Conduit Fill Calculation PDF
Conduit Fill Calculation PDF
Conduit Fill Calculation PDF
Home
ElectricalEngineering
CoursesList
PDFCourses
DownloadLibrary
Instruments
InspectionPhotos
ContactUs
Aboutme
ConduitFillCalculations
ElectricalGround
Wire
ChinaProfessional
ManufacturerOfElectrical
GroundWire,Order
Electrical-Knowhow
RECENTARTICLES
In Article " Electrical Boxes Volume and Fill Calculations ", I explained the following items:
NEC 314.16 Part (A): Box Volume Calculations,
NEC 314.16 Part (B): Box Fill Calculations,
NEC 314.16 Part (C): Conduit Bodies.
You can review the following articles in the same course for more information:
POPULARARTICLES
1. Metric designator,
2. Trade size.
Table 300.1(C) identifies a distinct metric designator for each circular raceway trade size.
http://electricalinspector.blogspot.com/2013/06/conduitfillcalculations.html
1/6
1/7/2015
ElectricalEngineering
You can download a PDF copy of Chapter 9 Tables by click on the link.
You can download a PDF copy of Annex C Tables by click on the link.
Chapter 9 Table 1
Table 1 establishes the maximum fill permitted for the circular conduit and tubing types. It is the
basis for Table 4 and for the information on conduit and tubing fill provided in the Informative Annex
C tables.
http://electricalinspector.blogspot.com/2013/06/conduitfillcalculations.html
2/6
1/7/2015
ElectricalEngineering
So, it is recommended that where a difficult installation is anticipated due to above reasons, the
available solutions will be as follows:
As an example:
Table C.1 in Informative Annex C permits three 8 AWG conductors in trade size 12 electrical
metallic tubing (EMT). An 8 AWG conductor has an outside diameter (OD) of 0.216 in. (from Table 5),
and a 12 in. EMT has an internal diameter (ID) of 0.622 in. (from Table 4).
The jam ratio is calculated as follows:
Jam ratio = ID of raceway / OD of conductor = 0.622 / 0.216 = 2.88
So, Jamming of conductors will occur, use the next larger trade size conduit.
A 34 in. EMT has an internal diameter (ID) of 0.824 in. (from Table 4).
So, Jam ratio = ID of raceway / OD of conductor = 0.824 / 0.216 = 3.815
Chapter 9 Table 4
Because conduits and tubing from different manufacturers have different
internal diameters for the same trade size, Table 4 provides the diameter
and the actual area of different conduit and tubing types at fill
percentages of 100, 60, 53 (one wire), 31 (two wires), and 40 (more than
two wires).
The 60 percent fill is provided in Table 4 to correlate with Note 4 (found in
the Notes to Tables section of this chapter) to the conduit and tubing fill
tables, which permits conduit or tubing nipples 24 in. or less in length to
have a conductor fill of up to 60 percent.
Separate sections in Table 4 cover metal, nonmetallic, rigid, and flexible
conduit and tubing types.
3/6
1/7/2015
ElectricalEngineering
Example#1:
Three 15kV single conductors are to be installed in rigid metal conduit (RMC). The outside diameter of each conductor
measures 158 in., or 1.625 in. What size RMC will accommodate the three conductors?
Solution:
Step 1: Find the crosssectional area within the conduit to be displaced by the three conductors:
1.625 in. x 1.625 in. x 0.7854 x 3 = 6.2218 in.2 or 6.222 in.2
Step 2: Determine the correct conduit size to accommodate the three conductors. Table 1 allows 40 percent conduit fill for
three or more conductors, and Table 4 indicates that 40 percent of trade size 5 RMC is 8.085 in.2.
Thus, trade size 5 RMC will accommodate three 15kV single conductors.
Example#2:
What traditional wire size does the size 125 mm2 represent (approximately)?
