Eaton 93E-15-80 KVA Manual
Eaton 93E-15-80 KVA Manual
Eaton 93E-15-80 KVA Manual
Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
SECTION 1Installation
3 UPS Installation Plan and Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1
3.2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Table of Contents
SECTION 2Operation
5 Understanding UPS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1
5.2
ii
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Table of Contents
7 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1
7.2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
iii
Table of Contents
iv
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
List of Figures
Figure 1-1.
Figure 3-1.
Figure 3-2.
Figure 3-3.
Figure 3-4.
Figure 3-5.
Figure 3-6.
Figure 3-7.
Figure 3-8.
Figure 3-9.
Figure 3-10.
Figure 3-11.
Figure 4-1.
Figure 4-2.
Figure 4-3.
Figure 4-4.
Figure 4-5.
Figure 4-6.
Figure 4-7.
Figure 4-8.
Figure 4-9.
Figure 4-10.
Figure 4-11.
Figure 4-12.
Figure 4-13.
Figure 4-14.
Figure 4-15.
Figure 5-1.
Figure 5-2.
Figure 5-3.
Figure 5-4.
Figure 5-5.
Figure 5-6.
Figure 6-1.
Figure 6-2.
Figure 6-3.
Figure 6-4.
Figure 6-5.
Figure 6-6.
Figure 6-7.
Figure 7-1.
Figure 8-1.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
List of Figures
vi
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
List of Tables
Table 3-1.
Table 3-2.
Table 3-3.
Table 3-4.
Table 3-5.
Table 3-6.
Table 3-7.
Table 3-8.
Table 3-9.
Table 4-1.
Table 4-2.
Table 4-3.
Table 4-4.
Table 4-5.
Table 6-1.
Table 6-2.
Table 6-3.
Table 6-4.
Table 6-5.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-2
3-3
3-3
3-4
3-17
3-18
3-19
3-19
3-20
4-9
4-11
4-14
4-15
4-16
6-3
6-6
6-7
6-10
6-10
vii
List of Tables
viii
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 1
Introduction
The Eaton93E 15-80 kVA uninterruptible power supply (UPS) is a true online, continuous-duty, transformerfree, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible AC power
to protect the customer's load from power failures.
The Eaton 93E 15-80 kVA online power protection system is used to prevent loss of valuable electronic
information, minimise equipment downtime, and minimise the adverse effect on production equipment due to
unexpected power problems.
The Eaton 93E 15-80 kVA UPS continually monitors incoming electrical power and removes the surges, spikes,
sags, and other irregularities that are inherent in commercial utility power. Working with a building's electrical
system, the UPS system supplies clean, consistent power that sensitive electronic equipment requires for
reliable operation. During brownouts, blackouts, and other power interruptions, batteries provide emergency
power to safeguard operation.
The UPS is housed in a single free-standing cabinet, with safety shields behind the door for hazardous voltage
protection.
This manual is for 93E series UPS, refer to Table 9-1 for product models.
Figure1-1 shows the Eaton 93E 15-80 kVA UPS.
NOTE 1
Startup may be performed by the customers qualified electrical contractor for single (not
parallel) UPS installations without any accessory cabinets.
NOTE 2
Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Eaton Customer Service Engineer, or the
warranty terms may become void. This service is offered as part of the sales contract for
the UPS. Contact an Eaton service representative in advance (usually a two-week notice
is required) to reserve a preferred startup date.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
1-1
Introduction
1.1
Building Alarm Monitoring Up to three inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See Chapter 7,
Communication, for additional information.
Mini-Slot Communication Bays Two communication bays are standard equipment. One to two optional
Mini-Slot connectivity cards can be installed in the UPS module at any time. Mini-Slot cards are quickly
installed at the front (behind door) of the UPS and are hot-pluggable. See Chapter 7, Communication, for
additional information.
1-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Introduction
1.2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
1-3
Introduction
1.3
Battery System
Dependant on UPS model, the battery system may be internal or external. The battery system provides
emergency short-term backup power to safeguard operation during brownouts, blackouts, and other power
interruptions. The battery system is equipped with lead-acid batteries.
1.4
The UPS system configuration can be enhanced by adding optional accessories such as a
Remote Emergency Power-off (REPO) control or Mini-Slot communication cards.
1.5
1.6
Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
Italic type highlights notes and new terms where they are defined.
Description
Note
[Keys]
Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system
refers to the entire power protection systemthe UPS cabinet, an external battery system, and options or
accessories installed.
1-4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Introduction
1.7
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric
shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for
additional information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in
the trash. This product contains sealed, lead-acid batteries and must be disposed of
properly. For more information, contact your local recycling/reuse or hazardous waste
centre.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse
or hazardous waste centre.
1.8
1.9
Getting Help
If help is needed with any of the following:
Scheduling initial startup
Regional locations and telephone numbers
A question about any of the information in this manual
A question this manual does not answer
Please call your local service representative.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
1-5
Introduction
1-6
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 2
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries. Read all instructions before operating the equipment and
save this manual for future reference.
The UPS is designed for industrial or computer room applications, and contains safety shields
behind the door and front panels. However, the UPS is a sophisticated power system and should be
handled with appropriate care.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORISED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the
UPS.
WARNING
The UPS is suitable for mounting on concrete or other non-combustible surfaces only.
The UPS is powered by its own energy source (batteries). The output terminals may carry live
voltage even when the UPS is disconnected from an AC source.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40C (104F). Do not operate near water or excessive humidity (95% maximum). The
system is not intended for outdoor use.
As a result of the connected loads high leakage current is possible. Connection to earth ground is
required for safety and proper product operation. Do not check UPS operation by any action that
includes removal of the earth (ground) connection with loads attached.
Ensure all power is disconnected before performing installation or service.
Batteries can present a risk of electrical shock or burn from high short-circuits current. The
following precautions should be observed: 1) Remove watches, rings, or other metal objects;
2) Use tools with insulated handles; 3) Do not lay tools or metal parts on top of batteries; 4) Wear
rubber gloves and boots.
ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors.
Attempting to alter wiring can cause injury.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
toxic.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.
CAUTION
Installation or servicing should be performed by qualified service personnel knowledgeable of
UPS and battery systems, and required precautions. Keep unauthorised personnel away from
equipment. Consider all warnings, cautions, and notes before installing or servicing equipment.
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
2-1
Safety Warnings
AVERTISSEMENT!
Les batteries peuvent prsenter un risque de dcharge lectrique ou de brlure par des courts
circuits de haute intensit. Prendre les prcautions ncessaires.
Pour le replacement, utiliser le mme nombre et modle des batteries.
ATTENTION!
Une mise au rebut rglementaire des batteries est obligatoire. Consulter les rglements en
vigueur dans votre localit.
Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser.
CE marking
The product has the CE marking in compliance with the following European directives:
LVD Directive (Safety)
2006/95/EEC
EMC Directive
2004/108/EEC
CAUTION
This product is designed for commercial and industrial applications. In a residential environment, the
product may cause radio interference, in which the user may be required to take additional measures.
2-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Section 1
Installation
Chapter 3
Startup and operational checks for parallel systems or installations with accessory
cabinets must be performed by an authorised Eaton Customer Service Engineer, or the
warranty terms may become void. This service is offered as part of the sales contract for
the UPS. Contact an Eaton service representative in advance (usually a two-week notice
is required) to reserve a preferred startup date.
CAUTION
It must be ensured that no line input source can accidentally be connected to the UPS during installation.
WARNING
3.1
Installation may only be carried out by qualified technicians and in conformity with the applicable
safety standards.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.
3.2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-1
Shipping
Installed
kg (lb.)
Point Loading
93E-15UI-N-649Ah-MBS
272 (599)
285 (627)
93E-15UI-N-0-MBS
102 (225)
120 (264)
93E-15U-N-MBS
72 (159)
85 (187)
93E-15UT-N-MBS
220 (484)
233 (513)
93E-20I-N-649Ah-MBS
272 (599)
285 (627)
93E-20I-N-0-MBS
102 (225)
120 (264)
93E-20-N-MBS
72 (159)
85 (187)
93E-20T-N-MBS
220 (484)
233 (513)
93E-30I-N-969Ah-MBS
376 (828)
391 (861)
93E-30I-N-0-MBS
128 (283)
147 (325)
93E-30-N-MBS
88 (194)
105 (231)
93E-30T-N-MBS
245 (539)
279 (614)
490 (1078)
507 (1116)
93E-40I-N-0-MBS
165 (364)
187 (413)
93E-40-N-MBS
120 (264)
137 (302)
93E-40T-N-MBS
328 (722)
345 (759)
93E-60-N-MBS
202 (445)
241 (531)
93E-60T-N-MBS
532 (1171)
571 (1257)
93E-80-N-MBS
245 (539)
285 (614)
93E-80T-N-MBS
575 (1265)
615 (1353)
93E-40I-N-1289Ah-MBS
3-2
Weight
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the back of the cabinet. Allow clearance in front of and in back of the cabinet
for proper air circulation. The clearances required around the UPS cabinet are shown in Table3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
15kVA/20kVA/30kVA/40kVA
L1(mm)
L2(mm)
120
60kVA/80kVA
L1(mm)
150
50
150
L2(mm)
50
200
Notes:
L1- clearance to the rear wall.
L2- clearance between the adjacent paralleled UPS or UPS and adjacent PDU. Parallel UPS should be as
close as possible.
Some models that feature rear connections also require additional rear clearance to enable installation and
connection.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-3
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table3-4.
Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation
3-4
Model
Model
Heat Rejection
BTU/hr x1000 (kg-cal/hr)
93E-15UI-N-649Ah-MBS
15 kVA
862
93E-15UI-N-0-MBS
15 kVA
862
93E-15U-N-MBS
15 kVA
862
93E-15UT-N-MBS
15 kVA
1306
93E-20I-N-649Ah-MBS
20 kVA
1149
93E-20I-N-0-MBS
20 kVA
1149
93E-20-N-MBS
20 kVA
1149
93E-20T-N-MBS
20 kVA
1743
93E-30I-N-969Ah-MBS
30 kVA
1723
93E-30I-N-0-MBS
30 kVA
1723
93E-30-N-MBS
30 kVA
1723
93E-30T-N-MBS
30 kVA
2612
93E-40I-N-1289Ah-MBS
40 kVA
2298
93E-40I-N-0-MBS
40 kVA
2298
93E-40-N-MBS
40 kVA
2298
93E-40T-N-MBS
40 kVA
3482
93E-60-N-MBS
60 kVA
3447
93E-60T-N-MBS
60 kVA
5224
93E-80-N-MBS
80 kVA
4596
93E-80T-N-MBS
80 kVA
6965
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
960 (37.8)
500 (19.69)
FRONT VIEW
706 (27.8)
RIGHT VIEW
REAR VIEW
960 (37.8)
93E-15U / 93E-20
500 (19.69)
FRONT VIEW
706 (27.8)
REAR VIEW
RIGHT VIEW
Figure 3-1. UPS Cabinet Dimensions (93E 15-20 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-5
1230
1230 (48.43)
(48.43)
500(19.69)
(19.69)
500
FRONT VIEW
706(27.8)
(27.8)
706
RIGHT VIEW
REAR VIEW
1230 (48.43)
93E-30
500 (19.69)
FRONT VIEW
706 (27.8)
RIGHT VIEW
REAR VIEW
93E-30I / 93E-30T
Figure 3-2. UPS Cabinet Dimensions (93E 30 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]
3-6
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
1500 (59.06)
93E-40
500 (19.69)
RIGHT VIEW
REAR VIEW
1500 (59.06)
FRONT VIEW
706 (27.8)
93E-40I / 93E-40T
500 (19.69)
706 (27.8)
FRONT VIEW
RIGHT VIEW
REAR VIEW
Figure 3-3. UPS Cabinet Dimensions (93E 40 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-7
1876 (73.9)
93E-60 / 93E-60T
600 (23.62)
RIGHT VIEW
REAR VIEW
1876 (73.9)
FRONT VIEW
796 (31.34)
93E-80 / 93E-80T
600 (23.62)
FRONT VIEW
796 (31.34)
RIGHT VIEW
REAR VIEW
Figure 3-4. UPS Cabinet Dimensions (93E 60-80 kVA Front and Right Side Views)
Dimensions are in millimetres [inches]
3-8
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
706 (27.8)
FRONT
FRONT
500 (19.69)
TOP VIEW
BOTTOM VIEW
706 (27.8)
FRONT
FRONT
500 (19.69)
TOP VIEW
BOTTOM VIEW
796 (31.34)
FRONT
FRONT
600 (23.62)
TOP VIEW
BOTTOM VIEW
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-9
611.5 (24.07)
611.5 (24.07)
611.5 (24.07)
960 (37.8)
611.5 (24.07)
960 (37.8)
353 (13.9)
353 (13.9)
250 (9.84)
250 (9.84)
706 (27.8)
706 (27.8)
500 (19.69)
500 (19.69)
FRONT VIEW
RIGHT VIEW
361.5 (14.23)
361.5 (14.23)
960 (37.8)
93E-15U / 93E-20
353 (13.9)
250 (9.84)
500 (19.69)
706 (27.8)
FRONT VIEW
RIGHT VIEW
3-10
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
765 (30.12)
765 (30.12)
1230 (48.43)
353 (13.9)
250 (9.84)
500 (19.69)
RIGHT VIEW
93E-30
445 (17.52)
445 (17.52)
1230 (48.43)
FRONT VIEW
706 (27.8)
500
250 (9.84)
353 (13.9)
500 (19.69)
706 (27.8)
FRONT VIEW
RIGHT VIEW
93E-30I / 93E-30T
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-11
93E-40
930 (36.61)
930 (36.61)
1500 (59.06)
500
250 (9.84)
353 (13.9)
500 (19.69)
706 (27.8)
FRONT VIEW
1500 (59.06)
RIGHT VIEW
550 (21.65)
550 (21.65)
93E-40I / 93E-40T
250 (9.84)
353 (13.9)
500 (19.69)
FRONT VIEW
706 (27.8)
RIGHT VIEW
3-12
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
1876
1876 (73.9)
(73.9)
970(36.22)
(38.19)
920
920
970(36.22)
(38.19)
93E-60
300 (11.81)
300 (11.81)
600(23.62)
(23.62)
600
796(31.34)
(31.34)
796
RIGHT VIEW
1876 (73.9)
FRONT VIEW
920 (36.22)
920 (36.22)
93E-60T
300 (11.81)
300 (11.81)
600 (23.62)
796 (31.34)
FRONT VIEW
RIGHT VIEW
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-13
1876 (73.9)
1020 (40.16)
1020 (40.16)
93E-80
600
300 (11.81)
300 (11.81)
600 (23.62)
796 (31.34)
RIGHT VIEW
1876 (73.9)
FRONT VIEW
970 (38.19)
970 (38.19)
93E-80T
300 (11.81)
600 (23.62)
FRONT VIEW
300 (11.81)
796 (31.34)
RIGHT VIEW
3-14
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
WARNING
WARNING
RISK OF ELECTRIC SHOCK. This ups receives power from more than one source disconnection of the AC and the DC source is required to de - energise this unit before
servicing. After disconnecting the utility power and the DC power, authorised service
personnel should wait at least five minutes for capacitor bleedoff before attempting internal
access to the UPS module.
Backfeed protection is an internally fitted option on this device. If this option, or an externally
fitted backfeed contactor are not installed.
The below label should be applied on all primary power isolators installed remote from the
UPS area and on external access points.
CAPACITORS INSIDE
REQUIRE 5 MINUTES
TO DISCHARGE
TO A SAFE LEVEL
AFTER ALL POWER
IS REMOVED.
SEE HANDBOOK
FOR INSTRUCTIONS.
Refer to national and local electrical codes for acceptable external wiring practices.
To allow for future kVA upgrades, consider installing a derated UPS using wiring and external overcurrent
protection breakers sized for a fully rated UPS.
For external wiring, use 90C copper wire. Wire sizes listed in Table3-5 are for copper wiring only. If wire is
run in an ambient temperature greater than 30C, higher temperature wire and/or larger size wire may be
necessary. Wire sizes are based on using the specified breakers.
Material and labour for external wiring requirements are to be supplied by designated personnel.
If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB)
(if installed) must have a service disconnect independent of the maintenance bypass power path. Most
maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance
bypass power path. If the maintenance bypass solution being installed does not provide such functionality,
DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-15
The bypass feed into this equipment uses four wires (three line conductors and neutral conductor), plus
grounding conductor (protective earthing conductor) . The rectifier feed into this equipment uses four wires
(three line conductors and neutral conductor), plus grounding conductor (protective earthing conductor). The
phases must be symmetrical about ground (from a Wye/Star source) for proper equipment operation.
Parallel UPS input wiring size requirements and output wiring size requirements from the UPSs to the Tie
Cabinet are the sames as those for single systems.
This device is not equipped with its own mains separation device. It is , therefore, essential that the customer
install such a device at the installation site near the UPS.
Install a proper three-pole overcurrent disconnect device before connecting to the UPS, the disconnect
device shall disconnect simultaneously all line conductors of the AC MAINS SUPPLY.
Do not disconnect neutral, neutral required for system operation.
If a disconnect device interrupts the neutral conductor, it shall simultaneously interrupt all line conductors.
When single-phase current exceeds 100A, switches of protective atmosphere should be equipped with
arc-control device.
The UPS requires an input neutral connection. Ensure that an input neutral is connected prior to energising
the UPS. If a 4 pole Automatic Transfer Switch is installed upstream of the UPS it must work with a break
before make transition with a minimum transfer time of 50ms.
Figure4-6 and Figure4-7 show the location of the UPS power cable terminals.
3-16
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Table 3-5. Input / Output Ratings and External Wiring Requirements for the Eaton 93E 15-80 kVA
cross-sections
Refer the IEC
62040-1
Units
Rating 50/60 Hz
kVA
kW
15
13.5
20
18
30
37
40
36
60
54
80
72
Volts
400/400
400/400
400/400
400/400
400/400
400/400
Amps
23
31
46
61
92
123
min
mm2
61
61
61
161
161
251
max
mm
61
101
251
251
501
701
Amps
22
29
43
58
87
115
min
mm2
61
61
61
61
161
251
max
mm
61
101
251
251
501
701
Total Amps
34
46
69
92
137
183
min
mm2
61
61
101
161
351
501
max
mm
161
251
351
501
502
702
Amps
22
29
43
58
87
115
min
mm2
61
61
61
61
161
251
max
mm2
61
101
251
251
501
701
Grounding
1.0times
1.7times
Clearance distance:2.0mm
NOTE
Break time:15s
CAUTION
External overcurrent protection is not provided by this product, but is required by codes. Refer to
table 3-5 for wiring requirements. If an input/output lockable disconnect is required, it is to be
supplied by the user.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-17
Table 3-6. UPS External Power Cable Terminations for the Eaton 93E 15-80 kVA
Tightening
Torque
Nm (lb in) Screw Size and Type
Terminal
Function Terminal
Function
Bus landing
15kVA/20kVA/30kVA
AC Input
to UPS
Rectifier
AC Input
to Bypass
AC Output
to Critical
Load
DC Input
from
External
Battery
Customer
Ground
NOTE
3-18
Tightening
Torque
Nm (lb in) Screw Size and Type
Bus landing
40 kVA/60kVA/80kVA
L1
Phase A
M6 bolt mounting
5 (44)
28.26 mm(M6).
M8 bolt mounting
12 (106)
50.24 mm(M8)
L2
Phase B
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L3
Phase C
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
Neutral
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L1
Phase A
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L2
Phase B
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L3
Phase C
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
Neutral
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L1
Phase A
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L2
Phase B
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
L3
Phase C
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
Neutral
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
Battery (+)
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
Battery (-)
M6 bolt mounting
5 (44)
28.26 mm(M6)
M8 bolt mounting
12 (106)
50.24 mm(M8)
M5 bolt mounting
3 (26)
19.63 mm(M5)
30 kVA Ground
M6 bolt mounting
9 (79)
28.26 mm(M6)
M8 bolt mounting
24 (212)
50.24 mm(M8)
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Load Derating
400V
80% Derated
29A
100% Rating
23A
80% Derated
38A
100% Rating
31A
80% Derated
57A
100%Rating
46A
80% Derated
77A
100% Rating
61A
80% Derated
115A
100% Rating
92A
80% Derated
153A
100% Rating
123A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuitbreakercurrent ratings from Table3-7 in accordance with local regulations.
