

I550-13

Deadbreak
Protective
Cap

15/25 kV

I550-13

Coppertop
Connectors
for Deadbreak
Elbows

15/25 kV

I550-13

Crimp Connectors
for Deadbreak
Straight
Probe and Probe
Wrench for
Deadbreak Elbow

15/25 kV

Bail Assembly
for DE225

15/25 kV

550-10
550-12

(see CR4 & CC3 Tables, page 15)


(see CR4 & CC3 Tables, page 15)
(3-way, Type 2)

I550-12

I550-13

I550-13

I550-13
550-10

14

CC2C CC3 T

(see CC3 Table, page 15)

CC2C CC3 S

(see CC3 Table, page 15)

2638370C01EX
(Probe)

2639205B01

(Probe Wrench)

2638409C06B

Specifiers Guide: Components Master Catalog

Use for
Base Number
DE225
DS225

Use for
Base Number
DE225
DS225
CC2C

TABLE CR4
Cable Diameter (Insulation) Range
Cable Diameter Range
Inches

Millimeters

CABLE
RANGE CODE

0.531-0.685

13.5-17.4

BA

0.640-0.820

16.3-20.8

DA

0.770-0.950

19.6-24.1

FA

0.910-1.130

23.1-28.7

HA

1.100-1.320

27.9-33.5

JA

TABLE CC3
Conductor Size and Type
Concentric or Compressed
AWG
mm2
No Connector
#6
16
#4
#3
25
#2
35
#1
1/0
50
2/0
70
3/0
4/0
95
250*
120
*Compressed stranding only.

Eaton's Cooper Power Systems

Compact or Solid
AWG
mm2
#4
#3
#2
#1
1/0
2/0
3/0
4/0
250
300

25
35
50
70
95
120
-

CONDUCTOR
CODE
00
01
02
03
04
05
06
07
08
09
10

15

200AAStacking
Stacking
Dimensions
200
Dimensions
S4
S3
S6

Dim.

15 kV
3.44"
(87 mm)
4.16"
(106 mm)
2.73"
(69 mm)
1.23"
(31 mm)

S3
S5

S4
S5
S6

25 kV
3.86"
(98.04 mm)
4.54"
(115.32 mm)
3.14"
(79.76 mm)
1.64"
(41.66 mm)

35 kV
4.13"
(105.0 mm)
5.01"
(127.3 mm)
3.58"
(91.0 mm)
1.77"
(45.0 mm)

Elbow Connector (25 kV POSI-BREAK shown)

S2
Dim.

15 kV
6.3"
(160 mm)
5.91"
(150 mm)

A
S2

25 kV
6.3"
(160 mm)
7.34"
(186 mm)

35 kV
7.1"
(181 mm)
11.67"
(296.4 mm)

Insulated Standoff Bushing (25 kV shown)

S4
S3
S1
S1

S6
S2
S2
Dim.

15 kV

25 kV Short

25 kV Long

S1

0.76"
(19.3 mm)

0.76"
(19.3 mm)

0.76"
(19.3 mm)

S2

6.3"
(106 mm)

7.14"
(181.4 mm)

9.97"
(253.2 mm)

Bushing Insert with Latch Ring Indicator (25 kV shown)

S7

S8

S2
S2

S5

AA

Dim.

15 kV

25 kV

7.1"
(179 mm)

7.1"
(179 mm)

S2

9.50"
(241 mm)

11.0"
(279 mm)

Rotatable Feedthru Insert (25 kV shown)

15 kV

S3

Dim.

Horizontal

25 kV
Vertical

Horizontal

5.6"
(142.2 mm)

35 kV
Vertical

Horizontal

5.6"
(142.2 mm)

7.2"
(182.9 mm)

Vertical

8.9"
(226 mm)

8.9"
(226 mm)

11.6"
(294 mm)

6.0"
(153 mm)

6.7"
(171 mm)

8.8"
(224 mm)

3.44"
(87 mm)

3.86"
(98 mm)

3.86
(98 mm)

4.13"
(105 mm)

4.13"
(105 mm)

Dim.

15 kV/25 kV

S3

5.1"
(130 mm)

S3

3.44"
(87 mm)

2.7"
(69 mm)

S4

4.16"
(106 mm)

4.16"
(106 mm)

4.54"
(115 mm)

4.54"
(115 mm)

5.01"
(127.3 mm)

5.01"
(127.3 mm)

S5

2.73"
(69 mm)

2.73"
(69 mm)

3.14"
(80 mm)

3.14"
(80 mm)

3.58"
(91 mm)

3.58"
(91 mm)

S6

1.23"
(31 mm)

1.23"
(31 mm)

1.64"
(42 mm)

1.64"
(42 mm)

1.77"
(45 mm)

1.77"
(45 mm)

S7

0.75"
(19 mm)

0.75"
(19 mm)

0.75"
(19 mm)

0.75"
(19 mm)

0.75"
(19 mm)

0.75"
(19 mm)

S8

7.07"
(180 mm)

7.20"
(183 mm)

8.63"
(219 mm)

8.77"
(223 mm)

11.8"
(300 mm)

11.8"
(300 mm)

Insulated Bushing Well Plug

Loadbreak Portable Feedthru (15 kV shown)


S3

Dim.
S3

15 kV
2.15"
(54.5 mm)

25 kV
2.61"
(66.3 mm)

35 kV
2.66"
(67.5 mm)

Loadbreak Protective Cap (25 kV POSI-BREAK shown)

16

Specifiers Guide: Components Master Catalog

S3

A
E

S10
S7

S11

S9

B
M4
MIN.
MAX.
CONFIGURATION 3*

2.2"
(55 mm)

MIN.
MAX.
CONFIGURATION 2*

M.O.V.E. Arrester

MIN.
MAX.
CONFIGURATION 1*

Dim.
E
S7
S9
S10
S11
M4

Dim.

15 kV
3.25" (83 mm)
0.75" (19 mm)
4.38" (111 mm)
6.77" (172 mm)
9.20" (234 mm)

25 kV
4.0" (102 mm)
0.75" (19 mm)
4.38" (111 mm)
8.34" (212 mm)
10.77" (274 mm)

35 kV
5.0" (127 mm)
1.02" (26 mm)
5.46" (139 mm)
11.8" (299 mm)
13.9" (163 mm)

See Table 15 kV

See Table 25 kV

See Table 35 kV

TABLE 15 kV

S3

15 kV/25 kV
8.5" (216 mm)
10.9" (276 mm)
4.2" (107 mm)

35 kV

13.3" (338 mm)


4.7" (120 mm)

M.O.V.E. Arrester
Dim.

Duty
Cycle (kV)

15 kV/25 kV

35 kV

3-27

8.5" (216 mm)

13.3" (338 mm)

S3

3-27

4.2" (107 mm)

4.7" (120 mm)

Underground Surge Arresters

Physical
Dimensions
in./mm

Configuration 1

Configuration 2

Configuration 3

Min.

Max.

Min.

Max.

Min.

Max.

12.5"
(318
mm)

6.0"
(152
mm)

10.8"
(275
mm)

14.4"
(366
mm)

7.2"
(183
mm)

10.8"
(275
mm)

3.6"
(92
mm)

7.2"
(183
mm)

19.6"
(498
mm)

9.2"
(230
mm)

14.7"
(374
mm)

18.3"
(465
mm)

11.1"
(282
mm)

14.7"
(374
mm)

7.4"
(188
mm)

11.1"
(282
mm)

22.9"
(582
mm)

12.4"
(315
mm)

17.9"
(455
mm)

21.5"
(547
mm)

14.3"
(364
mm)

17.9"
(455
mm)

10.7"
(272
mm)

14.3"
(364
mm)

Number
of
Interfaces

Duty
Cycle (kV)
9-15
18-27
9-27

M4 Mounting Dimensions in./mm

Configuration 1. Both feet turned out.


Configuration 2. One foot turned out, one in.
Configuration 3. Both feet turned in.

TABLE 25 KV
Number
of
Interfaces

Physical
Dimensions
in./mm

M4 Mounting Dimensions in./mm


Configuration
1

Configuration
2

Configuration
3

Min.

Max.

Min.

Max.

Min.

Max.

14.2"
(361
mm)

6.7"
(170
mm)

11.9"
(302
mm)

15.6"
(396
mm)

8.0"
(203
mm)

11.7"
(297
mm)

4.2"
(107
mm)

7.8"
(198
mm)

23.0"
(584
mm)

10.7"
(272
mm)

16.8"
(427
mm)

20.4"
(518
mm)

12.9"
(328
mm)

16.5"
(419
mm)

9.0"
(229
mm)

12.6"
(320
mm)

27.0"
14.7"
20.8"
24.4"
(686
(373
(528
(620
mm)
mm)
mm)
mm)
Configuration 1. Both feet turned out.
Configuration 2. One foot turned out, one in.
Configuration 3. Both feet turned in.

16.9"
(429
mm)

20.5"
(521
mm)

13.0"
(330
mm)

16.6"
(422
mm)

Number
of
Interfaces

Mounting Dimensions in./mm


A

23.1"
(587
mm)

8.8":
(223
mm)

**

**

33.3"
(846
mm)

13.8"
(350
mm)

**

**

38.5"
(978
mm)

18.8"
(477
mm)

**

**

MOV Parking Stand Arrester


Dim.
A
B

TABLE 35 kV

2.2"
(55 mm)

S8

S8

Duty
Cycle (kV)
9-15
18-21
9-15
18-21
9-21

15 kV
11.9" (302 mm)
14.5" (368 mm)
8.0" (203 mm)
10.6" (269 mm)
7.4" (188 mm)

25 kV
11.9" (302 mm)
14.5" (368 mm)
8.0" (203 mm)
10.6" (269 mm)
7.4" (188 mm)

MOV Parking Stand Arrester

** Refer to Catalog
Section 500-51 for
detailed drawing of 35 kV
junction.

Dim.
A
B
S8

Duty
Cycle (kV)
3-21
3-21
3-21

15 kV
11.9" (302 mm)
8.0" (203 mm)
7.4" (188 mm)

25 kV
11.9" (302 mm)
8.0" (203 mm)
7.4" (188 mm)

Parking Stand Arresters

Loadbreak Junctions (15 kV shown)

Eaton's Cooper Power Systems

17

600 A Loadbreak Connectors


Clr Loadbreak Connector: New 600 Amp Loadbreak Technology Provides Efficient,
Reliable Visible Break and Visible Ground
15 kV Class 600 A Clr Loadbreak
Connector System Ratings
Clr Loadbreak Connector System
The Clr Loadbreak Connector System is a 600 A
loadbreak device rated for operation on 15 and 25 kV class
systems. It is used to provide a visible break and visible ground
on 600 A network and distribution systems without having to
remove 600A terminations and move heavy cable. The Clr
Loadbreak connector System is fully shielded, submersible and
meets the applicable requirements of IEEE Std 386-2006
standard - "Separable Insulated Connector Systems".
Many configurations are possible with this connector system.
Under normal operating conditions, the current path is through
one of the 600 A loadbreak/deadbreak 2-position junctions
(DLJ6_ _), through the 600 A loadbreak "C" (LCN) connector
and through the second 600 A loadbreak/deadbreak junction.
When isolating underground cable, with the system energized
or de-energized, with or without rated load current, with the
use of a clampstick, the LCN connector can be removed. A
600 A loadbreak protective cap (LPC6_ _) can then be installed
on the two exposed loadbreak interfaces. All bushings of the
connector system are then insulated and deadfront. If a 600A
termination with a 200 A reducing tap plug is used on the
IEEE Std 386-2006 standard 600 A 15/25 kV deadbreak
interfaces of the junction, a grounding elbow can be installed,
providing a visible ground. It is then safe to perform work on the
underground cable.
Once an underground circuit is sectionalized, for maximum
safety, a visible break and visible ground must be achieved
prior to performing any repair or maintenance. Distribution
feeders can easily retrofit the Clr Loadbreak Connector
System into 600 A applications, allowing operators confidence
when working on a piece of underground equipment or cable
as they can clearly see the open circuit.
Clr Loadbreak Connectors allow the operator to safely pull the
loadbreak interface while the system is energized to sectionalize
the system into smaller segments to prevent taking longer
outages. The Clr 600 A Loadbreak Connector makes this easy:
The C-shaped connector breaks the circuit in two places
for twice the contact separation.
The new Clr Loadbreak Connector incorporates fieldproven Cooper Power Systems POSI-BREAK technology which provides:
Increased strike distance, greatly reducing the
possibility of partial vacuum flashovers
Added dielectric strength along the probes for superior
switching performance and reliability
The remainder of this simple system consists of:
Two Cooper Power Systems 600 A loadbreak interfaces
Two IEEE Std 386-2006 standard 600 A deadbreak
interfaces
A yellow latch indicator is included to assure positive connection
Fully submersible, and exceeds the applicable
requirements of IEEE Std 386-2006 standard for use in
above- and underground environments prone to flooding
When using BT-TAP or T-OP II connectors a visible
ground can be achieved by connecting a grounding
elbow directly to a 200 A loadbreak reducing tap plug.

18

600 A Loadbreak Interface


Continuous Current
600 A rms
Ten make and break operations at 600 A
at 14.4 kV Phase-Phase
Loadbreak Switching
Three make and break operations at 900
A at 14.4 kV Phase-Phase
16 kA rms symmetrical at 14.4 kV
Phase-Phase after ten 600 A loadbreak
switching operations for 0.17 seconds
Fault Closure
16 kA rms symmetrical at 14.4 kV
Phase-Phase after three 900 A loadbreak
switching operations for 0.17 seconds
4 Hour Overload Current

900 A rms

16 kA rms symmetrical for 0.17 seconds


(limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV Deadbreak
Interface
Continuous Current
600 A rms
4 Hour Overload Current 900 A rms
16 kA rms symmetrical for 0.17 seconds
Short Time Current
10 kA rms symmetrical for 3.0 seconds
Short Time Current

25 kV Class 600 A Clr Loadbreak


Connector System Ratings
600 A Loadbreak Interface
Continuous Current
600 A rms
Five make and break operations at 600 A
at 26.3 kV Phase-Phase
Loadbreak Switching
One make and break operation at 900 A
at 26.3 kV Phase-Phase
10 kA rms symmetrical at 26.3 kV
Phase-Phase after five 600 A loadbreak
switching operations for 0.17 seconds
Fault Closure
10 kA rms symmetrical at 26.3 kV
Phase-Phase after one 900 A loadbreak
switching operations for 0.17 seconds
4 Hour Overload Current

900 A rms

10 kA rms symmetrical for 0.17 seconds


(limited by fault closure rating)
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV Deadbreak
Interface
Continuous Current
600 A rms
4 Hour Overload Current
900 A rms
10 kA rms symmetrical for 0.17 seconds
Short Time Current
10 kA rms symmetrical for 3.0 seconds
Short Time Current

Current ratings and characteristics are in accordance with applicable IEEE Std
386-2006 standard requirements.

Specifiers Guide: Components Master Catalog

600 A Loadbreak Connectors


12.0
305
.8
19
2.0
51

Catalog Section

7.0
178
7.0
178

12.0
305

Description
Loadbreak Connector
Assembly includes: two
loadbreak/deadbreak
junctions with
loadbreak "C"
connector assembled in
an In-Line SS Bracket

kV Class
15 kV

Base Part Number


LCN2DLJ615_ _ILB

Notes

1. Recessed base allows for an


additional 1-1/2" stacking from
backplate.
2. A 30" deep SecTER cabinet is
required if a 200 A fused loadbreak
elbow is installed.

Loadbreak Connector
Assembly includes:
two loadbreak/
deadbreak junctions
with loadbreak "C"
connector assembled in
a Square SS Bracket

LCN2DLJ615_ _SQB

Loadbreak "C"
Connector

LCN615

.8
19

600-100

2.0
51

7.0
178
7.0
178

600-101

Loadbreak Protective Cap


Loadbreak Connector
Assembly includes:
two loadbreak/
deadbreak junctions
with loadbreak "C"
connector assembled in
an In-Line SS Bracket

25 kV

LPC615
LCN2DLJ625___ILB

Loadbreak Connector
Assembly includes:
two loadbreak/
deadbreak junctions
with loadbreak "C"
connector assembled in
a Square SS Bracket

LCN2DLJ625___SQB

Loadbreak "C"
Connector

LCN625

Loadbreak Protective Cap


Accessories:

LPC625

Loadbreak Standoff
Bushing (Parking Stand
Mount)

15/25 kV

PS625CLEER

Loadbreak Standoff
Bushing (Direct Wall
Mount)
Clr SecTER
12 Gauge Steel Tank
1-Phase

15/25 kV

PS625CLEERDM

15 kV

SEC1P15CLEERA2
(30H x 24W x 22D)
SEC1P15CLEERA2DP
(30H x 24W x 30D)
SEC3P15CLEERA2
(30H x 66W x 22D)
SEC3P15CLEERA2DP
(30H x 66W x 30D)
SEC1P15CLEERA2L
(30H x 24W x 22D)
SEC1P15CLEERA2DPL
(30H x 24W x 30D)
SEC3P15CLEERA2L
(30H x 66W x 22D)
SEC3P15CLEERA2DPL
(30H x 66W x 30D)
SEC1P25CLEERA2
(30H x 24W x 22D)
SEC1P25CLEERA2DP
(30H x 24W x 30D)
SEC3P25CLEERA2
(30H x 66W x 22D)
SEC3P25CLEERA2DP
(30H x 66W x 30D)
SEC1P25CLEERA2L
(30H x 24W x 22D)
SEC1P25CLEERA2DPL
(30H x 24W x 30D)
SEC3P25CLEERA2L
(30H x 66W x 22D)
SEC3P25CLEERA2DPL
(30H x 66W x 30D)

12 Gauge Steel Tank


3-Phase
Aluminum
1-Phase
Aluminum
3-Phase
12 Gauge Steel Tank
1-Phase
12 Gauge Steel Tank
3-Phase
Aluminum
1-Phase
Aluminum
3-Phase
1000-20

25 kV

Notes
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2
1, 2

Clr Ground Sleeves continued on Page 20

Eaton's Cooper Power Systems

19

600 A Loadbreak Connectors


Catalog Section

Description
kV Class
Clr GROUND SLEEVES
Fiberglass Ground
15/25 kV
Sleeve 1-Phase

Mild Steel Ground


Sleeve 1-Phase
Fiberglass Ground
Sleeve 3-Phase

15/25 kV

Mild Steel Ground


1000-20 Sleeve 1-Phase

Base Part Number

Notes

00400L00K02G
(18H x 24W x 22D)
00400L00K05G
(30H x 24W x 22D)
00450L00K32G
(18H x 24W x 30D)
0400L00K10GM
(24H x 24W x 22D)
00450L00K05G
(18H x 66W x 22D)
00450L00K08G
(30H x 66W x 22D)
00450L00K35G
(18H x 66W x 30D)
0450L00K18GM
(24H x 66W x 22D)

31.50
12.0
REF

IMPORTANT: A 30"
deep SecTER cabinet
is required if a 200A
fused loadbreak
elbow is installed.

30.00 REF

24.40

17.00

30.00 REF

24.00 REF

Single-phase SecTER Cabinet, Catalog Number SEC1P__CLEERA2DP.


31.50
12.0
REF

3.18

30.00 REF

24.40

19.79

17.00

66.00 REF

30.00 REF

Three-phase SecTER Cabinet, Catalog Number SEC3P__CLEERA2DP.

20

Specifiers Guide: Components Master Catalog

600 A Loadbreak Dimensions


26.88
[ 682.8

20.08
[ 510 ]
5.00
[ 127 ]

4.00
[ 101.6 ]

3.0

16.27

[ 76 ]

[ 413.3 ]
8.93
[ 226.8

]
2.04
[ 51.8 ]

4.64
[ 117.9 ]

14.4
[ 366 ]
18.1

6.3

[ 459 ]

[ 161 ]

CONFIGURATION - 3
20.0
[ 508 ]

Clr Loadbreak Connector Assembly


(In-Line SS Bracket).

20.0
[ 508 ]
CONFIGURATION - 2
21.9
[ 557 ]
25.6
[ 649 ]
CONFIGURATION - 1

12.79
(324.9 )
10.21
(259.3 )

5.0
(127 )

4.0
(101.6 )

15.30
(388.6 )

3.0
(76 )

7.90
(200.7 )
3.55
(90.2 )

10.5
(264 )

12.0
(305 mm)

.530
(13 mm)

1.0
(25 mm)

.8
(20 mm)
2.0
(51 mm)

11.5
(292 )

Clr Loadbreak Connector Assembly


(Square SS Bracket).

