GTC 081001
GTC 081001
GTC 081001
Power Generation
Oil and Gas
Petrochemical
Chemical
Water/Waste Water Treatment
Steel and Heavy Metals
Manufacturing
Pulp and Paper
Airport, Transit Stations
Amusement Theme Parks, and Tourist Sites
Oce Complexes and Shopping Centers
GAI-TRONICS
A Hubbell Company
System Capabilities
The NOVA PA/GA System oers a wide range of features and accommodates
the largest of system requirements. NOVA oers:
Technical Specications
Construction: 19 - 6U CPU plus 1U Keyboard
Dimensions: 482 x 267 x 330 mm (19 x 10.4 x 13 inches);
Keyboard: 482 x 45 x 243 mm
Power Supply: 24 VDC 25%
Power Consumption: 45W
Operating Temperature: 0 / 50C (32 / 122 F)
Fan Kit equipped: 0 / 60C (32 / 140 F)
Minimum Conguration
Processor: Intel 1600 MHz min.
Storage Device: Slot for Compact Flash, 2048 MB
Keyboard: 88 keys, integrated touchpad
Ports: Serial ports RS232/RS422/RS485
5 USB ports 2.0 compliant
2 100/1000 FAST Ethernet port
1 DVI Video interface
1 PCI Express slot
Operating System: Linux
GA I-TR ON I CS
A Hu b be ll Com pa ny
www.gai-tronics.com
Compact design 3U x 19
Up to 4 ampliers in a single module cage 3U (PA) + 1U (cage)
High eciency Class D 300Wrms Amplier
Thermal and output overload protections
Speakers line diagnostics function
Serial communication interface (RS485)
Forced cooling by means of dedicated fan activated on temperature threshold
Low frequency 30Hz test, setup and PA diagnostics, line ground leakage detection. A full set of front
panel LEDs is provided for fault indication (ground leakage, overload, over-heating temperature,
amplier fault), power on, Vu-meter function. An output transformer insulates the semiconductors
power rails from speaker line increasing safety for critical applications.
Technical Specications
Electrical
Nominal Power Output: 300Wrms (33.3 Load, 230Vac)
Line output voltage: 100Vrms (or client spec)
Input sensitivity: 0dBm (0.775V rms) // 68K
Frequency response: 40Hz - 16kHz (-3dB points)
Total harmonic distortion: <1% at 1kHz, 290Wrms
Signal to Noise ratio: >95dB (A)
Operating Voltage Options: AC Mains 120V or 230V
Input Mode: Mixed (CH1+CH2) / CH1 or CH2 priority
Power consumption: <450W or 550VA (at Nominal Power Output)
Mechanical
Mounting: 19 Standard Rack
Audio Connectors: 2 bal. 3 pin XLR + 3 pin screw terminals
AC Power: IEEE Standard, 3 pin
Operating temperature range: -10C to +45C
Storage temperature range: -40C to +70C
Relative humidity < 95 %
Data Comms (RS485): Connector type DB9
Weight: 9,3 Kg
Dimensions: (W x H x D) 100 x 130 x 395 mm, DIN standard 3U
Approvals
This mark indicates compliance with the following directives:
Radio & Telecommunications Terminal Equipment Directive 1999/5/EC (R&TTE)
A Hu bb e ll Compa ny
www.gai-tronics.com
Networking capability up to
64 devices
Up to 24 input/outputs
CE & UL approved
Graphic equalizer
Built-in diagnostics
Parametric equalizer
Feedback suppressor
Filters: HPF, LPF, high shelf, low shelf,
all pass
Mixers: standard, automatic, combiners
Controls: levels, invert, mute, preset, logic
Generators: tone, pink-noise, white-noise
Programmable delays: 0 to 2Sec
The Audio Processor AudiaFLEX oers a unique modular design. Conguration of the audio
matrix allows complete exibility in system design, including full redundancy. Audio input and
output are analogue with internal 24bit A/D & D/A converters. All internal processing is DSP, with
Ethernet communication for software control and DSP distribution. A multi-unit network
application is available by CobraNet, transporting digital audio over fast Ethernet.
Technical Specications
Frequency Response: 20Hz ~ 20kHz @ +4dBu
THD (20Hz ~ 20kHz @ +4dBu):
Line level < 0.006%
Mic level < 0.04%
Equiv. Input Noise (20Hz ~ 20kHz, 66dB, 150): -125dBu
Options:
Note:
- The standard module includes 1 Audio processor
(Base Unit), 2 Input Modules (4 channels), 4 Output
Modules (8 channels)
- Optional CobraNet interface supporting 64 channels
of digital audio (32 in / 32 out) over Fast Ethernet
A Hu b be ll Com pa ny
www.gai-tronics.com
The Input and Output signals of the Nova PA/GA system are managed by a Programmable Logic
Controller (PLC). The PLC is comprised of a Central Processing Unit (CPU) Module and Additional
I/O Modules (local or remote). Up to 250 I/O Modules can be connected over a three wire Bus to
up to 3000 I/O connections. Communication between PLC and CPU is via Modbus protocol.
