Eaton 93E-15-80 KVA Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 108

Eaton 93E UPS

1580 kVA (380/400/415V)


Installation and Operation Manual

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS


This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment
and save this manual for future reference.

CONSIGNES DE SCURIT IMPORTANTES CONSERVER CES INSTRUCTIONS


Ce manuel comporte des instructions importantes que vous tes invit suivre lors de toute
procdure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter
entirement ces instructions avant de faire fonctionner l'quipement et conserver ce manuel afin
de pouvoir vous y reporter ultrieurement

2014 Eaton Corporation


All Rights Reserved
The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts)
unless permission granted. Every care has been taken to ensure the accuracy of the information
contained in this manual, but no liability can be accepted for any errors or omission. The right to make
design modifications is reserved.

Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1

1.2

1.3
1.4
1.5
1.6
1.7
1.8
1.9

UPS Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2


1.1.1 Installation Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.1.2 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.1.3 Customer Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.1.4 High-Efficiency Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.1.5 Advanced Battery Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.1.6 Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Options and Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.1 External Battery Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.2 Parallel System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.3 Monitoring and Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.4 Dual Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Battery System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Basic System Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Conventions Used in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Symbols, Controls, and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
For More Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Getting Help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

Safety Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1

SECTION 1Installation
3 UPS Installation Plan and Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1
3.2

Creating an Installation Plan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1


Preparing the Site. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.1 Environmental and Installation Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.2 UPS System Power Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
3.2.3 UPS System Interface Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.3 Inspecting and Unpacking the UPS Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22

4 UPS System Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1


4.1
4.2
4.3
4.4
4.5

Preliminary Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1


Unloading the UPS Cabinetfrom the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
External Battery Cabinet Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
External Power Wiring Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Installing Interface Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4.5.1 Installing Building Alarm Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4.5.2 Installing Parallel Pull Chain and CAN Control Wiring and Connections. . . . . . . . . . . . . . . . . . . . . . . . . 4-11
4.5.3 Installing Mini-Slot Interface Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
4.6 Installing a REPO Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
4.7 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4.8 Completing the Installation Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Table of Contents

SECTION 2Operation
5 Understanding UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1
5.2

UPS System Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1


Single UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2.1 Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2.2 Standard Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2.3 High-Efficiency Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.2.4 Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.2.5 Battery Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.3 Single UPS Unit System Oneline Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6

6 UPS Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


6.1

UPS Controls and Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


6.1.1 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Using the Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.1 Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.2 System Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.2.3 Using the LCD and Pushbuttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
6.2.4 Using the Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.5 Mimic Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.2.6 Display Menu Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.2.7 System Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.3 Single UPS Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.3.1 Starting the UPS in Standard Normal Mode (Default Mode). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.3.2 Starting the UPS in Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
6.3.3 Transfer from Normal to Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
6.3.4 Transfer from Bypass to Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
6.3.5 Transfer from Standard Normal Mode to HE mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
6.3.6 Transfer from HE Mode to Standard Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
6.3.7 Transfer from Normal Mode to Internal Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
6.3.8 Transfer from Internal Maintenance Bypass to Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
6.3.9 UPS and Critical Load Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
6.3.10 Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
6.3.11 Battery Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
6.3.12 Using the UPS LOAD OFF Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
6.3.13 Using the Remote Emergency Power-off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
6.4 Multiple UPS Parallel Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
6.4.1 Starting the Parallel UPS in Standard Normal Mode (Default Mode). . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
6.4.2 Starting the Parallel UPS in Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
6.4.3 Transfer from Normal to Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
6.4.4 Transfer from Bypass to Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-19
6.4.5 Single UPS Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-19
6.4.6 Single UPS Restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
6.4.7 UPS and Critical Load Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
6.4.8 Charger Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
6.4.9 Battery Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
6.4.10 Using the UPS LOAD OFF Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-22
6.4.11 Using the Remote Emergency Power-off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-23

ii

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Table of Contents

7 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1
7.2

Mini-Slot Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1


Building Alarm Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1

8 UPS Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1


8.1
8.2

Important Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1


Performing Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2.1 DAILY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2.2 MONTHLY Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2.3 PERIODIC Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.2.4 ANNUAL Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.2.5 BATTERY Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.3 Installing Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
8.4 Recycling the Used Battery or UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
8.5 Maintenance Training. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4

Product Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1


9.1 Model Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2.1 UPS Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.2.2 UPS Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.2.3 UPS Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

iii

Table of Contents

This page intentionally left blank.

iv

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

List of Figures
Figure 1-1.
Figure 3-1.
Figure 3-2.
Figure 3-3.
Figure 3-4.
Figure 3-5.
Figure 3-6.
Figure 3-7.
Figure 3-8.
Figure 3-9.
Figure 3-10.
Figure 3-11.
Figure 4-1.
Figure 4-2.
Figure 4-3.
Figure 4-4.
Figure 4-5.
Figure 4-6.
Figure 4-7.
Figure 4-8.
Figure 4-9.
Figure 4-10.
Figure 4-11.
Figure 4-12.
Figure 4-13.
Figure 4-14.
Figure 4-15.
Figure 5-1.
Figure 5-2.
Figure 5-3.
Figure 5-4.
Figure 5-5.
Figure 5-6.
Figure 6-1.
Figure 6-2.
Figure 6-3.
Figure 6-4.
Figure 6-5.
Figure 6-6.
Figure 6-7.
Figure 7-1.
Figure 8-1.

Eaton 93E UPS (1580 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1


UPS Cabinet Dimensions (93E 15-20 kVA Front and Right Side Views). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
UPS Cabinet Dimensions (93E 30 kVA Front and Right Side Views). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
UPS Cabinet Dimensions (93E 40 kVA Front and Right Side Views). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
UPS Cabinet Dimensions (93E 60-80 kVA Front and Right Side Views). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
UPS Cabinet Dimensions (Top and Bottom Views). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
UPS Cabinet Centre of Gravity (93E 15-20 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
UPS Cabinet Centre of Gravity (93E 30 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
UPS Cabinet Centre of Gravity (93E 40 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
UPS Cabinet Centre of Gravity (93E 60 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
UPS Cabinet Centre of Gravity (93E 80 kVA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
UPS Cabinet as Shipped on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Removing the Shipping Bracket. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Attaching the Ramp to the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Rolling the Cabinet Down the Ramp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Power Terminal Locations 20-40 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Power Terminal Locations 60-80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Interface Terminal Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Interface Terminal Detail (Terminal Cover Removed). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Building Alarm Terminal Block Connector Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Interface Wiring Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Pull Chain Terminal Block Connector Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Parallel UPS Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Parallel UPS system connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
REPO Terminal Block Connector Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Normally-Open REPO Switch Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Normally-Closed REPO Switch Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Main Elements of the UPS System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Path of Current Through the UPS in standard Normal Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Path of Current Through the UPS in Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Path of Current Through the UPS in Battery Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
UPS System Oneline (Dual Input). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
UPS System Oneline (Single Input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
UPS Controls and Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
UPS Switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
UPS Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Parts of the LCD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Main Menu and Mimic Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Typical Initial Setup Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Typical System Control Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Optional Mini-Slot Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Air Filter Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

List of Figures

This page intentionally left blank.

vi

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

List of Tables
Table 3-1.
Table 3-2.
Table 3-3.
Table 3-4.
Table 3-5.
Table 3-6.
Table 3-7.
Table 3-8.
Table 3-9.
Table 4-1.
Table 4-2.
Table 4-3.
Table 4-4.
Table 4-5.
Table 6-1.
Table 6-2.
Table 6-3.
Table 6-4.
Table 6-5.

UPS Cabinet Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


UPS Cabinet Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93E Required Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Conditioning or Ventilation Requirements During Full Load Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input /Output Ratings and External Wiring Requirements for the Eaton 93E 15-80 kVA. . . . . . . . . . . . . . . . .
UPS External Power Cable Terminations for the Eaton 93E 15-80 kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended Input Circuit Breaker Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended Bypass and Output Circuit Breaker Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Recommended DC input circuit breaker rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Building Alarm Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pull Chain Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REPO Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normally-Open REPO Wire Terminations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normally-Closed REPO Wire Terminations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Function Menu Map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Menu Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Command Menu Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical System Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-2
3-3
3-3
3-4
3-17
3-18
3-19
3-19
3-20
4-9
4-11
4-14
4-15
4-16
6-3
6-6
6-7
6-10
6-10

vii

List of Tables

This page intentionally left blank.

viii

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 1

Introduction
The Eaton93E 15-80 kVA uninterruptible power supply (UPS) is a true online, continuous-duty, transformerfree, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible AC power
to protect the customer's load from power failures.
The Eaton 93E 15-80 kVA online power protection system is used to prevent loss of valuable electronic
information, minimise equipment downtime, and minimise the adverse effect on production equipment due to
unexpected power problems.
The Eaton 93E 15-80 kVA UPS continually monitors incoming electrical power and removes the surges, spikes,
sags, and other irregularities that are inherent in commercial utility power. Working with a building's electrical
system, the UPS system supplies clean, consistent power that sensitive electronic equipment requires for
reliable operation. During brownouts, blackouts, and other power interruptions, batteries provide emergency
power to safeguard operation.
The UPS is housed in a single free-standing cabinet, with safety shields behind the door for hazardous voltage
protection.
This manual is for 93E series UPS, refer to Table 9-1 for product models.
Figure1-1 shows the Eaton 93E 15-80 kVA UPS.
NOTE 1

Startup may be performed by the customers qualified electrical contractor for single (not
parallel) UPS installations without any accessory cabinets.

NOTE 2

Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Eaton Customer Service Engineer, or the
warranty terms may become void. This service is offered as part of the sales contract for
the UPS. Contact an Eaton service representative in advance (usually a two-week notice
is required) to reserve a preferred startup date.

Figure 1-1. Eaton 93E UPS (15-80 kVA)

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

1-1

Introduction

1.1

UPS Standard Features


The UPS has many standard features that provide cost-effective and consistently reliable power protection.
The descriptions in this section provide a brief overview of the UPS standard features.

1.1.1 Installation Features


Power wiring can be routed to the bottom or rear of the cabinet with connections made to easily accessible
terminals. Some models (93E-15UI / 93E-20I / 93E-30I / 93E-40I) provide rear-only cable access. Details in 4.4 section
of user manual.

1.1.2 Control Panel


The control panel, located on the front of the UPS, contains a liquid crystal display (LCD) and pushbutton
switches to control the operation of the UPS and to display the status of the UPS system. See Chapter6,
UPS Operating Instructions, for additional information.

1.1.3 Customer Interface


Building Alarm Monitoring Up to three inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See Chapter 7,
Communication, for additional information.

Mini-Slot Communication Bays Two communication bays are standard equipment. One to two optional
Mini-Slot connectivity cards can be installed in the UPS module at any time. Mini-Slot cards are quickly
installed at the front (behind door) of the UPS and are hot-pluggable. See Chapter 7, Communication, for
additional information.

1.1.4 High-Efficiency Mode


The 93E Series UPS offers a High-Efficiency (HE) normal mode with double-conversion on demand that allows
the UPS to operate in standby bypass mode. This mode allows the 93E UPS to achieve 98% efficiency while
still protecting the load. See Chapter6, UPS Operating Instructions, for additional information. On setting the
UPS to work in High Efficiency mode.

1.1.5 Advanced Battery Management


A three-stage charging system increases battery service life by optimising recharge time, and protects
batteries from damage due to high current charging and inverter ripple currents. Charging at high currents can
overheat and damage batteries.

1.1.6 Maintenance Bypass


The internal Maintenance Bypass for 15-80 kVA models consists of input, output , neutral and bypass input
(Dual feeds) switches used to control the AC input to the UPS the inverter output, and a Maintenance Bypass
switch used to partially isolate the UPS so that a limited number of components can be serviced without
interrupting power to critical systems.

1-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Introduction

1.2

Options and Accessories


Contact an Eaton sales representative for information about the following options.

1.2.1 External Battery Cabinet


Battery backup protection is provide by equipping the UPS system with up to four External Battery Cabinets
(EBCs) containing sealed lead-acid, maintenance-free batteries. The EBCs are housed in single, free-standing
cabinets designed for line-up-and-match installation, but may be installed separate from the UPS cabinet.

1.2.2 Parallel System


A parallel UPS system with up to four UPSs can be installed to provide a parallel capacity and/or redundant
system. This load sharing system provides more capacity than a single UPS, and can provide backup,
depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or
is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A
Controller Area Network (CAN) Bridge provides connectivity for system metering and operational mode
control.

1.2.3 Monitoring and Communication


Mini-Slot Cards Optional Mini-Slot cards support several protocols, such as WEB/SNMP, RELAY / RS232 and
Modbus. See Chapter7, Communication, for additional information on monitoring and communication
features.

1.2.4 Dual Input


Dual feed models are available for 93E 15-80 kVAUPS. To update a single feed UPS to dual feed, field update
kits for dual feed can be purchased from Eaton. Connectors on dual feed models provide a separated bypass
input to UPS.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

1-3

Introduction

1.3

Battery System
Dependant on UPS model, the battery system may be internal or external. The battery system provides
emergency short-term backup power to safeguard operation during brownouts, blackouts, and other power
interruptions. The battery system is equipped with lead-acid batteries.

1.4

Basic System Configurations


The following basic UPS system configurations are possible (model dependant):

Single UPS (internal battery).

Single UPS with external battery.

Single UPS with external batteries and accessory cabinets

The UPS system configuration can be enhanced by adding optional accessories such as a
Remote Emergency Power-off (REPO) control or Mini-Slot communication cards.

1.5

Using This Manual


This manual describes how to install and operate the Eaton 93E 15-80 kVA. Read and understand the
procedures described in this manual to ensure trouble-free installation and operation. In particular, be
thoroughly familiar with the REPO procedure (see paragraph6.3.13).
The information in this manual is divided into sections and chapters. Thesystem, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters1 through4
andChapter6 should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to
the UPS system being installed or operated.

1.6

Conventions Used in This Manual


This manual uses these type conventions:

Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.

Italic type highlights notes and new terms where they are defined.

Screen type represents information that appears on the screen or LCD.


Icon

Description

Note

Information notes call attention to important features or instructions.

[Keys]

Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].

In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system
refers to the entire power protection systemthe UPS cabinet, an external battery system, and options or
accessories installed.

1-4

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Introduction

1.7

Symbols, Controls, and Indicators


The following are examples of symbols used on the UPS or accessories to alert you to important information:

RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in
the trash. This product contains sealed, lead-acid batteries and must be disposed of
properly. For more information, contact your local recycling/reuse or hazardous waste
centre.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse
or hazardous waste centre.

1.8

For More Information


Refer to the External Battery Cabinet Installation Manual for the following additional information:
Installation instructions, including site preparation, planning for installation, wiring and safety information,
and detailed illustrations of cabinets with dimensional and connection point drawings
Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to
obtain copies of these manuals.

1.9

Getting Help
If help is needed with any of the following:
Scheduling initial startup
Regional locations and telephone numbers
A question about any of the information in this manual
A question this manual does not answer
Please call your local service representative.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

1-5

Introduction

This page intentionally left blank.

1-6

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 2

Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries. Read all instructions before operating the equipment and
save this manual for future reference.
The UPS is designed for industrial or computer room applications, and contains safety shields
behind the door and front panels. However, the UPS is a sophisticated power system and should be
handled with appropriate care.

DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORISED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the
UPS.