1.5
(38 )
7.0
(178 mm)

3.5
(89 )

7.0
(178 mm)

7.0
(178 )

Eaton's Cooper Power Systems

21

600/900
Deadbreak
Connectors
600
A/900 AADeadbreak
Connectors

200 A LOADBREAK & DEADBREAK CONNECTORS

Our 600/900 A Deadbreak Connector Systems are designed


to fill the demand for a deadfront underground installation
in 600/900 A main and lateral feeders. They provide a
completely shielded, deadfront, fully submersible cable
connection for high-voltage apparatus such as transformers,
switchgear, large motors, etc., and can also be used to make
splices, junctions, taps and deadends for main underground,
distribution feeders. They provide the same high degree of
operating flexibility and reliability as our 200 A products. All
components fit together easily and assembly variations are
available.
These connector systems are designed for installation on
various types of cables. The entire system can be applied to
concentric neutral cable, and with our CS & SA Series Shield
Adapter Kits to almost any other type of cable.
All of our Deadbreak Connectors meet the electrical,
mechanical and dimensional requirements of IEEE Std 386
standard and are designed to be fully interchangeable with
those currently available from other major manufacturers.
900 A RATING
A 900 A continuous rating can be achieved with BOL-T,
BT-TAP and T-OP II Systems when used with a coppertop
compression connector and all copper mating components
including apparatus bushing or junction. (See note 1 on page
23 for details when selecting a system.)

contact design eliminates cross-threading and normal thread


wear during repeated sectionalizing operations. It is the only
available system that allows operators to move the terminator
while it is fully grounded. The PUSH-OP System provides
stainless steel bracketry and a mechanical lever for the fastest
and easiest one-person hotstick operation possible. The
PUSH-OP System requires special apparatus bushings, which
makes it suitable for new installations only.

BOL-T Connector System


Our BOL-T Deadbreak Connector System is designed for
use on applications where the terminations would not be
operated after installation, would not need a 200 A interface
for grounding or arrester provisions, and would not require
direct conductor testing or the use of a hotstick. It is a bolted
design that is interchangeable with other manufacturers
bolted 600/900 A systems and requires no special tools for
installation.

U-OP Connector System


Our U-OP Deadbreak Connector System is used with
T-OPII and designed to provide a visible break and visible
ground without having to move large 600 A cable. The U-OP
System requires special apparatus bracketry, which makes it
suitable for new installations only.

BT-TAP Connector System


Our BT-TAP Deadbreak Connector System includes a 200A
loadbreak tap instead of the standard insulated plug. The
other components of BT-TAP are the same as BOL-T, making
it an ideal option to retrofit existing BOL-T (or other bolted
systems that use unthreaded compression connectors)
systems with a 200 A loadbreak tap for testing, grounding, or
overvoltage protection.
T-OP II Connector System
Our T-OP II Deadbreak Connector
System also has a 200 A loadbreak tap and
has all the advantages of the BT-TAP
System. In addition, the T-OP II is
single-person hotstick operable, making ER FCI
it ideal for terminations that may
require moving or sectionalizing to
achieve a visible open or visible
ground. The T-OP II design offers
added reliability (900 A rated all
copper alloy current path and copper
top connector) and has several
assembly/operating advantages.
PUSH-OP Connector System
Our PUSH-OP Deadbreak Connector
System is essentially a T-OP II
Termination with a non-bolted design
for use on any deadfront apparatus
where the terminations may be
operated frequently. The PUSH-OP
600 A deadbreak probe and finger

22

Note: 600 A Separable Splice kits can be found in the splice section starting

on page 36.
Bushing
Adapter
U-OP Connector**
Loadbreak
Elbow with
Fused
Optional
Loadbreak Integral
Elbow
Jacket
200 A
Connector Seal
Loadbreak Elbow
FCI

Deadbreak
Junction
T-OP II Connector

200 A
Protective
Cap

BOL-T Connector
600 A
Protective
Cap

M.O.V.E. Arrester

Bushing
Adapter

One-Piece
Bushing

Grounding Elbow
Type L
Cutout

BOL-T
Connector

Transformer
or Switchgear
Apparatus

BT-TAP Connector
Sectionalizing
Cabinets

FCI

Parking
Stand
Bracket

Junction
Bars

UltraSIL
Arrester

TPR FCI

Deadbreak
Junction

T-OP II
Connector/
BT-TAP
Connector

Shield
Adapter

PUSH-OP
Connector*

Loadbreak
Protective Cap
CR & LVR FCI

CR FCI

T-OP II
BOL-T
Splice
Connecting Plug
Cable Transition Module

BOL-T

Junction
Bars
Deadbreak Junction

requires modified bushing and tank hardware.


* PUSH-OP
** U-OP requires frontplate stud provisions. Refer to Installation Instructions S600-14-1 for details.

Standoff
Bushing

Catalog Section
600-10
600-30
600-50

Description

kV Class

BOL-T
Connector Kit

15/25 kV
35 kV

BT-TAP
Connector Kit

15 kV
25 kV

600-15
600-35
600-55

35 kV
T-OP II
Connector Kit

15 kV
25 kV

600-12
600-32
600-52

35 kV
PUSH-OP
Connector Kit

15 kV
25 kV

600-13
600-33
600-53
600-34
600-18
600-38
600-59
600-19
600-39
600-58

35 kV

Base Part Number

Notes

BT625 CR5 CC4

1, 2, 3, 4, 13,
14

BT635 CR6 CC4

1, 2, 3, 4, 13,
14

BTP615 CR5 CC4

1, 2, 3, 4, 6,
13, 14

BTP625 CR5 CC4

1, 2, 3, 4, 6,
13, 14

(see CR6 & CC4 Tables pg. 24)

BTP635 CR6 CC4

1, 2, 4, 6, 13,
14

TP615 CR5 CC4

2, 5, 6, 13, 14

TP625 CR5 CC4

2, 5, 6, 13, 14

TP635 CR6 CC4

2, 5, 6, 13, 14

POP615 CR5 CC4

2, 5, 6, 13, 14

POP625 CR5 CC4

2, 5, 6, 13, 14

POP635 CR6 CC4

2, 5, 6, 13, 14

(see CR5 & CC4 Tables pg. 24)


(see CR6 & CC4 Tables pg. 24)
(see CR5 & CC4 Tables pg. 24)
(see CR5 & CC4 Tables pg. 24)

(see CR5 & CC4 Tables pg. 24)


(see CR5 & CC4 Tables pg. 24)
(see CR6 & CC4 Tables pg. 24)
(see CR5 & CC4 Tables pg. 24)
(see CR5 & CC4 Tables pg. 24)
(see CR6 & CC4 Tables pg. 24)

U-OP
Connector Kit

15/25 kV

UOP625

Bushing Adapter
with LRTP
(Stud-T Included)

15 kV

DBA615

25 kV

DBA625

35 kV

DBA635

PUSH-OP Bushing
Adapter

Standoff
Bushings

15 kV

PDBA615

25 kV

PDBA625

35 kV

PDBA635

ISB625A

ISB625C

7, 8

ISB635A

7, 8

ISB635C

15/25 kV

(Aluminum)
(Copper)

35 kV
600-44
600-64

(Copper)

PUSH-OP
Standoff Bushings

DEADBREAK

15/25 kV

HERE

600-25
600-45
600-65

PISB625
PISB625HP

(with hitch pin)

RTE
PUSH

(Aluminum)

35 kV

PISB635
PISB635HP

(with hitch pin)

Standard
Protective Cap

15/25 kV

DPC625

DPC635

600-43
600-63

(with Permanent Stud)

35 kV

600-43
600-63

Protective Cap
for T-OP II and
U-OP

15/25 kV

DPC625UT

35 kV

DPC635UT

Deadbreak
Junctions

15/25 kV

DJ625A_

10, 11

DJ625C_

10, 11

(Aluminum)
(Copper)

35 kV
600-42
600-62

500-95

DJ635A_

10, 11

DJ635C_

10, 11

SA CJ3

12, 13, 14

CS CJ4

13, 14

(Aluminum)
(Copper)

SA Series Cold
Shrinkable Metallic
Shield Adapter Kit

15/25/35 kV

CS Series Cold
Shrinkable Metallic
Cable Seal Kit

15/25/35 kV

Eaton's Cooper Power Systems

(see CJ3 Table pg. 24)

(see CJ4 Table pg. 24)

1. Determine whether all aluminum


components or all copper
components are required:
BOL-T Kit with 600 A Rating - Insert
"A" in digit 10 (digit 9 for 35 kV) for
Aluminum.
BT-TAP Kit with 600 A Rating Insert "A" in digit 11 (digit 10 for 35
kV) for Aluminum.
BOL-T Kit with 900 A Rating - Insert
"C" in digit 10 (digit 9 for 35 kV) for
Copper (includes coppertop compression connector).
BT-TAP Kit with 900 A Rating Insert "C" in digit 11 (digit 10 for 35
kV) for Copper (includes coppertop
compression connector).
2. To specify an ALL copper connector,
add 50 to the conductor code from
Table CC4 (page 24). Example:
CC6C11T becomes CC6C61T.
3. To specify a stud:
BOL-T Kit - insert a "1" in digit 11 to
include stud, or a "2" in digit 11 for
kit without stud.
BT-TAP Kit - insert "S" in digit 12
to include standard length stud or
"L" in digit 12 to include extended
length stud.
4. To specify T-Body with test point
(optional):
BOL-T Kit - insert a "T" in digit 12.
BT-TAP Kit (15 & 25 kV) - insert a "T"
in digit 13.
BT-TAP Kit (35 kV) - insert a "T" in
digit 11.
5. For T-OP II and PUSH-OP kits only, to
specify a T-body with test point, add
T after the conductor code.
6. To specify a BOL-T, BT-TAP or T-OP
II kit with a loadbreak protective
cap, insert a "C" after the test point/
non-test point option. Bushing
Adapters - insert a "C" as the last
character of the part number. Note:
25 kV kits include a POSI-BREAK
protective Cap.
7. To specify stud in kit, add SA for
aluminum stud (only available with
aluminum interface); add SC for
copper stud; add ST for T-OP II
stud; or add SU for U-OP stud as
the last characters in the part number.
8. To specify a grounded standoff
bushing, replace the I with a G as
the first character in the part number.
9. For individually packaged product in
a corrugated cardboard box, insert an
X as the last character in the part
number.
10. It is required to specify the number of
interfaces by inserting a 2, 3, or 4
directly after the base part number.
11. To add a stainless steel bracket,
insert a B; or to add U-straps, insert
a U as the last character in the part
number.
12. For use with tape shield, drain wire,
linear corrugated, and Unishield cable.
13. To add a CS Series Sealing kit or a
SA Series Adapter kit to the 600 A
connector kit, add a SA _ or CS_
at end of catalog number. Refer to
Table CJ3 or CJ4 on page 24.
14. Each SA Series Kit includes:
(1) Cold Shrinkable Sleeve (1) Tinned
Copper Ground Strap with attached
elbow drain wire (1) Constant Force
Spring (1) Semi-Conductive Tape (3)
Mastic Sealing Strips (1) Installation
Instructions.
Each CS Series Sealing Kit includes:
(1) Cold shrinkable sleeve, (3) Mastic
sealing strips, and (1) Installation
Instructions.

23

600 A Deadbreak Connectors

600/900
200 AALoadbreak
Components
& Deadbreak
& Replacement
Connectors
Parts
200 A LOADBREAK & DEADBREAK CONNECTORS

TABLE CR5
Use for
Base Number Cable Diameter (Insulation) Range

BT625
BTP615
BTP625
TP615
TP625
POP615
POP625
CA625

Use for
Base Number

TABLE CR6
Cable Diameter (Insulation) Range
Cable Diameter Range

Cable Diameter Range


Inches

mm

CABLE RANGE
CODE

0.610-0.970

15.5-24.6

AB

0.750-1.080

19.1-27.4

CC

0.970-1.310

24.6-33.3

DD

BT635
BTP635
TP635
POP635
CA635

Inches

mm

CABLE RANGE
CODE

0.875-0.985

22.2-25.0

0.930-1.040

23.6-26.4

0.980-1.115

24.9-28.3

26.4-29.8

G
H

1.090-1.470

27.7-37.3

EE

1.040-1.175

1.260-1.640

32.0-41.7

FF

1.095-1.240

27.8-31.5

1.360-1.710

34.5-43.4

GG

1.160-1.305

29.5-33.1

31.0-34.9

1.500-1.850

38.1-47.0

HH

1.220-1.375

1.700-1.970

43.2-50.0

JJ

1.285-1.395

32.5-35.4

1.355-1.520

34.4-38.6

1.485-1.595

37.7-40.5

1.530-1.640

38.9-41.7

1.575-1.685

40.0-42.8

1.665-1.785

42.3-45.3

1.755-1.875

44.6-47.9

1.845-1.965

46.9-50.0

1.960-2.210

49.8-56.1

TABLE CC4

Use for
Conductor Size and Type
Base Number
BT625
BT635
BTP615
BTP625
BTP635
TP615
TP625
TP635
POP615
POP625
POP635
CC6A _ U
CC6C _ T
CC6C _ U

Concentric or
Compact or
Compressed
Solid
AWG or kcmil
mm2
AWG or kcmil
mm2
No Connector
#2
35
1
_
#1

1/0
50
1/0
50
2/0
70
2/0
70
3/0

3/0

4/0
95
4/0
95
250
120
250
120
300

300

350

350

400
185
400
185
450

240
450

500a
500
240
600
300
600
300
700

750c

650b
750d

900

900

1000
500
1000
500

1250
630

a. Also
b. Also
c. Also
d. Also

accepts
accepts
accepts
accepts

550
700
800
700

kcmil
kcmil
kcmil
kcmil

compact conductor.
compressed conductor.
compact conductor.
concentric conductor.

TABLE CJ3
Use for
Base Number Cable Jacket (Outside Diameter) Range

SA

24

Cable Jacket
OD (Inches)
0.590-1.050
0.830-1.640
1.270-2.170
1.600-2.600

CONDUCTOR
CODE
00
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

JACKET
CODE
1
2
3
4

Use for
Base Number
CS

TABLE CJ4
Jacketed Concentric Neutral Cable
Minimum
Seal
Diameter
(Inches)

Maximum
Installed Diameter
(Inches)

CODE

.950

1.94

1.28

2.67

1.60

3.50

Specifiers Guide: Components Master Catalog

600 A/900 A Components and Replacement Parts

200 A Loadbreak & Deadbreak Connectors

Catalog Section

Description
T-Body

Base Part Number


DT625
DT635

Cap for
Insulating
Plug

15/25/35 kV

DIPCAP

2. To add stud to kit, add a SA for


an aluminum stud, or a SC for a
copper stud as the last characters
in the part number.

Insulating
Plug
w/o Stud
(cap included)

15/25 kV

DIP625A

3. To add STUD to kit, add a S after


the base part number. Material of
stud supplied will match with material of the plug conductor ordered.

600-46
600-66
600-46
600-66

3, 7

DIP625C
(Copper)

35 kV
600-46
600-66

DIP635A

(Aluminum)

3, 7

(Copper)

15/25 kV

DCP625A
(Aluminum)

3, 7

DCP625C
(Copper)

35 kV

DCP635A
(Aluminum)

3, 7

DCP635C
(Copper)

BOL-T
Stud

15/25 kV

STUD-A
(Copper)

600-66
600-46
600-66
600-46
600-66
600-46
600-66
600-46
600-66

600-46
600-66
600-46
600-66
600-46
600-66

600-46
600-66
600-46
600-66
600-18
600-38
600-59
600-18
600-38
600-59
600-18
600-38
600-59
600-18
600-38
600-59

STUD635-A
(Copper)

15/25/35 kV

STUD-T

15/25/35 kV

STUD-U

15/25/35 kV

15/25/35 kV

15/25/35 kV

15/25 kV
35 kV

(see CC4 Table pg. 24)

CC6C CC4 U

(see CC4 Table pg. 24)

10. TWRENCH allows for installation of


loadbreak reducing tap plug for
BT-TAP or T-OP II Connector.
11. HD6_ allows for installation of
connecting plug in 600 A Separable
Splices.

CC6A CC4 U

(see CC4 Table pg. 24)

CC6C CC4 T

7. Stud comes loose in kit, add a P


as the last character for permanent
factory installation.

9. OTTQ6_ allows for installation and


single hotstick operation of either the
BT-TAP or T-OP II Connector.

(Aluminum)

STUD635-C
T-OP II
Stud
U-OP
Stud
11/16 in. Unthreaded
Aluminum
Compression
Connector
15/16 in.
Threaded Coppertop
Compression
Connector
11/16 in.
Unthreaded
Coppertop
Compression
Connector
Cable
Adapter

6. To specify an all copper connector, add 50 to the conductor code


from Table CC4 (page 24). Example:
CC6C11T becomes CC6C61T.

8. TQHD6_ allows for installation of


either BT-TAP or T-OP II Connector
to 600 A bushing.

(Aluminum)

STUD-C

35 kV

4. Copper alloy stud for use with


T-OP II Connectors only.
5. Copper stud for use with U-OP
Connector only.

DIP635C

Connecting
Plug
w/o Stud

600-46
600-66
600-46

(Aluminum)

Notes
1, 2
1, 2

1. To specify a test point insert a T


in the sixth digit.

kV Class
15/25 kV
35 kV

12. Specify "A" for 600 A rating or "C"


for 900 A rating in digit 9.
13. To add standard length stud to kit,
add "S" to end of part number.
To add an extended length stud to
kit add "L" to end of part number.

CA625 CR5

(see CR5 Table pg. 24)

CA635 CR6

(see CR6 Table pg. 24)

BT-TAP and T-OP II


Installation and
Torque Tool

15/25 kV
35 kV

T-OP II Combination
Operating, Test,
and Torque Tool
(For single person
hotstick operation)
T-WRENCH for
BT-TAP/T-OP II
5/16" Hex Shaft
with 3/8" Socket
Drive Tool
Bushing
Extender

15 kV
25 kV
35 kV

TQHD625
(15/25 kV-T-OP II Only)
TQHD635
(35 kV T-OP II Only)
OTTQ615
OTTQ625
OTTQ635

9
9
9

15/25/35 kV

TWRENCH

10

15/25 kV
35 kV

HD625
HD635

11
11

15/25 kV
35 kV

DBE625
DBE635

2
2

Loadbreak
Reducing Tap Plug
for T-OP II
(Stud-T included)

15 kV
25 kV
35 kV

LRTP615
LRTP625
LRTP635

BOL-T Loadbreak
Reducing Tap Plug
for BT-TAP

15 kV
25 kV
35 kV

BLRTP615
BLRTP625
BLRTP635

Eaton's Cooper Power Systems

12, 13
12, 13

25

600/900
200 AALoadbreak
Connector&Systems
Deadbreak Connectors
200 A LOADBREAK & DEADBREAK CONNECTORS
BOL-T Connector System

BT-TAP Connector System

The BOL-T Deadbreak Connector System is designed for


use on applications that will not be operated, do not need
grounding or arrester provisions, and do not require direct
conductor testing or the use of a hotstick. It is a bolted design
that is interchangeable with other manufacturers bolted 600 A
systems that require no special tools for installation.
The capacitive test point on the insulating plug provides a
means of confirming an energized circuit without disturbing
the bolted connection. In addition to the capacitive test point
feature on the insulating plug, we offer a capacitive test point
on the T-Body. This allows the use of our Type TPR Series
Faulted Circuit Indicators, and provides a means of confirming that a circuit is energized when used with high impedance
voltage sensing devices designed for test points.
Refer to Figure 1 for BOL-T Connector Kit Components.

The BT-TAP Deadbreak Connector System is designed for


use on applications where a 200 A interface is required for
testing, grounding, or overvoltage protection. It is primarily
used in retrofit applications of existing 600 A or 900 A BOL-T
installations (or other bolted systems that use unthreaded
compression connectors).
The BT-TAP Connector System uses the standard unthreaded
compression connector, which makes it ideal for retrofitting
existing BOL-T installations into a system with a 200A tap.
The BT-TAP provides the following features:
n Visible ground and visible break
n 200 A Interface for:
addition of our M.O.V.E. Arresters for overvoltage
protection
addition of our Grounding Elbows
access for direct conductor phasing and testing
hipot testing of switch or cables
Refer to Figure 2 for BT-TAP Connector Kit Components.

Installation of BOL-T on a 600/900 A Bushing


The BOL-T Connector is installed on any 600/900 A bushing
using a standard 1-inch socket. No special tools are required.

Installation of BT-TAP on a 600 A Bushing


The BT-TAP Connector is installed on an apparatus bushing
using a 600 A Torque Tool.

BOL-T Specification Information


To specify the BOL-T Connector System, include in your
specification:
n The

system must fully comply with IEEE Std 386 standard.

n All

BT-TAP Specification Information

cable adapters, insulating plugs, compression connectors


and other component parts must be interchangeable with other
manufacturers.

n For

900 A rating, full copper current carrying path with


coppertop compression connector, copper stud and insulating
plug with copper insert.

n BOL-T

Connector System base part number BT625 for 15 kV


and 25 kV systems and BT635 for 35 kV systems.