The PLC CPU can manage an extensive list of remote I/O modules.
The PLC includes, as a minimum, one (1) Ethernet port, one (1) RS 485, one (1) RS 232 serial link
and two (2) USB ports.
The I/O modules can also be installed separately from the CPU over the three wire bus, to control
I/O modules in remote amplier cabinets, to control the local equipment and/or temperature.
Technical Specications
Memory:
User Memory - Compact: 128 KB SRAM
Program Memory - Compact: 512 MB Flash
Back-up data: On Flash EPROM
Digital Inputs:
Voltage: 24 Vdc 15%
Input current @ 24 Vdc: 3.75 mA (Typ)
Switching threshold: Low < 5Vdc; High > 15 Vdc
Input Resistance 6.4 K
Isolation Voltage: 500V rms
Output:
Transistor: 24 Vdc 15%@ 0.5A or 2A
Switching Voltage: 110 Vdc / 115Vac - 0.5A
Rated Voltage: 30Vdc / 115Vac
Max. current per contact 1.0A @ 30 Vdc / 0.5A @ 115 Vac
10V Analog Inputs: Resolution 12 bit
Analog Inputs: Suitable for Fire & Gas remote interfacing and monitoring
Power Consumption: 24 Vdc / 3W (60W max.)
A Hu bb e ll Compa ny
www.gai-tronics.com
The Engineers Test Panel is used in conjunction with the NOVA CPU to provide
complete system monitoring from a single, central location.
Basic panel conguration includes a handheld Push-to-Talk microphone, Tick-Tone
push-button for speaker test and red fault lamp.
An internal loudspeaker with a volume control for multiple broadcast monitoring is
available on request.
To prevent unauthorised
access to the panel, a rotary
switch with a key is also
available as an option.
Technical Specications
Audio Output: Balanced, 600 , 0 to 6 dBm output signal
Microphone Preamplier: Built-in Audio Processor
Loudspeaker: (on request)
Output Power: 2,5 W 4
Dimensions: 2U 19 rack x 330 mm / 11 inches depth
Weight: 1 kg (2 lbs)
GA I-TR ON I CS
A Hu b be ll Com pa ny
www.gai-tronics.com
The NOVA touch screen access panels employ industrial grade fanless PCs, and rack-mount, or desk-top
LCD-TFT displays for convenience and maximum performance; are simple to install and have intuitive easy-to-use
graphic interfaces. NOVA access panels provide zone selection, broadcast command and alarm control as standard.
The touch screen display layout is fully congurable, with the units software managing up to 256 key and indicator
functions. Connection is via CAT5 cable for data with a shielded twisted pairs for audio. An optional Ethernet modem
available for distances over 90m.
Technical Specications
Audio
Audio Set: Electret or dynamic goose-neck microphone and microphone preamplier
Output: 600 , -9 to +6 dBm
Preamplied Microphone Station
Power supply: 12 Vcc / 24 Vcc
Current Consumption: <100 mA
Frequency resp: 100 15.000 Hz
Controller
Processor: Intel 1600 MHz Min.
GAI -TR O NI CS
A H ub be ll Com pa ny
www.gai-tronics.com
GA I-TR ON I CS
A Hu b be ll Com pa ny
www.gai-tronics.com
Ex Zones PANEL PC
All operating and visualisation components can be congured
according to the requirements of the plant.
Constructed as intrinsically safe panel mounting modules and certied for
Ex Zone 1 / 2 (Gas),
Zone 21 / 22 (Dusts),
The PANEL PC can easily be integrated into enclosures, walls and cabinets.
NOVA Multimedia PC
17" TFT LCD monitor supporting resolutions of up to 1280 x 1024
Keyboard, numeric keypad and touchpad
PS/2 and USB compatible
Background music
A Hu bb e ll Compa ny
www.gai-tronics.com
Ambient level based, real time level adjustment of paging audio to any area or zone
Automatic bypass feature for emergency alarms and/or messages
Automatic Level Control (ALC) is used in the NOVA public address systems to automatically adjust the
volume of paging and other audible media to overcome varying ambient noise levels. Customer
programmable levels vary the paging audio to combat ambient noise by matching amounts.
The ALC Kit includes one Control Module mounted within the NOVA central system, and one Remote
Module which is connected to a dummy speaker or other microphone device for sensing ambient noise.
In a typical system the ALC Control Module is located in-line between the low-level audio path switching
equipment and associated power amplier. The Control Module provides line power to the ALC Remote
Module which is located within the paging zone. The ambient noise sample is transmitted to the Control
Module to be measured and used to modify the level of the audio to the paging amplier.
The centrally mounted device is equipped with control pushbuttons and indicators to facilitate easy set-up
of the paging volume levels, eliminating the need for test meters and screwdriver adjustment.
During an emergency alarm or page the audio path through the module may be bypassed enabling full
volume audio to be broadcast.
Headphones or an external speaker may be connected to the Central Module to monitor audio in the
remote location.
