Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

Job No.

PREP'D
CHK'D
APP'D

Doc. No.

Rev.
C
SHEET : 1 OF 4

Date : 10-09-2014
Faisal
Sugeng
Sanur

DATA SHEET
FOR
HSD STORAGE TANK 5000 KL (01-T-002)
FOR DESIGN
CLIENT REVIEW
A: APPROVED
B: APPROVED W/ MINNOR COMMENTS
R: APPROVED W/ COMMENTS
N: NOT ACCEPTABLE

NAME :

DATE :

REV.

DATE

DESCRIPTION

PREP'D

CHECK'D

APP'D

A
B
C

10/9/2014
7/10/2014
20/10/2014

ISSUED FOR REVIEW


ISSUED FOR APPROVAL
ISSUED FOR APPROVAL

Fs
Fs
Fs

Sg
Sg
Sg

Sn
Sn
Sn

ATMOSPHERIC TANK DATA SHEET


Rev.

SHEET : 2 OF 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71

Design Code / Regulation


Specification
Equipment No.
Service Name
Type Of Tank
No. Required

API 650 11th Ed. Addendum

Nominal Capavity
Net Working Capacity (HLL-LLLL)
Inside Diamter
Tank Height
Bottom Slope / Type
Roof Slope / Type

m3
m3
mm
mm

Operating Pressure

Kg/cm2G
Kg/cm2G
Deg C
Deg C
mm
mm

Operating Temp.

Max.
Min.
Max.
Min.

High Liqiud Level


Low Low Liquid Level
Liquid Name
Desig Sp. Gr.
Design Internal Pressure
Design Temperature

Flash Point
Aromatic Content
Max. Pumping Rate

Max.
Min.
Max.
Min.

in
Out

Add. Outbreathing Capacity


Shell Plate
Roof Plate
Top Angle
Roof Structure / Structure shapes
Bottom Plate
Annular Plate (If Required)
Nozzle
Pipe
Plate
Forging Flanges
Gasktes
Bolt & Nut
Nozzles
Structural
Name plate
Name plate Bracket
Reinforcement Pad ( If Required)
Fittings ( If Required )
Earthing Lugs
Internal
External
Internal Surfaces (Painting)
External Surface (Painting)
Insulation
Tank Inside Cleaning Before Box Up
P>W>H>T For Operation Condition
Joint Design
Bottom
Shell
Roof

01-T-002
HSD Storage Tank
Rafter & Columns Supported Cone Roof Tank
1. (One)
DIMENSION
5499
5176
26200
10500
1 : 120 / Cone bottom down to center
1 : 6 (Appendix F)
Atmospheric
38
10050
450
DESIGN INFORMATION
HSD
0.87
Atmospheric

Kg/cm2G
Kg/cm2G
Deg C
50
Deg C
DESIGN INFORMATION FOR VENTING DEVICES
Deg C
%
m3/hr
m3/hr
m3/hr
MATERIAL AND CORROSION ALLOWANCE (CA)
Material : A283 Gr.C
Material : A283 Gr.C
Material : A 36
Material : A 36
Material : A283 Gr.C
Material : A283 Gr.C
Material
Material
Material
Material

:
:
:
:

CA
CA
CA
CA
CA
CA

:
:
:
:
:
:

3
1.5
1
1
3
3

A106 Gr.B
CA :
1.5
A283 Gr.C
CA :
1.5
A105
CA :
1.5
4.5t 316 SS Spiral Wound Non Asbesitos filled w/ 316 inner ring

Material : A193 Gr. B7 / A194 Gr. 2H


Material : A325 (HDG)
Material : 304 SS
Material : A283 Gr. C / A36
Material : A283 Gr.C
Material : A234 Gr. WPB
Material : 304 SS
Material : A283 Gr.C / A106 Gr.B
Material : A283 Gr.C / A36 / A106 Gr.B
PAINTING AND LINING
Yes
No
Material :
Yes
INSULATION
Hot
Cold
P.P
OTHER REQUIRMENTS
Yes
No
Yes
No
Butt
Butt
Butt
NOTES

Lap
Lap
Lap

VTA

1/. (VTA/*) : Vendor to Confirm / Advise


2. Painting of internal surface epoxy internal coating shall be applied up to +_ 1m height from bottom
3. Radiography shall be spot as per API 650

ATMOSPHERIC TANK DATA SHEET


Rev.

SHEET : 3 OF 4
1 Equipment No.
: 01-T-002
2 Service Name
: FUEL OIL STORAGE TANK
3
4
5 No.
Item
Quantity Size
6
7
N2 Suction nozzle
1
10"
8
N3 Air foam Chamber
1
4"
9
N4 Water Draw of
1
4"
10 M1 Shell Manhole
1
24"
11
12
13
14
15
16
17
18
19
20
21 No.
Item
Quantity Size
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68

N1
R1
R2
R3
M2

No.

Filling Nozzle
LEVEL INDICATOR
ROOF VENT NOZZLE
GAUGE HATCH
Roof Manhole

Item

SHELL NOZZLE
Rating
Facing
Intenal Pipe
ANSI 150#
ANSI 150#
ANSI 150#
API 650

WNRF
WNRF
WNRF
SOFF

Remark

W/ David

ROOF NOZZLE
Rating
Facing
Intenal Pipe

1
1
1
1
1

10"
3"
10"
8"
24"

ANSI 150#
ANSI 150#
ANSI 150#
ANSI 150#
API 650

WNRF
WNRF
WNRF
WNRF
SOFF

Quantity

Size

FLOATING ROOF NOZZLE


Rating
Facing
Intenal Pipe

Remark
w/ Inlet Pipe
W/ Elbow & bugs screen
W/ David

Remark

APPURTENANCES
Item
Roof periperal handrail
Earthing lugs
Name Palte
Support Lug for riser pipes
Stair & clips
Gauge Hatch
Breather Valve

Qty/size
1 set
2
1

Remarks
by vendor
by vendor
by vendor

1
1

by vendor
by vendor

Item

Qty/size

General notes for drawing :


1. All dimension are in millimeter unless otherwise specificied
2. All bolts holes shall straddle tank centerline (0,90 axis)
3. Anchor bolts shall straddle tank centerline (),90 axis)
4. The Indicates thickness of shell, roof, bottom plate are the minimum value, vendor has resposibility to check and supply
the material with thickness according to their calculation and requirment of specification & Standard
5. Size and quantity of breather valve and emergency vent shall detemined by vendor

Remarks