H&I. Condenser Performance Monitoring
H&I. Condenser Performance Monitoring
Jakarta Indonesia
The better the heat transfer rate, the better the vacuum, the
more efficient the Steam Turbine/Plant
Condenser
Design thermal and flow balance
Typically found in the Condenser Spec Sheet
Cooling
Cooling Tower spec sheet if applicable
For Once-Throughs, a thorough understanding of the pump
operation is needed, particularly number of pumps for each season
Thermal Kit
Extremely valuable in comparing actual to design under all
conditions
Contains information regarding Back Pressure vs Inlet Water
Temperatures, as well as flow and heat load on the condenser
11
Cooling Tower
Spec Sheet
12
13
Data Capture
HISTORIAN DOWNLOAD
Basic points
Plant load
Steam Load
Condenser Back Pressure
Cooling Water In and Out Temps
Heat Rate- both net and gross
Cogen Steam if applicable
Ambient Temperature
Hotwell Temperature
17
18
Data Import
20
Data Review
22
Graphing Options
23
Dashboard
Steam
CW Out
CW In
Condensate
Air-In-leakage
Temperature
TTD
ITD
TR
CF% = Ua / Ud
Ua = Q / A * LMTD
Ud = Ui * FL * F1 * F2
FL = Steam Load Factor
F1 = Inlet Water Correction Factor
F2 = Tube Gauge Correction Factor
Ui = Ideal Heat Transfer Coefficient
34
4.50
4.00
3.50
3.00
2.50
2.00
1.50
1.00
50
60
70
80
90
100
110
Condensate
Resistance = Rcond
Tube Resistance
= Rtube
Water Resistance =
Rwater
U = 1/( Resistances)
Important Considerations
Common Obstacles
Analyzing Data
Be patient
CASE STUDIES
Mechanical
Cleaning
Surfactant
Addition
DISCUSSION