The line-to-line unbalanced output capability of the UPS is limited only by the full load perphase current values
for AC output to critical load shown in Table3-5. The recommended line-to-line load unbalance is 50% or less.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass
and output circuit breakers.
Table 3-8. Recommended Bypass and Output Circuit Breaker Ratings
Circuit Breaker Rating
UPS Model
93E-15
93E-20
93E-30
93E-40
93E-60
93E-80
Load Derating
400V
80% Derated
27A
100% Rating
22A
80% Derated
36A
100% Rating
29A
80% Derated
54A
100% Rating
43A
80% Derated
72A
100% Rating
58A
80% Derated
108A
100% Rating
87A
80% Derated
144A
100% Rating
115A
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-19
There is no DC disconnect device within the UPS. A battery disconnect switch is recommended, And may be
required by local codes when batteries are remotely located. The battery disconnect switch should be installed
between the battery and the UPS
External DC input overcurrent protection and disconnect switch for the remote battery location is to be
provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit breakers satisfying the
criteria for both.
Table 3-9. Recommended DC input circuit breaker rating
Circuit Breaker Rating
UPS Model
93E-15
93E-20
93E-30
93E-40
93E-60
93E-80
Load Derating
80% Derated
43A
48A
100% Rating
34A
39A
80% Derated
57A
64A
100% Rating
46A
52A
80% Derated
86A
97A
100% Rating
69A
77A
80% Derated
114A
129A
100% Rating
92A
103A
80% Derated
172A
193A
100% Rating
137A
155A
80% Derated
229A
258A
100% Rating
183A
206A
Battery voltage is computed at 2 volts per cell. Rated battery current is computed at 2 volts per cell. The battery
wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC
voltage at rated battery current. If the conductors used for DC input from the battery cabinets to the UPS are
those provided by the UPS manufacturer, and the UPS and battery cabinets are manufactured by the same
supplier, then it is acceptable if they do not meet the noted minimum conductor sizes.
3-20
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
WARNING
Do not directly connect contactor contacts to the mains related circuits. Reinforced insulation is
required before connecting to the mains.
Read and understand the following notes while planning and performing the installation:
Interface wiring should be rated for 24V, 1A minimum.
For interface wiring from 30V to 600V, the wire should be rated for 600V, 1A minimum.
Because of the REPO and building alarm wiring route in the UPS cabinet, the wire should be rated for a
minimum of 300V.
Use twisted-pair wires for each input and return or common.
All interface wiring and conduit is to be supplied by the customer.
When installing external interface wiring between a REPO or building alarm and the UPS interface terminals,
conduit must be installed between each device and the UPS cabinet.
If using the power terminal wiring channel, keep interface wiring separate from power wiring or use shielded
wire.
If using conduit, install the interface wiring in separate conduit from the power wiring.
All building alarm inputs require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA
minimum) connected between the alarm input and common terminal. All control wiring and switch contacts
are customer-supplied.
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by the customer.
The REPO feature opens all contactors in the UPS cabinet and isolates power from your critical load. Local
electrical codes may also require tripping upstream protective devices to the UPS.
The REPO switch must be a latching-type switch not tied to any other circuits.
A jumper wire must be connected between pins3 and 4 on the REPO terminal block if using a normallyclosed REPO switch.
REPO wiring should be a minimum of 0.5~2.0 mm2.
The REPO switch wiring must be in accordance with local regulations.
The maximum distance between the REPO and the UPS cannot exceed 150metres (500feet).
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-21
3.3
WARNING
The UPS cabinet is heavy (see Table3-1). If unpacking and unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION
Do not install a damaged cabinet. Report any damage to the carrier and contact an
Eaton service representative immediately.
NOTE
For the following step, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table3-1 for cabinet weight).
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible,
before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks
between the supports on the bottom of the pallet (see Figure3-6 through Figure 3-10 for the UPS cabinet
centre of gravity measurements).
CAUTION
Do not tilt the UPS cabinets more than 10 from vertical or the cabinets may tip over.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m(10ft) on each side for
removing the cabinet from the pallet.
4. Remove the inner protective packaging. Retain the ramp brackets.
5. Recycle the remainder of the outer shipping container and the inner protective packaging in a responsible
manner.
6. Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.
3-22
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
NOTE
While waiting for installation, protect the unpacked cabinet from moisture, dust, and
other harmful contaminants. Failure to store and protectthe UPS properly may void
your warranty.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
3-23
3-24
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 4
4.1
WARNING
Installation should be performed only by qualified personnel. See installation instructions before
connecting to the supply.
Refer to the following while installing the UPS system:
Chapter3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
Do not tilt the cabinets more than 10 during installation.
If perforated floor tiles are required for ventilation, place them in front of the UPS.
The UPS unit is not suitable for IT or corner-earthed power distribution systems.
Suitable for mounting on concrete or other non-combustible surfaces only
4.2
WARNING
The UPS cabinet is heavy (see Table3-1). If unpacking and unloading instructions are not closely followed,
the cabinet may tip and cause serious injury.
CAUTION
Do not tilt cabinet more than 10 from vertical.
Lift the cabinets only with a forklift or damage may occur.
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight of
the cabinet (see Table3-1 for cabinet weight).
1. If not already accomplished, use a forklift or pallet jack to move the UPS cabinet to the installation area, or
as close as possible, before unloading from the pallet. Insert the forklift or pallet jack forks between the
supports on the bottom of the pallet (see Figure3-6 through Figure 3-10for the UPS cabinet centre of
gravity measurements).
2. Remove four bolts securing the front shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.
3. Attach the ramp to the front of the pallet (see Figure4-2):
4. If the leveling feet are not fully retracted, turn the leveling feet until they are retracted.
5. Remove four bolts securing the rear shipping bracket to the cabinet and four bolts securing the bracket to
the pallet (see Figure4-1). If installing the cabinet permanently, retain the shipping bracket and securing
hardware for later use.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-1
Front Door
Pallet
Shipping Bracket
WARNING
Do not stand directly in front of the pallet while unloading the cabinet. If unloading instructions are
not closely followed, the cabinet may cause serious injury.
6. Slowly roll the cabinet toward the front of the pallet. Continue rolling the cabinet down the ramp until the
cabinet is clear of the ramp (see Figure4-3).
7.
8. If installing the cabinet permanently, retain the shipping brackets and hardware; otherwise, recycle the
pallet, ramp, and shipping brackets in a responsible manner.
9. Secure the UPS cabinet in position by lowering the leveling feet until the cabinet is not resting on the
casters and the cabinet is level.
10. If permanently mounting the system, proceed to Step 11;
11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and
rear of the UPS cabinet with the angle facing outward (see Figure4-1).
12. Secure the cabinet to the floor with customer-supplied hardware.
4-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
UPS Cabinet
Pallet
Ramp
lU
se
On
ly
na
ter
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-3
4.3
WARNING
In the event of malfunction, the battery cabinet chassis or battery cabinet frames may become
live!
Special care should be taken when working with the battery cabinet associated with the
equipment. Ensure the battery number is suited to the setting of the battery charging voltage
before installing the battery. When the battery cabinet is connected the overall voltage exceeds
nominal voltage. It is very important to ensure that the batteries are installed separately, in a
dedicated battery cabinet.
Battery back-up time do not exceed one hour, if the battery setting shall be exceeded one hour,
consult to the professional personnel.
CAUTION
The most common battery type used in UPS installations is the valve regulated battery. Valve
regulated cells are not sealed. The amount of gas given off is less than for flooded cells, but
when planning the battery installation, allowance must be made for adequate ventilation and
heat dissipation. Valve regulated cells are not completely maintenace- free. They must be kept
clean and their connections checked periodically to ensure they are tight, and that there is no
evidence of corrosion. It is inevitable that the batteries will lose charge during transportation and
storage; before attempting to carry out an autonomy test, ensure that the batteries are fully
charged as this may take several hours. Cell performance typically improves after a few
discharge/recharge cycles.
The requirements of the EC directives are satisfied when battery cabinet are used with original
accessories. If alternative batteries are used, you must ensure that the applicable EC directives
are met and declare conformity.
Connect the battery cabinet as follows:
1. Turn off the UPS.
2. Check all the external battery breakers are open.
3. Connect PE first.
4. Connect the battery cabinet(s) with cables sized according to cable cross section and protective device.
5. Specification to terminals + (positive pole) and - (negative pole).
Refer to instructions provided with the battery cabinet or by vendor.
WARNING
ENSURE CORRECT POLARITY!
4-4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4.4
Without accessory cabinets, conduit and wiring enter from the bottom of the UPS
conduit landing plate. With accessory cabinets, wiring can be installed between the
UPS and accessory cabinets by using conduit or by routing wiring through the
power terminal cover base wiring channels.
To install wiring:
1. Route the wiring to the UPS terminal blocks in the UPS. Figure 4-4 and Figure 4-5 for wiring access
information and terminal locations.
2. Ground the UPS according to local and/or national electrical wiring codes by routing and connecting the
ground wire to the input ground lug.
3. Connect phase A, B and C rectifier input power wiring from the utility source to the rectifier input, See
paragraph 3.2.2 for wiring and termination requirements.
4. Bypass input power wiring from the utility source to the bypass input terminals and neutral terminals. See
paragraph 3.2.2 for wiring and termination requirements.
5. Connect phase A, B and C power wiring from output terminals to the critical load. See paragraph 3.2.2 for
wiring and termination requirements.
6. Mains input N , Output N and Bypass input N are connected together inside UPS
7.
WARNING
BAT+/BAT- are terminals connected to the battery cabinet, Battery+ polarity should use red
cable, battery - polarity should use black or blue cable.
This device may not be fitted with an optional internal mains disconnection device. If not
fitted, it is essential that the customer install such a device at the installation site near the
UPS.
Input neutral line should be directly connected to input N terminal of UPS wire connection
terminal bay without AC input idle-run.