WARNING
The UPS is suitable for mounting on concrete or other non-combustible surfaces only.
The UPS is powered by its own energy source (batteries). The output terminals may carry live
voltage even when the UPS is disconnected from an AC source.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40C (104F). Do not operate near water or excessive humidity (95% maximum). The
system is not intended for outdoor use.
As a result of the connected loads high leakage current is possible. Connection to earth ground is
required for safety and proper product operation. Do not check UPS operation by any action that
includes removal of the earth (ground) connection with loads attached.
Ensure all power is disconnected before performing installation or service.
Batteries can present a risk of electrical shock or burn from high short-circuits current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects;
2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Wear
rubber gloves and boots.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors.
Attempting to alter wiring can cause injury.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.

CAUTION
Installation or servicing should be performed by qualified service personnel knowledgeable of
UPS and battery systems, and required precautions. Keep unauthorised personnel away from
equipment. Consider all warnings, cautions, and notes before installing or servicing equipment.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

2-1

Safety Warnings

See installation instructions before connecting to the supply.


Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according
to the instructions.
Replace batteries with the same number and type of batteries as originally installed with the
UPS.
Disconnect the charging source prior to connecting or disconnecting terminals.
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock. An electric shock is
less likely if you disconnect the grounding connection before you work on the batteries.
Proper disposal of batteries is required. Refer to local codes for disposal requirements.
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to
protect personnel from dangerous voltages inside the unit.
Do not install or operate the UPS system close to gas or electric heat sources.
The operating environment should be maintained within the parameters stated in this manual.
Keep surroundings uncluttered, clean, and free from excess moisture.
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the
equipment.

AVERTISSEMENT!
Les batteries peuvent prsenter un risque de dcharge lectrique ou de brlure par des courts
circuits de haute intensit. Prendre les prcautions ncessaires.
Pour le replacement, utiliser le mme nombre et modle des batteries.

ATTENTION!
Une mise au rebut rglementaire des batteries est obligatoire. Consulter les rglements en
vigueur dans votre localit.
Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser.

CE marking
The product has the CE marking in compliance with the following European directives:
LVD Directive (Safety)

2006/95/EEC

EMC Directive

2004/108/EEC

CAUTION
This product is designed for commercial and industrial applications. In a residential environment, the
product may cause radio interference, in which the user may be required to take additional measures.

2-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Section 1
Installation

Chapter 3

UPS Installation Plan and Unpacking


Use the following basic sequence of steps to install the UPS:
1. Create an installation plan for the UPS system (Chapter3).
2. Prepare your site for the UPS system (Chapter3).
3. Inspect and unpack the UPS cabinet (Chapter3).
4. Unload and install the UPS cabinet, and wire the system (Chapter4).
5. Install features, accessories, or options, as applicable (Chapter4).
6. Complete the Installation Checklist (Chapter4).
7. Have authorised service personnel perform preliminary operational checks and start up the system.
NOTE

Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Eaton Customer Service Engineer, or the
warranty terms may become void. This service is offered as part of the sales contract for
the UPS. Contact an Eaton service representative in advance (usually a two-week notice
is required) to reserve a preferred startup date.

CAUTION
It must be ensured that no line input source can accidentally be connected to the UPS during installation.

WARNING

3.1

Installation may only be carried out by qualified technicians and in conformity with the applicable
safety standards.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.

Creating an Installation Plan


Before installing the UPS system, read and understand how this manual applies to the system being installed.
Use the procedures and illustrations in paragraph3.2 and Chapter4 to create a logical plan for installing the
system.

3.2

Preparing the Site


For the UPS system to operate at peak efficiency, the installation site should meet the environmental
parameters outlined in this manual. If the UPS is to be operated at an altitude higher than 1000m (3300ft),
contact an Eaton service representative for important information about high altitude operation. The operating
environment must meet the weight, clearance, and environmental requirements specified.

3.2.1 Environmental and Installation Considerations


The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment.
Suitable for mounting on concrete or other non-combustible surfaces only.
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-1

UPS Installation Plan and Unpacking

Failure to follow guidelines may void your warranty.


The UPS equipment operating environment must meet the weight requirements shown in Table3-1 and the
size requirements shown in Figure3-1 through Figure3-5. Dimensions are in millimetres (inches).
Table 3-1. UPS Cabinet Weights
Model

Shipping

Installed

kg (lb.)
Point Loading

93E-15UI-N-649Ah-MBS

272 (599)

285 (627)

46 (100)/wheel (total 6 wheels)

93E-15UI-N-0-MBS

102 (225)

120 (264)

17 (38)/wheel (total 6 wheels)

93E-15U-N-MBS

72 (159)

85 (187)

17 (40)/wheel (total 4 wheels)

93E-15UT-N-MBS

220 (484)

233 (513)

37 (81)/wheel (total 6 wheels)

93E-20I-N-649Ah-MBS

272 (599)

285 (627)

46 (100)/wheel (total 6 wheels)

93E-20I-N-0-MBS

102 (225)

120 (264)

17 (38)/wheel (total 6 wheels)

93E-20-N-MBS

72 (159)

85 (187)

17 (40)/wheel (total 4 wheels)

93E-20T-N-MBS

220 (484)

233 (513)

37 (81)/wheel (total 6 wheels)

93E-30I-N-969Ah-MBS

376 (828)

391 (861)

63 (138)/wheel (total 6 wheels)

93E-30I-N-0-MBS

128 (283)

147 (325)

21 (47)/wheel (total 6 wheels)

93E-30-N-MBS

88 (194)

105 (231)

23 (50)/wheel (total 4 wheels)

93E-30T-N-MBS

245 (539)

279 (614)

41 (90)/wheel (total 6 wheels)

490 (1078)

507 (1116)

82 (180)/wheel (total 6 wheels)

93E-40I-N-0-MBS

165 (364)

187 (413)

28 (61)/wheel (total 6 wheels)

93E-40-N-MBS

120 (264)

137 (302)

30 (66)/wheel (total 4 wheels)

93E-40T-N-MBS

328 (722)

345 (759)

55 (121)/wheel (total 6 wheels)

93E-60-N-MBS

202 (445)

241 (531)

25 (56)/wheel (total 8 wheels)

93E-60T-N-MBS

532 (1171)

571 (1257)

67 (147)/wheel (total 8 wheels)

93E-80-N-MBS

245 (539)

285 (614)

31 (68)/wheel (total 8 wheels)

93E-80T-N-MBS

575 (1265)

615 (1353)

72 (159)/wheel (total 8 wheels)

93E-40I-N-1289Ah-MBS

3-2

Weight

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet

300mm (12") working space

From Front of Cabinet

900 mm (36") working space

From Back of Cabinet

See Table No: 3-3

From Right Side of Cabinet

See Table No: 3-3

From Left Side of Cabinet

See Table No: 3-3

The basic environmental requirements for operation of the UPS are:


Ambient Temperature Range: 040C (32104F)
Recommended Operating Range: 2025C (6877F)
Maximum Relative Humidity: 95%, noncondensing
Table 3-3. 93E Required Clearance
93E Required Clearance for paralleled adjacent UPS or UPS and adjacent PDU
ambient
25 C
30 oC
35 oC
40 oC
o

15kVA/20kVA/30kVA/40kVA
L1(mm)

L2(mm)

120

60kVA/80kVA
L1(mm)
150

50
150

L2(mm)

50
200

Notes:
L1- clearance to the rear wall.
L2- clearance between the adjacent paralleled UPS or UPS and adjacent PDU. Parallel UPS should be as
close as possible.
Some models that feature rear connections also require additional rear clearance to enable installation and
connection.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-3

UPS Installation Plan and Unpacking

CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table3-4.
Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation

3-4

Model

Model

Input / Output Voltage

Heat Rejection
BTU/hr x1000 (kg-cal/hr)

93E-15UI-N-649Ah-MBS

15 kVA

380/380 400/400 415/415

862

93E-15UI-N-0-MBS

15 kVA

380/380 400/400 415/415

862

93E-15U-N-MBS

15 kVA

380/380 400/400 415/415

862

93E-15UT-N-MBS

15 kVA

380/380 400/400 415/415

1306

93E-20I-N-649Ah-MBS

20 kVA

380/380 400/400 415/415

1149

93E-20I-N-0-MBS

20 kVA

380/380 400/400 415/415

1149

93E-20-N-MBS

20 kVA

380/380 400/400 415/415

1149

93E-20T-N-MBS

20 kVA

380/380 400/400 415/415

1743

93E-30I-N-969Ah-MBS

30 kVA

380/380 400/400 415/415

1723

93E-30I-N-0-MBS

30 kVA

380/380 400/400 415/415

1723

93E-30-N-MBS

30 kVA

380/380 400/400 415/415

1723

93E-30T-N-MBS

30 kVA

380/380 400/400 415/415

2612

93E-40I-N-1289Ah-MBS

40 kVA

380/380 400/400 415/415

2298

93E-40I-N-0-MBS

40 kVA

380/380 400/400 415/415

2298

93E-40-N-MBS

40 kVA

380/380 400/400 415/415

2298

93E-40T-N-MBS

40 kVA

380/380 400/400 415/415

3482

93E-60-N-MBS

60 kVA

380/380 400/400 415/415

3447

93E-60T-N-MBS

60 kVA

380/380 400/400 415/415

5224

93E-80-N-MBS

80 kVA

380/380 400/400 415/415

4596

93E-80T-N-MBS

80 kVA

380/380 400/400 415/415

6965

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

960 (37.8)

UPS Installation Plan and Unpacking

500 (19.69)

FRONT VIEW

706 (27.8)

RIGHT VIEW

REAR VIEW

960 (37.8)

93E-15U / 93E-20

500 (19.69)

FRONT VIEW

706 (27.8)

REAR VIEW

RIGHT VIEW

93E-15UI / 93E-15UT / 93E-20I / 93E-20T

Figure 3-1. UPS Cabinet Dimensions (93E 15-20 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-5

1230
1230 (48.43)
(48.43)

UPS Installation Plan and Unpacking

500(19.69)
(19.69)
500

FRONT VIEW

706(27.8)
(27.8)
706

RIGHT VIEW

REAR VIEW

1230 (48.43)

93E-30

500 (19.69)

FRONT VIEW

706 (27.8)

RIGHT VIEW

REAR VIEW

93E-30I / 93E-30T

Figure 3-2. UPS Cabinet Dimensions (93E 30 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]

3-6

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

1500 (59.06)

UPS Installation Plan and Unpacking

93E-40

500 (19.69)

RIGHT VIEW

REAR VIEW

1500 (59.06)

FRONT VIEW

706 (27.8)

93E-40I / 93E-40T

500 (19.69)

706 (27.8)

FRONT VIEW

RIGHT VIEW

REAR VIEW

Figure 3-3. UPS Cabinet Dimensions (93E 40 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-7

1876 (73.9)

UPS Installation Plan and Unpacking

93E-60 / 93E-60T

600 (23.62)

RIGHT VIEW

REAR VIEW

1876 (73.9)

FRONT VIEW

796 (31.34)

93E-80 / 93E-80T

600 (23.62)

FRONT VIEW

796 (31.34)

RIGHT VIEW

REAR VIEW

Figure 3-4. UPS Cabinet Dimensions (93E 60-80 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]

3-8

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

706 (27.8)

UPS Installation Plan and Unpacking

FRONT

FRONT

500 (19.69)

TOP VIEW

BOTTOM VIEW

706 (27.8)

93E-15UI / 93E-15UT / 93E-20I / 93E-20T /93E-30I / 93E-30T /93E-40I / 93E-40T

FRONT

FRONT

500 (19.69)

TOP VIEW

BOTTOM VIEW

796 (31.34)

93E-15U / 93E-20 / 93E-30 / 93E-40

FRONT

FRONT

600 (23.62)

TOP VIEW

BOTTOM VIEW

93E-60 / 93E-60T / 93E-80 / 93E-80T

Figure 3-5. UPS Cabinet Dimensions (Top and Bottom Views)


Dimensions are in millimetres [inches]

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-9

611.5 (24.07)

611.5 (24.07)

611.5 (24.07)

960 (37.8)
611.5 (24.07)

960 (37.8)

UPS Installation Plan and Unpacking

353 (13.9)
353 (13.9)

250 (9.84)
250 (9.84)

706 (27.8)
706 (27.8)

500 (19.69)
500 (19.69)

FRONT VIEW

RIGHT VIEW

361.5 (14.23)

361.5 (14.23)

960 (37.8)

93E-15U / 93E-20

353 (13.9)

250 (9.84)
500 (19.69)

706 (27.8)

FRONT VIEW

RIGHT VIEW

93E-15UI / 93E-15UT / 93E-20I / 93E-20T

Figure 3-6. UPS Cabinet Centre of Gravity (93E 15-20 kVA)


Dimensions are in millimetres [inches]

3-10

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

765 (30.12)

765 (30.12)

1230 (48.43)

UPS Installation Plan and Unpacking

353 (13.9)

250 (9.84)
500 (19.69)

RIGHT VIEW

93E-30

445 (17.52)

445 (17.52)

1230 (48.43)

FRONT VIEW

706 (27.8)

500

250 (9.84)

353 (13.9)

500 (19.69)

706 (27.8)

FRONT VIEW

RIGHT VIEW

93E-30I / 93E-30T

Figure 3-7. UPS Cabinet Centre of Gravity (93E 30 kVA)


Dimensions are in millimetres [inches]

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-11

93E-40

930 (36.61)

930 (36.61)

1500 (59.06)

UPS Installation Plan and Unpacking

500

250 (9.84)

353 (13.9)

500 (19.69)

706 (27.8)

FRONT VIEW

1500 (59.06)

RIGHT VIEW

550 (21.65)

550 (21.65)

93E-40I / 93E-40T

250 (9.84)

353 (13.9)

500 (19.69)

FRONT VIEW

706 (27.8)

RIGHT VIEW

Figure 3-8. UPS Cabinet Centre of Gravity (93E 40 kVA)


Dimensions are in millimetres [inches]

3-12

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

1876
1876 (73.9)
(73.9)

UPS Installation Plan and Unpacking

970(36.22)
(38.19)
920

920
970(36.22)
(38.19)

93E-60

300 (11.81)

300 (11.81)

600(23.62)
(23.62)
600

796(31.34)
(31.34)
796

RIGHT VIEW

1876 (73.9)

FRONT VIEW

920 (36.22)

920 (36.22)

93E-60T

300 (11.81)

300 (11.81)

600 (23.62)

796 (31.34)

FRONT VIEW

RIGHT VIEW

Figure 3-9. UPS Cabinet Centre of Gravity (93E 60 kVA)


Dimensions are in millimetres [inches]

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-13

1876 (73.9)

UPS Installation Plan and Unpacking

1020 (40.16)

1020 (40.16)

93E-80

600

300 (11.81)

300 (11.81)

600 (23.62)

796 (31.34)

RIGHT VIEW

1876 (73.9)

FRONT VIEW

970 (38.19)

970 (38.19)

93E-80T

300 (11.81)
600 (23.62)

FRONT VIEW

300 (11.81)
796 (31.34)

RIGHT VIEW

Figure 3-10. UPS Cabinet Centre of Gravity (93E 80 kVA)


Dimensions are in millimetres [inches]

3-14

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

3.2.2 UPS System Power Wiring Preparation


The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment.
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table3-1 and the
size requirements shown in Figure3-1. Dimensions are in millimetres (inches).

WARNING

HIGH TOUCH CURRENT EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY.


As a result of the connected loads high leakage current is possible. Connection of the earth
(ground) is required for proper product operation. Do not check UPS operation by removal of
the Earth (ground) connection.
The UPS unit is not suitable for IT and corner-earthed power distribution systems.

