Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sirius10 120

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

TECHNICAL SPECIFICATION

SR10-120

10 12 15 - 20 kVA (1/1 and 3/1) UPS 10 12 15 - 20 - 30 40 60 80 - 100 - 120 kVA (3/3) UPS

Contents

..1.. OBJECTIVE .....................................................................................................................................2 ..2.. SYSTEM DESCRIPTION..................................................................................................................2 ..3.. REFERENCE STANDARDS.............................................................................................................3 ..4.. APPLICATIONS ...............................................................................................................................4 ..5.. CONFIGURATIONS .........................................................................................................................5 ..6.. UPS DESCRIPTION.........................................................................................................................6 > 6.1 PFC Converter (Zero Impact Source) .........................................................................................8 > 6.2 Battery Charger (Battery Care System) ......................................................................................9 > 6.3 Inverter .................................................................................................................................... 11 > 6.4 Static Switch (Automatic Bypass)............................................................................................. 13 ..7.. CONTROL PANEL ......................................................................................................................... 14 ..8.. ISOLATING SWITCHES................................................................................................................. 16 ..9.. COMMUNICATION ........................................................................................................................ 16 > 9.1 Emergency Shutdown (R.E.P.O.)............................................................................................. 19 > 9.2 External Synchronisation.......................................................................................................... 19 > 9.3 Monitoring and Control Software .............................................................................................. 19 > 9.4 Configuration Software............................................................................................................. 19 ..10.. UPS CABINET ............................................................................................................................. 22 ..11.. OPTIONS ..................................................................................................................................... 22 > 11.1 Communication...................................................................................................................... 22 > 11.2 External Battery Temperature Sensor .................................................................................... 24 > 11.3 External Maintenance Bypass ................................................................................................ 24 > 11.4 Battery Cabinets .................................................................................................................... 24 > 11.5 Additional Battery Charger ..................................................................................................... 25 > 11.6 Optional Transformers ........................................................................................................... 26 > 11.7 Separate Line Input................................................................................................................ 29 ..12.. ENVIRONMENTAL CONDITIONS ................................................................................................ 29 ..13.. TECHNICAL DATA 10-120 KVA three-phase output ............... Errore. Il segnalibro non definito. ..14.. TECHNICAL DATA 10-20 KVA single-phase output...................................................................... 34

1 - OBJECTIVE
This specification defines the technical characteristics of the SR10-120 uninterruptible power supply (UPS). The UPS is designed to supply a clean and stable electrical supply, irrespective of the condition of the mains or an alternative power supply. The SR10-120 series is another development G-TEC which is made up by a group of sales and tecncial teams with over 30 years of experience in UPS & power supply distribution.

2 - SYSTEM DESCRIPTION
The SR10-120 UPS is available in 10-12-15-20-30-40-60-80-100-120 kVA On Line double conversion technology. SR10-120 meeting the VFI-SS-111 classification defined by IEC EN 62040-3. SR10-120 is designed protect critical industrial and Information Technology (IT) systems with the following features: a) Cleaned Source low input current distortion - as low as 3% and with a 0.99 input power factor; Power Walk-In and start-up delay to reducing generator oversizing; these features also help to guarantee supply compatibility where available mains power is limited. b) Battery Care System two voltage level recharge according to the IU characteristic, in A-C temperature compensating recharge voltage; suitable for the charging of extended back-up battery sets with additional charger options; Battery test function to detect potential battery deterioration Cyclical recharge Recharging the commissioning charge. c) Inverter thermal oversizing in order to guarantee 110% overload (0.8pF) without time restrictions; d) Capability to power loads with cos from 0.9 inductive to 0.9 capacitive, without active power (kW) reduction; e) High performance design achieving a system efficiency of up to 96.5% for 10 to 40kVA; and up to 94% for 60 to 120kVA UPS. f) Backfeed protection;

g) Other available features include: the installation of an internal transformer option for 10 to 40kVA; Compatible with the addition of an optional battery charger. Dual input for 60 to 120kVA as standard; Wide range of communication options.