To specify a BT-TAP Connector System, include in your


specification:
n The

system must fully comply with IEEE Std 386 standard.

n The

connector system must provide operation with hot line


tools, direct conductor phasing and testing.

n It

must provide a location to add overvoltage arresters and


access for direct conductor phasing or hipot testing of switch
or cables.

n Must

be easy to install with proper torque such that concern


for cross threading is eliminated.

n Loadbreak

reducing tap plug must include latch indicator ring.

n BT-TAP

Connector System base part number BTP615 (A) (C) for


15 kV, BTP625 (A) (C) for 25 kV and BTP635 for 35 kV.

INSULATING PLUG WITH BOL-T


STUD (STUD-A)
DIP625AS
DIP635AS

T-BODY
DT625
DT635

ALUMINUM COMPRESSION
CONNECTOR 11/16"
UNTHREADED HOLE
CC6A _ _ U

LOADBREAK REDUCING
TAP PLUG
BLRTP615 (A) (C)
BLRTP625(A) (C)
BLRTP635

CABLE
ADAPTER
CA625
CA635

Figure 1.
BOL-T Connector Kit (BT6_5) Components. For more details,
see catalog sections 600-10, 600-30 and 600-50.

26

STUD-A
STUD-C
T-BODY
DT625
DT635

ALUMINUM COMPRESSION
CONNECTOR 11/16"
UNTHREADED HOLE
CC6A _ _ U
CABLE ADAPTER
CA625
CA635

Figure 2.
BT-TAP Connector Kit (BTP6_5_) Components. For more details,
see catalog sections 600-15, 600-35 and 600-55.

Specifiers Guide: Components Master Catalog

200 A Loadbreak & Deadbreak Connectors


T-OP II Connector System

U-OP Connector System

The T-OP II Deadbreak Connector System is designed for use


on applications where a 200 A interface is required for testing,
grounding, or overvoltage protection. It is single person hotstick
operable and is ideal for terminations that may require moving to
achieve a visible open or visible ground. One person can move
the T-OP II Deadbreak Terminator from the apparatus bushing
to a standoff bushing using a hotstick and Operating Test and
Torque Tool (OTTQ6_5).
The T-OP II Connector System uses a threaded coppertop (bimetal) compression connector for a threaded connection. It also
has an alignment segment and internal rotating nut feature in the
loadbreak reducing tap plug which, along with the extended length
stud, eliminates cross threading and ensures proper torque.
The T-OP II system provides the following features:
n Single person hotstick operable
n Mechanical assist
n Copper alloy current path and copper-top connector
n 900 A continuous current rating
n Visible ground and visible break
n 200 A Interface for:
addition of our M.O.V.E Arresters for overvoltage
protection
addition of our Grounding Elbows
access for direct conductor phasing and testing
hipot testing of switch or cables
Refer to Figure 3 for T-OP II Connector Kit Components.

The U-OP Connector System is used to provide a visible break


and visible ground on 600 A distribution systems without having
to move the heavy cable. The U-OP Connector is a deadbreak
system rated for operation on 15 or 25 kV class equipment,
including transformers, switches, switchgear, and other apparatus.
Under normal operating conditions, the current path is through
the apparatus bushing, through the U-connector, through a
two-way 600 A deadbreak junction, and through a T-OP II 600
A Connector (sold separately) to the underground cable. When
isolating underground cable, a grounded standoff bushing can
be put in the parking stand (with the system de-energized). The
U-connector can then be removed, rotated 90, and re-installed
over the apparatus bushing and grounded standoff bushing, to
ground the apparatus bushing.
A grounding elbow can be installed on the 200 A interface
of the T-OP II Connector to ground the cable. A 600 A U-OP
Protective Cap can then be put on the upper bushing of the
deadbreak junction to insulate that bushing. Since all bushings
of the connector system are then insulated or grounded, and
if the cable is grounded on the other end, it is safe to perform
work on the underground cable. See Figure 4 for a typical
U-OP Connector configuration.

Installation of T-OP II on a 600/900 A Bushing

The T-OP II Connector is installed on an apparatus bushing


using a T-Wrench and a 600 A Torque Tool.

U-OP Specification Information


To specify a 600 A U-OP Connector System that achieves a
visible break and visible ground without having to move heavy
cable, include in your specification:

T-OP II Specification Information

n The system must fully comply with IEEE Std 386 standard.

To specify a 900 A T-OP II System, include in your specification:


n The system must fully comply with IEEE Std 386 standard.
n Must include an all copper alloy current path and copper-top
connector.
n System must include disconnecting back-off feature.
n The connector system must provide operation with live line
tools, direct conductor phasing and testing, visible ground and
visible break.
n It must provide a location to add overvoltage arresters and access
for direct conductor phasing or hipot testing of switch or cables.
n Must be one-person hotstick operable and easy to install
with proper torque such that concern for cross threading is
eliminated.
n Loadbreak reducing tap plug must include extended length
stud, internal rotating nut and an alignment segment feature to
eliminate cross threading of this compression connector and
ensure proper torque.
n Loadbreak reducing tap plug must include latch indicator ring.
n T-OP II Connector System base part number TP615 for 15 kV,
TP625 for 25 kV and TP635 for 35 kV.

n The system must provide a visible break and visible ground

LOADBREAK REDUCING
TAP PLUG
LRTP615
LRTP625
LRTP635
COPPERTOP COMPRESSION
CONNECTOR 15/16" THREADED
HOLE
CC6C _ _ T

T-OP II STUD
STUD-T
T-BODY
DT625
DT635

CABLE
ADAPTER
CA625
CA635

Figure 3.
T-OP II Connector Kit (TP6_5_) Components. For more details,
see catalog sections 600-12, 600-32 and 600-52.

Eaton's Cooper Power Systems

without having to move 600 A cable.

n A U-connection shall remain connected on the equipment

even while performing repair to the underground cable to


ensure the interfaces are not exposed to the environment and
thus potentially contaminated.

n U-OP Connector System base part number UOP625 for both

15 and 25 kV.

U-CONNECTOR

APPARATUS
BUSHING

CURRENT PATH
THROUGH U-OP
CONNECTOR SYSTEM

T-OP II CONNECTOR
(not included, ordered
separately)
TP615 _ _
TP625 _ _

PARKING
STAND
2 BUSHING 600 A
DEADBREAK
JUNCTION
DJ625A2

Figure 4.
U-OP Connector Kit (UOP625) Components. For more details,
see catalog section 600-34.

27

600 A Stacking Dimensions


600 200
A Stacking
A Loadbreak
Dimensions
& Deadbreak Connectors
600 A Stacking Dimensions
S4

S3

S2

Dim.
S2

S5

15/25 kV
0.50"
(12.7 mm)
3.87"
(98.3 mm)
1.50"
(38.1 mm)
2.4"
(61 mm)

S3
S4
S5

35 kV
0.50"
(12.7 mm)
4.97"
(126 mm)
1.50"
(38 mm)
2.84"
(72 mm)

Dim.
A

15 kV
12.8"
(325.1
mm)
14.05"
(356.9
mm)

25 kV
15.5"
(393.7
mm)
14.05"
(356.9
mm)

35 kV
17.9"
(454.7
mm)

PUSH-OP Deadbreak Connector (15 kV shown)

BOL-T Deadbreak Connector

S3

S2

S3

S1

S2
Dim.
S2
S3

15/25 kV
0.50" (13 mm)
8.29" (210.6 mm)

35 kV
0.50" (13 mm)
12.46" (316.5 mm)

Bushing Adapter with LRTP (15 kV shown)


Dim.

15/25 kV

S1

4.93" (125.2 mm)

S2

0.50" (12.7 mm)

S3

8.29" (210.6 mm)

Dim.
A
B
C
D

BT-TAP and T-OP II Deadbreak Connector 15 kV and 25 kV

S3

A
S2

15/25 kV
4.0" (101.6 mm)
2.37" (60.2 mm)
5.25" (133.4 mm)
5.50" (139.7 mm)

35 kV
5.80" (147.3 mm)
2.88" (73.2 mm)
6.0" (152.4 mm)
6.27" (159.3 mm)

B
Dim.
A
B
D
S2
S3
S5

35 kV
18.10" (459.7 mm)
0.22" (5.59 mm)
12.89" (327.4 mm)
0.50" (12.7 mm)
12.46" (316.5 mm)
2.84" (72.1 mm)

S5

PUSH-OP Standoff Bushing (15/25 kV shown)


A

BT-TAP and T-OP II Deadbreak Connector 35 kV


Dim.
A
B

15/25 kV
7.6" (193 mm)
3.25" (82.6 mm)

C
35 kV
8.66" (220 mm)
3.25" (82.6 mm)

Dim.
A
B
C
S35

15/25 kV
5.4" (137.2 mm)
5.6" (142.2 mm)
4.4" (111.8 mm)
4.21" (106.9 mm)

5.4"
5.6"
4.4"
5.2"

35 kV
(137.2
(142.2
(111.8
(132.1

mm)
mm)
mm)
mm)

S35

Standoff Bushing
Standard Protective Cap
A
B

S3CP

Dim.
A
B

15/25 kV
5.8" (147.3 mm)
3.25" (82.6 mm)

35 kV
6.8" (173 mm)
3.5" (88.9 mm)

Protective Cap for T-OP II and U-OP (15/25 kV shown)

28

S2

S3IP S4

S5

Separable Splice

15/25 kV
Overall Length Deadend
Overall Length 2-Way Splice
Overall Length 3-Way Splice
Overall Length 4-Way Splice
S2
S3CP
S3IP
S4
S5

11.24" (285 mm)


19.97" (507 mm)
28.70" (729 mm)
37.43" (951 mm)
0.50" (12 mm)
8.23" (209 mm)
3.87" (98 mm)
1.50" (38 mm)
2.40" (61 mm)

B
E

S7

S10

S11

S11
S9

M4
2.00"
(51 mm)

MIN.
MAX.
CONFIGURATION - 3
MIN.
MAX.
CONFIGURATION - 2
MIN.
MAX.
CONFIGURATION - 1

0.56"
(1 mm)
1.4"
(37 mm)

Deadbreak Junction (15/25 kV shown)

Dim.

15/25 kV

4.0" (101 mm)

4.1" (102 mm)

TABLE 15/25 kV
Number of
Interfaces

Physical
Dimensions
in./(mm)

Configuration 1

Configuration 2

Configuration 3

Min.

Min.

Min.

M4 Mounting Dimensions in./(mm)


Max.

Max.

Max.

19.0"
7.0"
14.1 "
16.9"
9.7"
12.5"
5.6"
8.4"
(483 mm) (178 mm) (358 mm) (429 mm) (248 mm) (318 mm) (142 mm) (213 mm)

23.0"
11.0"
18.6"
21.4"
14.2"
17.0"
10.1"
12.9"
(584 mm) (279 mm) (472 mm) (544 mm) (361 mm) (432 mm) (257 mm) (328 mm)

27.1"
15.0"
24.1"
26.9"
19.7"
22.5"
15.6"
18.4"
(686 mm) (381 mm) (612 mm) (686 mm) (500 mm) (572 mm) (396 mm) (467 mm)

3.0" (76 mm)

S7

0.75" (19 mm)

S9

3.4" (86 mm)

S10 6.2" (157 mm)


S11 7.2" (182 mm)

Configuration 1. Both feet turned out.


Configuration 2. One foot turned out, the other in.
Configuration 3. Both feet turned in.

F
G

E
S7

S10

S11

S9

D
A

B
5/8 x 7/8" OBROUND
MOUNTING HOLES

Deadbreak Junction (35 kV shown)


TABLE 35 kV
Number of
Interfaces
2
3
4

Physical Dimensions
in. (mm)
A
B
21.5"
9.0"
(546 mm)
(229 mm)
27.5"
15.0"
(699 mm)
(381 mm)
33.5"
21.0"
(851 mm)
(533 mm)

Mounting Dimensions
in. (mm)
C
D
15.5"
12.5"
(394 mm
(318 mm)
21.5"
18.5"
(546 mm)
(470 mm)
27.5"
24.5"
(699 mm)
(622 mm)

Dim.
E
F
G
H
S7
S9
S10
S11

35 kV
6.0" (152 mm)
6.2" (158 mm)
3.0" (76 mm)
3.8" (96 mm)
0.75" (19 mm)
5.55" (141 mm)
7.0" (178 mm)
10.4" (264 mm)

Note: C and D are minimum and maximum stud centerline separations for mounting.

Eaton's Cooper Power Systems

29

Junction Bars/Cable Transition & Oil Stop Modules


Cooper Power Systems Junction Bars are designed
for vault or apparatus applications and can be used for
looping, tapping, and sectionalizing.
Cable Transition Modules (CTMs) and Oil Stop Modules
(OSMs) are designed for splicing paper insulated lead
cable (PILC) into solid dielectric cable.
Junction bars and cable transition modules are fully
shielded, submersible, resistant to harsh materials, and
are designed and manufactured in accordance with IEEE
Std 386 standard - "Separable Insulated connector
Systems".
Junction bars and cable transition and oil stop modules
are manufactured in 200 A, 600 A or 900 A configurations.
The 200 A designs incorporate a universal bushing well
design making it possible to use either a 200 A loadbreak
or deadbreak bushing well insert.

Junction Bar Catalog Numbering Key


JBI = Junction Bar, In-Line
JBL = Junction Bar, L Splice
JBY = Junction Bar, Y Splice
JBS = Junction Bar, Stacked
25 = 15/25 kV Rating
35 = 35 kV Rating***
335 = Three-Phase, 35 kV Rating
U = With U-Straps
PS = Bracket with (2) Parking Stands
W = 200 A Well
B = 600 A Bushing
S = 600 A Straight Interface Bushing
C = Copper
Available Mounting Provisions

Junction Type
In-Line Junction Bar

S.S. Mtg.
Bracket
0-60 Mtg.
Angles
Std.

Std.

Stacked Junction Bar


L Splice
Y Splice

NonAdjustable
S.S. Flush
Mtg.
Bracket

Std.
Std.

S.S. U-Straps*

S.S. Mtg. Bracket


with (2) Parking
Stands**

Yes

Yes

No

Yes

Yes

Yes

No

No

* For U-straps add suffix U on the end of the standard catalog number.
** For Parking Stand Bracket add suffix PS on the end of the standard catalog number.

30

Specifiers Guide: Components Master Catalog

15/25 and 35 kV In-Line Junction Bars with Stainless Steel Bracket


Catalog Section

Description

kV Class

Base Part Number

Notes

2 Point 200 A

15/25 kV
35 kV

JBI25C2W
JBI35C2W

1,2

3 Point 200 A

15/25kV
35 kV

JBI25C3W
JBI35C3W

1,2

4 Point 200 A

15/25kV
35 kV

JBI25C4W
JBI35C4W

1,2

5 Point 200 A

15/25kV
35 kV

JBI25C5W
JBI35C5W

1,2

6 Point 200 A

15/25kV
35 kV

JBI25C6W
JBI35C6W

1,2

2 Point 600/900 A*

15/25kV
35 kV

JBI25C2B
JBI35C2B

1,2

3 Point 600/900 A*

15/25kV
35 kV

JBI25C3B
JBI35C3B

1,2

4 Point 600/900 A*

15/25kV
35 kV

JBI25C4B
JBI35C4B

1,2

5 Point 600/900 A*

15/25kV
35 kV

JBI25C5B
JBI35C5B

1,2

6 Point 600/900 A*

15/25kV
35 kV

JBI25C6B
JBI35C6B

1,2

3 Point

1 x 200 A
2 x 600 A

15/25kV
35 kV

JBI25C1W2B
JBI35C1W2B

1,2

3 Point

1 x 600 A
1 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C1B1W1B
JBI35C1B1W1B

1,2

3 Point

2 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C2W1B
JBI35C2W1B

1,2

4 Point

1 x 200 A
3 x 600 A

15/25kV
35 kV

JBI25C1W3B
JBI35C1W3B

1,2

4 Point

2 x 200 A
2 x 600 A

15/25kV
35 kV

JBI25C2W2B
JBI35C2W2B

1,2

4 Point

3 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C3W1B
JBI35C3W1B

1,2

4 Point

1 x 600 A
2 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C1B2W1B
JBI35C1B2W1B

1,2

5 Point

1 x 200 A
4 x 600 A

15/25kV
35 kV

JBI25C1W4B
JBI35C1W4B

1,2

5 Point

2 x 200 A
3 x 600 A

15/25kV
35 kV

JBI25C2W3B
JBI35C2W3B

1,2

5 Point

4 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C4W1B
JBI35C4W1B

1,2

5 Point

1 x 600 A
3 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C1B3W1B
JBI35C1B3W1B

1,2

6 Point

3 x 200 A
3 x 600 A

15/25kV
35 kV

JBI25C3W3B
JBI35C3W3B

1,2

6 Point

1 x 600 A
4 x 200 A
1 x 600 A

15/25kV
35 kV

JBI25C1B4W1B
JBI35C1B4W1B

1,2

650-10

1. For U-Straps, add "U" on end of


catalog number.
2. For (2) parking stand brackets add
"PS" to end of catalog number.

* A 900 A rating can be achieved when mated with comparably rated seperable connectors.

Eaton's Cooper Power Systems

31

15/25 kV and 35 kV L-Splices and Y-Splices with Stainless Steel Brackets


1. for U-Straps, add "U" on end
of catalog number.

Catalog Section
650-10

2. For (2) parking stand brackets


add "PS" to end of catalog
number.

650-10

32

Description
kV Class
Base Part Number
L-SPLICES 15/25 AND 35 KV WITH STAINLESS STEEL BRACKETS

Notes

3 Point Single-Phase
2 x 200 A
1 x 200 A

15/25 kV
35 kV

JBL25C2W1W
JBL35C2W1W

1,2

6 Point Single-Phase
4 x 200 A
2 x 600 A

15/25 kV
35 kV

JBL25C4W2B
JBL35C4W2B

1, 2

Y SPLICES, THREE-PHASE 15/25 kV WITH STAINLESS STEEL BRACKETS


9 Point Three-Phase
3 x 200 A
Per Phase

15/25 kV
35 kV

JBY325C3W
JBY335C3W

9 Point Three-Phase
2 x 600 A
1 x 200 A
Per Phase

15/25 kV
35 kV

JBY325C1W2B
JBY335C1W2B

12 Point Three-Phase
3 x 600 A
1 x 200 A
Per Phase

15/25 kV
35 kV

JBY325C1W3B
JBY335C1W3B

Specifiers Guide: Components Master Catalog

15/25 & 35 kV Stacked Junction Bars with Stainless Steel Brackets


Catalog Section
650-10

Description

5 Point

5 Point

5 Point

6 Point

6 Point

6 Point

8 Point

kV Class

Base Part Number

Notes

5 x 200 A

15/25 kV
35 kV

JBS25C2W3W
JBS35C2W3W

2 x 200 A
3 x 600 A

15/25 kV
35 kV

JBS25C2W3B
JBS35C2W3B

2 x 600 A
1 x 200 A
2 x 600 A

15/25 kV
35 kV

JBS25C2B1W2B
JBS35C2B1W2B

6 x 200 A

15/25 kV
35 kV

JBS25C3W3W
JBS35C3W3W

3 x 200 A
1 x 600 A
2 x 200 A

15/25 kV
35 kV

JBS25C3W1B2W
JBS35C3W1B2W

3 x 200 A
1 x 200 A
2 x 600 A

15/25 kV
35 kV

JBS25C3W1W2B
JBS35C3W1W2B

8 x 200 A

15/25 kV
35 kV

JBS25C4W4W
JBS35C4W4W

Eaton's Cooper Power Systems

1. For (2) parking stand brackets add


"PS" to end of catalog number.

33

15 and 25 kV Cable Transition Modules


1.Cable Lug Size required at time of
order.