WARNING

RISK OF ELECTRIC SHOCK. This ups receives power from more than one source disconnection of the AC and the DC source is required to de - energise this unit before
servicing. After disconnecting the utility power and the DC power, authorised service
personnel should wait at least five minutes for capacitor bleedoff before attempting internal
access to the UPS module.
Backfeed protection is an internally fitted option on this device. If this option, or an externally
fitted backfeed contactor are not installed.
The below label should be applied on all primary power isolators installed remote from the
UPS area and on external access points.

CAPACITORS INSIDE
REQUIRE 5 MINUTES
TO DISCHARGE
TO A SAFE LEVEL
AFTER ALL POWER
IS REMOVED.
SEE HANDBOOK
FOR INSTRUCTIONS.

Refer to national and local electrical codes for acceptable external wiring practices.
To allow for future kVA upgrades, consider installing a derated UPS using wiring and external overcurrent
protection breakers sized for a fully rated UPS.
For external wiring, use 90C copper wire. Wire sizes listed in Table3-5 are for copper wiring only. If wire is
run in an ambient temperature greater than 30C, higher temperature wire and/or larger size wire may be
necessary. Wire sizes are based on using the specified breakers.
Material and labour for external wiring requirements are to be supplied by designated personnel.
If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB)
(if installed) must have a service disconnect independent of the maintenance bypass power path. Most
maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance
bypass power path. If the maintenance bypass solution being installed does not provide such functionality,
DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-15

UPS Installation Plan and Unpacking

The bypass feed into this equipment uses four wires (three line conductors and neutral conductor), plus
grounding conductor (protective earthing conductor) . The rectifier feed into this equipment uses four wires
(three line conductors and neutral conductor), plus grounding conductor (protective earthing conductor). The
phases must be symmetrical about ground (from a Wye/Star source) for proper equipment operation.
Parallel UPS input wiring size requirements and output wiring size requirements from the UPSs to the Tie
Cabinet are the sames as those for single systems.
This device is not equipped with its own mains separation device. It is , therefore, essential that the customer
install such a device at the installation site near the UPS.
Install a proper three-pole overcurrent disconnect device before connecting to the UPS, the disconnect
device shall disconnect simultaneously all line conductors of the AC MAINS SUPPLY.
Do not disconnect neutral, neutral required for system operation.
If a disconnect device interrupts the neutral conductor, it shall simultaneously interrupt all line conductors.
When single-phase current exceeds 100A, switches of protective atmosphere should be equipped with
arc-control device.
The UPS requires an input neutral connection. Ensure that an input neutral is connected prior to energising
the UPS. If a 4 pole Automatic Transfer Switch is installed upstream of the UPS it must work with a break
before make transition with a minimum transfer time of 50ms.
Figure4-6 and Figure4-7 show the location of the UPS power cable terminals.

3-16

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

Table 3-5. Input / Output Ratings and External Wiring Requirements for the Eaton 93E 15-80 kVA
cross-sections
Refer the IEC
62040-1

Basic Unit Rating

Units

Rating 50/60 Hz

kVA
kW

15
13.5

20
18

30
37

40
36

60
54

80
72

Volts

400/400

400/400

400/400

400/400

400/400

400/400

Amps

23

31

46

61

92

123

min

mm2

61

61

61

161

161

251

max

mm

61

101

251

251

501

701

Amps

22

29

43

58

87

115

min

mm2

61

61

61

61

161

251

max

mm

61

101

251

251

501

701

Total Amps

34

46

69

92

137

183

min

mm2

61

61

101

161

351

501

max

mm

161

251

351

501

502

702

Amps

22

29

43

58

87

115

min

mm2

61

61

61

61

161

251

max

mm2

61

101

251

251

501

701

Input and Output Voltage


A: AC Input to UPS Rectifier (0.99 Minimum PF)
Full load current plus battery recharge current
(3) Phases
Conductor Size (Phase A, B, C )
B: AC Input to UPS Bypass (Five Wire, Dual-Feed)
Full Load Current
(3) Phases
Conductor Size (Phase A, B, C )
C: DC Input from External Battery (432 Vdc)
(1) Positive, (1) Negative
Conductor Size
D: AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases
Conductor Size (Phase A, B,C )

Grounding

1.0times

Neutral (N) (Mains/Load):( Non-linear load )

1.7times
Clearance distance:2.0mm

Backfeed protection device

NOTE

Break time:15s

Callout letters A, B, C, and D map to Figure5-5.

CAUTION
External overcurrent protection is not provided by this product, but is required by codes. Refer to
table 3-5 for wiring requirements. If an input/output lockable disconnect is required, it is to be
supplied by the user.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-17

UPS Installation Plan and Unpacking

Table 3-6. UPS External Power Cable Terminations for the Eaton 93E 15-80 kVA
Tightening
Torque
Nm (lb in) Screw Size and Type

Terminal
Function Terminal

Function

Bus landing

15kVA/20kVA/30kVA
AC Input
to UPS
Rectifier

AC Input
to Bypass

AC Output
to Critical
Load

DC Input
from
External
Battery
Customer
Ground

NOTE

3-18

Tightening
Torque
Nm (lb in) Screw Size and Type

Bus landing

40 kVA/60kVA/80kVA

L1

Phase A

M6 bolt mounting

5 (44)

28.26 mm(M6).

M8 bolt mounting

12 (106)

50.24 mm(M8)

L2

Phase B

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L3

Phase C

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

Neutral

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L1

Phase A

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L2

Phase B

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L3

Phase C

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

Neutral

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L1

Phase A

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L2

Phase B

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

L3

Phase C

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

Neutral

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

Battery (+)

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

Battery (-)

M6 bolt mounting

5 (44)

28.26 mm(M6)

M8 bolt mounting

12 (106)

50.24 mm(M8)

15-20 kVA Ground

M5 bolt mounting

3 (26)

19.63 mm(M5)

30 kVA Ground

M6 bolt mounting

9 (79)

28.26 mm(M6)
M8 bolt mounting

24 (212)

50.24 mm(M8)

Callout letters A, B, C, and D map to Figure5-5.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

Table 3-7. Recommended Input Circuit Breaker Ratings


Circuit Breaker Rating
UPS Model
93E-15
93E-20
93E-30
93E-40
93E-60
93E-80

Load Derating

400V

80% Derated

29A

100% Rating

23A

80% Derated

38A

100% Rating

31A

80% Derated

57A

100%Rating

46A

80% Derated

77A

100% Rating

61A

80% Derated

115A

100% Rating

92A

80% Derated

153A

100% Rating

123A

CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuitbreakercurrent ratings from Table3-7 in accordance with local regulations.
The line-to-line unbalanced output capability of the UPS is limited only by the full load perphase current values
for AC output to critical load shown in Table3-5. The recommended line-to-line load unbalance is 50% or less.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass
and output circuit breakers.
Table 3-8. Recommended Bypass and Output Circuit Breaker Ratings
Circuit Breaker Rating
UPS Model
93E-15
93E-20
93E-30
93E-40
93E-60
93E-80

Load Derating

400V

80% Derated

27A

100% Rating

22A

80% Derated

36A

100% Rating

29A

80% Derated

54A

100% Rating

43A

80% Derated

72A

100% Rating

58A

80% Derated

108A

100% Rating

87A

80% Derated

144A

100% Rating

115A

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-19

UPS Installation Plan and Unpacking

There is no DC disconnect device within the UPS. A battery disconnect switch is recommended, And may be
required by local codes when batteries are remotely located. The battery disconnect switch should be installed
between the battery and the UPS
External DC input overcurrent protection and disconnect switch for the remote battery location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit breakers satisfying the
criteria for both.
Table 3-9. Recommended DC input circuit breaker rating
Circuit Breaker Rating

UPS Model
93E-15
93E-20
93E-30
93E-40
93E-60
93E-80

Rated battery voltage

Rated battery voltage

Load Derating

(DC 432V, External battery 36 blocks)

(DC 384V, Internal battery 32 blocks)

80% Derated

43A

48A

100% Rating

34A

39A

80% Derated

57A

64A

100% Rating

46A

52A

80% Derated

86A

97A

100% Rating

69A

77A

80% Derated

114A

129A

100% Rating

92A

103A

80% Derated

172A

193A

100% Rating

137A

155A

80% Derated

229A

258A

100% Rating

183A

206A

Battery voltage is computed at 2 volts per cell. Rated battery current is computed at 2 volts per cell. The battery
wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC
voltage at rated battery current. If the conductors used for DC input from the battery cabinets to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same
supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.

3-20

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

3.2.3 UPS System Interface Wiring Preparation


Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.

WARNING
Do not directly connect contactor contacts to the mains related circuits. Reinforced insulation is
required before connecting to the mains.
Read and understand the following notes while planning and performing the installation:
Interface wiring should be rated for 24V, 1A minimum.
For interface wiring from 30V to 600V, the wire should be rated for 600V, 1A minimum.
Because of the REPO and building alarm wiring route in the UPS cabinet, the wire should be rated for a
minimum of 300V.
Use twisted-pair wires for each input and return or common.
All interface wiring and conduit is to be supplied by the customer.
When installing external interface wiring between a REPO or building alarm and the UPS interface terminals,
conduit must be installed between each device and the UPS cabinet.
If using the power terminal wiring channel, keep interface wiring separate from power wiring or use shielded
wire.
If using conduit, install the interface wiring in separate conduit from the power wiring.
All building alarm inputs require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA
minimum) connected between the alarm input and common terminal. All control wiring and switch contacts
are customer-supplied.
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by the customer.
The REPO feature opens all contactors in the UPS cabinet and isolates power from your critical load. Local
electrical codes may also require tripping upstream protective devices to the UPS.
The REPO switch must be a latching-type switch not tied to any other circuits.
A jumper wire must be connected between pins3 and 4 on the REPO terminal block if using a normallyclosed REPO switch.
REPO wiring should be a minimum of 0.5~2.0 mm2.
The REPO switch wiring must be in accordance with local regulations.
The maximum distance between the REPO and the UPS cannot exceed 150metres (500feet).

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-21

UPS Installation Plan and Unpacking

3.3

Inspecting and Unpacking the UPS Cabinets


The cabinet is shipped bolted to a wooden pallet and protected with an outer wood container.

WARNING
The UPS cabinet is heavy (see Table3-1). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
1. Carefully inspect the outer packaging for evidence of damage during transit.

CAUTION
Do not install a damaged cabinet. Report any damage to the carrier and contact an
Eaton service representative immediately.

NOTE

For the following step, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table3-1 for cabinet weight).

2. Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks
between the supports on the bottom of the pallet (see Figure3-6 through Figure 3-10 for the UPS cabinet
centre of gravity measurements).

CAUTION
Do not tilt the UPS cabinets more than 10 from vertical or the cabinets may tip over.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m(10ft) on each side for
removing the cabinet from the pallet.
4. Remove the inner protective packaging. Retain the ramp brackets.
5. Recycle the remainder of the outer shipping container and the inner protective packaging in a responsible
manner.
6. Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.

3-22

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Installation Plan and Unpacking

NOTE

While waiting for installation, protect the unpacked cabinet from moisture, dust, and
other harmful contaminants. Failure to store and protectthe UPS properly may void
your warranty.

Figure 3-11. UPS Cabinet as Shipped on Pallet

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

3-23

UPS Installation Plan and Unpacking

This page intentionally left blank.

3-24

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 4
4.1

UPS System Installation

Preliminary Installation Information

WARNING
Installation should be performed only by qualified personnel. See installation instructions before
connecting to the supply.
Refer to the following while installing the UPS system:
Chapter3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
Do not tilt the cabinets more than 10 during installation.
If perforated floor tiles are required for ventilation, place them in front of the UPS.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.
Suitable for mounting on concrete or other non-combustible surfaces only

4.2

Unloading the UPS Cabinetfrom the Pallet


The UPS Cabinet is bolted to a wooden pallet supported by wood skids. To remove the pallet:

WARNING
The UPS cabinet is heavy (see Table3-1). If unpacking and unloading instructions are not closely followed,
the cabinet may tip and cause serious injury.

CAUTION
Do not tilt cabinet more than 10 from vertical.
Lift the cabinets only with a forklift or damage may occur.
NOTE

For the following steps, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table3-1 for cabinet weight).

1. If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see Figure3-6 through Figure 3-10for the UPS cabinet centre of
gravity measurements).
2. Remove four bolts securing the front shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.
3. Attach the ramp to the front of the pallet (see Figure4-2):
4. If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
5. Remove four bolts securing the rear shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-1

UPS System Installation

Front Door

Shipping Bracket Bolts

Pallet

Shipping Bracket

Figure 4-1. Removing the Shipping Bracket

WARNING
Do not stand directly in front of the pallet while unloading the cabinet. If unloading instructions are
not closely followed, the cabinet may cause serious injury.
6. Slowly roll the cabinet toward the front of the pallet. Continue rolling the cabinet down the ramp until the
cabinet is clear of the ramp (see Figure4-3).
7.

Roll the cabinet to the final installation location.

8. If installing the cabinet permanently, retain the shipping brackets and hardware; otherwise, recycle the
pallet, ramp, and shipping brackets in a responsible manner.
9. Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is not resting on the
casters and the cabinet is level.
10. If permanently mounting the system, proceed to Step 11;
11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and
rear of the UPS cabinet with the angle facing outward (see Figure4-1).
12. Secure the cabinet to the floor with customer-supplied hardware.

4-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

UPS Cabinet

Pallet

Ramp

Figure 4-2. Attaching the Ramp to the Pallet

lU

se

On

ly

UPS System Installation

na

Figure 4-4. Rolling the Cabinet Down the Ramp

ter

Figure 4-3. Rolling the Cabinet Down the Ramp

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-3

UPS System Installation

4.3

External Battery Cabinet Installation


Before connecting the external battery, please read the notice and warning label on the battery cabinet.

WARNING

In the event of malfunction, the battery cabinet chassis or battery cabinet frames may become
live!

Special care should be taken when working with the battery cabinet associated with the
equipment. Ensure the battery number is suited to the setting of the battery charging voltage
before installing the battery. When the battery cabinet is connected the overall voltage exceeds
nominal voltage. It is very important to ensure that the batteries are installed separately, in a
dedicated battery cabinet.

Battery back-up time do not exceed one hour, if the battery setting shall be exceeded one hour,
consult to the professional personnel.

CAUTION
The most common battery type used in UPS installations is the valve regulated battery. Valve
regulated cells are not sealed. The amount of gas given off is less than for flooded cells, but
when planning the battery installation, allowance must be made for adequate ventilation and
heat dissipation. Valve regulated cells are not completely maintenace- free. They must be kept
clean and their connections checked periodically to ensure they are tight, and that there is no
evidence of corrosion. It is inevitable that the batteries will lose charge during transportation and
storage; before attempting to carry out an autonomy test, ensure that the batteries are fully
charged as this may take several hours. Cell performance typically improves after a few
discharge/recharge cycles.
The requirements of the EC directives are satisfied when battery cabinet are used with original
accessories. If alternative batteries are used, you must ensure that the applicable EC directives
are met and declare conformity.
Connect the battery cabinet as follows:
1. Turn off the UPS.
2. Check all the external battery breakers are open.
3. Connect PE first.
4. Connect the battery cabinet(s) with cables sized according to cable cross section and protective device.
5. Specification to terminals + (positive pole) and - (negative pole).
Refer to instructions provided with the battery cabinet or by vendor.

WARNING
ENSURE CORRECT POLARITY!

