Inside
Description ................................................................................................3
Installation ................................................................................................4
Mounting...................................................................................................5
System Assembly......................................................................................7
Field Wiring Connections..........................................................................7
I/O Memory Mapping .............................................................................10
Specifications .........................................................................................11
Hazardous Location Considerations .......................................................13
Environnements dangereux ....................................................................14
Publication 1762-IN011A-EN-P
Pub. No.
1770-4.1
Publication 1762-IN011A-EN-P
Description
9
1a
Item Description
7
1a
1b
bus connector
with male pins
terminal block
pull loop
1b
4
1a
6
2
1b
Publication 1762-IN011A-EN-P
Installation
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use in
clean, dry environments (Pollution degree 2 (1)) and to circuits not exceeding Over
Voltage Category II(2) (IEC 60664-1).(3)
Remove Power
ATTENTION Remove power before removing or installing this module. When
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the products insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Publication 1762-IN011A-EN-P
Mounting
Minimum Spacing
Top
Side
MicroLogix
1200
1762 I/O
1762 I/O
Do not remove protective debris strip until after the module and
all other equipment near the module is mounted and wiring is
complete. Once wiring is complete and the module is free of
debris, carefully remove protective debris strip. Failure to remove
strip before operating can cause overheating.
1762 I/O
ATTENTION
Side
Bottom
NOTE
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into
the module. Debris that falls into the module could cause
damage when power is applied to the module.
Publication 1762-IN011A-EN-P
End Anchor
NOTE
Panel Mounting
Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6
panhead screws may also be used, but a washer may be needed to ensure a good
mechanical contact. Mounting screws are required on every module.
For more than 2 modules: (number of modules - 1) x 40 mm (1.58 in.)
14.5
(0.57)
40.4
(1.59)
NOTE: All
dimensions are in
mm (inches). Hole
spacing tolerance:
0.4 mm
(0.016 in.).
100 90
(3.94) (3.54)
40.4
(1.59)
Publication 1762-IN011A-EN-P
System Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a flat ribbon cable after mounting as shown below.
NOTE
ATTENTION
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
Page 6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
Publication 1762-IN011A-EN-P
Output Wiring
Basic wiring(1) of the 1762-OB16 is shown below.
+DC
VDC+
CR
CR
OUT 0
OUT 1
CR
OUT 3
CR
OUT 2
OUT 4
OUT 5
CR
OUT 6
CR
OUT 7
CR
OUT 8
CR
OUT 9
CR
OUT 11
24V dc (source)
OUT 10
OUT 12
CR
OUT 13
OUT 14
OUT 15
DC COM
-DC
A write-on label is provided with the module. Mark the identification of each
terminal with permanent ink, and slide the label back into the door.
ATTENTION
ATTENTION
(1) Surge Suppression Connecting surge suppressors across your external inductive load will extend the
life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-4.1.
Publication 1762-IN011A-EN-P
NOTE
Wire Size
Solid
Cu-90C (194F)
0.90 Nm (8 in-lbs)
Stranded
Cu-90C (194F)
0.90 Nm (8 in-lbs)
Publication 1762-IN011A-EN-P
10
Word
For each output module, the output data file contains the controller-directed state of
the discrete output points. Bit positions 0 through 15 correspond to output
terminals 0 through 15.
Bit Position
15
14
13
12
11
10
w = write only
Addressing
The addressing scheme for 1762 Expansion I/O is shown below.
Slot Number(1)
Data File
Output
O0:x.0/0
Slot Delimiter
Bit (0 to 15)
Bit Delimiter
Word Delimiter
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with
slot 1.
Publication 1762-IN011A-EN-P
11
Specifications
General Specifications
Specification
Value
Dimensions
Storage Temperature
Operating Temperature
Operating Humidity
5% to 95% non-condensing
Operating Altitude
Vibration
Shock
Agency Certification
EN50081-2 Class A
Electrical /EMC:
ESD Immunity (IEC1000-4-2)
2 kV, 5 kHz
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.
Publication 1762-IN011A-EN-P
12
Output Specifications
Specification
1762-OB16
Voltage Category
24V dc
20.4V dc to 26.4V dc
Number of Outputs
16
175 mA at 5V dc (0.88W)
turn-on = 0.1 ms
1.0 mA
turn-off = 1.0 ms
1.0 mA
1.0V dc
6 (The module may not be more than 6 modules away from the
power supply.)
Isolated Groups
Group 1: Outputs 0 to 15
Product Code
103
Publication 1762-IN011A-EN-P
13
Sourcing Output - Source describes the current flow between the I/O module and
the field device. Sourcing output circuits supply (source) current to sinking field
devices. Field devices connected to the negative side (DC Common) of the field
power supply are sinking field devices. Field devices connected to the positive side
(+V) of the field supply are sourcing field devices.
Typical Loading Resistor - To limit the effects of leakage current through
solid-state outputs, a loading resistor can be connected in parallel with your load.
Use a 5.6k ohm, 1/4W resistor for transistor outputs, 24V dc operation.
Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the
load for transistor outputs switching 24V dc inductive loads. For additional
information, refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1.
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
Page 6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
Publication 1762-IN011A-EN-P
14
Environnements dangereux
Cet quipement est conu pour tre utilis dans des environnements de Classe I,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
sapplique une utilisation dans des environnements dangereux.
MIS EN GARDE
DANGER DEXPLOSION
La substitution de composants peut rendre cet quipement
impropre une utilisation en environnement de Classe I,
Division 2.
Ne pas remplacer de composants ou dconnecter
l'quipement sans s'tre assur que l'alimentation est coupe.
Ne pas connecter ou dconnecter des composants sans s'tre
assur que l'alimentation est coupe.
Ce produit doit tre install dans une armoire.
Pour les applications de Classe I, Division 2, le connecteur de
bus doit tre correctement install et son couvercle enclench.
Pour les applications de Classe I, Division 2, tous les modules
doivent tre installs en contact direct les uns avec les autres,
comme indiqu Page 6. Si on utilise le montage sur rail DIN,
une bute doit tre place l'avant de l'automate et aprs la
dernire unit d'E/S 1762.
Publication 1762-IN011A-EN-P
15
Publication 1762-IN011A-EN-P
PN 40071-115-01(A)
2000 Rockwell International Corporation. Printed in MALAYSIA.