Solution:
Circular mil area = wire size (mm2) x conversion factor = 125 mm2 x 1973.53 circular mils / mm2 = 246,691 circular mils or
246.691 kcmil
Therefore, the 125 mm2 wire is larger than 4/0 AWG (211.6 kcmil) but smaller than a 250kcmil conductor.
Notes to example#2:
If a 125 mm2 wire is determined to be the minimum or recommended size conductor, it is important to
understand that size 250 kcmil would be the only Table 8 conductor with equivalent crosssectional area because
4/0 AWG is simply not enough metal.
It is important, however, to note that the 250kcmil conductor ampacity could not be used for a 125 mm2
conductor, because the metric conductor size is smaller. The 4/0 AWG ampacity can be used, or the ampacity
can be calculated under engineering supervision.
http://electricalinspector.blogspot.com/2013/06/conduitfillcalculations.html
4/6
1/7/2015
ElectricalEngineering
Example#3:
A 200ampere feeder is routed in various wiring methods [electrical metallic tubing (EMT); rigid polyvinyl chloride conduit
(PVC), Schedule 40; and rigid metal conduit (RMC)] from the main switchboard in one building to a distribution panelboard in
another building. The circuit consists of four 4/0 AWG XHHW copper conductors and one 6 AWG XHHW copper conductor.
Select the proper trade size for the various types of conduit and tubing to be used for the feeder.
Solution:
Step 2: Calculate the total area occupied by the conductors, using the approximate areas listed in Table 5:
Four 4/0 AWG XHHW: 4 x 0.3197 in.2 = 1.2788 in.2
One 6 AWG XHHW: 1 x 0.0590 in.2 = 0.0590 in.2
Total area = 1.3378 in.2 or 1.338 in.2
Step 3: Determine the proper trade size EMT, RMC, and PVC (Schedule 40) from Table 4.
The portion of this feeder installed in EMT requires a minimum trade size 2, which has 1.342 in.2 of available space for over
two conductors. The minimum required space is 1.338 in.2, which is less than the trade size 2 EMT 40 percent fill.
RMC also requires a minimum trade size 2, because trade size 2 RMC has 1.363 in.2 of available space for over two
conductors. PVC (Schedule 40), however, requires a minimum trade size 2 12.
Trade size 2 PVC has 1.316 in.2 allowable space for over two conductors and is less than the 1.338 in.2 required for this
combination of conductors. Therefore, it is necessary to increase the PVC size to 2 12 trade size, the next standard size
increment.
Example#4:
Determine how many 10 AWG THHN conductors are permitted in a trade size 1 14 rigid metal conduit (RMC).
Solution:
Note to example#4:
Although increasing the total to 29 conductors results in the raceway fill exceeding 40 percent, the amount by which it is
exceeded is a fraction of 1 percent and will not adversely affect the installation of the conductors.
In the next Article, I will explain how to verify Area Classification and Service Requirements of Conduit, Junction Boxes
and Pull Boxes. Please, keep following.
Back to Course WR2: Inspect conduits, junction boxes, and pull boxes
http://electricalinspector.blogspot.com/2013/06/conduitfillcalculations.html
5/6
1/7/2015
ElectricalEngineering
ElectricalBoxes
VolumeandFill
Calculations
HowToInspect
ElectricalConduits
andBoxes
GroundResistance
Calculations
ConduitFittings
andSupports
ReviewforCourse
WR2:Inspect
Conduits,Junction
andPull...
Linkwithin
Nocomments:
PostaComment
Enteryourcomment...
Commentas:
GoogleAccount
Publish
Preview
Home
FOLLOWERS
Jointhissite
withGoogleFriendConnect
Members(51) More
NEWARTICLES
POPULARARTICLES
Properties of Conductors
Electrical Boxes
Types of Electrical Conduits
Electrical Boxes
SUBSCRIBEVIAEMAIL
SubscribeforNewArticles
CopyRight@2013ElectricalInspectorPrivacy
Policy
Powered by Blogger.
http://electricalinspector.blogspot.com/2013/06/conduitfillcalculations.html
6/6