4-4

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

4.4

External Power Wiring Installation


NOTE

Without accessory cabinets, conduit and wiring enter from the bottom of the UPS
conduit landing plate. With accessory cabinets, wiring can be installed between the
UPS and accessory cabinets by using conduit or by routing wiring through the
power terminal cover base wiring channels.

To install wiring:
1. Route the wiring to the UPS terminal blocks in the UPS. Figure 4-4 and Figure 4-5 for wiring access
information and terminal locations.
2. Ground the UPS according to local and/or national electrical wiring codes by routing and connecting the
ground wire to the input ground lug.
3. Connect phase A, B and C rectifier input power wiring from the utility source to the rectifier input, See
paragraph 3.2.2 for wiring and termination requirements.
4. Bypass input power wiring from the utility source to the bypass input terminals and neutral terminals. See
paragraph 3.2.2 for wiring and termination requirements.
5. Connect phase A, B and C power wiring from output terminals to the critical load. See paragraph 3.2.2 for
wiring and termination requirements.
6. Mains input N , Output N and Bypass input N are connected together inside UPS
7.

If wiring interface connections, proceed to paragraph 4.5.

WARNING

HIGH TOUCH CURRENT. EARTH CONNECTION ESSENTIAL BEFORE CONNECTING


SUPPLY. As a result of the connected loads high leakage current is possible. Connection of the
earth (ground) is required for proper product operation. Do not check UPS operation by
removal of the Earth (ground) connection.

BAT+/BAT- are terminals connected to the battery cabinet, Battery+ polarity should use red
cable, battery - polarity should use black or blue cable.

This device may not be fitted with an optional internal mains disconnection device. If not
fitted, it is essential that the customer install such a device at the installation site near the
UPS.

Input neutral line should be directly connected to input N terminal of UPS wire connection
terminal bay without AC input idle-run.

There are protective earthing terminals within the UPS for mains supply, load supply and
battery. The battery cabinet earth protection can be connected either to the UPS or to a
common earthing terminal outside the UPS.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-5

UPS System Installation

AC Input to
UPS Bypass

Ground Terminals

RIGHT VIEW
AC Input to
UPS Rectifier

Phase C (L3)
Phase B (L2)
Phase A (L1)

Internal Battery +

Neutral (N)

Phase A (L1)
Phase B (L2)
Phase C (L3)

Internal Battery -

Phase C (L3)
Phase B (L2)

AC Output to
Critical Load

Phase A (L1)

FRONT VIEW

93E-15U / 93E-15UT / 93E-20 / 93E-20T / 93E-30 / 93E-30T / 93E-40 / 93E-40T


Note: Connection terminals for these models are accessible from the front of the UPS cabinet.

Internal Battery +

Phase C (L3)

Neutral (N)

Phase B (L2)

Internal Battery -

AC Input to UPS Bypass

Phase A (L1)

Ground Terminals
Phase A (L1)

Phase C (L3)
AC Output to Critical Load

Phase B (L2)

Phase B (L2)

AC Input to UPS Rectifier

Phase C (L3)

Phase A (L1)
REAR VIEW

93E-15UI / 93E-20I / 93E-30I / 93E-40I


Note: Connection terminals for these models are accessible from the rear of the UPS cabinet.
Figure 4-4. Power Terminal Locations 20-40 kVA

4-6

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

AC Input to
UPS Bypass

Neutral (N)

Internal Battery -

Phase C (L3)
Phase B (L2)

Internal Battery +

Phase A (L1)
Ground Terminals

RIGHT VIEW
AC Input to
UPS Rectifier

Phase A (L1)

Phase C (L3)

Phase B (L2)

Phase B (L2)

Phase C (L3)

FRONT VIEW

AC Output to
Critical Load

Phase A (L1)

93E-60 / 93E-60T / 93E-80 / 93E-80T


Note: Connection terminals for these models are accessible from the front of the UPS cabinet.

Figure 4-5. Power Terminal Locations 60-80 kVA

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-7

UPS System Installation

4.5

Installing Interface Connections


4.5.1 Installing Building Alarm Connections
To install wiring:
1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, UPS Operating
Instructions", for shutdown instructions.
2. To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph3.2.3, Table4-1, Figure4-6 and Figure4-7.
3. Interface cables can enter the UPS via right side panel or a knockout in the top of the cabinet, see Figure
4-9.
4. Connect the building alarm interface wiring as shown in Table4-1 and Figure4-8.
6. If wiring parallel connections, proceed to paragraph 4.5.2; if wiring Mini-Slot connections, proceed to
paragraph 4.5.3;

Mini-Slot Communication Bays


(See Figure 4-7 for detail)
Mini-Slot Communication Bays
(See Figure 4-7 for detail)
Interface Terminals
(See Figure 4-7 for detail)

FRONT MIDDLE
COVER PLATE

FRONT VIEW

FRONT VIEW

93E 15-40 kVA

93E 60-80 kVA


Figure 4-6. Interface Terminal Locations

4-8

Interface Terminals
(See Figure 4-7 for detail)

FRONT MIDDLE
COVER PLATE

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

Mini-Slot Communication Bay 2

Mini-Slot Communication Bay 1

Mini-Slot Communication Bay 1

Mini-Slot Communication Bay 2

Building Alarm (See Figure 4-8 for Detail)


Parallel CAN Output (RJ45)
Parallel CAN Input (RJ45)
Pull chain Terminals
REPO Terminals (See Figure 4-13 for Detail)
Building Alarm (See Figure 4-8 for Detail)

REPO Terminals (See Figure 4-13 for Detail)


Pull chain Terminals
Parallel CAN Input (RJ45)
Parallel CAN Output (RJ45)

93E 15-40 kVA

93E 60-80 kVA

Figure 4-7. Interface Terminal Detail (Terminal Cover Removed)

Building Alarm 1

Building Alarm 3

Building Alarm 2

Figure 4-8. Building Alarm Terminal Block Connector Assignments


Table 4-1. Building Alarm Connections
Building Alarm Terminal

Name

Building Alarm 1 +

Building Alarm 1

Building Alarm 2 +

Building Alarm 2

Building Alarm 3 +

Building Alarm 3

Description
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-9

UPS System Installation

Wiring Access

93E 15-40 kVA


IEW
FRONT V

Wiring Aaccess

93E 60-80 kVA


FRONT VIEW

Figure 4-9. Interface Wiring Access

4-10

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

4.5.2 Installing Parallel Pull Chain and CAN Control Wiring and Connections
To install wiring:
1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, UPS Operating
Instructions", for shutdown instructions.
2. Installing Parallel system, seeFigure4-10 and Figure 4-12.

CAUTION
Parallel system combined input and output cable length should be in accordance with the
following rule. It should be designed to ensure that wiring impedance from point of supply to
UPS input and from UPS output to load connection for each UPS module in a multi-module
system is equal, or within a tolerance of approximately 10%. This is to ensure approximately
equal current sharing when in static bypass mode and restrain input/output high frequency loop
current of parallel system. Suggest that parallel system combined input and output cable length
no less than 10m, 5m for input and 5m for output.
Total length of 1A =2A=3A=4A
1B=2B=3B=4B
1C=2C=3C=4C
If installing only two UPS modules (redundant), this requirement is no longer required as each
UPS is capable of supporting the full bypass requirement. However, this would preclude future
expansion.
Ensure that each UPS static bypass is fed from a single common source, as is an external
bypass switch if installed. If each UPS is fed with a separate rectifier source, please consult
Eaton for advice on compatibility.

3. To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph3.2.3, Table4-2, Figure4-7, Figure4-9, and Figure4-10.

Pull Chain
Figure 4-10. Pull Chain Terminal Block Connector Assignments
Table 4-2. Pull Chain Connections
Pull Chain Terminal

Name

Pull Chain +

Pull Chain

Description
Output: Backup control for parallel operation.

4. Remove the small parts from the knockout in the right side plate.
5. Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure4-7,
Figure4-11 and Figure4-12 for wiring information.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-11

UPS System Installation

6. Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm2) between the UPS cabinets and cabinet
MOBs. See Figure 4-7, Figure 4-10 and Figure 4-11 for wiring information.
7.

If wiring Mini-Slot connections, proceed to paragraph 4.5.3;

4.5.3 Installing Mini-Slot Interface Connections


NOTE

LAN drop for connection to UPS communications card is to be supplied by customer.

For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8)
To install wiring:
1. If not already installed, install the LAN drop.
2. Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure4-6 and Figure4-7
for Mini-Slot communication bay locations.
3. Refer to the manual supplied with the Mini-Slot card for operator instructions.
4. Install the power terminal cover using the provided hardware.

4-12

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

TERMINATING
JUMPER

RJ-45 CABLE

IN
OUT
CN3
CN6
CAN BUS

RJ-45 CABLE

IN
CN3

UPS 1
BUILDING
ALARM CN9
1
2

OUT
CN6

IN
CN3

CAN BUS

UPS 2

PULLCHAIN
CN4
1
2

BUILDING
ALARM CN9
1
2

TERMINATING
JUMPER

RJ-45 CABLE
OUT
CN6

IN
CN3

CAN BUS

UPS 3

PULLCHAIN
CN4
1
2

OUT
CN6

CAN BUS

UPS 4

BUILDING PULLCHAIN
ALARM CN9
CN4
1
2
1
2

BUILDING
ALARM CN9
1
2

PULLCHAIN
CN4
1
2

TWISTED
PAIRS

CUSTOMER
TERMINAL
BLOCK
CONNECTIONS

25

1
NO
COM

6
NC

M
O
B
1

NO

NC

COM
5

10

7
NO
COM

26
12

NC

M
O
B
2

NO
COM
11

NC

15 14

16

13
NO

27

21 20

18
NC

COM

M
O
B
3

NO

NC

COM
17

22

19
NO
COM

28
24

NC

M
O
B
4

NO

NC

COM
23

TIE CABINET

Figure 4-11. Parallel UPS Control Wiring

UPS 1
Bypass inputs
to UPSs

UPS 1
REC inputs
to UPSs

1A
2A

2C

Battery

3A

1C

UPS 2

Battery

3C

4A

UPS 2

4C

Battery

Battery

UPS 3

UPS 3
1B

Outputs from
UPSs

1B

2B

Battery

UPS 4

2B

Battery

UPS 4

3B

Outputs from
UPSs

4B

3B
4B

Battery

Battery

Figure 4-12. Parallel UPS system connections

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-13

UPS System Installation

4.6

Installing a REPO Switch


A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. Shows a
REPO switch.
NOTE 1

Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs 4.2 through 4.5.

NOTE 2

When installing the REPO switch, you must install conduit between the device and
the UPS cabinet for wiring the switch.

NOTE 3

The REPO switch must be a normally-open or normally-closed latching-type switch


not tied into any other circuits.

NOTE 4

This procedure is intended for installing the Eaton-supplied REPO switch. If


installing another manufacturer's switch, use this procedure, and Figure4-13 and
Figure4-14 as a guide.

NOTE 5

The REPO switch wiring must be in accordance with local regulations.

To Install a REPO switch:


1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, UPS Operating
Instructions, for shutdown instructions.

UPS System Installation

2. Securely mount the REPO switch. Recommended locations include operator's consoles or near exit doors.
3. To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph3.2.3, Table4-3, Figure4-6, Figure4-7, and Figure4-13.

Normally Open
REPO Contacts
Normally
Open
REPO Contacts

Figure
Terminal Block
Block Connector
Connector Assignments
Assignments
Figure 4-19.
4-13. REPO
REPO Terminal

REPO Terminal
1
2
3
4

Table 4-3. REPO Connections


REPO Terminal
Description
1

Description

Input: normally-closed dry contact used to activate UPS EPO from a remote switch.
2 dry contact used to activate UPS EPO from a remote switch.
Input: normally-closed
3
Input: normally-open dry contact used to activate UPS EPO from a remote switch.
Input: normally-open4dry contact used to activate UPS EPO from a remote switch.

4.

Us

Table 4-3. REPO Connections

eO

NormallyClosed
Closed
Normally
REPO
Contacts
REPO
Contacts

nl

UPS
UPS

Route the REPO wiring to the terminal block:

4. Normally-Open REPO Switch


see Table
4-4 and
Figurethe
4-14,Normally-Closed
REPO
Wiring
a. IfWiring
not already
removed,
remove
power terminal cover
rightSwitch
and left
sides (see Figure 4-9). R
seeTable 4-5 and Figure 4-15 .
the cover top and hardware for later use.

4-14

If not already removed, remove the power terminal cover top. Retain the cover top and hardwa
later use.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation


and Operation
NOTE
TheManual
two

c.

al

b.

upper fans are attached to the top rear panel.

Remove the screws securing the top rear panel (see Figure 4-10). Supporting the panel, tilt the

UPS System Installation

5. Connect the wiring as shown in Table4-4 and Figure4-14 for a normally-open REPO or Table4-5 and
Figure4-15 for a normally-closed REPO.
6. If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO
terminal block.
7.

If you are installing multiple REPO switches, wire additional switches in parallel with the first REPO.

8. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A
second contact block is provided on the REPO switch for this function . The REPO switch wiring must be in
accordance with local regulations.
Table 4-4. REPO Connections
From REPO Station(s)
Switch Contact Block
(Either Block)

To REPO Terminal Block


on Back of UPS Cabinet

3,4 NO

See Figure 4-14 for wiring

Wire Size

Tightening Torque

Twisted Wires (2)


(0.5 -2.0mm2)

7lbin
(0.8Nm)

2
3

REPRO
Switch
(No)

REPO TB

Twisted
Wires
4

Figure 4-14. Normally-Open REPO Switch Wiring

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-15

UPS System Installation

Table 4-5. REPO Connections


From REPO Station(s)
Switch Contact Block
(Either Block)

To REPO Terminal Block


on Back of UPS Cabinet

1,2,3,4 NC

See Figure 4-15 for wiring

REPRO
Switch
(NC)

Wire Size

Tightening Torque

Twisted Wires (2)


(0.5 -2.0mm2)

7lbin
(0.8Nm)

Twisted
Wires

REPO TB

Figure 4-15. Normally-Closed REPO Switch Wiring

4.7

Initial Startup
Startup may be performed by the customers qualified electrical contractor for single (not parallel) UPS
installations without any accessory cabinets.
Startup and operational checks for parallel systems or installations with accessory cabinets must be performed
by an authorised Eaton Customer Service Engineer, or the warranty terms may become void.This service is
offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a
two-week notice is required) to reserve a preferred startup date.

4.8

Completing the Installation Checklist


The final step in installing the UPS system is completing the following Installation Checklist. This checklist
ensures that you have completely installed all hardware, cables, and other equipment. Complete all items listed
on the checklist to ensure a smooth installation. Make a copy of the Installation Checklist before filling it out,
and retain the original.
After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS
system and commission it to support the critical load. The service representative cannot perform any
installation tasks other than verifying software and operating setup parameters. Service personnel may request
a copy of the completed Installation Checklist to verify all applicable equipment installations have been
completed.

NOTE

4-16

The Installation Checklist MUST be completed prior to starting the UPS system for
the first time.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS System Installation

Installation Checklist

All packing materials and restraints have been removed from each cabinet.
The UPS cabinet is placed in its installed location.
All conduits and cables are properly routed to the UPS and any ancillary cabinets.
All power cables are properly sized and terminated.
Neutral conductors are installed.
A ground conductor is properly installed.
Building alarms are wired appropriately. (Optional)
LAN drops are installed. (Optional)
LAN connections have been completed. (Optional)
The REPO device is mounted in its installed location and its wiring is terminated inside the UPScabinet.(Optional)
A jumper wire is connected between pins 3 and 4 on the REPO terminal block if using a normally-closed REPO switch.
(Optional)

All terminal cover plates are installed.


Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional)
Air conditioning equipment is installed and operating correctly.
The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a
level floor suitable for computer or electronic equipment.)

Adequate workspace exists around the UPS and other cabinets.


Adequate lighting is provided around all UPS equipment.
A 230Vac service outlet is located within 7.5metres (25 feet) of the UPS equipment.
Startup and operational checks are performed by an authorised Eaton Customer Service Engineer, for parallel systems
or installations with accessory cabinets.

Parallel System Installation Checklist

Each cabinet in the parallel system is placed in its installed location.


All conduits and cables are properly routed to the UPSs and to the parallel tie cabinet.
All power cables are properly sized and terminated.
Neutral conductors are installed between cabinets as required.
Ground conductors are properly installed.
CAN wiring between the UPSs is properly installed.
Pull chain wiring between the UPSs is properly installed.
Adequate workspace exists around the UPSs, parallel tie cabinet, and other cabinets.
Startup and operational checks are performed by an authorised Eaton Customer Service Engineer, for parallel systems.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

4-17

UPS System Installation

Notes

4-18

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Section 2
Operation

Chapter 5
5.1

Understanding UPS Operation

UPS System Overview


The Eaton 93E UPS is a continuous-duty, solid-state, three-phase, true online system that provides conditioned
and uninterruptible AC power to the UPS system's output and critical load.
The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated
communication server, and digital signal processor (DSP) logic. Figure5-1 shows the main elements of the UPS
system.
If utility power is interrupted or falls outside the parameters specified in Chapter9, Product Specifications, the
UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or until the
utility power returns. For extended power outages, the UPS allows you to either transfer to an alternative power
system (such as a generator) or shut down your critical load in an orderly manner.
External Battery cabinet

Battery
Relay
Battery
Converter

AC Input to
Rectifier/
Charger

Input
Switch

Input
Relay

Output
Relay

Rectifier

Inverter
Power Module
Digital Metering

(Optional Dual Input)


Bypass Input Switch
AC Input to
Bypass

Output switch
Static
Switch

AC Output to
Critical Load

(Optional)
Backfeed Contactor

Maintenance Bypass Switch


UPS Cabinet

Figure 5-1. Main Elements of the UPS System


The emergency bypass consists of a continuous static switch, and an optional backfeed protection contactor. The
backfeed protection contactor (if fitted) is located in series with the static switch. The static switch is armed and
ready during normal operation.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

5-1

Understanding UPS Operation

5.2

Single UPS
A single UPS operates independently to support an applied load from the inverter, providing conditioned and
uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter
continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied
loads are transferred to the internal bypass either automatically or manually. With the exception of an optional
external battery cabinet, no other cabinets or equipment are required for the single UPS to successfully support
its applied loads.

5.2.1 Modes
The Eaton 93E UPS supports a critical load in four different modes of operation:

In Standard Normal mode, the critical load is supplied by the inverter, which derives its power from rectified
utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed,
Standard mode is the standard normal operating mode.

In High-Efficiency (HE) mode, commercial AC power is supplied directly to the critical load through the
internal bypass and transfers automatically to Standard Normal mode (double-conversion on demand) if an
abnormal condition is detected.

In Bypass mode, the critical load is directly supported by utility power.

In Battery mode, the battery provides DC power, which maintains inverter operation. The battery supports
the critical load.

The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show
the power flow during each mode of operation.

5.2.2

Standard Normal Mode

During Standard Normal mode, power for the system is derived from a utility input source through the rectifier
input contactor. Three-phase AC input power is converted to DC using IGBT devices to produce a regulated DC
voltage to the inverter. When the battery contactor is closed the battery is charged directly from the regulated
rectifier output through a buck or boost DC converter, depending on the system voltage and the size of the
battery string attached to the unit.
Figure5-2 shows the path of electrical power through the UPS system when the UPS is operating in Normal
mode.
The battery converter derives its input from the regulated DC output of the rectifier and provides either a
boosted or bucked regulated DC voltage charge current to the battery. The battery is always connected to the
UPS and ready to support the inverter should the utility input become unavailable.
The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The
inverter derives regulated DC from the rectifier and uses IGBT devices and pulse-width modulation (PWM) to
produce a regulated and filtered AC output. The AC output of the inverter is delivered to the system output
through the output contactor.
If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode
to support the critical load without interruption. When utility power returns, the UPS returns to Normal mode.

5-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Understanding UPS Operation

Bypass Input

Bypass Switch (Optional Dual Input)

Static

Switch
Rectifier
Input

Input Switch

Output
Rectifier

Inverter

Input
Relay

Output
Relay
Battery
Converter

Battery
Switch

Relay

Relay
Closed

Main Power Flow


Trickle Current
Energised

Open

De-Energised
Battery

Figure 5-2. Path of Current Through the UPS in standard Normal Mode
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically
returns to Normal mode when the overload condition is cleared and system operation is restored within
specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until
the failure is corrected and the UPS is back in service.

5.2.3

High-Efficiency Mode

When the UPS is operating in HE mode, commercial AC power is supplied directly to the critical load through the
internal bypass with the power module in a standby state. If a commercial power brownout, blackout, overvoltage,
undervoltage, or out-of-tolerance frequency condition occurs the system forward transfers to normal mode
(double-conversion on demand) or battery mode. When the input line returns to normal operating range, the UPS
returns to HE operation. For charging batteries in HE mode, the UPS will revert to normal mode to charge the
batteries, then return to HE mode when charge cycle is complete.
HE mode, if selected, is a normal operating mode, and not an alarm condition. While the UPS is in this mode,
the NORMAL light on the front display will illuminate.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

5-3

Understanding UPS Operation

5.2.4

Bypass Mode

CAUTION
The critical load is not protected from voltage or frequency fluctuations or power outages while
the UPS is in Bypass mode.
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The
UPS can also be transferred from Normal mode to Bypass mode manually. The bypass source supplies the
commercial AC power to the load directly. Figure 5-3 shows the path of electrical power through the UPS
system when operating in Bypass mode.
In Bypass mode, the output of the system is provided with three-phase AC power directly from the system
input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or
power outages from the source. Some power line filtering and spike protection is provided to the load but no
active power conditioning or battery support is available to the output of the system in the Bypass mode of
operation.
The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) continuous static switch, and
an optional backfeed protection contactor. The static switch is used instantaneously anytime the inverter is
unable to support the applied load. The continuous static switch is wired in series with the backfeed protection
contactor (if fitted), and together they are wired in parallel with the rectifier and inverter.
The static switch, being an electronically-controlled device, can be turned on immediately to pick up the load
from the inverter while inverter output contactor opens to isolate the inverter. The backfeed protection
contactor (if fitted) is normally closed, ready to support the static switch unless the bypass input source
becomes unavailable.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute
period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to
transfer.
Bypass Input

Bypass Switch (Optional Dual Input)

Static

Switch
Rectifier
Input

Input Switch
Rectifier

Output

Inverter

Input
Relay

Output
Relay
Battery
Converter

Switch

Battery

Relay

Relay

Main Power Flow


Trickle Current

Closed
Energised
Open

De-Energised
Battery

Figure 5-3. Path of Current Through the UPS in standard Bypass Mode

5-4

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Understanding UPS Operation

5.2.5

Battery Mode

The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does
not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the
inverter converts to AC power.
Figure 5-4 shows the path of electrical power through the UPS system when operating in Battery mode.

Bypass Input

Bypass Switch (Optional Dual Input)

Static

Switch
Rectifier
Input

Input Switch
Rectifier

Output

Inverter

Input
Relay

Output
Relay
Battery
Converter

Switch

Battery
Relay

Relay

Main Power Flow


Trickle Current

Closed
Energised
Open

De-Energised
Battery

Figure 5-4. Path of Current Through the UPS in standard Battery Mode
During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC
output voltage required to support the inverter. The input contactor opens and the battery instantaneously
supplies energy to the battery converter. The converter boosts the voltage so that the inverter can support the
customer's load without interruption. If bypass is common with the rectifier input, the backfeed protection
contactor also opens. The opening of the input and the optional backfeed protection contactors prevent
system voltages from bleeding backwards through the static switch and rectifier snubber components to the
utility source.
If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.
If at any time during the battery discharge the input power becomes available again, the input and the backfeed
protection contactors close and the rectifier begins to supply DC current to the converter and inverter. At this
point, the unit returns to Normal mode. Depending on the total load and the duration of the battery discharge,
battery current limit alarms may be seen for a short time due to the current required to recharge the battery.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

5-5

Understanding UPS Operation

5.3

Single UPS Unit System Oneline Configurations


The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply,
and basic maintenance bypass.
Voltage

5-6

Oneline Drawing

UPS Model

Input

Output

System Type

See Figure 5-5

See Tab 9-1 for


Model

380/400/415

380/400/415

Single Reverse Transfer UPS with External Battery

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Understanding UPS Operation


AC Input to
UPS Rectifier
4 Wire A-B-C
Rotation

Parallel CAN

AC Input to
Bypass 4 Wire
A-B-C Rotation

Pull Chain
Mini-Slot
Interface

Remote EPO

Interface Board
L1, L2,

L1, L2,

L3, N

L3, N
(Optional)
Backfeed Contactor

Input Switch

Static
Switch

Bypass Input Switch


(Optional Dual Input)

Fuse
Input
relay

Rectifier

Inverter

MBS

Output
relay

L1, L2,
L3, N

Fuse

Output Switch

AC Output to
Critical Load

Battery
relay

(OPTIONAL)

Battery Contactor

INTERNAL BATTERY
Fuse
disconnector
UPS
CABINET
C

Battery
Breaker
EXTERNAL BATTERY
NOTE Callout letters A,B,C, and D map to Table 3-5.

CABINET

Figure 5-5. UPS System Oneline (Dual Input)

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

5-7

Understanding UPS Operation

AC Input to
UPS Rectifier
4 Wire A-B-C
Rotation

Parallel CAN
Pull Chain
Mini-Slot
Interface

Remote EPO

A,B

Interface Board
L1, L2,
L3, N
(Optional)
Backfeed Contactor

Input Switch

Static
Switch

Fuse
Input
relay

Rectifier

Inverter

MBS

Output
relay
L1, L2,
L3, N
Fuse

Output Switch

AC Output to
Critical Load

Battery
relay

(OPTIONAL)

Battery Contactor

INTERNAL BATTERY

Fuse

Fuse
disconnector
UPS
CABINET
C

Battery
Breaker
NOTE Callout letters A,B,C, and D map to Table 3-5.

EXTERNAL BATTERY
CABINET

Figure 5-6. UPS System Oneline (Single Input)

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

5-8

Chapter 6

UPS Operating Instructions


This section describes how to operate the UPS.

6.1

NOTE 1

Before starting the UPS, ensure all installation tasks are complete and a preliminary
startup has been performed by authorised service personnel. The preliminary
startup verifies all electrical interconnections to ensure the installation was
successful and the system operates properly.

NOTE 2

Read this section of the manual and have thorough knowledge of UPS operation before
attempting to operate any of the controls.

UPS Controls and Indicators


The controls and indicators identified and described in this section are used to control and monitor UPS
operation. Figure6-1 shows the controls and indicators and Figure6-2 shows the UPS switches.

Control Panel

Door Latch

Figure 6-1. UPS Controls and Indicators

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-1

UPS Operating Instructions

Neutral Switch
Output Switch
Maintenance
Bypass Switch

Input Switch
Bypass Switch (Optional)

93E 15-40 kVA Dual Input


(Example for 30 kVA)

Input Switch
Bypass Switch (Optional)

Neutral Switch
Output Switch

Input Switch
Maintenance
Bypass Switch

93E 15-40 kVA Single Input


(Example for 30 kVA)

Output Switch
Maintenance
Bypass Switch

Output Switch
Maintenance
Bypass Switch

Input Switch
Bypass Switch
(Optional)

Neutral Switch

Neutral Switch

93E 60 kVA

93E 80 kVA
Figure 6-2. UPS Switches

6.1.1 Control Panel


The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the
UPS control panel functions, see paragraph6.2.

6-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating
Operating Instructions
Instructions
UPS
UPS Operating Instructions
UPS Operating Instructions
6.2
6.2
6.2
6.2

Using
Using the
the Control
Control Panel
Panel
Using the
Control
Panel
The
following
paragraphs
describe the
UPS control
panel, including
controls and
indicators, and
how to
monitor
The following
paragraphs
following
paragraphs describe
describe the
the UPS
UPS control
control panel,
panel, including
including controls
controls and
and indicators,
indicators, and
and how
how to
to monitor
monitor
Using theThe
Control
Panel
UPS
operation.
The
control
panel
(see
Figure
6-3)
is
located
on
the
front
door
of
the
UPS.
The
following
paragraphs
describe
the
UPS
control
panel,
including
controls
and
indicators,
and
how
to
monitor
UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS.
UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS.
UPSfollowing
operation.
The control
panelthe
(see
Figure
6-3)panel,
is located
on the
front and
doorindicators,
of the UPS.
The
paragraphs
describe
UPS
control
including
controls
and how to monitor
UPS operation. The control panel (see Figure6-3) is located on the front door of the UPS.