There are protective earthing terminals within the UPS for mains supply, load supply and
battery. The battery cabinet earth protection can be connected either to the UPS or to a
common earthing terminal outside the UPS.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-5
AC Input to
UPS Bypass
Ground Terminals
RIGHT VIEW
AC Input to
UPS Rectifier
Phase C (L3)
Phase B (L2)
Phase A (L1)
Internal Battery +
Neutral (N)
Phase A (L1)
Phase B (L2)
Phase C (L3)
Internal Battery -
Phase C (L3)
Phase B (L2)
AC Output to
Critical Load
Phase A (L1)
FRONT VIEW
Internal Battery +
Phase C (L3)
Neutral (N)
Phase B (L2)
Internal Battery -
Phase A (L1)
Ground Terminals
Phase A (L1)
Phase C (L3)
AC Output to Critical Load
Phase B (L2)
Phase B (L2)
Phase C (L3)
Phase A (L1)
REAR VIEW
4-6
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
AC Input to
UPS Bypass
Neutral (N)
Internal Battery -
Phase C (L3)
Phase B (L2)
Internal Battery +
Phase A (L1)
Ground Terminals
RIGHT VIEW
AC Input to
UPS Rectifier
Phase A (L1)
Phase C (L3)
Phase B (L2)
Phase B (L2)
Phase C (L3)
FRONT VIEW
AC Output to
Critical Load
Phase A (L1)
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-7
4.5
FRONT MIDDLE
COVER PLATE
FRONT VIEW
FRONT VIEW
4-8
Interface Terminals
(See Figure 4-7 for detail)
FRONT MIDDLE
COVER PLATE
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Building Alarm 1
Building Alarm 3
Building Alarm 2
Name
Building Alarm 1 +
Building Alarm 1
Building Alarm 2 +
Building Alarm 2
Building Alarm 3 +
Building Alarm 3
Description
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Input: Programmable UPS alarm, activated by a remote dry contact closure.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-9
Wiring Access
Wiring Aaccess
4-10
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4.5.2 Installing Parallel Pull Chain and CAN Control Wiring and Connections
To install wiring:
1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, UPS Operating
Instructions", for shutdown instructions.
2. Installing Parallel system, seeFigure4-10 and Figure 4-12.
CAUTION
Parallel system combined input and output cable length should be in accordance with the
following rule. It should be designed to ensure that wiring impedance from point of supply to
UPS input and from UPS output to load connection for each UPS module in a multi-module
system is equal, or within a tolerance of approximately 10%. This is to ensure approximately
equal current sharing when in static bypass mode and restrain input/output high frequency loop
current of parallel system. Suggest that parallel system combined input and output cable length
no less than 10m, 5m for input and 5m for output.
Total length of 1A =2A=3A=4A
1B=2B=3B=4B
1C=2C=3C=4C
If installing only two UPS modules (redundant), this requirement is no longer required as each
UPS is capable of supporting the full bypass requirement. However, this would preclude future
expansion.
Ensure that each UPS static bypass is fed from a single common source, as is an external
bypass switch if installed. If each UPS is fed with a separate rectifier source, please consult
Eaton for advice on compatibility.
3. To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph3.2.3, Table4-2, Figure4-7, Figure4-9, and Figure4-10.
Pull Chain
Figure 4-10. Pull Chain Terminal Block Connector Assignments
Table 4-2. Pull Chain Connections
Pull Chain Terminal
Name
Pull Chain +
Pull Chain
Description
Output: Backup control for parallel operation.
4. Remove the small parts from the knockout in the right side plate.
5. Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure4-7,
Figure4-11 and Figure4-12 for wiring information.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-11
6. Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm2) between the UPS cabinets and cabinet
MOBs. See Figure 4-7, Figure 4-10 and Figure 4-11 for wiring information.
7.
For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8)
To install wiring:
1. If not already installed, install the LAN drop.
2. Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure4-6 and Figure4-7
for Mini-Slot communication bay locations.
3. Refer to the manual supplied with the Mini-Slot card for operator instructions.
4. Install the power terminal cover using the provided hardware.
4-12
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
TERMINATING
JUMPER
RJ-45 CABLE
IN
OUT
CN3
CN6
CAN BUS
RJ-45 CABLE
IN
CN3
UPS 1
BUILDING
ALARM CN9
1
2
OUT
CN6
IN
CN3
CAN BUS
UPS 2
PULLCHAIN
CN4
1
2
BUILDING
ALARM CN9
1
2
TERMINATING
JUMPER
RJ-45 CABLE
OUT
CN6
IN
CN3
CAN BUS
UPS 3
PULLCHAIN
CN4
1
2
OUT
CN6
CAN BUS
UPS 4
BUILDING PULLCHAIN
ALARM CN9
CN4
1
2
1
2
BUILDING
ALARM CN9
1
2
PULLCHAIN
CN4
1
2
TWISTED
PAIRS
CUSTOMER
TERMINAL
BLOCK
CONNECTIONS
25
1
NO
COM
6
NC
M
O
B
1
NO
NC
COM
5
10
7
NO
COM
26
12
NC
M
O
B
2
NO
COM
11
NC
15 14
16
13
NO
27
21 20
18
NC
COM
M
O
B
3
NO
NC
COM
17
22
19
NO
COM
28
24
NC
M
O
B
4
NO
NC
COM
23
TIE CABINET
UPS 1
Bypass inputs
to UPSs
UPS 1
REC inputs
to UPSs
1A
2A
2C
Battery
3A
1C
UPS 2
Battery
3C
4A
UPS 2
4C
Battery
Battery
UPS 3
UPS 3
1B
Outputs from
UPSs
1B
2B
Battery
UPS 4
2B
Battery
UPS 4
3B
Outputs from
UPSs
4B
3B
4B
Battery
Battery
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-13
4.6
Before installing a REPO switch, verify that the UPS was installed according to the
instructions in paragraphs 4.2 through 4.5.
NOTE 2
When installing the REPO switch, you must install conduit between the device and
the UPS cabinet for wiring the switch.
NOTE 3
NOTE 4
NOTE 5
2. Securely mount the REPO switch. Recommended locations include operator's consoles or near exit doors.
3. To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph3.2.3, Table4-3, Figure4-6, Figure4-7, and Figure4-13.
Normally Open
REPO Contacts
Normally
Open
REPO Contacts
Figure
Terminal Block
Block Connector
Connector Assignments
Assignments
Figure 4-19.
4-13. REPO
REPO Terminal
REPO Terminal
1
2
3
4
Description
Input: normally-closed dry contact used to activate UPS EPO from a remote switch.
2 dry contact used to activate UPS EPO from a remote switch.
Input: normally-closed
3
Input: normally-open dry contact used to activate UPS EPO from a remote switch.
Input: normally-open4dry contact used to activate UPS EPO from a remote switch.
4.
Us
eO
NormallyClosed
Closed
Normally
REPO
Contacts
REPO
Contacts
nl
UPS
UPS
4-14
If not already removed, remove the power terminal cover top. Retain the cover top and hardwa
later use.
c.
al
b.
Remove the screws securing the top rear panel (see Figure 4-10). Supporting the panel, tilt the
5. Connect the wiring as shown in Table4-4 and Figure4-14 for a normally-open REPO or Table4-5 and
Figure4-15 for a normally-closed REPO.
6. If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO
terminal block.
7.
If you are installing multiple REPO switches, wire additional switches in parallel with the first REPO.
8. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A
second contact block is provided on the REPO switch for this function . The REPO switch wiring must be in
accordance with local regulations.
Table 4-4. REPO Connections
From REPO Station(s)
Switch Contact Block
(Either Block)
3,4 NO
Wire Size
Tightening Torque
7lbin
(0.8Nm)
2
3
REPRO
Switch
(No)
REPO TB
Twisted
Wires
4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-15
1,2,3,4 NC
REPRO
Switch
(NC)
Wire Size
Tightening Torque
7lbin
(0.8Nm)
Twisted
Wires
REPO TB
4.7
Initial Startup
Startup may be performed by the customers qualified electrical contractor for single (not parallel) UPS
installations without any accessory cabinets.
Startup and operational checks for parallel systems or installations with accessory cabinets must be performed
by an authorised Eaton Customer Service Engineer, or the warranty terms may become void.This service is
offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a
two-week notice is required) to reserve a preferred startup date.
4.8
NOTE
4-16
The Installation Checklist MUST be completed prior to starting the UPS system for
the first time.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Installation Checklist
All packing materials and restraints have been removed from each cabinet.
The UPS cabinet is placed in its installed location.
All conduits and cables are properly routed to the UPS and any ancillary cabinets.
All power cables are properly sized and terminated.
Neutral conductors are installed.
A ground conductor is properly installed.
Building alarms are wired appropriately. (Optional)
LAN drops are installed. (Optional)
LAN connections have been completed. (Optional)
The REPO device is mounted in its installed location and its wiring is terminated inside the UPScabinet.(Optional)
A jumper wire is connected between pins 3 and 4 on the REPO terminal block if using a normally-closed REPO switch.
(Optional)
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
4-17
Notes
4-18
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Section 2
Operation
Chapter 5
5.1
Battery
Relay
Battery
Converter
AC Input to
Rectifier/
Charger
Input
Switch
Input
Relay
Output
Relay
Rectifier
Inverter
Power Module
Digital Metering
Output switch
Static
Switch
AC Output to
Critical Load
(Optional)
Backfeed Contactor
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5-1
5.2
Single UPS
A single UPS operates independently to support an applied load from the inverter, providing conditioned and
uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter
continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied
loads are transferred to the internal bypass either automatically or manually. With the exception of an optional
external battery cabinet, no other cabinets or equipment are required for the single UPS to successfully support
its applied loads.
5.2.1 Modes
The Eaton 93E UPS supports a critical load in four different modes of operation:
In Standard Normal mode, the critical load is supplied by the inverter, which derives its power from rectified
utility AC power. In this mode, the battery charger also provides charging current for the battery, if needed,
Standard mode is the standard normal operating mode.
In High-Efficiency (HE) mode, commercial AC power is supplied directly to the critical load through the
internal bypass and transfers automatically to Standard Normal mode (double-conversion on demand) if an
abnormal condition is detected.
In Battery mode, the battery provides DC power, which maintains inverter operation. The battery supports
the critical load.
The following paragraphs describe the differences in the UPS operating modes, using block diagrams to show
the power flow during each mode of operation.