Catalog Section
650-20
a

Description
STRAIGHT THROUGH

b
d
c

aa

bb

cc

aa

cc

650-20
a

bb
b
b

bb

ccc

a
aaa

cccc

a
aa
a
aa
aa
a

a
a
c
cc

ccc

a
aa

cc

c
cc
c

cc

a aa
a
aa
aa
a
aa

c
c
cc c
c

a aa
aa
a
aa
a
aa

cc

a
a
aaa a

a
a

a
a
a

aa
650-20
a a
aa

aa
a
aa
a
a

aa a
aa
a

a
a
a
a

a aa
a
aa a
a
aa
a
a

aa

a
a a
a a
a
a
a

a
a

a
a
aa
a
a
a
a
aa
a
a a
a
a
a
aa
aa

a
a

c
cc
cc
c c
ccc

c
c
c
cc

c
c
cc

c
c
a

bb
bc
b
bb
b
b
bb
bc b
bbb
bb
bc
c
bb
bc b
b
b
bbb
bccb
c
bb
bb b
bb
b
b
b
ccbcb
b
bb
bbb cb
cb
b
ccbb
b b
bbc c
bb b
cb
bcb
cbb
cb
cc
c ccb
bb
bc
bb b
bbcc
b

3 Point 600 A

15 kV and 25 kV

CTM012A

3 Point 200 A

15 kV and 25 kV

CTM015A

6 Point 200 A

15 kV and 25 kV

CTM025A

3 Point 600 A

15 kV and 25 kV

CTM011A

6 Point 600 A

15 kV and 25 kV

CTM020A

d
ddd
d

dd

d d
dd
d
d
dd
d
dddd
dd
dd
d
dd d
dd
d
dd
d dd
dd d
ddd
dd
d
ddd
dd d
d
d
dd
ddd
dddd

dd d

STRAIGHT THROUGH AND TAP


3 Point 200 A

15 kV and 25 kV

CTM010A

6 Point 200 A

15 kV and 25 kV

CTM024A

3 Point 600 A

15 kV and 25 kV

CTM009A

6 Point 600 A

15 kV and 25 kV

CTM019A

3 Point 200 A

15 kV and 25 kV

CTM029A

3 Point 600 A

15 kV and 25 kV

CTM030A

Wiping Sleeve

15 kV and 25 kV

WS1112
WS1118

Wiping Flange

15 kV and 25 kV

WS12

d
dd d
d dd
dd d

d
dd d
dd

dd
dd

d
d
d
d d
dd
dd
d
d
d d
d
d
d
d
d
dd
d d
dd
d
d d
d
d
d
dd
d d

d d

b
cc
b
b
b
b
c
b
c
b
bc
c

a
650-20

CTM005A

ddd

c
c
bb b

c
a

dd
d
ddd

c b
c
b
c c c cb
bc
b bc
c
bcc
bb
c b
b c
cb
c
bc
c bc bc
c
bb bc c
b
c bc
bb c
c b bc
c
bcb b c
c
cb b c
bb
cc c
b
b cb
c
cc
b cb
c c
b
b
b cc

aa

15 kV and 25 kV

d
d
ddd

a
a

bc
c cb
b
bbb bc
bcbcb

3 Point 200 A

TAP

dd
d

b
b
c

c
ccc

dd
d
d

b
b
cc
b
b

aaa
aa

dd

b
b
b
c
bb

c
aa

aa
a
a

Notes

c
cc

Base Part Number

dd

b
b
b

a
aa
a

kV Class

dd d

d
d
d
d
d
d
d
d

c
b
d

ACCESSORIES

Lead Pipe Diameter


6 3 8 (162 mm) for 15 and 25 kV
8 17 6 4 (210 mm) for 35 kV
Lead Pipe Diameter
(305mm)
mm)for
for15
15and
kV 25 kV
6 3 812(162
18 (457 mm) for 25 kV
6 4 (210 mm) for 35 kV
8 17 25
(635 mm) for 35 kV
12 (305 mm) for 15 kV
18 (457 mm) for 25 kV
25 (635 mm) for 35 kV

34

1 (44 mm) for 15 kV


and 25 kV
2 (51 mm) for 35 kV

1 (44 mm) for 15 kV


and 25 kV
2 (51 mm) for 35 kV

Specifiers Guide: Components Master Catalog

15 and 25 kV Cable Transition & Oil Stop Modules


Catalog Section
650-20

Description

kV Class

Base Part Number

15 kV and 25 kV

BRK469

Three-Phase 600 A
PILC to PILC Splice

15 kV and 25 kV

OSM004

Tap Transition, Paper


Insulated Lead Cable
(PILC) Run to
3 Point 200 A and
3 Point 600 A Tap

15 kV and 25 kV

CTM035A

Saddle
650-20

Notes

MOUNTING BRACKET

1.Cable Lug Size required at time of


order.

OIL STOP MODULES

Eaton's Cooper Power Systems

35

Splices
200 A Loadbreak & Deadbreak Connectors
Splices
We offer various types of splices for your underground needs
on 200 A and 600 A systems. The EZ II One-Piece Splices at
15, 25, and 35 kV include advantages for typical applications
of repair, replacement, or extension of high voltage
underground cables. These all peroxide-cured EPDM rubber
splices provide a highly reliable, permanent, fully shielded,
and submersible cable joint with a current rating equal to
that of the mating cable. EZ II Splices can be installed in
conduit, direct buried or in vault applications. The EZ II Splice
line meets or exceeds all requirements of IEEE Std 404
standard.
We offer a full line of 600/900 A Separable Splice kits for
application on feeder circuits. These use standard BOL-T
type components along with a peroxide-cured EPDM rubber
connecting plug that allows for installation of multiple way
splices. Separable splices are used to splice multiple cables
or to deadend a single cable. The splices are rated for
600 A (900 A ratings are available) and are suitable for the
repair or extension of underground feeders. Separable splice
kits meet or exceed the requirements of IEEE Std 386
standard.

EZ II Splices
The EZ II One-Piece Splices offer a number of features and
benefits, including:
Easiest to Install The design features of the EZ II Splice
including the tapered cable entrance, smooth bore, relieved
conductive insert, and reformulated rubber provide for
easier field installation. EZ II Splices have been shown to be
30% easier to install than other manufacturers splices.
Wide Range Taking The wide range taking cable entrances
are sized to accept all common cable insulation diameters.
The wider cable ranges increase installation flexibility.
Sure Grip The contoured EZ II Splice body provides an
easy gripping location during installation.
Long Term Reliability The EZ II Splice has successfully
passed all requirements of the IEEE Std 404 standard and
our exclusive field-proven multi-stress test to show the long
term reliability of the design.

THREADED
STUD

CAP

CONNECTING
PLUG

INSULATION
PLUG

COMPRESSION
CONNECTOR

T-BODY

CAPACITIVE
TEST POINT
CABLE
ADAPTER

EZ ll Splice Specification Information


Typical components of a 600 A 2-way separable splice.

To ensure you have the most reliable, economical,


installation friendly premolded one-piece splice available, your
specification for EZ II Splice should include:
n

Manufactured in full compliance with all applicable IEEE


Std 404 standard.

Manufactured from peroxide-cured EPDM rubber.

Tapered ribs of the inside diameter of the conductive


insert.

Molded in compression connector diameters.

Conductive insert ends encapsulated with insulating


rubber.

Splice Applications

Sectionalizing
Cabinets

Protective Cap

Separable
Splice
Connecting Plug
Cable Transition Module

36

Transformer
or Switchgear
Apparatus

FCI

T-OP II
BOL-T
Connector

Junction Bars
Deadbreak Junction

Specifiers Guide: Components Master Catalog

200
200AALoadbreak
Loadbreak&&Deadbreak
DeadbreakConnectors
Connectors
Catalog Section

Description
EZ II
Splice

700-15
(both tables)

TABLE CR6
Cable Diameter (Insulation) Range
Cable Diameter Range
0.640-0.910
0.750-1.010
0.890-1.140
0.840-1.110
1.000-1.310
1.140-1.450

Base Part Number

Notes

15 kV

1, 2, 3, 4

25 kV

SP15 CR6 CC5


(see CR6 & CC5 Tables Below)
SP25 CR6 CC5

35 kV

SP35 CR6 CC5

1, 2, 3, 4

(see CR6 & CC5 Tables Below)

1. For an all copper connector, change


digit six from a 0 to a C.
2. For a splice with a single-piece
rejacketing kit, insert a S or a
2-piece rejacketing kit, insert a D
as the ninth character in the part
number.

1, 2, 3, 4

(see CR6 & CC5 Tables Below)

Use for Base Number


SP15 SP25 SP35

Inches

kV Class

CABLE
RANGE
Millimeters CODE
16.3-23.1
19.1-25.7
22.6-29.0
21.3-28.2
25.4-33.3
29.0-36.8

A
B
C
D
E
F

3. For individually packaged product


in a corrugated cardboard box, insert
an X as the last character in the part
number.

TABLE CC5
Conductor Size and Type
Stranded or
Compressed
AWG
mm2
#3
25
#2
35
#1

1/0
50
2/0
70
3/0

4/0
95
250*
120

Voltage
Class
15 kV
15 & 25
kV
15, 25 &
35 kV

Compact or
Solid
AWG
mm2
#2
35
#1

1/0
50
2/0
70
3/0

4/0
95
250
120

4. To splice different sized cables, refer


to transition splice information in
catalog section 700-15.

CONDUCTOR
CODE
001
002
003
004
005
006
007
008

5. For 900 A rating (copper components)


replace the A with a C.
6. For T-bodies with test points, insert
a T directly after the base part
number.
7. Studs are bagged and loose in kit. To
have studs permanently installed
at the factory, add a P after the test
point designation (if applicable) or
after the base part number.

* Compressed stranding only

700-22
700-31

600 A Separable Splices


(Kits Do Not Include
Cable Adapters or
Compression
Connector.
Refer to 600 A
Replacement Parts
Page 25)

15/25 kV
Deadend Kit
2-way Splice Kit
3-way Splice Kit
4-way Splice Kit
35 kV
Deadend Kit
2-way Splice Kit
3-way Splice Kit
4-way Splice Kit

T-OP II 600 A Separable


Splices with 200 A Tap
(Kits Do Not Include
Required Threaded and
Unthreaded Compression
Connectors or Cable
Adapters. Refer to 600 A
Replacement Parts Page
25)

15 kV
T-OP II
T-OP II
T-OP II
T-OP II
25 kV
T-OP II
T-OP II
T-OP II
T-OP II
35 kV
T-OP II
T-OP II
T-OP II
T-OP II

700-17
700-57

SSPL625A1
SSPL625A2
SSPL625A3
SSPL625A4

5,
5,
5,
5,

6,
6,
6,
6,

7,
7,
7,
7,

8
8
8
8

SSPL635A1
SSPL635A2
SSPL635A3
SSPL635A4

5,
5,
5,
5,

6,
6,
6,
6,

7,
7,
7,
7,

8
8
8
8

Deadend Kit
2-way Splice Kit
3-way Splice Kit
4-way Splice Kit

SSPLT615A1
SSPLT615A2
SSPLT615A3
SSPLT615A4

5,
5,
5,
5,

6,
6,
6,
6,

7,
7,
7,
7,

8,
8,
8,
8,

9
9
9
9

Deadend Kit
2-way Splice Kit
3-way Splice Kit
4-way Splice Kit

SSPLT625A1
SSPLT625A2
SSPLT625A3
SSPLT625A4

5,
5,
5,
5,

6,
6,
6,
6,

7,
7,
7,
7,

8,
8,
8,
8,

9
9
9
9

Deadend Kit
2-way Splice Kit
3-way Splice Kit
4-way Splice Kit

SSPLT635A1
SSPLT635A2
SSPLT635A3
SSPLT635A4

5,
5,
5,
5,

6,
6,
6,
6,

7,
7,
7,
7,

8,
8,
8,
8,

9
9
9
9

8. Installation requires a standard 5/16"


hex key (HD625).
9. To include 200 A loadbreak
protective cap, add a C as the
last character in the part number.

TABLE 4
Separable Splice Kits
Splice Kit Contents
Assembly

T-Body

Insulating
Plug
w/Cap

Insulating
Plug w/Cap
and Stud

Order Separately (Refer to pg 25)


Connecting
Plug
w/Stud

Loadbreak
Reducing
Tap Plug
(Includes STUD-T)

Cable
Adapter

Unthreaded
Compression
Connector

Threaded
Coppertop
Connector

Deadend

2-Way Splice

3-Way Splice

4-Way Splice

T-OP II Deadend

T-OP II 2-Way Splice

T-OP II 3-Way Splice

T-OP II 4-Way Splice

Eaton's Cooper Power Systems

37

Underground
Surge
Arresters
Underground
Surge
Arresters

200 A LOADBREAK & DEADBREAK CONNECTORS

Our Metal Oxide Varistor Elbow (M.O.V.E.) and Parking Stand Arresters are used
in pad-mounted transformer and entry cabinets, vaults, switching enclosures and
other installations to provide shielded deadfront arrester protection. These arresters
are designed for use with 200 A loadbreak interfaces to limit overvoltages to
acceptable levels, protect equipment and extend cable life.

POSI-BREAK M.O.V.E. Elbow Arrester


The POSI-BREAK M.O.V.E. Arrester provides the same safety benefits of the
POSI-BREAK connector system with over-voltage protection. Cooper Power
Systems is the only manufacturer to offer a solution to the partial vacuum
flashover in elbow arresters.
The POSI-BREAK M.O.V.E. Arrester is available for 9-21 kV for 25 kV class
interfaces.

M.O.V.E. DirectConnect Elbow Arrester


M.O.V.E. DirectConnect Elbow Arresters are used on underground systems in
pad-mounted transformer and entry cabinets, vaults, switching enclosures and
other installations to provide shielded deadfront arrester protection. They are
designed for use with 600 A, 35 kV Class deadbreak interfaces that conform
to IEEE Std 386 standard to limit overvoltages to acceptable levels, protect
equipment and extend cable life.

M.O.V.E. DirectConnect Elbow Arrester


Specification Information

Design Tests

IEEE Std 386-2006 standard,


Separable Insulated Connector Systems
IEEE Std C62.11 standard, Metal Oxide
Surge Arresters for AC Power Circuits

TABLE 1
Commonly Applied Voltage Ratings of M.O.V.E. and Parking Stand Arresters
System Voltage (V rms)
Nominal
Voltage
2400
4160 Y/2400
4260
4800
6900
8320 Y/4800
12000 Y/6930
12470 Y/7200
13200 Y/7620
13800 Y/7970
13800
20780 Y/12000
22860 Y/12000
24940 Y/14400
27600 Y/15935
34500 Y/19920
46000 Y/26600

Maximum
Voltage
2540
4400 Y/2540
4400
5080
7260
8800 Y/5080
12700 Y/7330
13200 Y/7620
13970 Y/8070
14520 Y/8388
14520
22000 Y/12700
22000 Y/12700
26400 Y/15240
29255 Y/16890
36510 Y/21080
48300 Y/28000

Commonly Applied Arrester Duty-cycle (MCOV)


Voltage Rating (kV rms) on Distribution Systems
Delta and
4-Wire
3-Wire Low
3-Wire High
Multigrounded
Impedance
Impedance
Neutral Wye
Grounded
Grounded

3 (2.55)
3 (2.55)
6 (5.1)
6 (5.1)

6 (5.1)

6 (5.1)

9 (7.65)
6 (5.1)
9 (7.65)

9 (7.65)
12 (10.2)

9 (7.65) or 10 (8.4)
15 (12.7)

10 (8.4)
15 (12.7)

10 (8.4) and 12 (10.2)


15 (12.7)

18 (15.3)
15 (12.7)
21 (17.0)

15 (12.7)
21 (17.0)

18 (15.3)
27 (22.0)

21 (17.0)

27 (22.0) or 30 (24.4)

36 (29.0)

2.2

DirectConnect Elbow Arrester.

PER UNIT MCOV

M.O.V.E. ARRESTER
(Catalog Section 235-65)
DirectConnect ARRESTER
(Catalog Section 235-101)

1.8

1.6

1.4

IEEE Std.
C62.22
MINIMUM

1.2

0.01

0.1

10
TIME (Seconds)

100

10

10

Temporary overvoltage curve. No prior duty at


85 C ambient.

38

Specifiers Guide: Components Master Catalog

Catalog Section

Description

kV Class

Metal Oxide
Elbow
(M.O.V.E.)
Arrester

15 kV

25 kV

25 kV
POSI-BREAK
Elbow Arrester

35 kV
(Interface 1A
Large Interface per
IEEE Std 386 standard)
235-65

Metal Oxide
(MOV)
Parking Stand
Arrester

15 kV

25 kV

235-68
DEADBREAK
ONLY

M.O.V.E.
DirectConnect
Elbow Arrester

35 kV

Base Part
Number

3238018C03M
3238018C06M
3238018C09M
3238018C10M
3238018C12M
3238018C15M
3238018C18M
3238019C09M
3238019C10M
3238019C12M
3238019C15M
3238019C18M
3238019C21M
PLEA225N03
PLEA225N06
PLEA225N09
PLEA225N10
PLEA225N12
PLEA225N15
PLEA225N18
PLEA225N21
3238020C18M
3238020C21M
3238020C24M
3238020C27M
3238020C30M
3238020C33M
3238020C36M
3237686C03M
3237686C06M
3237686C09M
3237686C10M
3237686C12M
3237686C15M
3237686C18M
3237758C09M
3237758C10M
3237758C12M
3237758C15M
3237758C18M
3237758C21M
DCEA635M27
DCEA635M30
DCEA635M33
DCEA635M36

MCOV
(kV)
2.55
5.1
7.65
8.4
10.2
12.7
15.3
7.65
8.4
10.2
12.7
15.3
17.0
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17.0
15.3
17.0
19.5
22.0
24.4
27
29
2.55
5.1
7.65
8.4
10.2
12.7
15.3
7.65
8.4
10.2
12.7
15.3
17.0

The following notes apply to all part


numbers on this page.
n Digits 9 & 10 designate duty cycle
voltage rating. For other protective
characteristics, refer to Table
2 for M.O.V.E. and Parking
Stand Arresters and Table 3 for
DirectConnect Elbow Arresters.
n Refer to page 17 for dimensional
information or referenced catalog
section.

22.0
24.4
27.0
29.0

DEADBREAK
ONLY

27KV

22.0 KV MCOV

235-101

TABLE 2
M.O.V.E. and Parking Stand Arrester Protective Characteristics
Maximum Discharge Voltage (kV crest)
Duty Cycle
Equivalent Front-of8/20 s Current Wave
Voltage Rating
MCOV
Wave
(kV)
(kV)
(kV crest)*
1.5 kA
3 kA
5 kA
10 kA
20 kA
3
2.55
11
9
9.7
10.7
11.4
13
6
5.1
22
18.0
19.4
20.8
22.7
26
9
7.65
31.7
26
28
30
32.8
37.4
10
8.4
33
27
29.1
31.2
34.1
38.9
12
10.2
41.5
33.9
36.6
39.2
42.9
48.9
15
12.7
51.8
42.4
45.7
49
53.6
61.1
18
15.3
62.2
50.9
54.9
58.8
64.3
73.4
21
17.0
66
54.0
58.2
62.4
68.2
77.9
24
19.5
77
63.0
67.9
72.8
79.6
90.8
27
22.0
87.2
71.4
76.9
82.4
90.1
103
30
24.4
97.1
79.5
85.7
91.8
100.0
115.0
33
27
108
87.8
95.1
102
112
127
36
29
116
95.3
103
110
120
137
* Equivalent front-of-wave voltage is the expected discharge voltage of the arrester when tested with a 5 kA
current surge cresting in 0.5 s.

TABLE 3
M.O.V.E. DirectConnect Elbow Arrester Electrical Ratings and Characteristics
Maximum Discharge Voltage 8/20 s Current Wave (kV crest)
Duty Cycle Voltage MCOV
Front-of-Wave Protective
Rating (kV)
(kV)
Level* (kV crest)
1.5 kA
3 kA
5 kA
10 kA
20 kA
27
22.0
105.0
75.0
82.0
87.4
96.2
110.0
30
24.4
112.0
79.5
85.7
91.8
100.0
115.0
33
27
108
87.8
95.1
102
112
127
36
29
116
95.3
103
110
120
137
* Equivalent front-of-wave voltage is the expected discharge voltage of the arrester when tested with a 5 kV
current surge cresting in 0.5 s.

Eaton's Cooper Power Systems

39

Tools & Maintenance


200 A LOADBREAK & DEADBREAK CONNECTORS
Cooper Power Systems, Kearney operation offers a wide
variety of Hi-Line Tools and maintenance equipment
including Insulated Sticks, Fit-On Tools, Tree Trimmers,
Fuse Pullers, Cover-up Equipment, Jumpering/Grounding
Equipment, Compression Tools, Cutters and Accessories.
Kearney also offers a wide range of connectors. Products
include:
n Aqua Seal and Airseal Insulating and Sealing Material
n Compression Squeezon Connectors, Tee-Taps, Stirrups,
Terminals, Grounding Lugs, Spacers
n Secondary Terminal Connnectors, and a wide variety of
sleeves
O-Tool Dies
Catalog Number
30554CPS
B
26994
D
48410
J
40495CPS
K
26993
O
30611CPS
P
40493CPS
T
30084
737
30450
781
30124
840
3/16
36181CPS
1/4
30154
5/16
30043
3/8
30042
1
30041
/2
9/16
26958
19/32
30914
5/8-1
26992CPS
11/16
40114
Non-Bow Dies
100625CPS
500
100600CPS
510
100613
620
100601
635
100618
702
100602
747
100609
845
100606
980
EEI Dies
100603-7
7A
100603-9
9A
100603-11
11A
Other Dies &
Accessories
30744
BU-C
49341
Orange
36559
Plum
Wire Cutter Die for
2/0 ACSR Max
30500
Plum

40

WH3 & PH13 Dies


Catalog Number
36457
D
36459-3
N
36467*
O
36472
U
15/16
36474*
36476*
840
36478*
781
36480*
737
36482CPS*
635
5/8-1
36484*
19/32
36486*
9/16
36488*
1/2
36490CPS*
3/8
36494CPS*
5/16
36496*
1/4
36498*
36828CPS*
P
36830CPS
C
36832CPS*
B-K-T
36834CPS*
747
36836*
572
36838*
510
40063*
727
11/16
40151CPS*
40517
1 1/4 (Hex)
3/4 (Hex)
49435*
29/32 (Hex)
49437*
15/16 (Hex)
100370CPS
100399
1-2 (Hex)
100400
1 1/8-2 (Hex)
100433CPS
1 5/16 (Hex)
100434CPS
1 1/2 (Hex)
9/16 Wide
100455
100456

PH4 & PH15 Dies


Catalog Number
100472
D
100473
N
100474
U
100057
R
100470
1-2
100471
1-1/8-2
100440
1-5/16
100460
1-1/2
100459
1-5/8
100075
1-3/4
100096
Adapter
PH25 DIES
100005
Die Holder
5/8-1
100006-4
100006-16
1- 1/8-1
100006-7
727
100006-12
840
100006-15
1.00 (Hex)
100006-18
D
100007-1
1 9/32 (Hex)
100007-2
1 5/16 (Hex)
100007-3
1 1/2 (Hex)
100007-4
1 5/8 (Hex)
100007-6
1 3/4 (Hex)
100007-9
2 1/8 (Hex)
100007-23
R

Cases for O-Tools


For Tool Model
O-60 Series
O-60 Series

Description
Steel Carrying Case
Die Case

Catalog
Number
26962-5
30642CPS

Net Wt.
Each
9 Ibs.
1 lb.