22
2
2

93E

33
3
3

11
1
Figure 6-3. UPS Control Panel
1

Figure
6-3. UPS
Control Panel
Figure
Figure 6-3.
6-3. UPS
UPS Control
Control Panel
Panel
Figure 6-3. UPS Control Panel
The
control
panel
consists
of:of:
The control
control panel consists
consists
The
The control panel
panel consists of:
of:
The
control
paneldisplay
consists
of:(1)

AAliquid
crystal
(LCD)
liquid crystal
display (LCD)
(1)
A
A liquid
liquid crystal
crystal display
display (LCD)
(LCD) (1)
(1)
A
liquid
crystal
display
(LCD)
(1)
Menu
navigation
pushbutton
switches
(2)
Menu
navigation
pushbutton
Menu navigation
navigation pushbutton
pushbutton switches
switches (2)
(2)
Menu
switches
(2)
AMenu
vertical
column
of
status
indicators
(3).
See
paragraph6.2.1.
navigation
pushbutton
switches
(2)
A vertical
vertical column of
of status indicators
indicators (3).
See
paragraph 6.2.1.
6.2.1.
A
A vertical column
column of status
status indicators (3).
(3). See
See paragraph
paragraph 6.2.1.
TheAfollowing
paragraphs
describe
using the
UPS
control
panel6.2.1.
to monitor the UPS. See paragraph6.3 for use
vertical
column
of
status
indicators
(3).
See
paragraph
The
following
paragraphs
describe
The
following
paragraphs
describe using
using the
the UPS
UPS control
control panel
panel to
to monitor
monitor the
the UPS.
UPS. See
See paragraph
paragraph 6.3
6.3 for
for use
use
The
paragraphs
using
the
UPS
control
panel
to
monitor
the
UPS.
See
paragraph
6.3
for
use
of
thefollowing
operational
controls. describe
of
the
operational
controls.
The
following
paragraphs
describe
using
the
UPS
control
panel
to
monitor
the
UPS.
See
paragraph
6.3
for use
of
of the
the operational
operational controls.
controls.
of thethe
operational
controls.
When
unit powers
up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main
When
the
unit
powers up,
the
screen
displays
the
Eaton logo
as
shown in
Figure 6-3.
To advance
to the
Main
When
the
unit
the
screen
displays
the
as
Menu
screen,up,
press
control
panel pushbutton
once.
Whenand
theMimic
unit powers
powers
up,
theany
screen
displays
the Eaton
Eaton logo
logo
as shown
shown in
in Figure
Figure 6-3.
6-3. To
To advance
advance to
to the
the Main
Main
Menu
and
Mimic
screen,
press
any
control
panel
pushbutton
once.
When
the
unit
powers
up,
the
screen
displays
the
Eaton
logo
as
shown
in
Figure
6-3.
To
advance
to
the
Main
Menu
Menu and
and Mimic
Mimic screen,
screen, press
press any
any control
control panel
panel pushbutton
pushbutton once.
once.
Menu
and
Mimic
screen,
press
any
control
panel
pushbutton
once.
6.2.1 Status Indicators
l
l
l
l
l
l
l
l
l
l
l

IInntt
eerrnn
aall

6.2.1
6.2.1

Status
Status Indicators
Indicators

The
four
symbols
on
the
side
ofof
the
control
panel
areare
status
indicators.
These
colored
lightlight
emitting
diodediode
6.2.1
Indicators
The
fourStatus
symbols
on
theright
right
side
the
control
panel
status
indicators.
These
colored
emitting
The
symbols
on
right
side
of
the
control
panel
are
status
These
colored
The four
four
symbols
on the
the
right
side
ofto
the
control
panel
are
status indicators.
indicators.
These
colored light
light emitting
emitting diode
diode
(LED)
lamps
work
with
the
alarm
horn
let
you
know
the
operating
status
of
the
UPS.
(LED)
lamps
workon
with
the
alarm
horn
to control
let you
you know
knoware
thestatus
operating
status These
of the
the UPS.
UPS. light emitting diode
The
four
symbols
thethe
right
sidehorn
of the
indicators.
(LED)
lamps
work
alarm
to
status
(LED)
lamps
work with
with
the
alarm
horn
to let
let you panel
know the
the operating
operating
status of
of the colored
UPS.
(LED) lamps
work withstatus
the alarm
horn to let you know the operating status of the UPS.
Table6-1
indicators.
Table
6-1describes
describesthe
the status
indicators.
Table
Table 6-1
6-1 describes
describes the
the status
status indicators.
indicators.
Table 6-1 describes the status indicators.
Table 6-1. Status Indicators
Table
6-1.
Status
Indicators
Table
Table 6-1.
6-1. Status
Status Indicators
Indicators
Description
TableIndicator
6-1. Status IndicatorsStatus
Indicator
Status
Description
Indicator
Status
Description
Indicator
Status
Description
Indicator
Status
Description
On
The
UPS
Normal
mode.
power
module
is
supplying
power
the
critical
On
The
UPS
is
in
Normal
mode.
The
power
module
is
power
to
the
load.
On
The
is is
in in
Normal
mode.
TheThe
power
module
is supplying
power
to theto
load. load.
On
TheUPS
UPS
is
in
Normal
mode.
The
power
module
is supplying
supplying
power
tocritical
the critical
critical
load.
On
The UPS is in Normal mode. The power module is supplying power to the critical load.

Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow

Red
Red
Red
Red
Red

Off
Off
Off
Off
Off
On
On
On
On
On

The
UPS
turned
The
is is
turned
off.off.
The
UPS
is
turned
off.
TheUPS
UPS
is
turned
off.
turned
off.
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is
a normal
condition
the
UPS,
the
Normal
indicator
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is a normal
condition
of theof
Normal
indicator
also also
The
mode.
Because
Battery
mode
is
condition
of
the
UPS,
the
indicator
also
The UPS
UPS is
is in
in Battery
Battery
mode.
Because
Battery
mode
is aa normal
normal
condition
ofUPS,
thethe
UPS,
the Normal
Normal
indicator
also
remains
illuminated.
remains
illuminated.
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is
a
normal
condition
of
the
UPS,
the
Normal
indicator
also
remains
illuminated.
remains illuminated.
remains illuminated.

On
On
On
On
On

The
UPS
Bypass
mode.
critical
is
supported
the
bypass
source.
The
Normal
indicator
not
The
is is
in in
Bypass
mode.
TheThe
critical
loadload
is supported
by theby
source.
The Normal
indicator
is not is
The
UPS
is
in
Bypass
mode.
The
critical
load
is
by
the
source.
The
indicator
is
TheUPS
UPS
is
in
Bypass
mode.
The
critical
load
is supported
supported
bybypass
the bypass
bypass
source.
The Normal
Normal
indicator
is not
not
illuminated
when
the
system
is
in
Bypass
mode.
illuminated
when
the
system
is
in
Bypass
mode.
The
UPS is inwhen
Bypass
load
is supported by the bypass source. The Normal indicator is not
illuminated
the
system
is
Bypass
mode.
illuminated
when
the mode.
systemThe
is in
incritical
Bypass
mode.
illuminated when the system is in Bypass mode.

On
On
On
On
On

The
UPS
has
anan
active
alarm
andand
requires
immediate
attention.
The LCD
the highest
prioritypriority
active alarms.
All
The
UPS
has
active
alarm
requires
immediate
attention.
The shows
LCD shows
the highest
active alarms.
The
The UPS
UPS has
has an
an active
active alarm
alarm and
and requires
requires immediate
immediate attention.
attention. The
The LCD
LCD shows
shows the
the highest
highest priority
priority active
active alarms.
alarms.
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
Alarm
All
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
The
UPS has
active alarmby
and
attention.
The LCD
the highest
activeonce.
alarms.
All alarms
alarms
areanaccompanied
accompanied
by
anrequires
audible immediate
horn. To
To silence
silence
the horn,
horn,
pressshows
any control
control
panelpriority
pushbutton
once.
The
All
are
an
audible
horn.
the
press
any
panel
pushbutton
The
indicator
may
be
illuminated
along
with
other
indicators.
Alarm
indicator
may
be
illuminated
along
with
other
indicators.
All
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
Alarm indicator
indicator may
may be
be illuminated
illuminated along
along with
with other
other indicators.
indicators.
Alarm
Alarm
may
be condition.
illuminated
with flashes
other
indicators.
There
is is
aindicator
new
UPS
alarm
Thealong
indicator
until until
acknowledged
by pressing
any control
panel panel
There
a
new
UPS
alarm
condition.
The
indicator
flashes
acknowledged
by
pressing
any
control
There
There is
is aa new
new UPS
UPS alarm
alarm condition.
condition. The
The indicator
indicator flashes
flashes until
until acknowledged
acknowledged by
by pressing
pressing any
any control
control panel
panel
pushbutton
pushbutton
once.
There is aonce.
new
UPS alarm condition. The indicator flashes until acknowledged by pressing any control panel
pushbutton
once.
pushbutton
once.
pushbutton once.

Flashing
Flashing
Flashing
Flashing
Flashing

nnllyy

Green
Green
Green
Green
Green

Eaton
9E UPS
(4060 kVA,
208/220V)
Installation
and
Operation Manual
P-164000058Rev
22
Eaton
kVA,
208/220V)
Installation
and
Manual
P-164000058Rev
Eaton 93E
UPS
(15-80 kVA,
380/400/415V)
Installation
and Operation
Manual
Eaton 9E
9E UPS
UPS (4060
(4060
kVA,
208/220V)
Installation
and Operation
Operation
Manual
P-164000058Rev
2
Eaton 9E UPS (4060 kVA, 208/220V) Installation and Operation Manual P-164000058Rev 2

6-3

6-3
6-3
6-3
6-3

UPS Operating Instructions

6.2.2 System Events


When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power.
In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change
from Normal mode. System events on the UPS can be indicated by horns, lights, messages, or all three.
Select the EVENTS symbol from the menu bar on the main menu screen to display the active events screen.
This screen shows any currently active alarms, notices, or commands. This screen shows any currently active
alarms, notices, orcommands. For more information on using the events screen, see paragraph6.2.6.
System Event Horns The system event horn beeps to alert an operator that an event needing attention is
taking place. The horn cycles at a half-second rate.
System Event Indicators The status indicators on the UPS control panel work with the event horn to let the
operator know when the UPS is operating in any mode other than normal. Only the Normal modeindicator is
illuminated during normal UPS system operation. The other indicators illuminate to indicate alarms or events.
When an alarm occurs, first check these indicators to see what type of event has taken place. For
descriptions of the status indicators, see paragraph6.2.1.
System Event Messages When a system event occurs, a message appears on the LCD in the UPS status
area. This message is also written to the Events Log and may be added to the History Log. The messages are
divided into four categories: alarms, notices, status, and commands.

6-4

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.2.3 Using the LCD and Pushbuttons


The LCD on the control panel provides an operator interface with the UPS system. Figure6-4 identifies the
display areas discussed in the following sections.

Alarm: Output AC Under Voltage

Meter

Events

History

Controls

Setup

Figure 6-4. Parts of the LCD


A

The UPS status area automatically scrolls between the Eaton model number, current date and time, active
alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while
scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible
horn. To silence the horn, press any control panel pushbutton once. Shown is a typical alarm message. For
more information about alarms and notices, see paragraph 6.2.2.

The information area contains data about UPS status and operations.

The menu bar shows the symbols of the available screens. To select a screen, highlight the screen symbol
using the navigation pushbuttons and then press the RETURN pushbutton.

The navigation pushbuttons function depending on the screen displayed. Use the Up, Down, Left, and
Right pushbuttons to scroll through available screens and the Esc and Enter pushbuttons to select menu
screens and functions.

You can use the LCD and the pushbuttons to:


Look at a log of UPS events (alarms, notices, and commands) (see paragraph6.2.6)
Monitor UPS operation (see paragraph6.2.6)
Set UPS parameters (see paragraph6.2.6)
Control UPS operation (see paragraphs6.2.6 and 6.2.7)
After approximately 10minutes, the display screen darkens. To restore the screen, press any pushbutton once.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-5

UPS Operating Instructions

6.2.4 Using the Menu


The UPS menu bar allows you to display data in the information area to help you monitor and control UPS
operation. Table6-2 shows the basic menu structure.
Table 6-2. Display Function Menu Map
Menu Option

Description

METERS

Displays performance meters for the system or critical load.

EVENTS

Displays the list of Active System Events.

HISTORY

Displays a historical log of system events.

CONTROLS
SETUP

ESC

Displays the System Control screen.


Allows you to set the date and time for the time stamp, set the display language, the unit name, and
meter subscripts, change the password, and view the firmware version numbers.
Returns to Main Menu and Mimic screen from the Meters, Events, History, Controls, or Setup
screens. Returns to the main System Setup Level screen from a setup submenu.
Return arrow acknowledges or executes a command, or saves a setting.
Up and down arrows scroll through screens and lists or highlight settings.
Left and right arrows select or adjust settings displayed on the screen.

6.2.5 Mimic Screen


Figure6-5 shows the Main Menu and Mimic screen. To select the Mimic screen from the Meters, Events,
History, Controls, or Setup screens, press the ESC pushbutton on the current menu bar.
The Mimic screen shows the internal components of the UPS cabinet and a real-time graphical representation
of the operating status of the system.

Figure 6-5. Main Menu and Mimic Screen

6-6

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.2.6 Display Menu Operation


Table6-3 describes the menu functions and how to use them.
Table 6-3. Display Menu Operation
Function

Subfunction

Meters UPS

The Meter screens show the UPS meter readings for the unit. The default voltage displayed on these
screens is phase-to-neutral. These can be changed to display the voltage phase-to-phase (AB,B-C,C-A). Use the LEFT or RIGHT arrow pushbuttons to select the METER symbol on the main menu
bar, to display the Meter screens. To scroll through the meter screens, press the UP or DOWN arrow
pushbutton. The current UPS readings are displayed in the information area of the screen.
Output UPS

The Output screen shows output voltage (phase to neutral), output current (each phase), and frequency
being supplied by the UPS, as well as the kVA, kW, and power factor measurements.

Input UPS

The Input screen shows input voltage (phase to neutral), input current (each phase), and frequency of
the incoming utility source, as well as the kVA, kW, and power factor measurements.

Bypass

The Bypass screen shows the bypass input voltage (phase to neutral), input current (each phase), and
frequency of the incoming utility source, as well as the kVA, kW, and power factor measurements.

Battery UPS

The Battery screen displays the battery voltage (Vdc) and the battery current (Idc).

Events

Use the LEFT or RIGHT arrow pushbuttons to select the EVENTS symbol on the main menu bar to display
the Events screens. A listing of all system events that are currently active is displayed. The most recent
event is listed first. As events clear, they are removed from the Events listing. To scroll through the
events, press the UP or DOWN arrow pushbutton.

History

Use the LEFT or RIGHT arrow pushbuttons to select the HISTORY symbol on the main menu bar to
display the History screen. The history Log lists up to 512 events in chronological order, with the most
recent event listed last (once 512 is reached, the earliest event is overwritten). The end of the log (the
most recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the UP or DOWN arrow pushbutton.

Setup User

Setup Config
(System Level 1 Setup)

Operation

Function Selection

This screen can be used to display user information and show the firmware versions installed. Use the
LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar to display the
Setup screen. Use the UP or DOWN arrow pushbutton to highlight the function desired, then press the
RETURN pushbutton to display the function screen. See Figure6-6 for a typical screen display.

User Info

The User Info screen provides the model, CTO and serial numbers of the UPS, the Output voltage,
frequency, and kVA rating, the input voltage rating, and the battery run time rating. Use the LEFT or
RIGHT arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow
pushbutton. to select Info, then press the RETURN pushbutton to display the function screen. To return
to the System Setup screen, press the ESC pushbutton.

About

The About screen provides the firmware version numbers installed on the UPS. Use the LEFT or RIGHT
arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow pushbutton. to
select About. To return to the System Setup screen, press the ESC pushbutton.
To enter a password if required, use the LEFT or RIGHT arrow pushbutton to select the password
character position. Use the UP or DOWN arrow pushbutton to change the password character. Once the
password is entered, select DONE and then press the RETURN pushbutton. The System Setup Level 1
menu screen is displayed. The default System Setup Level 1 password is 0101.

Password

Function Selection

This screen can be used to set the date and time, change the display language, enter a unit name,
change the meter style, perform lamp test, clear the history log, and enter a password to access Level1
functions. Use the LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar
to display the Setup screen. Use the LEFT or RIGHT arrow pushbutton to select CONFIG on the Setup
menu bar. Enter a password if required.

Clock

The Clock Setup screen allows the selection of either month/day/year or day/month/year formats and
daylight savings time for display on the screen and for logging events in the Event and History Logs. Use
the UP or DOWN arrow pushbutton to select CLOCK to display the Clock screen. Use the UP or DOWN
arrow pushbutton to highlight the desired format, then press the RETURN pushbutton to display the Set
Date and Time screen. To return to the System Setup screen, press the ESC pushbutton.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-7

UPS Operating Instructions

Table 6-3. Display Menu Operation


Function

Subfunction

Operation

Setup Config
(System Level 1 Setup)
(continued)

Set Date and Time


MM/DD/YYYY

The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in
the month/day/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.

Set Date and Time


DD/MM/YYYY

The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in
the day/month/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.

Language

The Language Setup screen allows the display menu language to be selected. Use the UP or DOWN
arrow pushbutton to highlight Language, then press the RETURN pushbutton to display the Language
screen. Use the UP or DOWN arrow pushbutton to highlight the desired language, then press the
RETURN pushbutton. To return to the System Setup screen, press the ESC pushbutton.