5.2.2
During Standard Normal mode, power for the system is derived from a utility input source through the rectifier
input contactor. Three-phase AC input power is converted to DC using IGBT devices to produce a regulated DC
voltage to the inverter. When the battery contactor is closed the battery is charged directly from the regulated
rectifier output through a buck or boost DC converter, depending on the system voltage and the size of the
battery string attached to the unit.
Figure5-2 shows the path of electrical power through the UPS system when the UPS is operating in Normal
mode.
The battery converter derives its input from the regulated DC output of the rectifier and provides either a
boosted or bucked regulated DC voltage charge current to the battery. The battery is always connected to the
UPS and ready to support the inverter should the utility input become unavailable.
The inverter produces a three-phase AC output to a customer's load without the use of a transformer. The
inverter derives regulated DC from the rectifier and uses IGBT devices and pulse-width modulation (PWM) to
produce a regulated and filtered AC output. The AC output of the inverter is delivered to the system output
through the output contactor.
If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode
to support the critical load without interruption. When utility power returns, the UPS returns to Normal mode.
5-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Bypass Input
Static
Switch
Rectifier
Input
Input Switch
Output
Rectifier
Inverter
Input
Relay
Output
Relay
Battery
Converter
Battery
Switch
Relay
Relay
Closed
Open
De-Energised
Battery
Figure 5-2. Path of Current Through the UPS in standard Normal Mode
If the UPS becomes overloaded or unavailable, the UPS switches to Bypass mode. The UPS automatically
returns to Normal mode when the overload condition is cleared and system operation is restored within
specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until
the failure is corrected and the UPS is back in service.
5.2.3
High-Efficiency Mode
When the UPS is operating in HE mode, commercial AC power is supplied directly to the critical load through the
internal bypass with the power module in a standby state. If a commercial power brownout, blackout, overvoltage,
undervoltage, or out-of-tolerance frequency condition occurs the system forward transfers to normal mode
(double-conversion on demand) or battery mode. When the input line returns to normal operating range, the UPS
returns to HE operation. For charging batteries in HE mode, the UPS will revert to normal mode to charge the
batteries, then return to HE mode when charge cycle is complete.
HE mode, if selected, is a normal operating mode, and not an alarm condition. While the UPS is in this mode,
the NORMAL light on the front display will illuminate.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5-3
5.2.4
Bypass Mode
CAUTION
The critical load is not protected from voltage or frequency fluctuations or power outages while
the UPS is in Bypass mode.
The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The
UPS can also be transferred from Normal mode to Bypass mode manually. The bypass source supplies the
commercial AC power to the load directly. Figure 5-3 shows the path of electrical power through the UPS
system when operating in Bypass mode.
In Bypass mode, the output of the system is provided with three-phase AC power directly from the system
input. While in this mode, the output of the system is not protected from voltage or frequency fluctuations or
power outages from the source. Some power line filtering and spike protection is provided to the load but no
active power conditioning or battery support is available to the output of the system in the Bypass mode of
operation.
The internal bypass is comprised of a solid-state, silicon-controlled rectifier (SCR) continuous static switch, and
an optional backfeed protection contactor. The static switch is used instantaneously anytime the inverter is
unable to support the applied load. The continuous static switch is wired in series with the backfeed protection
contactor (if fitted), and together they are wired in parallel with the rectifier and inverter.
The static switch, being an electronically-controlled device, can be turned on immediately to pick up the load
from the inverter while inverter output contactor opens to isolate the inverter. The backfeed protection
contactor (if fitted) is normally closed, ready to support the static switch unless the bypass input source
becomes unavailable.
If the UPS transfers to Bypass mode from Normal mode due to any reason other than operator intervention,
the UPS automatically attempts to transfer back to Normal mode (up to three times within a ten minute
period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to
transfer.
Bypass Input
Static
Switch
Rectifier
Input
Input Switch
Rectifier
Output
Inverter
Input
Relay
Output
Relay
Battery
Converter
Switch
Battery
Relay
Relay
Closed
Energised
Open
De-Energised
Battery
Figure 5-3. Path of Current Through the UPS in standard Bypass Mode
5-4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5.2.5
Battery Mode
The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does
not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the
inverter converts to AC power.
Figure 5-4 shows the path of electrical power through the UPS system when operating in Battery mode.
Bypass Input
Static
Switch
Rectifier
Input
Input Switch
Rectifier
Output
Inverter
Input
Relay
Output
Relay
Battery
Converter
Switch
Battery
Relay
Relay
Closed
Energised
Open
De-Energised
Battery
Figure 5-4. Path of Current Through the UPS in standard Battery Mode
During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC
output voltage required to support the inverter. The input contactor opens and the battery instantaneously
supplies energy to the battery converter. The converter boosts the voltage so that the inverter can support the
customer's load without interruption. If bypass is common with the rectifier input, the backfeed protection
contactor also opens. The opening of the input and the optional backfeed protection contactors prevent
system voltages from bleeding backwards through the static switch and rectifier snubber components to the
utility source.
If the input power fails to return or is not within the acceptance windows required for normal operation, the
battery continues discharging until a DC voltage level is reached where the inverter output can no longer
support the connected loads. When this event occurs, the UPS issues another set of audible and visual alarms
indicating SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output can be supported
for only two minutes before the output of the system shuts down. If the bypass source is available, the UPS
transfers to bypass instead of shutting down.
If at any time during the battery discharge the input power becomes available again, the input and the backfeed
protection contactors close and the rectifier begins to supply DC current to the converter and inverter. At this
point, the unit returns to Normal mode. Depending on the total load and the duration of the battery discharge,
battery current limit alarms may be seen for a short time due to the current required to recharge the battery.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5-5
5.3
5-6
Oneline Drawing
UPS Model
Input
Output
System Type
380/400/415
380/400/415
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Parallel CAN
AC Input to
Bypass 4 Wire
A-B-C Rotation
Pull Chain
Mini-Slot
Interface
Remote EPO
Interface Board
L1, L2,
L1, L2,
L3, N
L3, N
(Optional)
Backfeed Contactor
Input Switch
Static
Switch
Fuse
Input
relay
Rectifier
Inverter
MBS
Output
relay
L1, L2,
L3, N
Fuse
Output Switch
AC Output to
Critical Load
Battery
relay
(OPTIONAL)
Battery Contactor
INTERNAL BATTERY
Fuse
disconnector
UPS
CABINET
C
Battery
Breaker
EXTERNAL BATTERY
NOTE Callout letters A,B,C, and D map to Table 3-5.
CABINET
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5-7
AC Input to
UPS Rectifier
4 Wire A-B-C
Rotation
Parallel CAN
Pull Chain
Mini-Slot
Interface
Remote EPO
A,B
Interface Board
L1, L2,
L3, N
(Optional)
Backfeed Contactor
Input Switch
Static
Switch
Fuse
Input
relay
Rectifier
Inverter
MBS
Output
relay
L1, L2,
L3, N
Fuse
Output Switch
AC Output to
Critical Load
Battery
relay
(OPTIONAL)
Battery Contactor
INTERNAL BATTERY
Fuse
Fuse
disconnector
UPS
CABINET
C
Battery
Breaker
NOTE Callout letters A,B,C, and D map to Table 3-5.
EXTERNAL BATTERY
CABINET
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
5-8
Chapter 6
6.1
NOTE 1
Before starting the UPS, ensure all installation tasks are complete and a preliminary
startup has been performed by authorised service personnel. The preliminary
startup verifies all electrical interconnections to ensure the installation was
successful and the system operates properly.
NOTE 2
Read this section of the manual and have thorough knowledge of UPS operation before
attempting to operate any of the controls.
Control Panel
Door Latch
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-1
Neutral Switch
Output Switch
Maintenance
Bypass Switch
Input Switch
Bypass Switch (Optional)
Input Switch
Bypass Switch (Optional)
Neutral Switch
Output Switch
Input Switch
Maintenance
Bypass Switch
Output Switch
Maintenance
Bypass Switch
Output Switch
Maintenance
Bypass Switch
Input Switch
Bypass Switch
(Optional)
Neutral Switch
Neutral Switch
93E 60 kVA
93E 80 kVA
Figure 6-2. UPS Switches
6-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
UPS Operating
Operating Instructions
Instructions
UPS
UPS Operating Instructions
UPS Operating Instructions
6.2
6.2
6.2
6.2
Using
Using the
the Control
Control Panel
Panel
Using the
Control
Panel
The
following
paragraphs
describe the
UPS control
panel, including
controls and
indicators, and
how to
monitor
The following
paragraphs
following
paragraphs describe
describe the
the UPS
UPS control
control panel,
panel, including
including controls
controls and
and indicators,
indicators, and
and how
how to
to monitor
monitor
Using theThe
Control
Panel
UPS
operation.
The
control
panel
(see
Figure
6-3)
is
located
on
the
front
door
of
the
UPS.
The
following
paragraphs
describe
the
UPS
control
panel,
including
controls
and
indicators,
and
how
to
monitor
UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS.
UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS.
UPSfollowing
operation.
The control
panelthe
(see
Figure
6-3)panel,
is located
on the
front and
doorindicators,
of the UPS.
The
paragraphs
describe
UPS
control
including
controls
and how to monitor
UPS operation. The control panel (see Figure6-3) is located on the front door of the UPS.
22
2
2
93E
33
3
3
11
1
Figure 6-3. UPS Control Panel
1
Figure
6-3. UPS
Control Panel
Figure
Figure 6-3.
6-3. UPS
UPS Control
Control Panel
Panel
Figure 6-3. UPS Control Panel
The
control
panel
consists
of:of:
The control
control panel consists
consists
The
The control panel
panel consists of:
of:
The
control
paneldisplay
consists
of:(1)
AAliquid
crystal
(LCD)
liquid crystal
display (LCD)
(1)
A
A liquid
liquid crystal
crystal display
display (LCD)
(LCD) (1)
(1)
A
liquid
crystal
display
(LCD)
(1)
Menu
navigation
pushbutton
switches
(2)
Menu
navigation
pushbutton
Menu navigation
navigation pushbutton
pushbutton switches
switches (2)
(2)
Menu
switches
(2)
AMenu
vertical
column
of
status
indicators
(3).
See
paragraph6.2.1.
navigation
pushbutton
switches
(2)
A vertical
vertical column of
of status indicators
indicators (3).
See
paragraph 6.2.1.
6.2.1.
A
A vertical column
column of status
status indicators (3).