The SR10-120 series consists of the following models:

MODEL
SR010M SR012M SR015M SR020M SR010T SR012T SR015T SR020T SR030T SR040T SR060T SR080T SR100T SR120T

DESCRIPTION
10kVA UPS (1/1 or 3/1) 12kVA UPS (1/1 or 3/1) 15kVA UPS (1/1 or 3/1) 20kVA UPS (1/1 or 3/1) 10kVA UPS (3/3) 12kVA UPS (3/3) 15kVA UPS (3/3) 20kVA UPS (3/3) 30kVA UPS (3/3) 40kVA UPS (3/3) 60kVA UPS (3/3) 80kVA UPS (3/3) 100kVA UPS (3/3) 120kVA UPS (3/3)

3 - REFERENCE STANDARDS
SR10-120 UPS operates a Quality Management System certified to ISO 9001/2000 (Certification No. CERT04116-99-AQ-MIL-SINCERT) covering all company functions from design and manufacture to after sales services. In addition, the UPS meets the VFI-SS-111 classification (according to EN 62040-3) and complies with the following specific standards for UPS: IEC EN62040-1: Static uninterruptible power supplies (UPS): general and safety provisions; IEC EN62040-1-1: Static uninterruptible power supplies (UPS): general and safety provisions for operator-accessible areas; IEC EN 62040-2: Electromagnetic compatibility (EMC) requirements category C2 EN 62040-3: Methods of specification of performances and test provisions; The SR10-120 series also satisfies the following general standards, where applicable: IEC 60529: Degree of protection provided by enclosures; IEC 60664: Insulation for low-voltage equipment; IEC 60755: General Requirements for Residual Current Operated Protective Devices; IEC 60950: General safety provisions for "Information Technology" equipment; IEC 61000-2-2: Electromagnetic compatibility immunity; IEC 61000-4-2: Electrostatic discharge immunity test; IEC 61000-4-3: Radio frequencies, electromagnetic immunity test; IEC 61000-4-4 : Transitory overvoltage immunity test; IEC 61000-4-5 : Overvoltage immunity test; IEC 61000-4-11: Voltage dips, short interruptions and voltage variations immunity test. IEC 61000-3-12: Harmonic current emissions (for equipment with rated current > 16 A 75)

European Directives: LV 2006/95/EC Low voltage Directive: contains provisions relating to equipment safety and imposes the EC marking obligation from 1/1/97. EMC 2004/108/EC Electromagnetic compatibility directive: contains provisions relating to UPS immunity and emissions in its installation environment and imposes the EC marking obligation from 1/1/96.

4 - APPLICATIONS
SR10-120 UPS are suitable for applications requiring critical load protection including: LAN, Server and Datacenters: the 0.9 output power factor ensures greater active power availability for efficient UPS loading. e-business and Telecommunications: parallel operation means that the installed UPS size can be increased (up to 6 units) to keep pace with the growth of the organisation. Industrial processes and electro-medical systems: the UPS is designed to protect a range of loads, from industrial processes to electro-medical applications. This has been achieved through careful load analysis at the design stage of the SR10-120 project, to ensure the following characteristics: optimum input technical characteristics to achieve cleaned power supply source high short circuit and overload capacity high battery recharge capacity with the option to use a variety of battery types (sealed valve regulated and open-vented) for long back-up times. Emergency systems: the UPS can be configured to operate in any one of four operating modes to comply with EN 50171 (the Centralised Power Supply Systems) standard:

Operating modes (EN50171)

SR10-120 Configurations
The UPS operates in the following mode: ON-LINE (See chapter 6 "Ups descriptions")

The UPS operates in the following mode: ECO-MODE (See chapter 6 "Ups descriptions") The UPS operates in the following mode: STAND BY-OFF (See chapter 9.4 "Configuration Software") The UPS operates in the "ON LINE" MODE by using the POWERSHARE socket (see the operating manual)

5 - CONFIGURATIONS
The UPS can be installed as a single, stand-alone UPS and this format is most commonly used for relatively straight forward installations. This can be expanded up to 6 units (4 units in the 3/1 version) in order to meet load power demands or to introduce a level of redundancy.

Parallel configuration Up to 6 UPSs (4 units in the 3/1 version) can be connected in parallel either to increase the power of the uninterruptible power system (power parallel) or to enhance its reliability (redundant parallel). The system is defined as redundant parallel when the stoppage of one or several UPSs does not determine the loss of the power supply. All the UPSs power the load simultaneously with automatic sharing of the current. The units exchange information on the operating status and the sync signals by means of the RS485 connections in loop with dual redundancy. This means that even in the event of the accidental interruption of both connections, only the UPS affected by this interruption cuts itself off, while the other one continues to operate without any interference. The Hot Plug-in feature means that a new UPS can be added to the system while the other units are on-line and powering the load from the inverter. The integrated UPS will configure itself automatically with the system data without any disturbance to the load.
MAINS MAINS MAINS