Unit Name

The Unit Name Setup screen allows a unit name to be entered. Use the UP or DOWN arrow pushbutton
to highlight Unit Name, then press the RETURN pushbutton to display the Unit Name screen. Use the
LEFT or RIGHT arrow pushbutton to highlight the character to be changed. Use the UP or DOWN arrow
pushbutton to make the change. When finished making changes, use the LEFT or RIGHT arrow
pushbutton to highlight SAVE and the UP or DOWN arrow pushbutton to select YES. To complete the
save function and return to the System Setup screen, select the RETURN arrow pushbutton. To return to
the System Setup screen, press the ESC pushbutton.

Meters

The Meters Setup screen allows the Meters Screen display style to be selected. Use the UP or DOWN
arrow pushbutton to highlight Meters, then press the RETURN pushbutton to display the Meters
screen. Use the UP or DOWN arrow pushbutton. to highlight the desired style, then press the RETURN
pushbutton. To return to the System Setup screen, press the ESC pushbutton.

Lamp Test

The Lamp Test screen allows the control panel status lamps to be tested. Use the UP or DOWN arrow
pushbutton to highlight Lamp Test, then press the RETURN pushbutton to illuminate the status lamps.
To return to the System Setup screen, press the ESC pushbutton.

Clear Log

The Clear Log screen allows the history log to be cleared. Use the UP or DOWN arrow pushbutton to
highlight Clear Log, then press the RETURN pushbutton to clear the log. To return to the System Setup
screen, press the ESC pushbutton.

P/W

The P/W screen is used to change the System Setup Level 1 password. Use the UP or DOWN arrow
pushbutton to highlight P/W, then press the RETURN pushbutton to display the P/W screen. Use the
LEFT or RIGHT arrow pushbutton to select the password character position. Use the UP or DOWN arrow
pushbutton to change the password character. Once the password is entered, select CHANGE and then
press the RETURN pushbutton.

Controls

6-8

See paragraph6.2.7 for details.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

Status: Load Off


Load Off

Normal

Load Off

Bypass

UPS

Battery

UPM

Figure 6-6. Typical Initial Setup Screen

6.2.7 System Controls


Select the CONTROLS symbol on the main menu bar, then press the RETURN pushbutton to display the
Controls screen. Normal operation, transfer to bypass, load off, and charger control commands are controlled
through this screen. In addition, the screen displays the current status of the UPS. Figure6-7 shows the
System Control screen.
Use the
or
pushbutton to highlight the command screen desired, then press the RETURN pushbutton to
display the command menu screen.
Use the

or

pushbutton to highlight the command desired.

Table6-4 describes the control functions and provides instructions to access and use the command menu
screens.
Table6-5 lists the typical System Status Screen Messages that are displayed during UPS operation.
For detailed information about using the System Controls, see paragraph 6.3.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-9

UPS Operating Instructions

Status: Load Off


Status:
Load Load
Off Off

Normal

Load Off

Bypass
Normal

HE:Enable
Load
Off

Bypass
Disable

UPS

Battery

UPM

UPS

Battery

UPM

Figure 6-7. Typical System Control Screen


Table 6-4. Command Menu Operation
Function

Subfunction

Operation

UPS Control
Commands

Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command or proceed to further command
screens.
Normal Mode

Starts the UPS in Standarad Normal mode or transfers the UPS to Standard Normal mode
from Bypass mode.

Bypass Mode

Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.

High-Efficiency (HE) Mode

Transfers the UPS from Standard Normal mode to HE mode.


Transfers the from HE mode to Standard Normal mode.

Battery Control
Commands

Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command.
Charger

Turns the battery charger on.

Resting

Turns the battery charger off.

Table 6-5. Typical System Status Messages

6-10

Function

Message

UPS

Load Off; Bypass; Online, HE

Bypass

Off; On; Available

Charger

Charger Resting; Charger

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.3

Single UPS Operation


NOTE

Note switch operation nomenclature: Open = O = Off, Closed = I = On.


Refer to the External Battery Cabinet Installation Manual for EBC battery breaker
location.

6.3.1 Starting the UPS in Standard Normal Mode (Default Mode)


To start the UPS system:
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure6-1).
2. Verify that the input and output switches are open.
3. Verify the bypass input switch is open (Dual Input).
4. Verify that the maintenance bypass switch is open and the Neutral Switch is closed.
5. Close the UPS input feeder circuit breaker.
6. If the UPSs are wired for dual input, close the UPS Bypass input feeder circuit breaker.
7. Close the input switch.
8. If the UPSs are wired for dual input, close the bypass input switch.
9. If the UPS contains an output switch, close the output switch.
10. Make sure MBS cover is installed.
11. Close the door and secure the latch.
12. Close the external battery breakers.
13. Observe the UPS control panel display becoming active, indicating logic power.
14. Verify no alarms are active.
15. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
16. If not already selected, select UPS on the System Control screen.
17. On the UPS System Control screen, select the LOAD OFF
RETURN pushbutton.

NORMAL command, then press the

18. If requested, enter the Level 1 password. Default password is 1111.


After entering password, UPS will transfer to bypass first and the Bypass LED will illuminate.
The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
Once the inverter reaches full voltage, the UPS output contactor closes and the static switch turns off.
Power is now supplied to the critical load in Standard Normal mode. It takes approximately one minute for
the UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-11

UPS Operating Instructions

6.3.2 Starting the UPS in Bypass Mode


If the inverter output of the UPS is not available and the critical load needs to be energised:

CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
To start the UPS system:
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure6-1).
2. Verify that the input and output switches are open.
3. Verify that the bypass input switch is open (Dual Input). .
4. Verify that the bypass switch is open and the Neutral Switch is closed.
5. Close the UPS input feeder circuit breaker.
6. If the UPSs are wired for dual input, close the UPS Bypass input feeder circuit breaker.
7. Close the input switch.
8. If the UPS contains two input sources, close the bypass input switch.
9. Close the output switch.
10. Make sure MBS cover is installed.
11. Close the door and secure the latch.
12. Close the external battery breakers.
13. Observe the UPS control panel display becoming active, indicating logic power.
14. Verify no alarms are active.
15. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
16. If not already selected, select UPS on the System Control screen.
17. On the UPS System Control screen, select the LOAD OFF
pushbutton.

BYPASS command, then press the RETURN

6.3.3 Transfer from Normal to Bypass Mode


To transfer the critical load to Bypass mode:

CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
pushbutton.

BYPASS command, then press the RETURN

The UPS transfers to Bypass mode.


The BYPASS status indicator is illuminated. The power module remains on.

6-12

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

WARNING
Power is present inside the UPS cabinet.

6.3.4 Transfer from Bypass to Normal Mode


To transfer the critical load to Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the BYPASS
pushbutton.

NORMAL command, then press the RETURN

The UPS transfers to Normal mode. If the power module is not available, the system remains on bypass
and an alarm sounds.
The NORMAL status indicator is illuminated.

6.3.5 Transfer from Standard Normal Mode to HE mode


To transfer the load to HE mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the HE: DISABLE
RETURN pushbutton.

ENABLE command, then press the

After battery is fully charged, the UPS transfers to HE mode if no abnormal power conditions are detected.
If abnormal power conditions are detected, the UPS will wait and transfer to HE mode when conditions are
cleared.
The NORMAL status indicator is illuminated.

6.3.6 Transfer from HE Mode to Standard Normal Mode


To transfer the load to Standard Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the HE: ENABLE
RETURN pushbutton.

DISABLE command, then press the

The UPS transfers to Standard Normal mode.


The NORMAL status indicator is illuminated.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-13

UPS Operating Instructions

6.3.7 Transfer from Normal Mode to Internal Maintenance Bypass


To transfer the load to maintenance bypass:
1. On the UPS System Control screen, select the NORMAL
pushbutton.

BYPASS command, then press the RETURN

2. Loosen the screws that fix the cover over the maintenance bypass switch. This action will signal the UPS
to transfer to static bypass. Refer to Figure 6-2 for switch arrangement.
3. Verify that the LCD/LED display indicates the UPS is in Bypass mode.
4. Close the Maintenance Bypass switch.
5. Open the Bypass Input and Output switches separately (Dual Input).
6. Loosen the screws that fix the cover over the Neutral switch (60-80 kVA), open the Neutral switch.
NOTE

The Neutral Switch should remain closed unless operated by a service technician.

Maintenance Bypass operate must be performed by an authorized Eaton Customer


Service Engineer.

WARNING
Power is present inside the UPS cabinet.

6.3.8 Transfer from Internal Maintenance Bypass to Normal Mode


To transfer the load to Normal mode:
1. Close the Neutral switch, slide the cover plate right and tighten the screws.
2. Close the Input and Bypass input switches.
3. Command the UPS to run in Bypass mode via the Control panel.
4. Verify that the LCD/LED display indicates the UPS is in Bypass mode.
5. Close the Output switch.
6. Open the Maintenance Bypass switch, slide the cover plate left and tighten the screws.
7. Command the UPS to transfer to Normal mode via the control panel.

6-14

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.3.9 UPS and Critical Load Shutdown


To perform maintenance or service on the critical load, shut down power to the load:
1. Turn off all equipment that is being powered by the UPS.
2. Perform the LOAD OFF procedure in paragraph6.3.12.
The output and bypass backfeed relay (if fitted) open, and the power module is turned off.
3. Perform the battery charger off procedure in paragraph 6.3.10.
The input and battery relay open.

WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
4. Open the UPS Input switch.
5. If the UPSs are wired for dual input, open the Bypass input switch.
6. Open the Maintenance Bypass switch.
7.

Open the UPS input and bypass feeder circuit breakers.

8. Open all external battery breakers.

6.3.10 Charger Control


To turn the battery charger on:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the RESTING
RETURN pushbutton.

CHARGING command, then press the

To turn the battery charger off:


1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the CHARGING
RETURN pushbutton.

RESTING command, then press the

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-15

UPS Operating Instructions

6.3.11 Battery Test


NOTE 1

This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.

NOTE 2

The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.

To start the battery test:


1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the RESTING
RETURN pushbutton.

TESTING command, then press the

6.3.12 Using the UPS LOAD OFF Command


A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls
the UPS output by powering down the UPS and de-energising the critical load.
The UPS (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. Select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
LOAD OFF or BYPASS
command depending on the UPS mode, then press the RETURN pushbutton.

LOAD OFF

The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.

CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4. Select Yes or No, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.

CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
5. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph6.3.1 or
6.3.2.

WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.

6-16

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.3.13 Using the Remote Emergency Power-off Switch


A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energises the critical load and powers down the UPS
immediately, without asking for verification.
The UPS, including Bypass, remains off until restarted.

CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE

The following instructions are for the Eaton-supplied REPO switch. If a customersupplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.

To use the REPO switch:


1. Firmly push the red pushbutton until it locks into place. The switch latches into the activated state.
The input, output, battery, and bypass backfeed contactors open, and the power module is turned off
immediately, without asking for verification.

CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases. To remove the key, rotate the key back to the vertical position.
3. Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-17

UPS Operating Instructions

6.4

Multiple UPS Parallel Operation


The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs.
NOTE 1
NOTE 2

Refer to the External Battery Cabinet Installation Manual listed in paragraph 1.8 for
EBC battery breaker location.
Start and control system wide function from UPS 1.

6.4.1 Starting the Parallel UPS in Standard Normal Mode (Default Mode)
To start the UPS system:
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure6-1).
2. Verify that all input breakers are open.
3. Verify that the maintenance bypass breakers are open.
4. Close all Module Output Breakers (MOBs).
5. Close all UPS input feeder circuit breakers.
6. If the UPSs are wired for dual input, close all of the UPSs Bypass input feeder circuit breakers.
7. Close all input breakers.
8. If the UPSs are wired for dual input, close all bypass input switches.
9. Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close all external battery breakers.
12. Observe the UPS control panel display becoming active, indicating logic power.
13. Verify no alarms are active.
14. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
15. If not already selected, select UPS on the System Control screen.
16. On the UPS System Control screen, select the LOAD OFF
RETURN pushbutton.

NORMAL command, then press the

17. If requested, enter the Level 1 password. Default password is 1111.


After entering password, UPS will transfer to bypass first and the Bypass LED will illuminate.
All rectifiers and inverters turn on. The inverters continue to ramp up to full voltage.
Once all inverters reach full voltage, the UPS output contactor closes and the static switch turns off. Power
is now supplied to the critical load in Standard Normal mode. It takes approximately one minute for the
UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.

6-18

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.4.2 Starting the Parallel UPS in Bypass Mode


If the inverter output of the parallel UPS is not available and the critical load needs to be energised:

CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure6-1).
2. Verify that all input breaker are open.
3. Verify that the Maintenance bypass switches are open.
4. Close all Module Output Breakers (MOBs).
5. Close all UPS input feeder circuit breakers.
6. If the UPSs are wired for dual input, close all of the UPS Bypass input feeder circuit breakers.
7. Close all input breakers.
8. If the UPSs are wired for dual input, close all of the bypass input switches.
9. Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close the external battery breakers.
11. Observe the UPS control panel display becoming active, indicating logic power.
12. Verify no alarms are active.
13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF
pushbutton.

BYPASS command, then press the RETURN

The critical load is immediately supplied by the bypass source, in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-19

UPS Operating Instructions

6.4.3 Transfer from Normal to Bypass Mode


To transfer the critical load to Bypass mode:

CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
pushbutton.

BYPASS command, then press the RETURN

All of the UPSs transfer to Bypass mode.


The BYPASS status indicator is illuminated. The power module remains on.

WARNING
Power is present inside the UPS cabinet.

6.4.4 Transfer from Bypass to Normal Mode


To transfer the critical load to Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the BYPASS
pushbutton.

NORMAL command, then press the RETURN

All of the UPSs transfer to Normal mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The NORMAL status indicator is illuminated.

WARNING
Power is present inside the UPS cabinet.

6-20

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Operating Instructions

6.4.5 Single UPS Shutdown


To shut down the UPS:
1. Open the MOB for the UPS being shut down.
2. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
3. If not already selected, select UPS on the System Control screen.
4. On the UPS System Control screen, select the NORMAL
pushbutton.

UPS OFF command, then press the RETURN

The output and bypass backfeed relay open, and the power module is turned off on the UPS being shut
down.
Logic power remains on.

WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
5. Open the UPS input and the bypass feeder circuit breakers for the UPS being shut down.
6. If EBCs are installed, open all battery breakers
The UPS is now completely shut down.

6.4.6 Single UPS Restart


To restart a single UPS from a shutdown state:
1. Close the MOB for the UPS being restarted.
2. Close the UPS input and bypass feeder circuit breakers for the UPS being restarted.
3. Close the input switch.
4. If the UPSs are wired for dual input, close the bypass input switch.
5. Close the output switch.
6. Close the external battery breakers.
7. On the UPS being restarted, observe the UPS control panel display becoming active, indicating logic
power.
8. Verify no alarms are active on the UPS being restarted.
9. On the UPS being restarted, select the CONTROLS symbol on the main menu bar. The System Control
screen is displayed.
10. If not already selected, select UPS on the System Control screen.
11. On the UPS System Control screen, select the UPS OFF
pushbutton.