840 Wide

* These dies may be used


with adapter #100096 in
PH3, PH4 and PH15 tools.

Specifiers Guide: Components Master Catalog

Catalog Section

Description

kV Class

TYPE OS TOOLS
5/8 Fixed Die
620 Fixed Die

Base Part
Number

Notes

2. For an insulated head, replace


the 1 with a 2.

OS50
OS-620

3. For an insulated head, replace


the 50 with a 53.

325-10

325-10

325-10

325-10

325-10

325-10

TYPE O-62 TOOLS 5/8" FIXED NOSE DIE


17" Straight Handles
Non-Insulated Head
21" Straight Handles
Non-Insulated Head
17" Bent Handles
Non-Insulated Head
TYPE O-63 TOOLS WITH FIXED O NOSE DIE
17" Straight Handles
Non-Insulated Head
21" Straight Handles
Non-Insulated Head
17" Bent Handles
Non-Insulated Head
TYPE O-620 TOOLS WITH FIXED 620 NOSE DIE
17" Straight Handles
Non-Insulated Head
21" Straight Handles
Non-Insulated Head
17" Bent Handles
Non-Insulated Head
TYPE O-65 TOOLS WITH FIXED 5/8" AND D DIE
17" Straight Handles
Non-Insulated Head
21" Straight Handles
Non-Insulated Head
17" Bent Handles
Non-Insulated Head
TYPE O-68 TOOLS WITH FIXED O AND D DIE
17" Straight Handles
Non-Insulated Head
21" Straight Handles
Non-Insulated Head
17" Bent Handles
Non-Insulated Head
WH SERIES 12-TON COMPRESSION TOOLS
Type WH3 12 Ton
Compression Tool
12" Handles w/Case

1. For an insulated head, insert a


-3 between the 2 and the F.
Example: 0-62-3F.

4. To include D insert die, add a B


as the last character in the part
number.

O-62F

1, 4, 8

O-62-21F

2, 4, 8

O-62-50F

3, 4, 8

O-63F

4, 5, 8

O-63-21F

2, 4, 8

7. For an insulated head, insert a


-3 between the 0 and the F.
Example: 0-620-3F.

O-63-50F

3, 4, 8

8. Accepts Burndy Type W dies.

O-620F

6
4, 7, 8

9. For an insulated head, insert a


-3 between the 5 and the F.
Example: 0-65-3FB.

O-620-21F

2, 4, 8

O-620-50F

3, 4, 8

10. For an insulated head, insert a


-3 between the 8 and the F.
Example: 0-68-3FB.

5. For an insulated head, insert a


-3 between the 3 and the F
Example: 0-63-3F.
6. Consult customer service for
availability.

11. For tool without case, insert a


K as the first character in the
part number.

O-65FB

8, 9

O-65-21FB

2, 8

O-65-50FB

3, 8

13. Case fits standard tool with 12"


handles.

O-68FB

8, 10

O-68-21FB

2, 8

14. To add a complete set of die


holder assemblies, insert a K
as the first character in the part
number.

O-68-50FB

3, 8

WH3

11, 12, 13

12. For tool with 18" handles, add a


-18 at the end of the part number
or for 24" handles, add a -24.

325-10
PH13 SERIES 12-TON REMOTE HYDRAULIC TOOL
12 Ton, 4,000 PSI
PH13-4
Remote Hydraulic Tool
325-10 w/Case 13" length
RH15 SERIES 15-TON REMOTE HYDRAULIC TOOL
RH15 Remote Head,
RH15-10
325-10 15 Ton, 10,000 PSI

Eaton's Cooper Power Systems

11

14

41

Tools & Maintenance


200 A LOADBREAK & DEADBREAK CONNECTORS
Catalog Section

Description

kV Class

Hand Operated Cutters


General Purpose Center Cut

Base Part
Number

Notes

0190FC
0113C (Cutter Head)
0290MCX
0213CX (Cutter Head)
8690FSK
8613FSK (Cutter Head)
8690FH
8613FH (Cutter Head)
8690CK
8613CK (Cutter Head)
8690TN
8613TN (Cutter Head)
0290FHJ
0290FCS
0213CSS (Cutter Head)
0890CSJ
6990FHL

Heavy-Duty
Ratchet Type Soft Cable
Ratchet Type Hard Cable
Ratchet Type Guy Strand
Ratchet Type Wire Rope
ACSR Wire Rope and Cable
Shear Type Hand Operated
Compact Electric Cable
325-10 Compact Ratcheting Cable
CLAMPSTICKS
Clampstick

See Table 1
See Table 1

Clampstick, Cam-EL
Clampstick, Hinged
325-30 Clampstick Leverage Tool

See Table 1
CS125UFLTOOL

18" Fit-On Leverage tool provides mechanical advantage


during loadbreak switching.
Note: Use external rod clampsticks only.

TABLE 1. Clampstick Significant Digit Catalog Number System



Digits:

1 2 3 4 5 6 7 8 9 10 11 12

C S 1 2 5 E 1 2 8 C U F
Digits 1-5
CS125

Digit 6 Stick Type

Digit 10 Clamp Type

Clampstick
1 1/4 pole

Digits 7-9 Length

Cam-EL

Standard

Approx. Folded
Length for
Hinged Sticks

External

Internal

048*

4 feet 8 inches

N/A

EC

Rubber End Cap

Hinged

060

6 feet

3 feet

UF

080

8 feet

4 feet

(Universal) Fit-On*
Head

100

10 feet

5 feet

120

12 feet

6 feet

128*

12 feet 8 inches

N/A

Digits 11 and 12 End Fitting

* Adds 2 inches to the length


of the stick

* Not available in the hinged type stick.

42

Specifiers Guide: Components Master Catalog

200 A Loadbreak & Deadbreak Connectors


Catalog Section

Description

kV Class

Temporary Grounding Sets


Single-Phase
Three-Clamp Set
Pad-mounted
Three-Phase
Four-Clamp Set
Pad-mounted

Base Part Number Notes

2. Single kit with (1) elbow with 1/0


cable, (1) portable feedthru, (1)
protective cap and (1) test probe in
a carrying bag.

133040
(1/0 Black Cable)

133040-1
(1/0 Black Cable)

3. Single kit with (1) elbow with 2/0


cable, (1) portable feedthru, (1)
protective cap and (1) test probe in
a carrying bag.

133040-2

(2/0 Black Cable)

Single Replacement
Clamp for 1/0 Cable
Single Replacement
K-SEC 200 Clamp for 2/0 Cable
GROUNDING ELBOWS
Grounding
15 kV
Elbow
25 kV
35 kV

K-SEC 200
Grounding Kit

15 kV

25 kV

K-SEC 200

35 kV

INSULATING AND SEALING MATERIALS


Aqua Seal
3 3/4" x 3 3/4" Pads 25 per Box
3 3/4" x 10' Roll
Air Seal
4" x 4" Pads 25 per Box
325-24 4" x 10' Roll
KEARNALEX INHIBITOR
Specification 118 (Non-Petroleum Base)
4 oz. Plastic Dispenser Bottle
8 oz. Plastic Dispenser Bottle
8 oz. Plastic Dispenser Bottle Gritless
CONDUCTOR CLEANING BRUSHES
Hand Element and Replacement Brush for
Fit-On Head 477 kcmil ACSR MAX
Hand Element and Replacement Brush for
Fit-On Head 954 kcmil ACSR MAX
V-Brush with Handle and Guard
325-30 Single Replacement Brush for V-Brush

Eaton's Cooper Power Systems

133045CPS

4. Triple kit with (3) elbows with 1/0


cable, (3) portable feedthrus, (3)
protective caps and (1) test probe in
a carrying bag.

133045Z20

GE215-1Y06-1/0 Cable
GE215-2Y06-2/0 Cable
GE225-1Y06-1/0 Cable
GE225-2Y06-2/0 Cable
GE235-1Y06-1/0 Cable
GE235-2Y06-2/0 Cable
GE215-1Y06-K1
GE215-2Y06-K1
GE215-1Y06-K3
GE215-2Y06-K3
GE225-1Y06-K1
GE225-2Y06-K1
GE225-1Y06-K3
GE225-2Y06-K3
GE235-1Y06-K1
GE235-2Y06-K1

1. Clamp and ferrule are not included


with the grounding elbow.

1
1
1

5. Triple kit with (3) elbows with 2/0


cable, (3) portable feedthrus, (3)
protective caps and (1) test probe
in a carrying bag.
6. Other material sizes available.

2
3
4
5
2
3
4
5
2
3

104742-2
104742

6
6

18415-8
18415-3

6
6

30584-25
30584-3
30584-30
48900
48900-2
118004
19100

43

Bushings
Bushings
Cooper Power Systems has a full line of one-piece bushings,
bushing wells, bushing well inserts, and feed-thru inserts for
installation on transformers and/or sectionalizing cabinets.
The 15 kV and 25 kV class bushing inserts use a knurled
piston providing maximum copper-to-copper current transfer
and maximum thermal stability. After fault close operation, it
locks the piston in the outward position, providing a visible
indication against dangerous repetitive fault closure.
Type Primary
Bushings

Current
Rating (A)

Voltage
Rating (kV)

Bushing wells

200

15, 25, 35

Integral loadbreak bushing 3 rated

200

35

Deadbreak apparatus bushing

600

15/25, 35

Deadbreak PUSH-OP Apparatus Bushing

600

15/25, 35

200 A Integral Loadbreak Bushing Specification


Information
n

200 A, 35 kV three-phase rated integral loadbreak bushing meeting the requirements of IEEE
Std 386 standard No. 1A (large 35 kV class
interface).

Voltage and current ratings in accordance with


IEEE Std 386 standard.

600 A PUSH-OP Deadbreak Bushing


Specification Information
n

Bushing Well Insert w/


Latch Indicator Ring

600 A Deadbreak Apparatus Bushing shall be


compatible with Cooper 600 A PUSH-OP
Connectors.
Complete with plated copper finger contacts to
accept PUSH-OP probe, to achieve a non-bolted
connection.
Voltage and current ratings in accordance with
IEEE Std 386 standard.

200 A HTN Tri-Clamp Bushing Well


Specification Information
n

Molded-In Semi-Conductive Shield.

35 kV, 150 kV BIL.

HTN Material.

Removable stud shall have provisions for easy


removal of broken parts from both the bushing
well and insert.

Voltage and current ratings in accordance with


IEEE Std 386 standard.

U-OP
Connector

Rotatable Feedthru
Insert

Bushing
Well

Bushing Well Plug

One-Piece
Bushing
35 kV Only

Standoff
Bushing

Transformer
or Switching
Apparatus

Deadbreak
Junction

T-OP II
Connector
Transformer
or Switchgear
Apparatus
BOL-T
Connector

600 A
Protective
Cap
One-Piece
Bushing

T-OP II
Connector

Parking
Stand
Bracket
Portable Feedthru

Parking
Stand Arrester

200 A Applications

44

Bushing
Adapter

FCI
Shield
Adapter

Standoff
PUSH-OP Bushing
Connector*
FCI

600 A Applications

Specifiers Guide: Components Master Catalog

Catalog Section

800-32

800-33

800-34

Description
200 A Plastic (HTN)
TRI-Clamp Bushing Well
2 9/16" Dia Hole Size

kV Class
15/25/35 kV

200 A Plastic (HTN) Bushing


Well
2 9/16" Dia.Hole Size

15/25/28 kV

200 A Epoxy Bushing Well

15/25/28 kV

800-45
800-47
600 A Deadbreak
800-46 PUSH-OP Bushing
800-48 (Externally Clamped)
3-STUD CLAMPS
800-33 4.688 B.C. w/flange
800-34 4 Bail Tabs
4-STUD CLAMPS
3.25 C-C
800-33 3.25 C-C
800-34 2 Bail Tabs
800-39 3.25 C-C
800-45 4 Bail Tabs
800-46
800-47 3.90 C-C
800-48 3.43 C-C (600 A)
800-32 2 9/16" Dia. Hole Gasket
800-33
800-34 2 9/16" Dia. Hole Gasket
800-39 2 3/4" Dia. Hole Gasket
800-45 2 9/16" Dia. Hole Gasket
800-46
800-47
800-48
800-32 Red Shipping Cap
800-33
800-34
800-39 Red Shipping Cap
800-45 Red Shipping Cap
800-46
800-47 Red Shipping Cap
800-48 Red Shipping Cap
800-32 Removable Stud (Well)
800-33 Replacement Kit
800-34
Removable Threaded Stud
(600 A Bushings)

(with fixed stud

Notes
2

BW150R

(with removable stud)

2638372C01

1, 2, 5

2638372C02R

1, 2, 5

2603973B02T

1, 2

2603973B02R

1, 2

2637024C01M

2637019B02 (Aluminum)
2637019B04 (Copper)
DB635B150 (150 kV BIL)
DB635B200 (200 kV BIL)
(Aluminum) (2 9/16")
DB935B150 (150 kV BIL)
DB935B200 (200 kV BIL)
(Copper) (2 9/16")
2637604C01 (2 9/16")
2637939C01

3
3
3

(with fixed stud)

(with removable stud)

2 9/16" Dia.Hole Size

200 A Three-Phase Integral


800-39 Loadbreak Bushing
600 A Deadbreak Bushing
(Externally Clamped without
Stud)

Base Part Number


BW150F

(with fixed stud)

(with removable stud)

35 kV
15/25 kV
15/25 kV
35 kV
35 kV
15/25 kV
35 kV

(Externally Clamped 2 3/4")

15/25/35 kV

2085399A01
2085399A02 (Stainless Steel)

15/25/28 kV
15/25/28 kV

2606821A01
2606823A02

15/25/28 kV

2606823A04

35 kV
15/25/35 kV
15/25/28/35 kV

2603989B01
2637023B01
0537980C22

15/25 kV
35 kV
15/25/35 kV

0537980C07
0537980C12
0537980C06

15/25/35 kV

2638640C01

35 kV
15/25 kV

2606754A03
2637700B02

35 kV
35 kV
15/25/28/35 kV

2610082P01
2637700B02
2639081B01B

15/25 kV

1. Clamp must be ordered separately.


2. Bushing includes gasket and
shipping cap.
3. Clamp and gasket must be ordered
separately.
4. Clamp, gasket and bracket
assembly must be ordered
separately.
5. For 35 kV (150 kV BIL) add S
to end of the part number.
6. Latch handle standard on left side.
For latch handle on right side,
change digit 10 from a 3 to a 5.

3
4
4

STUD-A
(Aluminum)

STUD-C
(Copper)

35 kV
800-45
800-47
800-39 Contact Tube Assembly
Contact Tool Replacement
800-39 Tool
800-46 PUSH-OP Bail Bracket
800-48 Assembly
800-46 PUSH-OP Bracket Alignment
800-48 Fixture
800-32 Grounding tab

Eaton's Cooper Power Systems

STUD635-A
(Aluminum)

STUD635-C
(Copper)

35 kV
35 kV

2637407B03B
2637585B01

15/25/35 kV

2638772B03M

15/25/35 kV

2637904C01

15/25/35 kV

0739658A02

45

Fusing
Fusing

200 A LOADBREAK & DEADBREAK CONNECTORS

Cooper Power Systems offers fuses under multiple


tradenames: Cooper, Kearney, McGraw-Edison and
Combined Technologies. We have the broadest range of
overcurrent protective devices to meet your application needs.

Bay-O-Net Fuse Assembly


In the late 1960s, we introduced the Bay-O-Net Assembly and
links to the industry for pad-mounted transformer protection.
The Bay-O-Net Fuse has grown into the industry standard
protection package for single- and three-phase transformers.
The assembly combines the ease of hotstick operation with
the safety of deadfront construction and is used with an
isolation link to prevent line personnel from closing into a fault
when replacing a blown Bay-O-Net Link. Alternately, a backup, current-limiting fuse can be used in place of the isolation
link to increase interrupting ratings to 50 kA.
TABLE 1
ELSP Fuse Combinations

Flapper Valve Bay-O-Net Assembly Specification


Information
n Bay-O-Net Assembly shall include a valve that will shut when
the inner holder is removed from the housing and minimize oil
from spilling out of the Bay-O-Net Assembly.

Voltage (kV)

TransFusion Coordination Program


This free, web-based, easy-to-use coordination tool makes
transformer protective device selection for pad-mounted
transformers effortless. By simply inputting a few pieces of
data and selecting the desired level of protection, you can
quickly find the right Cooper Power Systems ELSP fuse, BayO-Net fuse, or MagneX interrupter for your application. The
TransFusion Coordination Program provides you the flexibility
of trying various combinations before deciding on the one
that best fits your application needs. A simple click of the
print button allows you to print your TCC curves and part
numbers.

8.3

9.9

Go to this site for your coordination program


www.coopertransfusion.com.
15.5

17.2

23

23 kV fuse for
use on 35 kV
systems

46

Current
Rating (A)
30
40
50
65
80
100
125
150
165
180
250
30
40
50
65
30
40
50
65
80
100
125
150
165
180
30
40
50
65
30
40
50
65
80
100
125
150
165

ELSP Part
Numbers
CBUC08030C100
CBUC08040C100
CBUC08050C100
CBUC08065C100
CBUC08080C100
CBUC08100C100
CBUC08125C100
CBUC08150D100
CBUC08165D100
CBUC08180D100
CBUC08250D100
CBUC09030C100
CBUC09040C100
CBUC09050C100
CBUC09065C100
CBUC15030C100
CBUC15040C100
CBUC15050C100
CBUC15065C100
CBUC15080C100
CBUC15100C100
CBUC15125C100
CBUC15150D100
CBUC15165D100
CBUC15180D100
CBUC17030C100
CBUC17040C100
CBUC17050C100
CBUC17065C100
CBUC23030C100
CBUC23040C100
CBUC23050C100
CBUC23065C100
CBUC23080C100
CBUC23100C100
CBUC23125D100
CBUC23150D100
CBUC23165D100

150

CBUC35150D100

Description
8.3 kV 30 A
8.3 kV 40 A
8.3 kV 50 A
8.3 kV 65 A
8.3/9.9 kV 80 A
8.3/9.9 kV 100 A
8.3 kV 125 A
8.3 kV 150 A
8.3 kV 165 A
8.3 kV 180 A
8.3 kV 250 A
9.9 kV 30 A
9.9 kV 40 A
9.9 kV 50 A
9.9 kV 65 A
15.5 kV 30 A
15.5 kV 40 A
15.5 kV 50 A
15.5 kV 65 A
15.5/17.2 kV 80 A
15.5/17.2 kV 100 A
15.5/17.2 kV 125 A
15.5 kV 150 A
15.5 kV 165 A
15.5 kV 180 A
17.2 kV 30 A
17.2 kV 40 A
17.2 kV 50 A
17.2 kV 65 A
23 kV 30 A
23 kV 40 A
23 kV 50 A
23 kV 65 A
23 kV 80 A
23 kV 100 A
23 kV 125 A
23 kV 150 A
23 kV 165 A
23 kV 150 A fuse
for use on a 35 kV
System

Specifiers Guide: Components Master Catalog

Catalog Section

240-40

240-45

240-46

240-48

240-49
240-47
240-82
240-98

Description

kV Class

Base Part
Number

SIDE- AND COVER-MOUNTED BAY-O-NET FUSE ASSEMBLY


Flapper Side Wall-Mount
4000361C99FV
Side Wall
4000361C99MC
w/o Flapper Valve
Cover-Mount (Short)
4001177B51MC
Cover-Mount (Long)
4001177B53MC
CURRENT SENSING BAY-O-NET FUSE LINK
6A
4000353C04
10 A
4000353C06
15 A
4000353C08
25 A
4000353C10
40 A
4000353C12
65 A
4000353C14
100 A
4000353C16
140 A
4000353C17
DUAL SENSING BAY-O-NET FUSE LINK
3A
4000358C03
8A
4000358C05
15 A
4000358C08
25 A
4000358C10
50 A
4000358C12
65 A
4000358C14
100 A
4000358C16CB
140 A
4000358C18CB
DUAL ELEMENT BAY-O-NET FUSE LINK
5A
4038108C03
6A
4038108C04
8A
4038108C05
12 A
4038108C06
15 A
4038108C07
25 A
4038108C09
40 A
4038108C11
50 A
4038108C12
65 A
4038108C14
HIGH AMPERE OVERLOAD BAY-O-NET FUSE LINK
65 A
4038361C03CB
100 A
4038361C04CB
125 A
4038361C05CB
Shorting Bar (Solid Link)
4038361C10CB
ISOLATION LINK
3001861A_ _ _
ELSG FULL RANGE
359_ _ _ _M_ _M
(See Table 2 Below)
Current-Limiting Fuse
ELSP BACKUP
CBUC_ _ _ _ _ _
(See Table 1 Page 46)
Current-Limiting Fuse

Notes

1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4

1. Add suffix B to order individual


fuse; add M to order bag of 50.
2. When ordering high ampere overload
Bay-O-Net Fuse Link, a silver-plated
Bay-O-Net Fuse Assembly, part
number 4038804B03M, must be
ordered.
3. To coordinate an isolation link with
a Bay-O-Net Fuse when an ELSP
Fuse is not used, see Catalog
Section 240-47.
4. For recommended ELSP backup
CLF ratings, see Catalog Section
240-98 or TransFusion Coordination
Program.