Technical Specications
Control Module
Power Input: 24 V dc +/-20% @ 350 mA maximum
Physical Size: 101 W 355 L 76 D mm
Operating Environment: 0 C to 50 C @ 95% humidity (non-condensing)
Paging Input Impedance: 100 k, or jumper-selected 600 ohms
Paging Audio I/O Range: -40 dBm to 0 dBm RMS
Paging Adjustment Range: -3 dB to -50 dB minimum
Emergency Paging Level: Direct wire connection from input to output, no attenuation
Paging Audio Distortion: Less than 1% THD
Output Impedance: 100 ohms, electronically balanced
Monitor Amp Output: 250 W maximum into a standard 30-ohm headset
Remote Module
Phantom Power Input: (Phantom from master) 20 to 30 V dc @ 35 mA maximum
Physical Size: 101 W 101 L ~50 D mm
Operating Environment: -40 C to 80 C @ 95% humidity (non-condensing)
Remote Input: Dedicated 8-ohm speaker or dynamic mic, Input is transformer-isolated and protected
against directly-applied signals up to 120 V ac
G AI -T RO N ICS
A Hu bbe ll Com pa ny
www.gai-tronics.com
The NOVA Speaker Monitoring Subsystem Modules are either housed in the central cabinet (test tone
generator and speaker master) or in eld locations (speaker remote). A complete system can support up
to 40 speaker remote units per amplier loop.
The Test Tone Generator provides inaudible source signal generation and mixing to speaker lines, providing
power to the speaker remote boards. It is controlled from the NOVA CPU via an RS-485 serial link.
Technical Specications
Power Input: 24 V dc +/-20% @ 150 mA max
Physical Size: 101 W 165 L 32 D mm
Operating Environment: 0 C to 50 C
Inputs: Four (4) channels, low level (0 dBm) balanced line
Input Inpedance: 600 ohms or 100 k
System Connection: RS-485 I/O non-isolated
Outputs: Four channels, low level (0 dBm) balanced audio line
Output Impedance: 100 ohms
Tone Output Level: Variable from +4 dBm to 46 dBm
GAI -TR O NI CS
A H ub be ll Com pa ny
www.gai-tronics.com
Speaker Master
The Speaker Master communicates with the NOVA CPU via an RS-485 connection, and transmits speaker
commands to the remote speaker modules in order to control broadcast volume levels and locations.
It receives acknowledgment messages and speaker integrity messages from the remote modules.
The module has four channels, and transmits and receives communication at 245 kHz. Each channel is
connected to the speaker line output of an associated paging zone power amplier. The module also
controls an associated test tone generator module via a dedicated RS-485 connection.
Technical Specications
Power Input: 24 V dc +/-20% @ 100 mA maximum
Physical Size: 101 W 190 L 32 D mm
Operating Environment: 0 C to 50 C
Speaker Remote
The Speaker Remote module may be installed inside each speaker that
is to be remotely adjusted and monitored. The module receives speaker
commands from the speaker master and is powered by the inaudible
source signal generated by the test tone generator. The unit monitors
the current into the associated loudspeaker to perform a health check
of the speaker coil. The transmission of acknowledgments and data
back to the speaker master module is performed only on command
from the master.
The Speaker Remote provides a selection of three available speaker tap
settings. In the two ranges, the jumper P6 selects between the low and
high output ranges. Two models of Speaker Remotes are available to
allow the NOVA system to accept various loudspeakers. The rmware
also provides the assignment of four page groups out of a possible 255
for systems that utilise subzoning.
Technical Specications
Power Input: 35 Hz tone @ 50 V
Physical Size: 105 W 100 L 65 D mm
Operating Environment: -40 C to 70 C @ 85% humidity (non-condensing)
Model 13317-001: 100V line transformer to 8 ohms @ 25W.
High taps: 25W, 12.5W, 6.25W; Low taps: 6W, 3W, 1.5W
Model 13317-002: 100V line transfomer to 16 ohms @ 30W.
High taps: 30W, 15W, 7.5W; Low taps: 6W, 3W, 1.5W
GA I-TR ON I CS
A Hu b be ll Com pa ny
www.gai-tronics.com
www.gai-tronics.com
GAI-Tronics - USA (Corporate) Toll Free: 1 (800) 492-1212 Tel: (610) 777-1374 Fax: (610) 796-5954 www.gai-tronics.com
GAI-Tronics United Kingdom Tel: +44 (0)1283 500500 Fax: +44 (0)1283 500400 www.gai-tronics.co.uk
GAI-Tronics S.r.l - Italy Tel: +39 02 4588801 Fax: +39 02 93663110 www.gai-tronics.it
GAI-Tronics - Malaysia Tel: +60-3-8945-4035 / 8945-7348 Fax: +60-3-8945-4675 www.gai-tronics.com
GAI-Tronics Austdac - Australia Tel: 011-61-28-851-5000 Fax: 011-61-29-899-2490 www.austdac.com.au
Quality Management System Certified by DNV - ISO 9001:2008