(3). See
See paragraph
paragraph 6.2.1.
TheAfollowing
paragraphs
describe
using the
UPS
control
panel6.2.1.
to monitor the UPS. See paragraph6.3 for use
vertical
column
of
status
indicators
(3).
See
paragraph
The
following
paragraphs
describe
The
following
paragraphs
describe using
using the
the UPS
UPS control
control panel
panel to
to monitor
monitor the
the UPS.
UPS. See
See paragraph
paragraph 6.3
6.3 for
for use
use
The
paragraphs
using
the
UPS
control
panel
to
monitor
the
UPS.
See
paragraph
6.3
for
use
of
thefollowing
operational
controls. describe
of
the
operational
controls.
The
following
paragraphs
describe
using
the
UPS
control
panel
to
monitor
the
UPS.
See
paragraph
6.3
for use
of
of the
the operational
operational controls.
controls.
of thethe
operational
controls.
When
unit powers
up, the screen displays the Eaton logo as shown in Figure6-3. To advance to the Main
When
the
unit
powers up,
the
screen
displays
the
Eaton logo
as
shown in
Figure 6-3.
To advance
to the
Main
When
the
unit
the
screen
displays
the
as
Menu
screen,up,
press
control
panel pushbutton
once.
Whenand
theMimic
unit powers
powers
up,
theany
screen
displays
the Eaton
Eaton logo
logo
as shown
shown in
in Figure
Figure 6-3.
6-3. To
To advance
advance to
to the
the Main
Main
Menu
and
Mimic
screen,
press
any
control
panel
pushbutton
once.
When
the
unit
powers
up,
the
screen
displays
the
Eaton
logo
as
shown
in
Figure
6-3.
To
advance
to
the
Main
Menu
Menu and
and Mimic
Mimic screen,
screen, press
press any
any control
control panel
panel pushbutton
pushbutton once.
once.
Menu
and
Mimic
screen,
press
any
control
panel
pushbutton
once.
6.2.1 Status Indicators
l
l
l
l
l
l
l
l
l
l
l
IInntt
eerrnn
aall
6.2.1
6.2.1
Status
Status Indicators
Indicators
The
four
symbols
on
the
side
ofof
the
control
panel
areare
status
indicators.
These
colored
lightlight
emitting
diodediode
6.2.1
Indicators
The
fourStatus
symbols
on
theright
right
side
the
control
panel
status
indicators.
These
colored
emitting
The
symbols
on
right
side
of
the
control
panel
are
status
These
colored
The four
four
symbols
on the
the
right
side
ofto
the
control
panel
are
status indicators.
indicators.
These
colored light
light emitting
emitting diode
diode
(LED)
lamps
work
with
the
alarm
horn
let
you
know
the
operating
status
of
the
UPS.
(LED)
lamps
workon
with
the
alarm
horn
to control
let you
you know
knoware
thestatus
operating
status These
of the
the UPS.
UPS. light emitting diode
The
four
symbols
thethe
right
sidehorn
of the
indicators.
(LED)
lamps
work
alarm
to
status
(LED)
lamps
work with
with
the
alarm
horn
to let
let you panel
know the
the operating
operating
status of
of the colored
UPS.
(LED) lamps
work withstatus
the alarm
horn to let you know the operating status of the UPS.
Table6-1
indicators.
Table
6-1describes
describesthe
the status
indicators.
Table
Table 6-1
6-1 describes
describes the
the status
status indicators.
indicators.
Table 6-1 describes the status indicators.
Table 6-1. Status Indicators
Table
6-1.
Status
Indicators
Table
Table 6-1.
6-1. Status
Status Indicators
Indicators
Description
TableIndicator
6-1. Status IndicatorsStatus
Indicator
Status
Description
Indicator
Status
Description
Indicator
Status
Description
Indicator
Status
Description
On
The
UPS
Normal
mode.
power
module
is
supplying
power
the
critical
On
The
UPS
is
in
Normal
mode.
The
power
module
is
power
to
the
load.
On
The
is is
in in
Normal
mode.
TheThe
power
module
is supplying
power
to theto
load. load.
On
TheUPS
UPS
is
in
Normal
mode.
The
power
module
is supplying
supplying
power
tocritical
the critical
critical
load.
On
The UPS is in Normal mode. The power module is supplying power to the critical load.
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Red
Red
Red
Red
Red
Off
Off
Off
Off
Off
On
On
On
On
On
The
UPS
turned
The
is is
turned
off.off.
The
UPS
is
turned
off.
TheUPS
UPS
is
turned
off.
turned
off.
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is
a normal
condition
the
UPS,
the
Normal
indicator
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is a normal
condition
of theof
Normal
indicator
also also
The
mode.
Because
Battery
mode
is
condition
of
the
UPS,
the
indicator
also
The UPS
UPS is
is in
in Battery
Battery
mode.
Because
Battery
mode
is aa normal
normal
condition
ofUPS,
thethe
UPS,
the Normal
Normal
indicator
also
remains
illuminated.
remains
illuminated.
The
UPS
is
in
Battery
mode.
Because
Battery
mode
is
a
normal
condition
of
the
UPS,
the
Normal
indicator
also
remains
illuminated.
remains illuminated.
remains illuminated.
On
On
On
On
On
The
UPS
Bypass
mode.
critical
is
supported
the
bypass
source.
The
Normal
indicator
not
The
is is
in in
Bypass
mode.
TheThe
critical
loadload
is supported
by theby
source.
The Normal
indicator
is not is
The
UPS
is
in
Bypass
mode.
The
critical
load
is
by
the
source.
The
indicator
is
TheUPS
UPS
is
in
Bypass
mode.
The
critical
load
is supported
supported
bybypass
the bypass
bypass
source.
The Normal
Normal
indicator
is not
not
illuminated
when
the
system
is
in
Bypass
mode.
illuminated
when
the
system
is
in
Bypass
mode.
The
UPS is inwhen
Bypass
load
is supported by the bypass source. The Normal indicator is not
illuminated
the
system
is
Bypass
mode.
illuminated
when
the mode.
systemThe
is in
incritical
Bypass
mode.
illuminated when the system is in Bypass mode.
On
On
On
On
On
The
UPS
has
anan
active
alarm
andand
requires
immediate
attention.
The LCD
the highest
prioritypriority
active alarms.
All
The
UPS
has
active
alarm
requires
immediate
attention.
The shows
LCD shows
the highest
active alarms.
The
The UPS
UPS has
has an
an active
active alarm
alarm and
and requires
requires immediate
immediate attention.
attention. The
The LCD
LCD shows
shows the
the highest
highest priority
priority active
active alarms.
alarms.
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
Alarm
All
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
The
UPS has
active alarmby
and
attention.
The LCD
the highest
activeonce.
alarms.
All alarms
alarms
areanaccompanied
accompanied
by
anrequires
audible immediate
horn. To
To silence
silence
the horn,
horn,
pressshows
any control
control
panelpriority
pushbutton
once.
The
All
are
an
audible
horn.
the
press
any
panel
pushbutton
The
indicator
may
be
illuminated
along
with
other
indicators.
Alarm
indicator
may
be
illuminated
along
with
other
indicators.
All
alarms
are
accompanied
by
an
audible
horn.
To
silence
the
horn,
press
any
control
panel
pushbutton
once.
The
Alarm indicator
indicator may
may be
be illuminated
illuminated along
along with
with other
other indicators.
indicators.
Alarm
Alarm
may
be condition.
illuminated
with flashes
other
indicators.
There
is is
aindicator
new
UPS
alarm
Thealong
indicator
until until
acknowledged
by pressing
any control
panel panel
There
a
new
UPS
alarm
condition.
The
indicator
flashes
acknowledged
by
pressing
any
control
There
There is
is aa new
new UPS
UPS alarm
alarm condition.
condition. The
The indicator
indicator flashes
flashes until
until acknowledged
acknowledged by
by pressing
pressing any
any control
control panel
panel
pushbutton
pushbutton
once.
There is aonce.
new
UPS alarm condition. The indicator flashes until acknowledged by pressing any control panel
pushbutton
once.
pushbutton
once.
pushbutton once.
Flashing
Flashing
Flashing
Flashing
Flashing
nnllyy
Green
Green
Green
Green
Green
Eaton
9E UPS
(4060 kVA,
208/220V)
Installation
and
Operation Manual
P-164000058Rev
22
Eaton
kVA,
208/220V)
Installation
and
Manual
P-164000058Rev
Eaton 93E
UPS
(15-80 kVA,
380/400/415V)
Installation
and Operation
Manual
Eaton 9E
9E UPS
UPS (4060
(4060
kVA,
208/220V)
Installation
and Operation
Operation
Manual
P-164000058Rev
2
Eaton 9E UPS (4060 kVA, 208/220V) Installation and Operation Manual P-164000058Rev 2
6-3
6-3
6-3
6-3
6-3
6-4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Meter
Events
History
Controls
Setup
The UPS status area automatically scrolls between the Eaton model number, current date and time, active
alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while
scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible
horn. To silence the horn, press any control panel pushbutton once. Shown is a typical alarm message. For
more information about alarms and notices, see paragraph 6.2.2.
The information area contains data about UPS status and operations.
The menu bar shows the symbols of the available screens. To select a screen, highlight the screen symbol
using the navigation pushbuttons and then press the RETURN pushbutton.
The navigation pushbuttons function depending on the screen displayed. Use the Up, Down, Left, and
Right pushbuttons to scroll through available screens and the Esc and Enter pushbuttons to select menu
screens and functions.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-5
Description
METERS
EVENTS
HISTORY
CONTROLS
SETUP
ESC
6-6
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Subfunction
Meters UPS
The Meter screens show the UPS meter readings for the unit. The default voltage displayed on these
screens is phase-to-neutral. These can be changed to display the voltage phase-to-phase (AB,B-C,C-A). Use the LEFT or RIGHT arrow pushbuttons to select the METER symbol on the main menu
bar, to display the Meter screens. To scroll through the meter screens, press the UP or DOWN arrow
pushbutton. The current UPS readings are displayed in the information area of the screen.
Output UPS
The Output screen shows output voltage (phase to neutral), output current (each phase), and frequency
being supplied by the UPS, as well as the kVA, kW, and power factor measurements.