NORMAL command, then press the RETURN

12. If requested, enter the Level 1 password. Default password is 1111.


The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
Once the inverter reaches full voltage, the UPS output contactor closes and the static switch turns off.
Power is now supplied to the critical load in Standard Normal mode along with the other UPSs online. It
takes approximately one minute for the UPS to achieve Standard Normal mode.
The Normal status indicator is illuminated.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-21

UPS Operating Instructions

6.4.7 UPS and Critical Load Shutdown


To perform maintenance or service on the critical load, shut down power to the load:
1. Turn off all equipment that is being powered by the UPS parallel system.
2. Transfer the UPSs to bypass by performing the procedure in paragraph 6.4.3.
3. Perform the LOAD OFF procedure in paragraph6.4.10.
The output and bypass backfeed contactors open, and the power module is turned off.
4. Perform the battery charger off procedure in paragraph 6.4.8 for each UPS.
The input and battery relay open.

WARNING
Power is present inside the UPS cabinets after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
5. Open all input switches.
6. Open all of the maintenance bypass switches.
7.

Open the output switch.

8. Open all of the MOBs.


9. Open all of the UPSs input and bypass feeder circuit breakers.
10. Open all external battery breakers

6.4.8 Charger Control


To turn an individual UPS battery charger on:
1. Select the CONTROLS symbol on the main menu bar on the UPS requiring the charger to be turned on. The
System Control screen is displayed.
2. Select Battery on the System Control screen
3. On the Battery System Control screen, select the RESTING
RETURN pushbutton.

CHARGING command, then press the

To turn an individual UPS battery charger off:


1. Select the CONTROLS symbol on the main menu bar on the UPS requiring the charger to be turned off. The
System Control screen is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the CHARGING
RETURN pushbutton.

6-22

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

RESTING command, then press the

UPS Operating Instructions

6.4.9 Battery Test


NOTE 1

This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.

NOTE 2

The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.

To start an individual UPS battery test:


1. Select the CONTROLS symbol on the main menu bar on the UPS to be tested. The System Control screen
is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the RESTING
RETURN pushbutton.

TESTING command, then press the

6.4.10 Using the UPS LOAD OFF Command


A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls
the UPSs output by powering down the UPS and de-energising the critical load.
The UPSs (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1. Select the CONTROLS symbol on the main menu bar on the UPS to be shut down. The System Control
screen is displayed.
2. Select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
LOAD OFF or BYPASS
command depending on the UPS mode, then press the RETURN pushbutton.

LOAD OFF

The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.

CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4. Select Yes or no, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.
5. If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step 4.

CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
6. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph6.4.1 or
6.4.2.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

6-23

UPS Operating Instructions

WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.

6.4.11 Using the Remote Emergency Power-off Switch


A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energises the critical load and powers down the UPS
immediately, without asking for verification.
The UPSs, including Bypass, remains off until restarted.

CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE

The following instructions are for the Eaton-supplied REPO switch. If a customersupplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.

To use the REPO switch:


1. Firmly push the red pushbutton until it locks into place. The switch latches into the activated state .
The input, output, battery, and optional bypass backfeed contactors open, and the power module is turned
off immediately, without asking for verification.

CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases. To remove the key, rotate the key back to the vertical position.
3. Restart the UPS by following the procedure in paragraph 6.4.1 or 6.4.2.

WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.

6-24

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 7 Communication
Chapter 7 Communication

7.1

This chapter describes the communication features of theEaton 93E UPS. For terminal wiring information, see
This chapter
describes theFor
communication
ofinterface
the Eaton
9E UPS.
For terminal
information, see
paragraph3.2.3
and paragraph4.4.
location of thefeatures
customer
panel
and terminals,
seewiring
Figure4-6
paragraph
3.2.3 and paragraph 4.11. For location of the customer interface panel and terminals, see Figure 4-10
and Figure4-7
.
and Figure 4-11.

Mini-Slot Cards
7.1
Mini-Slot Cards

The Eaton 93E UPS has two standard, factory-installed Mini-Slot communication bays. See Figure4-7 for bay
UPS has with
two standard,
factory-installed
Mini-Slot
communication bays. See Figure 4-10 for bay
locations.The
The Eaton
UPS is9E
compatible
the following
Mini-Slot cards
(see Figure7-1):
locations. The UPS is compatible with the following Mini-Slot cards (see Figure 7-1):
Network Management Card and Modbus/Jbus provides remote monitoring through a Web browser
Management
Card and Modbus/Jbus
provides
remote
monitoring
a Web browser
interface,Network
e-mail, and
a network management
system (NMS)
using SNMP
and
connects through
to a twisted-pair
interface, e-mail,
and a network
system
(NMS) using
SNMP
and connects
to and
a twisted-pair
Ethernet (10/100BaseT)
network.
The card management
also provides direct
integration
of UPS
information
(meters
The card
also
integration of UPS information (meters and
status) to Ethernet
a Building(10/100BaseT)
Managementnetwork.
System (BMS)
using
theprovides
Modbusdirect
RTU protocol.
status) to a Building Management System (BMS) using the Modbus RTU protocol.
Network Management Card provides remote monitoring through a Web browser interface, e-mail, and a
Network Management
Cardusing
provides
monitoring
a Web
browser
interface, e-mail, and a
network management
system (NMS)
SNMPremote
and connects
to a through
twisted-pair
Ethernet
(10/100BaseT)
network. network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network.
Management Card Contact and RS232 / Serial two types of interfaces via a DB9 connector are available
Management
Card
Contact
and RS232
/ Serial
two types
of interfaces
DB9
connector
with this card.
Dry contact
mode
provides
a simple
way to transmit
UPS
informationvia
toaan
alarm
system,are available
with
this
card.
Dry
contact
mode
provides
a
simple
way
to
transmit
UPS
information
to
system,
PLC, or computer system via dry relay contacts. The transmitted information is load powered, load an
on alarm
bypass,
PLC, or
computer
system
dry and
relaylow
contacts.
transmitted
information
is load
powered,
load on battery,
load
on utility,
batteryvia
fault,
battery.The
RS232
mode provides
an RS232
interface
for load on
bypass,
ona battery,
load on
utility,
battery
fault,are
and
lowto
battery.
mode (contacts
provides an
connection
to a PCload
or to
UPS Control
display
unit.
Jumpers
used
select RS232
the interface
or RS232
RS232). interface for connection to a PC or to a UPS Control display unit. Jumpers are used to select the interface
(contacts or RS232).
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.
For installation and setup of a Mini-Slot card, contact an Eaton service representative (see paragraph1.8). Refer
For installation
and setup
of a Mini-Slot
an Eaton service representative (see paragraph 1.8). Refer
to the manual
supplied withthe
Mini-Slot
card forcard,
usercontact
instructions.
to the manual supplied with the Mini-Slot card for user instructions.
l

Management Card Contact and


Management
RS232/Serial Card Contact and
RS232/Serial

Network Management Card

NetworkManagement
ManagementCard
Cardand
and
Network
Modbus/Jbus
Modbus/Jbus

Figure 7-1. Optional Mini-Slot Cards


Figure 7-1. Optional Mini-Slot Cards

7.2

7.2
Building Alarm Monitoring
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or

overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
This standard
lets you
connect
thealarm
UPS to
yourand
building
alarms, such as smoke detectors or
Use feature
twisted-pair
wires
for each
input
common.
overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
Use twisted-pair
wiresalarms
for each
alarm
input and common.
The building
can
be programmed
to display the alarm functional name.

Fo

The building alarms can be programmed to display the alarm functional name.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Eaton 9E UPS (4060 kVA, 208/220V) Installation and Operation Manual P-164000058Rev 2

7-1
7-1

Communication

This page intentionally left blank.

7-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 8

UPS Maintenance
The components inside the UPS cabinet are secured to a sturdy metal frame. Allrepairable parts and
assemblies are located for easy removal, with very little disassembly. This design allows authorised service
personnel to perform routine maintenance and servicing quickly.
You must schedule periodic performance checks of your UPS system to keep it running properly. Regular
routine checks of operation and system parameters enable your system to function efficiently for many troublefree years.

8.1

Important Safety Instructions


Remember that your UPS system is designed to supply power EVEN WHEN DISCONNECTED FROM THE
UTILITY POWER. The UPS module interiors are unsafe until the DC power source is disconnected and the
electrolytic capacitors are discharged. After disconnecting the utility power and the DC power, authorised
service personnel should wait at least five minutes for capacitor bleedoff before attempting internal access to
the UPS module.

WARNING
Servicing and maintenance should be performed by qualified service personnel only.
LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open or
protective panels removed. Do not make any assumptions about the electrical state of any
cabinet in the UPS system.
Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE
BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect
that a battery string needs service, contact an Eaton service representative.
If the string requires service contact an Eaton service representative.
Observe these precautions when working on or around batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the charging source prior to connecting or disconnecting terminals.
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any
part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such
grounds are removed during installation and maintenance.
When replacing batteries, use the same number of sealed, lead-acid batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

8-1

UPS Maintenance

8.2

Performing Preventative Maintenance


The UPS system requires very little preventative maintenance. However, the system should be inspected
periodically to verify that the units are operating normally and that the batteries are in good condition.

8.2.1 DAILY Maintenance


Perform the following steps daily:
1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2. Ensure the air intakes (vents on the front door of the UPS cabinet and the exhaust openings (on the rear of
the UPS cabinet) are not blocked.
3. Ensure the operating environment is within the parameters specified in paragraph3.2.1 and Chapter9,
Product Specifications.
4. Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated
or the Normal status indicator is not illuminated, contact an Eaton service representative.

8.2.2 MONTHLY Maintenance


Perform the following steps monthly:
1. Monitor system parameters as described in paragraph6.2, Using the Control Panel.
2. Check the UPS air filters (located behind the front door) and wash or replace as necessary. See Figure8-1
for filter location. Contact an Eaton service representative for replacement filters. To remove the filters:

CAUTION
Verify washed filter is thoroughly dry before reinstalling.
a. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise)
and swing the door open (see Figure6-1).
b. Remove the upper and lower foam filters from the frame on the front door.
c. Replace the washed or new foam filters into the frame on the front door.
d. Close the front door and secure the latch.
3. Record maintenance results and any corrective actions in a suitable log.

8-2

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

UPS Maintenance

Filters

Figure 8-1. Air Filter Location

8.2.3 PERIODIC Maintenance


Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to the compression lug connections.
Maintenance procedures should specify that the compression lug connections be retorqued to values listed in
this manual.

8.2.4 ANNUAL Maintenance


Annual preventive maintenance should be performed only by authorised service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.

8.2.5 BATTERY Maintenance


Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance
should be performed only by authorised service personnel.

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

8-3

UPS Maintenance

8.3

Installing Batteries
NOTE There is no manual DC disconnect device within the UPS.
Install batteries in accordance with the battery and battery system manufacturer's instructions.

8.4

Recycling the Used Battery or UPS


Contact your local recycling or hazardous waste centre for information on proper disposal of the used battery or
UPS.

WARNING
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of
batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
A battery can cause electrical shock, burn from high short-circuit current, or fire. Observe proper
precautions.

ATTENTION!
Une batterie peut prsenter un risque de choc lectrique, de brulure, ou d'incendie. Suivre les
prcautions qui s'imposent.
Pour le remplacement, utiliser le mme nombre et modle des batteries.
L'limination des batteries est rglemente. Consulter les codes locaux cet effet.

CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste centre.

CAUTION
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste centre.

8.5

Maintenance Training
A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the
UPS system operation and teaches you how to perform first level corrective maintenance. For more
information about training and other services, contact the Help Desk (see paragraph 1.8).

8-4

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

Chapter 9

Product Specifications

9.1 Model Numbers


The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50or60 Hz with various output power ratings.
Models

Power Rating

Frequency

description

93E-15UI-N-649Ah-MBS

15 kVA

50/60 Hz

N- Normal type with single feed

93E-15UI-N-0-MBS

15 kVA

50/60 Hz

I- Internal battery can be selected

93E-15U-N-MBS

15 kVA

50/60 Hz

0-without battery for internal battery type

93E-15UT-N-MBS

15 kVA

50/60 Hz

T-Transformer UPS

93E-20I-N-649Ah-MBS

20 kVA

50/60 Hz

MBS-with internal MBS

93E-20I-N-0-MBS

20 kVA

50/60 Hz

U-upgradable

93E-20-N-MBS

20 kVA

50/60 Hz

93E-20T-N-MBS

20 kVA

50/60 Hz

93E-30I-N-969Ah-MBS

30 kVA

50/60 Hz

93E-30I-N-0-MBS

30 kVA

50/60 Hz

93E-30-N-MBS

30 kVA

50/60 Hz

93E-30T-N-MBS

30 kVA

50/60 Hz

93E-40I-N-1289Ah-MBS

40 kVA

50/60 Hz

93E-40I-N-0-MBS

40 kVA

50/60 Hz

93E-40-N-MBS

40 kVA

50/60 Hz

93E-40T-N-MBS

40 kVA

50/60 Hz

93E-60-N-MBS

60 kVA

50/60 Hz

93E-60T-N-MBS

60 kVA

50/60 Hz

93E-80-N-MBS

80 kVA

50/60 Hz

93E-80T-N-MBS

80 kVA

50/60 Hz

9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.

9.2.1 UPS Environmental


Operating Temperature

UPS: 0 to 40C (32 to 104F) without derating. The recommended operating


temperature is25C(77F).
Battery: 525C

Operating Altitude

Maximum 1000m (3300 ft) at 30C without derating

Storage Temperature

-15 to +55C, excluding batteries (prolonged storage above 40C causes


rapid battery self-discharge)

Relative Humidity (operating and storage)

5% to 95% maximum noncondensing


55 dB (15-20 kVA)

Acoustical Noise

62 dB (30-40 kVA)
65 dB (60-80 kVA)

at a 1m distance, per ISO 7779

EMC

Meets IEC 62040-2 2005 C3

Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual

9-1

Product Specifications

9.2.2 UPS Input


Operating Input Voltage
Input Voltage Range

380/400/415 Vac
190/330276/478V (-15%, +20%) at 100% load
116/201-276/478V (-50%, +20%) at 50% load

Operating Input Frequency Range

50/60 Hz

Input Frequency Range

40-72Hz

Operating Input Current

See Table3-5.
Adjustable

Input Current Harmonic Content

5% THD at full load

Power Factor

Minimum 0.99

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4

Battery Voltage

384 Vdc Installed


432 Vdc External
5.3A maximum at any load up to100% load for 15 kVA UPS
5.3A maximum at any load up to100% load for 20 kVA UPS

Battery Charging Capacity (384 Vdc)

8A maximum at any load up to100% load for 30 kVA UPS


10.6A maximum at any load up to100% load for 40 kVA UPS
16A maximum at any load up to100% load for 60 kVA UPS
24A maximum at any load up to100% load for 80 kVA UPS

9.2.3 UPS Output


UPS Output Capacity

100% rated current

Output Voltage Regulation

1% (10% to 100% load)

Nominal Output Voltage

380 Vac, 400 Vac and 415 Vac nominal

Output Voltage Harmonic Content

2% maximum THD (linear load)


5% maximum THD (nonlinear load)

Output Current

See Table3-5.

Output Voltage Balance

< 2% for 100% maximum load imbalance (linearload)

Output Voltage Phase Displacement < 2.5 for 100% maximum load imbalance (linear load)
Frequency Regulation

0.1 Hz free running

Synchronous to Bypass

4 Hz (default setting)

Frequency Slew Rate

3 Hz per second (default setting)

Load Compatibility

0.9 PF Leading
0.7 PF Lagging
110% for 60 minutes

Overload Capability

125% for 10 minutes


150 % for 1 minutes
150% for 500 milliseconds

9-2