1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
1, 3, 4
2,
2,
2,
2,

3,
3,
3,
3,

4
4
4
4

TABLE 2
E-rated ELSG Fuse Ordering Information for 15 kV Wetwell Holder*
E-Rating
4
8
12
15
20
25
30
40
50
60

Continuous
Current Rating
(A)
9
14
18
24
34
35
46
53
65
76

Fuse kV and Catalog Number


8.3 kV
3593004M02M
3593008M02M
3593012M02M
3593015M02M
3593020M02M
3593025M02M
3593030M02M
3593040M02M
3593050M02M
3593060M02M

15.5 kV
3594004M83M
3594008M83M
3594012M83M
3594015M83M
3594020M83M
3594025M83M
3594030M83M
3594040M83M
3594050M83M
3594060M83M

E-Rating
65
65
80
80
100
100
120
125
150

Continuous
Current Rating
(A)
92
95
106
125
130
155
150
180
200

Fuse kV and Catalog Number


8.3 kV

3593065M01M

3593080M01M
3593100M01M

3593125M01M

15.5 kV
3594065M83M

3594080M83M

3594100M83M

3594120M83M

3594150M83M

* 15 kV Wetwell Holder part numbers KP3437322C1M (mild steel). For 25 kV and 35 kV ordering information, refer to Catalog Section 240-82.

Eaton's Cooper Power Systems

47

MagneX Single-Phase Interrupter


200 A LOADBREAK & DEADBREAK CONNECTORS
The MagneX single-phase interrupter offers a solution to the utility
wanting to eliminate oil exposure in the field when operation occurs due
to transformer overloads. There is no need for replacement fuse links,
resulting in economic value to the user. In addition, a MagneX interrupter
in series with a back-up, current-limiting fuse offers additional protection.
TABLE 1
Voltage Ratings and Characteristics
Description
Impulse 1.2x50 Microsecond Wave
60 Hz-1 Minute Voltage Withstand
Continuous Current Rating
Switching Load Currents, 200 Times
Magnetizing Current Switching

Rating
150 kV
50 kV
42 A
42 A
200 Times

TABLE 2
Interrupting Rating
Voltage
kV-LG

RMS
RMS
Symmetric Asymmetric
(A)
(A)
2800
4200
1500
2250
500
750

8.3
15.5
23.0

Continuous current ratings and dielectric testing are in


accordance with ANSI/IEEE Std C57.12 standard.
Switching and Fault Close IEEE Std C37.41 standard.
Overload Protection IEEE Std C57.41 standard.

TABLE 3
MagneX Significant Digit Catalog Number System
Example: To order a single-phase MagneX interrupter without indicator, single-phase trip, with float
and E12 sensor, the catalog number would be MX1BN1SYE12. (Refer to Catalog Section 240-34.)

Standard
Options
Standard Options

Digits: 1 2 3 4 5 6 7 8 9 10 11

M X 1 A E 1 S Y E 1 2
System
Connection
Y-Wye

Product
MagneX

Phases
1-One

Indicator
A-w/Indicator
B-w/o Indicator

Trip Type
S-Single-Phase Trip
Float
1-w/Float
2-w/o Float

TABLE 4
Isolation Link MagneX Correlation Chart

Sensor
Size
E01
E03
E06
E10
E12
E18
E25
E30
E40
E50

Overload
E-EO
N-Non EO

ORDERING INFORMATION
Use Table 6 to determine the correct MagneX interrupter
suffix (sensor number) for the application.
Use Table 3 to determine the catalog number.
When ordering a MagneX interrupter with a standard handle,
a hardware kit must be ordered separately. Use Table 7 to
determine the hardware kit catalog number.
To select the correct isolation link, use Table 4 to cross
reference the isolation link to the selected MagneX interrupter.
An isolation link is required if the MagneX is not in
series with a current-limiting fuse.
Example MagneX interrupter with an emergency overload,
indicator, and a float in series with an ELSP Current-Limiting
Fuse for a single-phase, 7.2 kV phase-to-ground, 25 kVA
transformer, specify:
1 40 A ELSP Fuse 3543040M61M
1 MagneX interrupter MX1AE1SYE06
1 Hardware Kit (with Emergency Overload, indicator, and
no adaptor) 3638535A05
See the following Catalog Sections for further information:
ELSP Fuse Holder 240-53
ELSP Current-Limiting Backup Fuse 240-98

48

To select the correct isloation link, use Table


1 to cross reference the isolation link to the
selected MagneX sensor. An isolation link is
required if the MagneX is not in series with
a current-limiting fuse.

Sensor

Number

Isolation Link

E01
E03
E06
E10
E12
E18
E25
E30
E40
E50

3637803B01
3637803B08
3637803B02
3637803B09
3637803B10
3637803B03
3637803B03
3637803B05
3637803B05
3637803B05

MagneX with Current-Limiting Fuse


To order a MagneX interrupter and current-limiting fuse
combination, see Table 5.
TABLE 5
Hardware Kits
Description

Catalog Number

Without emergency overload

3638535A04

With emergency overload

3638535A05

With adaptor without emergency overload

3638535A07

With adaptor with emergency overload

3638535A08

Hotstick adaptor only

3639585A01

Using TCC Curves


To determine or confirm the MagneX interrupter will coordinate
with upstream and down stream system requirements, use
the time-current characteristic curves (See R240-91-310).
For full size TCC curves, contact your Cooper Power systems
representative.

Specifiers Guide: Components Master Catalog

MagneX with hotstick adapter and indicator


TABLE 6
Single-Phase Transformer (Phase-to-Ground) Applications Correlation Chart

kVA/kV

10

15

25

37.5

50

75

100
167

2.4
E06
E10
E18
E25
E30
E50
-
-

4.16
E06
E06
E10
E18
E18
E30
E40
-

4.8
E03
E06
E10
E12
E18
E25
E30
E50

Primary Voltage kV
6.9
7.2
7.62-7.97
E03
E03
E03
E03
E03
E03
E06
E06
E06
E10
E10
E10
E12
E12
E12
E18
E18
E18
E25
E25
E25
E40 E40
E30

8.32
E03
E03
E06
E10
E10
E18
E18
E30

12.00 12.47-13.2 13.8-14.4 19.92


E01
E01
E01
E01
E03
E03
E03
E01
E03
E03
E03
E03
E06
E06
E06
E03
E06
E06
E06
E06
E10
E10
E10
E06
E12
E12
E12
E10
E18
E18
E18 E12

Notes:
Recommendations are based on:
Minimum trip curves, and Maximum trip and clear curves, R240-91-310.
Deration factor of 0.5% per C above 25 C.
Allowable loading greater than 140% for four hours in accordance with IEEE Std C57.91-1981 standard Guide for Loading Distribution Transformers, Table 6.

TABLE 7
Recommended MagneX Interrupter Sensor and ELSP Current-Limiting Fuse Combinations
Nominal Single Phase
(kV Phasetoground)
10 kVA
ELSP Rating with Emergency Overload
MagneX Element
15 kVA .
ELSP Rating with Emergency Overload
MagneX Element
25 kVA
ELSP Rating with Emergency Overload
MagneX Element
37.5 kVA
ELSP Rating with Emergency Overload
MagneX Element
50 kVA
ELSP Rating with Emergency Overload
MagneX Element
75 kVA
ELSP Rating with Emergency Overload
MagneX Element
100 kVA
ELSP Rating with Emergency Overload
MagneX Element
167 kVA
ELSP Rating with Emergency Overload
MagneX Element

8.3 kV

15.5 kV
12.014.4
16.34

23 kV
19.92

2.4

4.16-4.8

6.9-8.0

30
E06

30
E03

30
E03

30
E01

30
E01

30
E01

50
E10

30
E06

30
E03

30
E03

30
E01

30
E01

80
E18

50
E10

30
E06

30
E03

30
E03

30
E03

100
E18

80
E12

50
E10

30
E06

30
E03

30
E03

150
E30

100
E18

50
E12

30
E06

30
E06

30
E03

150
E40

125
E25

100
E18

40
E10

30
E06

30
E06

250
E50

165
E40

100
E18

50
E12

40
E10

30
E06

180
E50

150
E40

80
E18

80
E18

50
E12

Notes:
Table shows minimum recommended ELSP Fuse ratings. Recommended ELSP Backup Fuse (described in Catalog Section 240-98) will coordinate with the MagneX interrupter
and melt on internal transformer faults. The MagneX interrupter recommendations are based on:
Minimum trip curves, and Maximum trip and clear curves R240-91-310.
Deration factor of 0.5% per C above 25C.
Allowable loading greater than 140% for four hours in accordance with IEEE Std C57.41-1981 standard guide for Loading Distribution Transformers, Table 6.

Eaton's Cooper Power Systems

49

MagneX Three-Phase Interrupter


TABLE 4
The Three-Phase MagneX interrupter offers a
MagneX Significant Digit Catalog Number System
solution to the utility wanting to eliminate oil
exposure in the field when operation occurs due
Example: To order a two- or three- phase MagneX interrupter without indicator, single- and
to transformer overloads. There is no need for
three-phase trip, with float and E12 sensor, the catalog number would be MX3BN1SYE12.
replacement fuse links, resulting in economic value (Refer to Catalog Section 240-33.)
to the user. In addition, a MagneX interrupter in

Standard
Options
series with a back-up, current-limiting fuse offers
Digits: 1
2 3 4 5 6 7 8 9 10 11
additional protection.

MagneX Interrupter Specification Information


n Breaker shall be installed on the primary side of
transformer.
n

TABLE 1
Voltage Ratings and Characteristics
kV
150 kV

60 Hz-1 Minute Voltage Withstand

Rating
-

50 kV

Continuous Current Rating

42

Switching Load Currents

42

Indicator
B-w/o Indicator

Trip Type
M-Multi-Phase Trip*
S-Single-Phase Trip**
Note: For 2-Phase MagneX
digit 7 must be "M"
* If M, only select "D" for
System Connection (digit 8)
** If S, only select "Y" for
System Connection (digit 8)

Digits
7 8
M
D
MD-Multi-Phase Trip with Delta System Connection
S
Y
SY-Single-Phase Trip with Wye System Connection

RMS
Asymmetric
(A)

8.3

2800

4200

15.5

1500

2250

23.0

500

750

NOTE: Choose "MD" for Two-Phase MagneX

ORDERING INFORMATION
Use Table 4 to determine the catalog number.
When ordering a MagneX interrupter with a standard handle,
a hardware kit must be ordered separately. Use Table 3 to
determine the hardware kit catalog number.

TABLE 3
Hardware Kits
Description

Phases
2-Two
3-Three

Sensor
Size
E01
E03
E06
E10
E12
E18
E25
E30
E40
E50

Float
1-w/Float
2-w/o Float

TABLE 2
Interrupting Rating
RMS
Symmetric
(A)

Overload
N-Non EO

Continuous current ratings and dielectric testing are in accordance with


IEEE Std C57.12 standard.
Switching and Fault Close IEEE Std C37.41 standard.
Overload Protection IEEE Std C57.41 standard.

Voltage
kV-LG
(A)

System
Connection
D-Delta
Y-Wye
Note: For 2-Phase
MagneX digit 8
must be "D"

Product
MagneX

Breaker shall have the capability to energize


and de-energize the 3 transformer by one
hotstick operation.

Description
Impulse 1.2x50 Microsecond Wave

X 3 B N 1 M D E 1 2

Catalog Number

Standard Handle Kit & Hardware


without Emergency Overload

3638535A09

Hotstick Adapter

3639585A01

TransFusion Coordination Program


This free, web-based, easy-to-use coordination tool makes
transformer protective device selection for pad-mounted
transformers effortless. By simply inputting a few pieces of
data and selecting the desired level of protection, you can
quickly find the right Cooper Power Systems ELSP fuse, BayO-Net fuse, or MagneX interrupter for your application. The
TransFusion Coordination Program provides you the flexibility
of trying various combinations before deciding on the one
that best fits your application needs. A simple click of the
print button allows you to print your TCC curves and part
numbers.
Go to this site for your coordination program
www.coopertransfusion.com.

50

Specifiers Guide: Components Master Catalog

TWO- AND THREE-PHASE MAGNEX INTERRUPTER


OPERATION
Figure 1 demonstrates the circuit diagram for the three-phase
MagneX interrupter with single-phase sense, single-phase
trip. The three-phase MagneX interrupter with single-phase
sense, single-phase trip contains one sensors per phase. It
reacts to fault currents on one phase and will cause tripping of
that phase only. The MagneX interrupter then can be reset
via the single operating handle by opening all three phases and
closing all phases back in simultaneously.
Figure 2 demonstrates the circuit diagram for the three-phase
MagneX interrupter with single-phase sense, three-phase
trip, containing one sensor in two of the three phases. This
product should only be applied to delta-connected primary
transformers, where any fault current flow in one phase will
also flow in an adjacent phase. It reacts to fault currents on
one phase and will cause tripping of all three phases. The
MagneX interrupter then can be reset via the single operating
handle by opening all three phases and closing all phases
back in simultaneously.
The three-phase MagneX interrupter with single-phase sense,
three-phase trip should always be used in series with at least
one backup current-limiting fuse in each of the three phases.
The backup current limiting fuses (see ELSP catalog section
240-98) provide high-current interruption capability.
Figure 3 shows the circuit diagram for the two-phase MagneX
interrupter. The two-phase MagneX interrupter was specifically
designed for single-phase, two bushing transformers, where
disconnection of both bushings is desired following fault/
overload detection. The MagneX interrupter will react to a fault
sensed in either leg of the transformer primary. Interruption
takes place in both interruption chambers simultaneously,
disconnecting both legs of the transformer from the circuit.

Sensor

Interrupter
Chambers

Sensor
Ganged
Trip
Sensor

Figure 1.
Three-phase MagneX interrupter, singlephase sense, single-phase trip.

Sensor

Interrupter
Chambers

Sensor
Ganged
Trip
Sensor

Figure 2.
Three-phase MagneX interrupter, singlephase sense three-phase trip.

Interrupter
Chambers

Sensor
Ganged
Trip
Sensor

Figure 3.
Two-phase MagneX interrupter.

Eaton's Cooper Power Systems

51

200
Faulted
A Loadbreak
Circuit Indicators
& Deadbreak Connectors
Faulted Circuit Indicators
Cooper Power Systems offers a wide variety of faulted circuit indicators (FCIs) ranging from basic circuitry models in
the Delayed Reset style to the more sophisticated circuitry
of the Test Point Reset and Electrostatic Reset types. Our
S.T.A.R. Faulted Circuit Indicator product line offers six
basic types of FCIs and each unit is tailored to be the most
reliable for the intended application. Each type varies by reset
method and the type of system it connects to.
Standard S.T.A.R. features include:
n LO/HI Trip Rating Selection Innovative trip ratings
greatly simplify FCI selection application
n Current Transformer Sensing Design For maximum trip
accuracy and elimination of false tripping on adjacent cable
events
n Inrush Restraint Eliminates false tripping by ignoring
inrush currents caused by reclosing operations of protective
devices on the system. A dead time of 200 ms will activate
the inrush restraint feature.
n Low-Pass Filter Technology Prevents false tripping due
to capacitive cable discharge
n Design Tested to IEEE Std 495 standard and
Manufactured in ISO 9001 Facility To ensure highest
performance and quality
In addition to the above features, the Pathfinder FCIs
include:
n Variable Trip Technology Single trip rating for one-sizefits-all application
n Auto Adjusting Trip Technology Detects average load
current over time above or below 75 A and adjusts trip
rating to 200 A or 800 A automatically.
n Self Adjusting Reset Restraint (test point mounted model)
Learns your system voltage and wont allow false
resetting due to backfeed voltage
n BLOC Battery Life Optimization Circuitry for maximizing
battery life
n Remote Fiber Optic Cable (test point mounted model)
Optional remote for convenient remote indication
Pathfinder Test Point Faulted Circuit
Indicator Specification Information
n Fault indication on minimum 200 A di/dt
within 100 ms (variable trip).
n Response time of 3 ms or less, for
coordination with current-limiting fuses
(fixed trip).
n Inrush restraint to prevent false tripping
due to current inrush conditions.
n Low pass filter specifically tuned to
prevent false tripping on high frequency
transients, but to allow proper indication
on systems using current-limiting fuses.
n Temperature compensation for accurate
and reliable performance over a
temperature range of -40 C to +85 C.
n Reset restraint to prevent false reset due
to excessive voltage feedback levels
up to 80% of nominal system voltage
(STVT).
n Installation using single hotstick.

52

Bushing
Adapter
Loadbreak
Elbow
Connector
with
Fused
Loadbreak Optional
Loadbreak
Integral
Elbow
Elbow
Connector Jacket Seal Connector
FCI

Bushing
Adapter

FCI

U-OP
Connector

T-OP II
Connector
Transformer
or Switchgear
Apparatus

Loadbreak
Protective
Cap

M.O.V.E.
Elbow
Arrester

600 A
Protective
Cap

BOL-T
Connector

One-Piece
Bushing

T-OP II
Connector
Grounding
Elbow

BOL-T
Connector
Junction
Bars

FCI

FCI
T-OP II
Connector/
BT-TAP
Connector

Deadbreak
Junction

Deadbreak
Junction

Standoff
Bushing

Shield
Adapter

Loadbreak
Protective Cap

CR FCI

PUSH-OP

Parking
Stand
Bracket

CR & LVR FCI

T-OP II

Connecting Plug
Junction Bars
BOL-T Connector

Deadbreak Junction
Cable Transition Module

Specifiers Guide: Components Master Catalog

200 A Loadbreak & Deadbreak Connectors


For 15 kV, 25 kV and 35 kV Class
Catalog Section

Description

TEST POINT RESET



Adapter Kit

High (HI)-Trip
High (HI)-Trip w/Aux. Contact
High (HI)-Trip w/Adapter Kit

Low (LO)-Trip
Low (LO)-Trip w/Aux. Contact
320-40 Low (LO)-Trip w/Adapter Kit
PATHFINDER TEST POINT RESET

Variable Trip
Variable Trip w/Aux. Contact
Fiber Optic Remote Cable (6 ft.)

Reset Tool
320-42


Adapter Kit
LOW VOLTAGE RESET

High (HI)-Trip
High (HI)-Trip w/Aux. Contact

Low (LO)-Trip
320-50 Low (LO)-Trip w/Aux. Contact
ELECTROSTATIC RESET
High (HI)-Trip
High (HI) Trip with LED (LIght Emitting Diode) Indication
Low (LO)-Trip
Low (LO) Trip with LED (Light Emitting Diode) Indication
320-60 Replaceable Battery
CURRENT RESET
High (HI)-Trip
Low (LO)-Trip
High (HI) Trip with Auxiliary Contacts
320-75 Low (LO) Trip with Auxiliary Contacts
PATHFINDER CURRENT RESET
Variable Trip
Variable Trip with Auxiliary Contacts
320-77
TEST POINT HOT LINE INDICATOR
Hot Line Indicator
Adapter Kit

Notes:
1. To add remote FISHEYE display
add an R as the last character in
the part number, or a S for the
small remote display.