Input UPS
The Input screen shows input voltage (phase to neutral), input current (each phase), and frequency of
the incoming utility source, as well as the kVA, kW, and power factor measurements.
Bypass
The Bypass screen shows the bypass input voltage (phase to neutral), input current (each phase), and
frequency of the incoming utility source, as well as the kVA, kW, and power factor measurements.
Battery UPS
The Battery screen displays the battery voltage (Vdc) and the battery current (Idc).
Events
Use the LEFT or RIGHT arrow pushbuttons to select the EVENTS symbol on the main menu bar to display
the Events screens. A listing of all system events that are currently active is displayed. The most recent
event is listed first. As events clear, they are removed from the Events listing. To scroll through the
events, press the UP or DOWN arrow pushbutton.
History
Use the LEFT or RIGHT arrow pushbuttons to select the HISTORY symbol on the main menu bar to
display the History screen. The history Log lists up to 512 events in chronological order, with the most
recent event listed last (once 512 is reached, the earliest event is overwritten). The end of the log (the
most recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the UP or DOWN arrow pushbutton.
Setup User
Setup Config
(System Level 1 Setup)
Operation
Function Selection
This screen can be used to display user information and show the firmware versions installed. Use the
LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar to display the
Setup screen. Use the UP or DOWN arrow pushbutton to highlight the function desired, then press the
RETURN pushbutton to display the function screen. See Figure6-6 for a typical screen display.
User Info
The User Info screen provides the model, CTO and serial numbers of the UPS, the Output voltage,
frequency, and kVA rating, the input voltage rating, and the battery run time rating. Use the LEFT or
RIGHT arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow
pushbutton. to select Info, then press the RETURN pushbutton to display the function screen. To return
to the System Setup screen, press the ESC pushbutton.
About
The About screen provides the firmware version numbers installed on the UPS. Use the LEFT or RIGHT
arrow pushbuttons to select USER on the Setup menu bar. Use the UP or DOWN arrow pushbutton. to
select About. To return to the System Setup screen, press the ESC pushbutton.
To enter a password if required, use the LEFT or RIGHT arrow pushbutton to select the password
character position. Use the UP or DOWN arrow pushbutton to change the password character. Once the
password is entered, select DONE and then press the RETURN pushbutton. The System Setup Level 1
menu screen is displayed. The default System Setup Level 1 password is 0101.
Password
Function Selection
This screen can be used to set the date and time, change the display language, enter a unit name,
change the meter style, perform lamp test, clear the history log, and enter a password to access Level1
functions. Use the LEFT or RIGHT arrow pushbuttons to select the SETUP symbol on the main menu bar
to display the Setup screen. Use the LEFT or RIGHT arrow pushbutton to select CONFIG on the Setup
menu bar. Enter a password if required.
Clock
The Clock Setup screen allows the selection of either month/day/year or day/month/year formats and
daylight savings time for display on the screen and for logging events in the Event and History Logs. Use
the UP or DOWN arrow pushbutton to select CLOCK to display the Clock screen. Use the UP or DOWN
arrow pushbutton to highlight the desired format, then press the RETURN pushbutton to display the Set
Date and Time screen. To return to the System Setup screen, press the ESC pushbutton.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-7
Subfunction
Operation
Setup Config
(System Level 1 Setup)
(continued)
The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in
the month/day/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.
The Set Date and Time DD/MM/YYYY screen allows the internal date and time of the UPS to be set in
the day/month/year format. The date and time information is used for display on the screen and for
logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the
setting to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished
making changes, use the LEFT or RIGHT arrow pushbutton to highlight SAVE and the UP or DOWN
arrow pushbutton to select YES. To complete the save function and return to the System Setup screen,
select the RETURN arrow pushbutton.
Language
The Language Setup screen allows the display menu language to be selected. Use the UP or DOWN
arrow pushbutton to highlight Language, then press the RETURN pushbutton to display the Language
screen. Use the UP or DOWN arrow pushbutton to highlight the desired language, then press the
RETURN pushbutton. To return to the System Setup screen, press the ESC pushbutton.
Unit Name
The Unit Name Setup screen allows a unit name to be entered. Use the UP or DOWN arrow pushbutton
to highlight Unit Name, then press the RETURN pushbutton to display the Unit Name screen. Use the
LEFT or RIGHT arrow pushbutton to highlight the character to be changed. Use the UP or DOWN arrow
pushbutton to make the change. When finished making changes, use the LEFT or RIGHT arrow
pushbutton to highlight SAVE and the UP or DOWN arrow pushbutton to select YES. To complete the
save function and return to the System Setup screen, select the RETURN arrow pushbutton. To return to
the System Setup screen, press the ESC pushbutton.
Meters
The Meters Setup screen allows the Meters Screen display style to be selected. Use the UP or DOWN
arrow pushbutton to highlight Meters, then press the RETURN pushbutton to display the Meters
screen. Use the UP or DOWN arrow pushbutton. to highlight the desired style, then press the RETURN
pushbutton. To return to the System Setup screen, press the ESC pushbutton.
Lamp Test
The Lamp Test screen allows the control panel status lamps to be tested. Use the UP or DOWN arrow
pushbutton to highlight Lamp Test, then press the RETURN pushbutton to illuminate the status lamps.
To return to the System Setup screen, press the ESC pushbutton.
Clear Log
The Clear Log screen allows the history log to be cleared. Use the UP or DOWN arrow pushbutton to
highlight Clear Log, then press the RETURN pushbutton to clear the log. To return to the System Setup
screen, press the ESC pushbutton.
P/W
The P/W screen is used to change the System Setup Level 1 password. Use the UP or DOWN arrow
pushbutton to highlight P/W, then press the RETURN pushbutton to display the P/W screen. Use the
LEFT or RIGHT arrow pushbutton to select the password character position. Use the UP or DOWN arrow
pushbutton to change the password character. Once the password is entered, select CHANGE and then
press the RETURN pushbutton.
Controls
6-8
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Normal
Load Off
Bypass
UPS
Battery
UPM
or
Table6-4 describes the control functions and provides instructions to access and use the command menu
screens.
Table6-5 lists the typical System Status Screen Messages that are displayed during UPS operation.
For detailed information about using the System Controls, see paragraph 6.3.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-9
Normal
Load Off
Bypass
Normal
HE:Enable
Load
Off
Bypass
Disable
UPS
Battery
UPM
UPS
Battery
UPM
Subfunction
Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command or proceed to further command
screens.
Normal Mode
Starts the UPS in Standarad Normal mode or transfers the UPS to Standard Normal mode
from Bypass mode.
Bypass Mode
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Battery Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then
press the RETURN pushbutton to execute the command.
Charger
Resting
6-10
Function
Message
UPS
Bypass
Charger
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6.3
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-11
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
To start the UPS system:
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure6-1).
2. Verify that the input and output switches are open.
3. Verify that the bypass input switch is open (Dual Input). .
4. Verify that the bypass switch is open and the Neutral Switch is closed.
5. Close the UPS input feeder circuit breaker.
6. If the UPSs are wired for dual input, close the UPS Bypass input feeder circuit breaker.
7. Close the input switch.
8. If the UPS contains two input sources, close the bypass input switch.
9. Close the output switch.
10. Make sure MBS cover is installed.
11. Close the door and secure the latch.
12. Close the external battery breakers.
13. Observe the UPS control panel display becoming active, indicating logic power.
14. Verify no alarms are active.
15. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
16. If not already selected, select UPS on the System Control screen.
17. On the UPS System Control screen, select the LOAD OFF
pushbutton.
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
pushbutton.
6-12
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
WARNING
Power is present inside the UPS cabinet.
The UPS transfers to Normal mode. If the power module is not available, the system remains on bypass
and an alarm sounds.
The NORMAL status indicator is illuminated.
After battery is fully charged, the UPS transfers to HE mode if no abnormal power conditions are detected.
If abnormal power conditions are detected, the UPS will wait and transfer to HE mode when conditions are
cleared.
The NORMAL status indicator is illuminated.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-13
2. Loosen the screws that fix the cover over the maintenance bypass switch. This action will signal the UPS
to transfer to static bypass. Refer to Figure 6-2 for switch arrangement.
3. Verify that the LCD/LED display indicates the UPS is in Bypass mode.
4. Close the Maintenance Bypass switch.
5. Open the Bypass Input and Output switches separately (Dual Input).
6. Loosen the screws that fix the cover over the Neutral switch (60-80 kVA), open the Neutral switch.
NOTE
The Neutral Switch should remain closed unless operated by a service technician.
WARNING
Power is present inside the UPS cabinet.
6-14
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
4. Open the UPS Input switch.
5. If the UPSs are wired for dual input, open the Bypass input switch.
6. Open the Maintenance Bypass switch.
7.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-15
This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.
NOTE 2
The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.
LOAD OFF
The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4. Select Yes or No, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
5. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph6.3.1 or
6.3.2.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
6-16
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customersupplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases. To remove the key, rotate the key back to the vertical position.
3. Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-17
6.4
Refer to the External Battery Cabinet Installation Manual listed in paragraph 1.8 for
EBC battery breaker location.
Start and control system wide function from UPS 1.
6.4.1 Starting the Parallel UPS in Standard Normal Mode (Default Mode)
To start the UPS system:
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (see Figure6-1).
2. Verify that all input breakers are open.
3. Verify that the maintenance bypass breakers are open.
4. Close all Module Output Breakers (MOBs).
5. Close all UPS input feeder circuit breakers.
6. If the UPSs are wired for dual input, close all of the UPSs Bypass input feeder circuit breakers.
7. Close all input breakers.
8. If the UPSs are wired for dual input, close all bypass input switches.
9. Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close all external battery breakers.
12. Observe the UPS control panel display becoming active, indicating logic power.
13. Verify no alarms are active.
14. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
15. If not already selected, select UPS on the System Control screen.
16. On the UPS System Control screen, select the LOAD OFF
RETURN pushbutton.
6-18
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure6-1).
2. Verify that all input breaker are open.
3. Verify that the Maintenance bypass switches are open.
4. Close all Module Output Breakers (MOBs).
5. Close all UPS input feeder circuit breakers.
6. If the UPSs are wired for dual input, close all of the UPS Bypass input feeder circuit breakers.
7. Close all input breakers.
8. If the UPSs are wired for dual input, close all of the bypass input switches.
9. Make sure MBS cover is installed.
10. Close the door and secure the latch.
11. Close the external battery breakers.
11. Observe the UPS control panel display becoming active, indicating logic power.
12. Verify no alarms are active.
13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF
pushbutton.