Base Part
Number

Notes

STAK
STHI
STHIA
STHIK
STLO
STLOA
STLOK

4
1
1

2. SFOC (Star Fiber Optic Cable) standard


length is 6 ft. add 09F for 9 ft. fiber
optic display, 12 for 12 ft., 25 for
25 ft.

1
1

3. To add universal power supply


(120, 208 or 277 VAC power
connection), add a U as the last
character in the part number.
4. Accessories to be ordered separately.

STVT
STVTA
SFOC
SMRT

2
4

STAK

SLHI
SLHIA
SLLO
SLLOA

3
3
3
3

SEHI
SEHIL
SELO
SELOL
SRPB

SCHI
SCLO
SCHIA
SCLOA

1
1
1
1

SCVT
SCVTA

1
1

STHL
STAK

320-80
PROGRAMMABLE DELAYED RESET
Auto Adjusting Trip, Programmable Reset
2, 4, 8, 24-Hour Reset
Reset Tool

SDOH
SMRT

320-95

Eaton's Cooper Power Systems

53

Faulted
200 Circuit
A Loadbreak
Indicators
& Deadbreak Connectors
200 A LOADBREAK & DEADBREAK CONNECTORS
Type
Description

Typical
System
Application

Test Point Reset

Underground

Low-Voltage Reset

Underground

Electrostatic Reset

Overhead

Programmable
Delayed Reset

Overhead

Current Reset

Underground
and Overhead

Physical
Mounting Location
On the test point of the
connector
On the URD shielded cable below
the connector
On bare or insulated non-shielded
cable

Voltage/Current
Requirements
Min. 5 kV L-G (2.4 kV for
Pathfinder)
A secondary voltage source
(min. 105 volts)
Min. 6.9 kV L-G (2.4 kV for
Pathfinder)

On overhead bare or insulated


non-shielded cable

None (Lithium battery powered


with programmable reset)

On the URD shielded cable below


the connector and on overhead
Min. 2.4 A continuous
bare or insulated non-shielded
cable

Catalog Number

Digits:

Standard Options
1 2 3 4 5 6 7 8
S




Options

S.T.A.R. FCI Line

54

FCI Type

Trip Rating

T: Test point
E: Electrostatic
C: Current
L: Low Voltage
D: Delayed

HI: High trip


LO: Low trip
VT: Variable trip
OH: Overhead

Specifiers Guide: Components Master Catalog

200 A Loadbreak & Deadbreak Connectors


S.T.A.R. Faulted Circuit Indicators Features
Model/Type

Application

Base Part Numbers


Catalog Section
Overhead
Underground/Pad-mounted

Trip Rating

High/Low Trip Rating

Test
Point
Reset
STLO
STHI
320-40

Pathfinder
Test
Point

Variable Trip Rating (Pathfinder)

STVT
320-42

Low
Voltage
Reset
SLLO
SLHI
320-50

Electrostatic Programmable
Reset
Delayed Reset
SELO
SEHI
320-60

SDOH
320-95

Auto Adjusting Trip


Standard
Features

Inrush Restraint
Temperature Compensation
Low Pass Filter

Battery Life Optimization Circuitry


Reset Restraint
Single Hot-Stick Installation
Automatic Reset
Open-Core CT Design

LED Display

FISHEYE Display
Flag Display
Available
Options

Auxiliary Contacts for SCADA


Remote FISHEYE Display
Small Remote Display

Remote Fiber Optic Display


Manual Testing/Reset Tool
Test Point Adapter Kit

Optional

Optional

2.4 Amps Continuous

2.0 Amps Continuous


Other

7.2 kV L-G
90 VAC

SCVT
320-77

Secondary Source
Externally Replaceable Battery
Reset
2.4 kV L-G
Requirements
5 kV L-G

SCLO
SCHI
320-75

Standard

Universal Power Supply


Power
Battery Powered
Requirements
Line Powered

PATHFINDER
Current
Reset

Closed-Core CT Design
Display Type

Current
Reset

Programmable

Product/Feature unique to the Cooper Power Systems S.T.A.R. Faulted Circuit Indicators

Eaton's Cooper Power Systems

55

Sectionalizing
Cabinets
Sectionalizing
Cabinets

200 A LOADBREAK & DEADBREAK CONNECTORS

Our single- and three-phase SecTER Sectionalizing Cabinets


and single-phase sectionalizing pedestals are designed as
cable sectionalizing centers, or as permanent or temporary
transformer pad covers.
The aesthetic low profile design provides unobtrusive
installations for sectionalizing, tapping, or terminating
underground cable. They are available in various sizes for
use on 15 kV through 35 kV, 200 A or 600/900 A singlephase and three-phase rated systems. For highly corrosive
environments, either stainless steel or aluminum is also
available. Heavy mild steel gauge designs along with a
continuous seam welding ensures a sturdy, smooth, long
lasting cabinet.
Universal mounting plates with optional our two-, three-
or four-way junctions can be factory installed. Junction
installations are available in either 200 A or 600 A versions.
SecTER features:
n Munsell Green, TGIC powder paint finish
n Designed for easy one-person opening and
improved access to interior terminations
n Door stop prevents accidentally closing
n Seams are designed to exceed ANSI tamperproof
standards
n Optional installed junctions
SecTER Specification Information
To capitalize on the benefits of our SecTER Sectionalizing
Cabinets, include the following information in your
specification:
n Diagonally cut removable cover and cabinet.
n Munsell Green TGIC powder paint finish.
n All welded, continuous seam construction.
n Cooper Power Systems 200 A or 600/900 A
junctions or junction bars installed.

Transformer
or Switchgear
Apparatus

FCI (pg 53)


Sectionalizing
Cabinets

Protective Cap
(pg 11)

Connecting Plug
BOL-T Connector

T-OP II
Connector

Deadbreak Junction
Loadbreak Junction

Cabinets with Junctions Installed


Single-Phase Cabinets Include (1) Junction, Three-Phase Cabinets Include (3) Junctions
Catalog
Number
(cabinet
only)

15 KV
25 KV
35 KV
600 A 15/25 KV
LJ215C2U LJ215C3U LJ215C4U LJ225C2U LJ225C3U LJ225C4U LJ235C2U LJ235C3U LJ235C4U DJ625A2U DJ625A3U DJ625A4U
Dimensions 15 KV LBC-2 15 KV LBC-3 15 KV LBC-4 25 KV LBC-2 25 KV LBC-3 25 KV LBC-4 35 KV LBC-2 35 KV LBC-3 35 KV LBC-4
VBJ -2
VBJ-3
VBJ-4
SERIES I SecTER 15/25/35 kV Class, 12 Gauge Steel Tank

Single-Phase
00400L00K54A 30H x 24W x 22D 00400L01K49A 00400L01K29A 00400L02K35B 00400L02K87A 00400L02K88A 00400L00K35A 00400L00K12D 00400L00K22D 00400L00K32D 00400L01K38A 00400L01K58A 00400L01K68A
00400L00K58A 30H x 30W x 22D 00400L02K24E 00400L02K37B 00400L02K81B 00400L02K17B 00400L02K27B 00400L02K47B 00400L00K72D 00400L00K82C 00400L00K92C 00400L01K22J 00400L01K32J 00400L01K42J
00400L00K62A 30H x 36W x 22D 00400L02K76A 00400L02K42B 00400L02K80B 00400L01K28A 00400L01K48A 00400L01K50A 00400L00K62D 00400L00K95D 00400L00K62C 00400L01K12M 00400L01K22M 00400L01K32M

Three-Phase
00450L00K02A 30H x 48W x 22D 00450L00K21E 00450L00K14D

00450L00K29C 00450L00K83C

00450L00K28D

00450L00K06A 30H x 66W x 22D 00450L00K36D 00450L00K10D 00450L00K15D 00450L00K09D 00450L00K19D 00450L01K53A 00450L00K08D 00450L00K18D

00450L01K71A 00450L00K01D

00450L00K35C 00450L00K97B 00450L01K63A

00450L00K10A 30H x 84W x 22D 00450L00K82D 00450L00K92D 00450L00K33C 00450L00K74E 00450L00K84E 00450L00K84C 00450L00K96C 00450L00K97C 00450L00K36C 00450L00K55A 00450L01K65A 00450L00K41E

SERIES II SecTER 15/25 kv Class, 14 Gauge Steel Tank


Single-Phase
00400L00K72A 30H x 24W x 15D 00400L02K62A 00400L02K51A 00400L02K44A 00400L02K71A 00400L02K26A 00400L02K45A

00400L00K73A 30H x 30W x 18D 00400L02K57A 00400L01K10A 00400L01K44A 00400L02K91A 00400L01K16A 00400L02K55A

Three-Phase
00450L00K28A 30H x 48W x 15D 00450L01K54A 00450L00K05C

00450L00K30A 30H x 60W x 15D 00450L00K89C 00450L00K04C 00450L00K80B 00450L00K66B 00450L00K86B 00450L00K64B

00450L00K29A 30H x 48W x 18D 00450L01K67A 00450L00K63B

00450L00K56B 00450L00K96B
00450L00K76B 00450L00K81B

00450L00K31A 30H x 60W x 18D 00450L00K49D 00450L00K82B 00450L00K83B 00450L00K36A 00450L01K26A 00450L00K54B

Single-Phase
00400L02K12A 48H x 18W x 18D 00400L01K39P 00400L01K23A 00400L02K61A 00400L02K46N 00400L02K56B 00400L02K64B

56

Specifiers Guide: Components Master Catalog

Catalog Section

Description
SERIES I SecTER
12 Gauge
Steel Tank
1-Phase

12 Gauge
Steel Tank
3-Phase

kV Class

Base Part Number

Notes

15/25/35 kV

00400L00K54A
(30H x 24W x 22D)
00400L00K58A
(30H x 30W x 22D)
00400L00K62A
(30H x 36W x 22D)
00450L00K02A
(30H x 48W x 22D)
00450L00K06A
(30H x 66W x 22D)
00450L00K10A
(30H x 84W x 22D)

00400L00K72A
(30H x 24W x 15D)
00400L00K73A
(30H x 30W x 18D)
00450L00K28A
(30H x 48W x 15D)
00450L00K30A
(30H x 60W x 15D)
00450L00K29A
(30H x 48W x 18D)
00450L00K31A
(30H x 60W x 18D)

15/25/35 kV

1000-05
SERIES II SecTER
14 Gauge
Steel Tank
1-Phase
14 Gauge
Steel Tank
3-Phase

15 kV
15/25 kV
15 kV

15/25 kV
1000-05
SERIES I GROUND SLEEVES
Ground Sleeve
15/25/35 kV
1-Phase

Ground Sleeve
3-Phase

15/25/35 kV

1000-05
SERIES II GROUND SLEEVES
Ground Sleeve
15/25/35 kV
1-Phase
Fiberglass
Ground Sleeve
3-Phase
Fiberglass

Ground Sleeve
Steel
1-Phase

Ground Sleeve
Steel
3-Phase

15/25/35 kV

15/25/35 kV

15/25/35 kV

1000-05
SECTIONALIZING
PEDESTAL
14 Gauge Steel
1-Phase

15/25 kV

1
1
1
1
1

1
1
1
1
1

00400L00K02G
(18H x 24W x 22D) (Fiberglass)
00400L00K05G
(30H x 24W x 22D) (Fiberglass)
0400L00K10GM
(24H x 24W x 22D) (Steel)
00450L00K04G
(18H x 48W x 22D) (Fiberglass)
00450L00K07G
(30H x 48W x 22D) (Fiberglass)
0450L00K17GM
(24H x 48W x 22D) (Steel)

2, 3

00400L00K00G
(18H x 24W x 15D)
00400L00K01G
(18H x 30W x 18D)
00450L00K00G
(18H x 48W x 15D)
00450L00K02G
(18H x 60W x 15D)
00450L00K01G
(18H x 48W x 18D)
00450L00K03G
(18H x 60W x 18D)
0400L00K13GM
(18H x 24W x 15D)
0400L00K14GM
(18H x 30W x 18D)
0400L00K16GM
(24H x 30W x 18D)
0450L00K20GM
(18H x 48W x 15D)
0450L00K22GM
(18H x 48W x 18D)
0450L00K26GM
(24H x 48W x 18D)

2, 4
2, 5
2, 6
2, 7
2, 8

Notes:
1. For stainless steel tank change
the A in digit 12 to a S. For
aluminum tank change the A in
digit 12 to a L.
2. Width and depth dimensions must
be matched to corresponding
SecTER dimensions.
3. To change width of fiberglass
ground sleeve, change digit 11 from
a 2 to a 3 for 30" width, to a 4
for 36" width.
4. To change width of fiberglass
ground sleeve, change digit 11 from
a 5 to a 6 for 30" width and to a
7 for 36" width.
5. To change width of steel ground
sleeve, change digit 10 from a 0
to a 1 for 30" width and a 2 for
36" width.
6. To change width of fiberglass
ground sleeve, change digit 11 from
a 4 to a 5 for 66" width or to a 6
for 84" width.
7. To change width of fiberglass
ground sleeve, change digit 11 from
a 7 to a 8 for 66" width or to a 9
for 84" width.
8. To change width of steel ground
sleeve, change digit 10 from a 7
to a 8 for 66" width or a 9 for 84"
width.
9. To change width of steel ground
sleeve, change digit 10 from a 0
to a 1 for 60" width.
10. To change width of steel ground
sleeve, change digit 10 from a 2
to a 3 for 60" width.
11. To change width of steel ground
sleeve, change digit 10 from a 6
to a 7 for 60" width.

2
2
2
2
2
2
2
2, 9
2, 10
2, 11

00400L02K12A
(48H x 18W x 18D)

1000-10

Note: Clr SecTER Cabinet information can be found on page 19.

Eaton's Cooper Power Systems

57

PartNumber
Number
Index
Part
Index

200 A LOADBREAK & DEADBREAK CONNECTORS

Base Part Number


0113C
0190FC
0213CSS
0213CX
0290FCS
0290FHJ
0290MCX
359_ _ _ _M_ _M
00400L00K00G
00400L00K01G
00400L00K02G
00400L00K05G
00400L00K12D
00400L00K22D
00400L00K32D
00400L00K35A
00400L00K54A
00400L00K58A
00400L00K62A
00400L00K62C
00400L00K62D
00400L00K72A
00400L00K72D
00400L00K73A
00400L00K82C
00400L00K92C
00400L00K95D
00400L01K10A
00400L01K12M
00400L01K16A
00400L01K22J
00400L01K22M
00400L01K23A
00400L01K28A
00400L01K29A
00400L01K32J
00400L01K32M
00400L01K38A
00400L01K39P
00400L01K42J
00400L01K44A
00400L01K48A
00400L01K49A
00400L01K50A
00400L01K58A
00400L01K68A
00400L02K12A
00400L02K17B
00400L02K24E
00400L02K26A
00400L02K27B
00400L02K35B
00400L02K37B
00400L02K42B
00400L02K44A
00400L02K45A
00400L02K46N
00400L02K47B
00400L02K51A
00400L02K55A
00400L02K56B
00400L02K57A
00400L02K61A
00400L02K62A
00400L02K64B
00400L02K71A
00400L02K76A
00400L02K80B
00400L02K81B
00400L02K87A
00400L02K88A
00400L02K91A

58

Page Base Part Number Page


42 00400L00K02G 20
42 00400L00K05G 20
57
42 00450L00K00G
56
42 00450L00K01D
57
42 00450L00K01G
56, 57
42 00450L00K02A
57
42 00450L00K02G
57
47 00450L00K03G
56
57 00450L00K04C
57
57 00450L00K04G
56
57 00450L00K05C
57 00450L00K05G 20
56, 57
56 00450L00K06A
57
56 00450L00K07G
56
56 00450L00K08D
56 00450L00K08G 20
56
56, 57 00450L00K09D
56, 57
56, 57 00450L00K10A
56
56, 57 00450L00K10D
56
56 00450L00K14D
56
56 00450L00K15D
56
56, 57 00450L00K18D
56
56 00450L00K19D
56
56, 57 00450L00K21E
56, 57
56 00450L00K28A
56
56 00450L00K28D
56, 57
56 00450L00K29A
56
56 00450L00K29C
56, 57
56 00450L00K30A
56, 57
56 00450L00K31A
56 00450L00K32G 20
56
56 00450L00K33C
56
56 00450L00K35C
56 00450L00K35G 20
56
56 00450L00K36A
56
56 00450L00K36C
56
56 00450L00K36D
56
56 00450L00K41E
56
56 00450L00K49D
56
56 00450L00K54B
56
56 00450L00K55A
56
56 00450L00K56B
56
56 00450L00K63B
56
56 00450L00K64B
56
56 00450L00K66B
56
56 00450L00K74E
56
56, 57 00450L00K76B
56
56 00450L00K80B
56
56 00450L00K81B
56
56 00450L00K82B
56
56 00450L00K82D
56
56 00450L00K83B
56
56 00450L00K83C
56
56 00450L00K84C
56
56 00450L00K84E
56
56 00450L00K86B
56
56 00450L00K89C
56
56 00450L00K92D
56
56 00450L00K96B
56
56 00450L00K96C
56
56 00450L00K97B
56
56 00450L00K97C
56
56 00450L01K26A
56
56 00450L01K53A
56
56 00450L01K54A
56
56 00450L01K63A
56
56 00450L01K65A
56
56 00450L01K67A
56
56 00450L01K71A
57, 20
56 0400L00K10GM
57
56 0400L00K13GM
57
56 0400L00K14GM
0400L00K16GM
57

Base Part Number


Page
0450L00K17GM
57
0450L00K18GM 20
0450L00K20GM
57
0450L00K22GM
57
0450L00K26GM
57
0890CSJ
42
6990FHL
42
8613CK
42
8613FH
42
8613FSK
42
8613TN
42
8690CK
42
8690FH
42
8690FSK
42
8690TN
42
18415-3
43
18415-8
43
19100
43
26958
40
26962-5
40
26992CPS
40
26993
40
26994
40
30041
40
30042
40
30043
40
30084
40
30124
40
30154
40
30450
40
30500
40
30554CPS
40
30584-3
43
30584-25
43
30584-30
43
30611CPS
40
30642CPS
40
30744
40
30914
40
36181CPS
40
36457
40
36459
40
36467
40
36472
40
36474
40
36476
40
36478
40
36480
40
36482CPS
40
36484
40
36486
40
36488
40
36490CPS
40
36494CPS
40
36496
40
36498
40
36559
40
36828CPS
40
36830CPS
40
36832CPS
40
36834CPS
40
36836
40
36838
40
40063
40
40114
40
40151CPS
40
40493CPS
40
40495CPS
40
40517
40
48410
40
48900
43
48900-2
43

Base Part Number


49341
49435
49437
100005
100006-4
100006-7
100006-12
100006-15
100006-16
100006-18
100007-1
100007-2
100007-3
100007-4
100007-6
100007-9
100007-23
100057
100075
100096
100370CPS
100399
100400
100433CPS
100434CPS
100440
100455
100456
100459
100460
100470
100471
100472
100473
100474
100600CPS
100601
100602
100603-7
100603-9
100603-11
100606
100609
100613
100618
100625CPS
104742
104742-2
118004
133040
133040-1
133040-2
133045CPS
133045Z20
0537980C06
0537980C07
0537980C12
0537980C22
0739658A02
2085399A01
2085399A02
2603393A03
2603973B02R
2603973B02T
2603989B01
2604688B01B
2604688B02B
2604688B03B
2605670A02M
2606754A03
2606821A01

Page
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
43
43
43
43
43
43
43
43
45
45
45
45
45
45
45
12
45
45
45
12
12
12
12
45
45

Base Part Number


Page
2606823A02
45
2606823A04
45
2610082P01 45
2625439A16B
12
2625439A17B
12
2637019B02
45
2637019B04
45
2637023B01
45
2637024C01M
45
2637160B01BS
12
2637160B02BS
12
2637160B03BS
12
2637172B01BS
12
2637172B02BS
12
2637172B03BS
12
2637407B03B
45
2637570A01B
12
2637585B01
45
2637604C01
45
2637700B01
45
2637700B02 45
2637904C01
45
2637939C01
45
2638370C01EX
14
2638372C01
45
2638372C02R
45
2638409C06B
14
2638640C01
45
2638772B03M
45
2639081B01B
45
2639205B01
14
3001861A_ _ _
47
3237686C03M
39
3237686C06M
39
3237686C09M
39
3237686C10M
39
3237686C12M
39
3237686C15M
39
3237686C18M
39
3237758C09M
39
3237758C10M
39
3237758C12M
39
3237758C15M
39
3237758C18M
39
3237758C21M
39
3238018C03M
39
3238018C06M
39
3238018C09M
39
3238018C10M
39
3238018C12M
39
3238018C15M
39
3238018C18M
39
3238019C09M
39
3238019C10M
39
3238019C12M
39
3238019C15M
39
3238019C18M
39
3238019C21M
39
3238020C18M
39
3238020C21M
39
3238020C24M
39
3238020C27M
39
3238020C30M
39
3238020C33M
39
3238020C36M
39
3593004M02M
47
3593008M02M
47
3593012M02M
47
3593015M02M
47
3593020M02M
47
3593025M02M
47
3593030M02M
47
3593040M02M
47

Specifiers Guide: Components Master Catalog

Base Part Number


3593050M02M
3593060M02M
3593065M01M
3593080M01M
3593100M01M
3593125M01M
3594004M83M
3594008M83M
3594012M83M
3594015M83M
3594020M83M
3594025M83M
3594030M83M
3594040M83M
3594050M83M
3594060M83M
3594065M83M
3594080M83M
3594100M83M
3594120M83M
3594150M83M
3637803B01
3637803B02
3637803B03
3637803B05
3637803B08
3637803B09
3637803B10
3638535A04
3638535A05
3638535A07
3638535A08
3638535A09
3639585A01
4000353C04
4000353C06
4000353C08
4000353C10
4000353C12
4000353C14
4000353C16
4000353C17
4000358C03
4000358C05
4000358C08
4000358C10
4000358C12
4000358C14
4000358C16CB
4000358C18CB
4000361C99FV
4000361C99MC
4038108C03
4038108C04
4038108C05
4038108C06
4038108C07
4038108C09
4038108C11
4038108C12
4038361C03CB
4038361C04CB
4038361C05CB
4038361C10CB
4001177B51MC
4001177B53MC
BLRTP615
BLRTP625
BLRTP635
BRK469
BT625

Page
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
48, 51
48, 51
48, 51
48, 51
48, 51
48, 51
48, 51
48
48
48
48
50
48
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
25, 26
26
25, 26
35
23, 24

Base Part Number


Page
BT635
23, 24
BTP615
23, 24
BTP625
23, 24
BTP635
23, 24
BW150F
45
BW150R
45
CA225A
12
CA225B
12
CA625
24, 25, 26, 27
CA635
24, 25, 26, 27
CBUC
47
CBUC08030C100
46
CBUC08040C100
46
CBUC08050C100
46
CBUC08065C100
46
CBUC08080C100
46
CBUC08100C100
46
CBUC08125C100
46
CBUC08150D100
46
CBUC08165D100
46
CBUC08180D100
46
CBUC08250D100
46
CBUC09030C100
46
CBUC09040C100
46
CBUC09050C100
46
CBUC09065C100
46
CBUC15030C100
46
CBUC15040C100
46
CBUC15050C100
46
CBUC15065C100
46
CBUC15080C100
46
CBUC15100C100
46
CBUC15125C100
46
CBUC15150D100
46
CBUC15165D100
46
CBUC15180D100
46
CBUC17030C100
46
CBUC17040C100
46
CBUC17050C100
46
CBUC17065C100
46
CBUC23030C100
46
CBUC23040C100
46
CBUC23050C100
46
CBUC23065C100
46
CBUC23080C100
46
CBUC23100C100
46
CBUC23125D100
46
CBUC23150D100
46
CBUC23165D100
46
CBUC35150D100
46
CC2C
13, 15
CC2C_S
14
CC2C_T
12, 14
CC6A _ _ U
26
CC6A _ U
24
CC6A_U
25, 26
CC6C _ T
24
CC6C_T
25, 27
CC6C _ U
24
CC6C_U
25
CS
12, 13, 23, 24
CS125UFLTOOL
42
CTM005A
34
CTM009A
34
CTM010A
34
CTM011A
34
CTM012A
34
CTM015A
34
CTM019A
34
CTM020A
34
CTM024A
34

Eaton's Cooper Power Systems

Base Part Number


Page
CTM025A
34
CTM029A
34
CTM030A
34
CTM035A
35
DB250
14
DB250L
14
DB250S
14
DB635B150 45
DB635B200 45
DB935B150 45
DB935B200 45
DBA615
23
DBA625
23
DBA635
23
DBE625
25
DBE635
25
DCEA635M27
39
DCEA635M30
39
DCEA635M33
39
DCEA635M36
39
DCP625A
25
DCP625C
25
DCP635A
25
DCP635C
25
DE225
15
DE225__T
14
DIP625A
25
DIP625AS
26
DIP625C
25
DIP635A
25
DIP635AS
26
DIP635C
25
DIPCAP
25
DJ250-2
14
DJ250-T2
14
DJ625A_
23
DJ625A2
27
DJ625C_
23
DJ635A_
23
DJ635C_
23
DLJ615A2
19
DPC625
23
DPC625UT
23
DPC635
23
DPC635UT
23
DPD250
14
DPE250
14
DPS250
14
DRC250
14
DS225
15
DS225__T
14
DT625
25, 26, 27
DT635
25, 26, 27
FECC
13
FEF083A006
13
FEF083A008
13
FEF083A010
13
FEF083A012
13
FEF083A018
13
FEF083A020
13
FEF083A025
13
FEF083A030
13
FEF083A040
13
FEF155A006
13
FEF155A008
13
FEF155A010
13
FEF155A012
13
FEF155A018
13

Base Part Number


FEF155A020
GE215-1Y06
GE215-1Y06-K1
GE215-1Y06-K3
GE215-2Y06
GE215-2Y06-K1
GE215-2Y06-K3
GE225-1Y06
GE225-1Y06-K1
GE225-1Y06-K3
GE225-2Y06
GE225-2Y06-K1
GE225-2Y06-K3
GE235-1Y06
GE235-1Y06-K1
GE235-2Y06
GE235-2Y06-K1
HD625
HD635
IBWP225
ISB215
ISB225
ISB235
ISB625A
ISB625C
ISB635A
ISB635C
JBI25C1B1W1B
JBI25C1B2W1B
JBI25C1B3W1B
JBI25C1B4W1B
JBI25C1W2B
JBI25C1W3B
JBI25C1W4B
JBI25C2B
JBI25C2W
JBI25C2W1B
JBI25C2W2B
JBI25C2W3B
JBI25C3B
JBI25C3W
JBI25C3W1B
JBI25C3W3B
JBI25C4B
JBI25C4W
JBI25C4W1B
JBI25C5B
JBI25C5W
JBI25C6B
JBI25C6W
JBI35C1B1W1B
JBI35C1B2W1B
JBI35C1B3W1B
JBI35C1B4W1B
JBI35C1W2B
JBI35C1W3B
JBI35C1W4B
JBI35C2B
JBI35C2W
JBI35C2W1B
JBI35C2W2B
JBI35C2W3B
JBI35C3B
JBI35C3W
JBI35C3W1B
JBI35C3W3B
JBI35C4B
JBI35C4W

Page
13
43
43
43
43
43
43
43
43
43
43
43
43
43
43
43
43
25
25
11
12
12
12
23
23
23
23
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31

Base Part Number


Page
JBI35C4W1B
31
JBI35C5B
31
JBI35C5W
31
JBI35C6B
31
JBI35C6W
31
JBL25C2W1W
32
JBL25C4W2B
32
JBL35C2W1W
32
JBL35C4W2B
32
JBS25C2B1W2B
33
JBS25C2W3B
33
JBS25C2W3W
33
JBS25C3W1B2W
33
JBS25C3W1W2B
33
JBS25C3W3W
33
JBS25C4W4W
33
JBS35C2B1W2B
33
JBS35C2W3B
33
JBS35C2W3W
33
JBS35C3W1B2W
33
JBS35C3W1W2B
33
JBS35C3W3W
33
JBS35C4W4W
33
JBY325C1W2B
32
JBY325C1W3B
32
JBY325C3W
32
JBY335C1W2B
32
JBY335C1W3B
32
JBY335C3W
32
KP3437322C1M 47
LBI215
11
LBI225
11
LBITOOL
12
LCN2CLJ615_ _SQB 19
LCN2DLJ615_ _ILB
19
LCN2CLJ625_ _SQB 19
LCN2DLJ625_ _ILB
19
LCN615
19
LCN625 19
LE215
11, 13
LE225
11, 13
LE235
11, 13
LEJ215
11, 13
LEJ225
11, 13
LFEP215
13
LFEP215TFEC
11
LFEP225
13
LFEP225TFEC
11
LFI215
11
LFI225
11
LJ215C
11
LJ225C
11
LJ235C
11
LPC215
11
LPC225
12
LPC235
12
LPC615
19
LPD625 19
LPF215H
11
LPF215U
11
LPF215V
11
LPF225H
11
LPF225U
11
LPF225V
11
LPF235H
11
LPF235V
11
LRTP615
25, 27
LRTP625
25, 27
LRTP635
25, 27
O-62-21F
41
O-62-50F
41
O-62F
41
O-63-21F
41

59

Part Number Index


200 A LOADBREAK & DEADBREAK CONNECTORS
Base Part Number
Page
O-63-50F
41
O-63F
41
O-65-21FB
41
O-65-50FB
41
O-65FB
41
O-68-21FB
41
O-68-50FB
41
O-68FB
41
O-620-21F
41
O-620-50F
41
O-620F
41
OS50
41
OS-620
41
OSM004
35
OTTQ615
25
OTTQ625
25
OTTQ635
25
PDBA615
23
PDBA625
23
PDBA635
23
PH13-4
41
PISB625
23
PISB625HP
23
PISB635
23
PISB635HP
23
PK215
12
PK225
12
PK235
12
PKPB225
12
PLE225
11, 13
PLEA225N03
39
PLEA225N06
39
PLEA225N09
39
PLEA225N10
39
PLEA225N12
39
PLEA225N15
39
PLEA225N18
39
PLEA225N21
39
PLEJ225
11, 13
PLPC225
12
POP615
23, 24
POP625
23, 24
POP635
23, 24
PS625CLEER 19
PS625CLEERDM 19
RH15-10
41
SA
12, 13, 23, 24
SCHI
54
SCHIA
54
SCLO
54
SCLOA
54
SCVT
54
SCVTA
54
SDOH
53
SEC1P15CLEERA2 19
SEC1P15CLEERA2DP 19
SEC1P15CLEERA2L 19
SEC1P15CLEERA2DPL 19
SEC1P25CLEERA2 19
SEC1P25CLEERA2DP 19
SEC1P25CLEERA2L 19
SEC1P25CLEERA2DPL 19
SEC3P15CLEERA2 19
SEC3P15CLEERA2DP 19
SEC3P15CLEERA2L 19
SEC3P15CLEERA2DPL 19
SEC3P25CLEERA2 19

60

Base Part Number


Page
SEC3P25CLEERA2DP 19
SEC3P25CLEERA2L 19
SEC3P25CLEERA2DPL 19
SEHI
53
SEHIL
53
SELO
53
SELOL
53
SFOC
53
SLHI
53
SLHIA
53
SLLO
53
SLLOA
53
SMHI
53
SMLO
53
SMRT
53
SP15
37
SP25
37
SP35
37
SRPB
53
SSPL625A1
37
SSPL625A2
37
SSPL625A3
37
SSPL625A4
37
SSPL635A1
37
SSPL635A2
37
SSPL635A3
37
SSPL635A4
37
SSPLT615A1
37
SSPLT615A2
37
SSPLT615A3
37
SSPLT615A4
37
SSPLT625A1
37
SSPLT625A2
37
SSPLT625A3
37
SSPLT625A4
37
SSPLT635A1
37
SSPLT635A2
37
SSPLT635A3
37
SSPLT635A4
37
STAK
53, 54
STHI
53
STHIA
53
STHIK
53
STHL
54
STLO
53
STLOA
53
STLOK
53
STUD635-A
25, 45
STUD635-C
25, 45
STUD-A
25, 26, 45
STUD-C
25, 26, 45
STUD-T
25, 27, 37
STUD-U
25
STVT
53
STVTA
53
TP615
23, 24, 27
TP625
23, 24, 27
TP635
23, 24
TQHD625
25
TQHD635
25
TWRENCH
25
UOP625
23
WH3
41
WS12
34
WS1112
34
WS1118
34

Specifiers Guide: Components Master Catalog

Support Available When You Need It!


But Wait, Theres More
In addition to rubber goods, we also
supply surge arresters, tools, hotsticks,
connectors, bushings, fusing, faulted
circuit indicators, sectionalizing
equipment and more. Now, you can get
all of your products in one place from
one manufacturer Eaton's Cooper
Power Systems! If you need more detail
than what is contained in this easy to
use Specifiers Guide, we have additional
information available on the internet at
www.cooperpower.com.

Technical Support When You


Need It
If you cannot find what youre looking
for, or need more detailed information,
please contact Customer Service at
1-877-277-4636 (within domestic
USA), or email your questions to info@
cooperpowercentral.com. Technical
support and application information are
readily available. Eaton's Cooper Power
Systems can also provide practical,
hands-on training using actual products
so you can learn the easiest way to fit
our products into your application.
Following is additional information available to you from a variety of
resources.

Eaton
www.eaton.com

Eaton's Cooper Power Systems Website


www.cooperpower.com

Additional Industry Websites

IEEE industry standards


http://www.ieee.org/publications_standards/index.html
IEEE
http://www.ieee.org
Specific energy statistics from the U.S. government
http://www.eia.doe.gov/
U.S. Department of Energy
http://www.energy.gov/

Eaton's Cooper Power Systems

61

PRODUCT APPLICATION OVERHEAD AND UNDERGROUND

X-Limiter Direct-Connect Cap Fuses


AZE, US, UH, UX Station Class Arresters

NXC Fuse
Fuse Links

UI Intermediate Class Arresters


ELF Fuse (service transformer)

AZU Unde
Evolution H

D-73, H-72

ELF, X-Lim
K, D, or T F

Type L, HX

DR, ER, M
GENERATING STATION
TRANSFORMER

GENERATING PLANT

CAPACITOR
BANK

Tension Sl

DISTRIBUTION
SUBSTATION

Elbow and Parking Stand Arresters

Storm Trapper
Low Voltage Arresters

ELG, JOE, X-Limiter


NX, ELX, X-Limiter Clip-mount
SecTER
600 A Clr Loadbreak Connector System
600 A Deadbreak &
200 A Loadbreak Junctions
LINE TAP

TPR, CR, DR Fault Indicators

COMMERCIAL
CUSTOMER
AIR-INSULATED
PAD-MOUNTED
SECTIONALIZING
CABINET

AZU Under-oil Arrester


CLU Under-oil Arrester
M.O.V.E., Parking Stand Arresters
Storm Trapper and Storm Trapper H.E.,
Low Voltage Arresters
Bay-O-Net Link in Bay-O-Net Assembly,
Bay-O-Net with ELSP, MagneX Interrupter,
MagneX with ELSP, ELS in EL Bay-O-Net Assembly
(Air-insulated, NX Mounts, NX Arc Strangler)
Tap Changer, Dual Voltage Switch,
On/Off Loadbreak Switch,
Under-oil Arrester Disconnecter,
Secondary Bushings
Loadbreak Elbows, Fused Loadbreak Elbow Connectors,
Shield Adapters
1-pc Bushing, Bushing Well, Bushing Well Insert,
Rotatable Feedthru Insert, Bushing Well Plug
Standoff Insulator and Portable Feedthru Insert
Grounding Elbows
TPR, CR, DR, LV Fault Indicators

RECLOSER

Cable Splices
Type R Bypass Switch
Elbow and Parking Stand Arresters
BOL-T, BT-TAP, T-OP-II, PUSH-OP
Stirrups/Taps
U-OP 600 A Connector System
(Bushing Adapter, Shield Adapter)
DR, ER, MR Fault Indicators
600 A Clr Loadbreak Connector System
600 A Deadbreak & 200 A Loadbreak Junctions
URS, URT
Fused Loadbreak Elbow Connectors
UltraSIL VariSTAR
and Evolution HD/RP
ELSG in Wetwell Holder,
Pole Arresters
ELS in Bay-O-Net Assembly
(Air-insulated ELG)
Type L Cutouts
ELF, X-Limiter
Sectionalizing Switches
Hinge-mount,
(V-Blade/T-Blade/Straight Blade)
Companion Fuses,
1-pc Bushings
Fuse Links

UNS, UHS, UHG


Distribution Class
Arresters
Tension Sleeves
Stirrups/Taps

TPR, CR, DR Fault Indicators

AZU Un
and M.O.V.

NXC, D

RESIDENTIAL
CUSTOMER

RISER
POLE
SINGLE-PHASE PADMOUNT
TRANSFORMER

Cable Racks/Supports/Insulators

62

ENCLOSED
CAPACITO
BANK

OIL-FILLED
PADMOUNTED
SECTIONALIZING CABINET

Cable Splices

Specifiers Guide: Components Master Catalog

DISTRIBUTION SYSTEMS

ers

AZU Under-oil, CLU Under Oil UltraSIL VariSTAR and


Evolution HD/RP Distribution Class Polymer Arresters

r)

D-73, H-72 Disconnect Switches

AZU Under-oil, CLU Under Oil UltraSIL VariSTAR and


Evolution HD/RP Distribution Class Polymer Arresters
Storm Trapper H.E. Low Voltage Arrester
Tap Changer, Dual Voltage Switch

ELF, X-Limiter Hinge-mount, Companion Fuses


K, D, or T Fuse Links
Type L, HX, HX-CB Cutouts
Fuse Links
X-Limiter Hinge-mount Fuse
ELF Fuse

DR, ER, MR Fault Indicators


Tension Sleeves

Under-oil Cartridge Fuse


ELSP Fuse
Magne X Interrupter
Type L Cutouts
D, K, T, S, N, H, C Fuse Link
Companion Fuse
ELF Fuse
Service EntranceTerminals

Storm Trapper H.E.


Low Voltage Arresters
Service EntranceTerminals

LINE TAP

CAPACITOR RACK

POLETYPE
TRANSFORMER

RESIDENTIAL CUSTOMER

RECLOSER

AZU Under-oil Arresters CLU Under-oil Arresters,


Elbow Arresters, Parking Stand Arresters

R Bypass Switch

, UHS, UHG
ibution Class
sters

Bay-O-Net Link in Bay-O-Net Assembly,


Bay-O-Net with ELSP, MagneX Interrupter,
Three-Phase MagneX with ELSP, ELS in EL Bay-O-Net Assembly
(Air-insulated, NX Mounts, NX Arc Strangler)

sion Sleeves
ups/Taps

Tap Changer, Dual Voltage Switch,


Sectionalizing Switch, On/Off Loadbreak Switch,
Under-oil Arrester Disconnecter,
Secondary Bushings
Loadbreak Elbows, Fused Loadbreak Elbow Connectors,
Shield Adapters
1-pc Bushing, Bushing Well, Bushing Well Insert,
Rotatable Feedthru Insert, Bushing Well Plug
AZU Under-oil, CLU Under Oil,
and M.O.V.E. Parking Stand Arresters
NXC, Direct Connect Cap Fuse
X-Limiter Fuses

ENCLOSED
CAPACITOR
BANK

Hi-Line Tools,
Compression Tools,
Grounding Elbows

Standoff Insulator and Portable Feedthru Insert


ELF, NXD Fault Guard Tools

TPR, CR, DR, LV Fault Indicators

DR, ER, MR Fault Indicators (Kits)

Terminals and Grounding Elbows

THREE-PHASE PADMOUNT
TRANSFORMER

Eaton's Cooper Power Systems

INDUSTRIAL
CUSTOMER

LINE TRUCK
TOOLS

63

Eaton, Cooper Power Systems,


POSI-BREAK, BOL-T, BT-TAP, T-OP,
U-OP, SecTER, S.T.A.R., Kearnelex,
Pathfinder, BLOC, Kearney, FISHEYE,
Combined Technologies, Cam-EL,
PUSH-OP, EX, Aqua Seal, Airseal,
Squeezon, MagneX, Flapper, Hi-Line,
Fit-On, Storm Trapper, Companion,
NX, ELF, X-Limiter, JOE, NXC, ELX,
Cleer, and McGraw-Edison are
valuable trademarks of Eaton in the
U.S. and other countries. You are not
permitted to use these trademarks
without the prior written consent
of Eaton.

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton's Cooper Power
Systems Business
2300 Badger Drive
Waukesha, WI 53188
Cooperpower.com
2013 Eaton
All Rights Reserved
Printed in USA
December 2013

IEEE Std 386TM, IEEE Std 404TM,


IEEE Std 592TM, IEEE Std C62.11TM,
IEEE Std C57.91TM standards are
trademarks of the institute of
Electrical and Electronics Engineers,
Inc. (IEEE). This publication/product
is not endorsed or approved by the
IEEE.
ANSI is a registered trademark of
the American National Standards
Institute.
Unishield is a registered trademark
of Unitech, LLC. Burndy is a
registered trademark of FCI.
All other trademarks are property of
their respective owners.

For Eaton's Cooper Power


Systems information call
1-877-277-4636 or visit
www.CooperPower.com

You might also like