The critical load is immediately supplied by the bypass source, in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-19
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
pushbutton.
WARNING
Power is present inside the UPS cabinet.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The NORMAL status indicator is illuminated.
WARNING
Power is present inside the UPS cabinet.
6-20
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
The output and bypass backfeed relay open, and the power module is turned off on the UPS being shut
down.
Logic power remains on.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
5. Open the UPS input and the bypass feeder circuit breakers for the UPS being shut down.
6. If EBCs are installed, open all battery breakers
The UPS is now completely shut down.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-21
WARNING
Power is present inside the UPS cabinets after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
5. Open all input switches.
6. Open all of the maintenance bypass switches.
7.
6-22
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
This UPS has a user initiated battery test intended to determine if the batteries are
able to support the load.
NOTE 2
The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will
not be shown if the test is not able to be run.
LOAD OFF
The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energise the critical load.
4. Select Yes or no, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energising the critical load. Selecting No will
abort the shutdown.
5. If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step 4.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
6. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph6.4.1 or
6.4.2.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6-23
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energise the critical load.
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customersupplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been
identified and cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases. To remove the key, rotate the key back to the vertical position.
3. Restart the UPS by following the procedure in paragraph 6.4.1 or 6.4.2.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are
opened because of the installed external battery cabinet.
6-24
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 7 Communication
Chapter 7 Communication
7.1
This chapter describes the communication features of theEaton 93E UPS. For terminal wiring information, see
This chapter
describes theFor
communication
ofinterface
the Eaton
9E UPS.
For terminal
information, see
paragraph3.2.3
and paragraph4.4.
location of thefeatures
customer
panel
and terminals,
seewiring
Figure4-6
paragraph
3.2.3 and paragraph 4.11. For location of the customer interface panel and terminals, see Figure 4-10
and Figure4-7
.
and Figure 4-11.
Mini-Slot Cards
7.1
Mini-Slot Cards
The Eaton 93E UPS has two standard, factory-installed Mini-Slot communication bays. See Figure4-7 for bay
UPS has with
two standard,
factory-installed
Mini-Slot
communication bays. See Figure 4-10 for bay
locations.The
The Eaton
UPS is9E
compatible
the following
Mini-Slot cards
(see Figure7-1):
locations. The UPS is compatible with the following Mini-Slot cards (see Figure 7-1):
Network Management Card and Modbus/Jbus provides remote monitoring through a Web browser
Management
Card and Modbus/Jbus
provides
remote
monitoring
a Web browser
interface,Network
e-mail, and
a network management
system (NMS)
using SNMP
and
connects through
to a twisted-pair
interface, e-mail,
and a network
system
(NMS) using
SNMP
and connects
to and
a twisted-pair
Ethernet (10/100BaseT)
network.
The card management
also provides direct
integration
of UPS
information
(meters
The card
also
integration of UPS information (meters and
status) to Ethernet
a Building(10/100BaseT)
Managementnetwork.
System (BMS)
using
theprovides
Modbusdirect
RTU protocol.
status) to a Building Management System (BMS) using the Modbus RTU protocol.
Network Management Card provides remote monitoring through a Web browser interface, e-mail, and a
Network Management
Cardusing
provides
monitoring
a Web
browser
interface, e-mail, and a
network management
system (NMS)
SNMPremote
and connects
to a through
twisted-pair
Ethernet
(10/100BaseT)
network. network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network.
Management Card Contact and RS232 / Serial two types of interfaces via a DB9 connector are available
Management
Card
Contact
and RS232
/ Serial
two types
of interfaces
DB9
connector
with this card.
Dry contact
mode
provides
a simple
way to transmit
UPS
informationvia
toaan
alarm
system,are available
with
this
card.
Dry
contact
mode
provides
a
simple
way
to
transmit
UPS
information
to
system,
PLC, or computer system via dry relay contacts. The transmitted information is load powered, load an
on alarm
bypass,
PLC, or
computer
system
dry and
relaylow
contacts.
transmitted
information
is load
powered,
load on battery,
load
on utility,
batteryvia
fault,
battery.The
RS232
mode provides
an RS232
interface
for load on
bypass,
ona battery,
load on
utility,
battery
fault,are
and
lowto
battery.
mode (contacts
provides an
connection
to a PCload
or to
UPS Control
display
unit.
Jumpers
used
select RS232
the interface
or RS232
RS232). interface for connection to a PC or to a UPS Control display unit. Jumpers are used to select the interface
(contacts or RS232).
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.
For installation and setup of a Mini-Slot card, contact an Eaton service representative (see paragraph1.8). Refer
For installation
and setup
of a Mini-Slot
an Eaton service representative (see paragraph 1.8). Refer
to the manual
supplied withthe
Mini-Slot
card forcard,
usercontact
instructions.
to the manual supplied with the Mini-Slot card for user instructions.
l
NetworkManagement
ManagementCard
Cardand
and
Network
Modbus/Jbus
Modbus/Jbus
7.2
7.2
Building Alarm Monitoring
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or
overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
This standard
lets you
connect
thealarm
UPS to
yourand
building
alarms, such as smoke detectors or
Use feature
twisted-pair
wires
for each
input
common.
overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
Use twisted-pair
wiresalarms
for each
alarm
input and common.
The building
can
be programmed
to display the alarm functional name.
Fo
The building alarms can be programmed to display the alarm functional name.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Eaton 9E UPS (4060 kVA, 208/220V) Installation and Operation Manual P-164000058Rev 2
7-1
7-1
Communication
7-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 8
UPS Maintenance
The components inside the UPS cabinet are secured to a sturdy metal frame. Allrepairable parts and
assemblies are located for easy removal, with very little disassembly. This design allows authorised service
personnel to perform routine maintenance and servicing quickly.
You must schedule periodic performance checks of your UPS system to keep it running properly. Regular
routine checks of operation and system parameters enable your system to function efficiently for many troublefree years.
8.1
WARNING
Servicing and maintenance should be performed by qualified service personnel only.
LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open or
protective panels removed. Do not make any assumptions about the electrical state of any
cabinet in the UPS system.
Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE
BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect
that a battery string needs service, contact an Eaton service representative.
If the string requires service contact an Eaton service representative.
Observe these precautions when working on or around batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the charging source prior to connecting or disconnecting terminals.
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any
part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such
grounds are removed during installation and maintenance.
When replacing batteries, use the same number of sealed, lead-acid batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
8-1
UPS Maintenance
8.2
CAUTION
Verify washed filter is thoroughly dry before reinstalling.
a. Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise)
and swing the door open (see Figure6-1).
b. Remove the upper and lower foam filters from the frame on the front door.
c. Replace the washed or new foam filters into the frame on the front door.
d. Close the front door and secure the latch.
3. Record maintenance results and any corrective actions in a suitable log.
8-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
UPS Maintenance
Filters
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
8-3
UPS Maintenance
8.3
Installing Batteries
NOTE There is no manual DC disconnect device within the UPS.
Install batteries in accordance with the battery and battery system manufacturer's instructions.
8.4
WARNING
Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of
batteries is required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
A battery can cause electrical shock, burn from high short-circuit current, or fire. Observe proper
precautions.
ATTENTION!
Une batterie peut prsenter un risque de choc lectrique, de brulure, ou d'incendie. Suivre les
prcautions qui s'imposent.
Pour le remplacement, utiliser le mme nombre et modle des batteries.
L'limination des batteries est rglemente. Consulter les codes locaux cet effet.
CAUTION
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid
batteries and must be disposed of properly. For more information, contact your local recycling/
reuse or hazardous waste centre.
CAUTION
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal,
contact your local recycling/reuse or hazardous waste centre.
8.5
Maintenance Training
A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the
UPS system operation and teaches you how to perform first level corrective maintenance. For more
information about training and other services, contact the Help Desk (see paragraph 1.8).
8-4
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Chapter 9
Product Specifications
Power Rating
Frequency
description
93E-15UI-N-649Ah-MBS
15 kVA
50/60 Hz
93E-15UI-N-0-MBS
15 kVA
50/60 Hz
93E-15U-N-MBS
15 kVA
50/60 Hz
93E-15UT-N-MBS
15 kVA
50/60 Hz
T-Transformer UPS
93E-20I-N-649Ah-MBS
20 kVA
50/60 Hz
93E-20I-N-0-MBS
20 kVA
50/60 Hz
U-upgradable
93E-20-N-MBS
20 kVA
50/60 Hz
93E-20T-N-MBS
20 kVA
50/60 Hz
93E-30I-N-969Ah-MBS
30 kVA
50/60 Hz
93E-30I-N-0-MBS
30 kVA
50/60 Hz
93E-30-N-MBS
30 kVA
50/60 Hz
93E-30T-N-MBS
30 kVA
50/60 Hz
93E-40I-N-1289Ah-MBS
40 kVA
50/60 Hz
93E-40I-N-0-MBS
40 kVA
50/60 Hz
93E-40-N-MBS
40 kVA
50/60 Hz
93E-40T-N-MBS
40 kVA
50/60 Hz
93E-60-N-MBS
60 kVA
50/60 Hz
93E-60T-N-MBS
60 kVA
50/60 Hz
93E-80-N-MBS
80 kVA
50/60 Hz
93E-80T-N-MBS
80 kVA
50/60 Hz
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
Operating Altitude
Storage Temperature
Acoustical Noise
62 dB (30-40 kVA)
65 dB (60-80 kVA)
EMC
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
9-1
Product Specifications
380/400/415 Vac
190/330276/478V (-15%, +20%) at 100% load
116/201-276/478V (-50%, +20%) at 50% load
50/60 Hz
40-72Hz
See Table3-5.
Adjustable
Power Factor
Minimum 0.99
Line Surges
Battery Voltage
Output Current
See Table3-5.
Output Voltage Phase Displacement < 2.5 for 100% maximum load imbalance (linear load)
Frequency Regulation
Synchronous to Bypass
4 Hz (default setting)
Load Compatibility
0.9 PF Leading
0.7 PF Lagging
110% for 60 minutes
Overload Capability
9-2
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
614-01802-00