UPS1

UPS2

UPS6 UPS3---5

BATTERY

BATTERY

BATTERY

Maintenance Bypass cabinet (option)

LOAD

6 - UPS DESCRIPTION
The UPS can be operated in four main operating modes: ON-LINE, FREQUENCY CONVERTER, ECO and SMART ACTIVE and in their mode of operations are descriped below:

Mode: ON-LINE
Normal Operation: the rectifier, drawing power from the mains power supply, supports the Inverter and charges the batteries; the load is powered by the Inverter which provides a clean and secure supply, synchronised to the bypass supply. Emergency Operation: if the mains power supply is outside the permitted input range (voltage and frequency), the rectifier is shut down and the Inverter is automatically powered by the battery set for the preset back-up time and without disruption to the load. When the mains power supply returns, the rectifier gradually starts up, charging the batteries and eventually powers the Inverter. Operation from By-pass: if an Inverter overload exceeds permitted limits (or is manually shutdown), the load automatically transfers to the emergency bypass via the static switch and without disruption to the load.

Mode: FREQUENCY CONVERTER


The UPS can be configured as a frequency converter (with UPS tools), therefore when the input frequency is 50Hz the output frequency can be 60Hz and vice versa. During this mode of operation the automatic by-pass is disable. In frequency converter mode the battery installation is anyway necessary.

Mode: ECO
The load is normally powered from the emergency bypass supply and the rectifier maintains battery charge. When the mains power supply wanders outside the permitted input range, the load is automatically transferred to the output of the Inverter until the mains power supply returns within range. This mode is useful when powering loads that do not require the regulated no-break supply from the Inverter and allows the system to achieve an efficiency up to 98%.

Mode: SMART
When the UPS is configured to operate in SMART ACTIVE mode, it automatically selects whether to operate in ON-LINE or ECO mode. The decision is made based on statistical calculations performed by the UPS and based on the quality of the mains and bypass supplies: if the latter remains suitable for a certain period, the unit selects ECO mode, otherwise it remains in ON-LINE mode.

The SR10-120 block diagram is as follows:

Typical schematic for 10 to 40kVA

Typical schematic for 60 to 120kVA

> 6.1 PFC CONVERTER (Cleaned SOURCE)


The PFC Converter converts the AC voltage into a DC supply to power the Inverter; if the mains or alternative power supply fails, the Converter will raise the battery voltage to a value suitable with which to power the Inverter. The PFC control technology using Digital Signal Processing (DSP) microprocessors and IGBT power semiconductors to achieve a low impact on the power supply source, low harmonic distortion and high input power factor. A zero impact on the supply source is achieved due to the following characteristics: Negligible Input Harmonics: upstream generators and transformers (including distribution) can be reduced due to the negligible input harmonic distortion of < 3% and high input power factor > 0.99. Delayed switching of UPS t0-T1 (Power on Delay): when the mains power supply returns, the UPS delays switching of the input stage for a period of time that can be set between 0 and 255 seconds (5 seconds standard). This function is particularly useful when the mains power supply returns after an interruption (or when the generator set is started) and the source must supply various UPS or, more typically, multiple users. Progressive rectifier start-up T1-t2 (Power Walk-in): when the mains power supply returns, absorption of the mains power supply progressively reaches the nominal value within a time period that can be set from 5 to 30 seconds. This function is normally disabled.

> 6.2 BATTERY CHARGER (Battery Care System)


The "Battery Care System" is a set of functions arranged to help extend the working life the battery set and optimise its performance. a) Battery recharging: the UPS can be used with sealed lead batteries (VRLA), AGM, open-vented and NiCd batteries. According to the type of battery used two recharge methods are available: Modalit di ricarica (Selezionabili via UPS tools) Configuration SR10-120

V
272.6

Floating (standard configuration): the charge state of the battery is continuously monitored; when the mains power supply is present, the batteries are charged at a preset voltage level and limited current relative to the recharge time required and the capacity of the battery itself.

V I

286 272.6

Two-level recharge (configurable): this recharge is at limited current with two levels of voltage. In the first instance, the process uses a quick charge voltage, whilst in the second stage a float charge. This type of charging is mainly used with open-vented batteries or other types when an accelerated recharge time is required.

I<50mA/Ah max 3h

V I

286 272.6

286 262
battery test

Cyclical recharge: this recharge is sometimes recommended by battery manufacturers to prolong the battery life. It consists of battery charge and discharge cycles as indicated in the diagram.

I<50mA/Ah max 3h

12h

48h

14gg max

V
290 272.6 272.6

Commissioning charge: this charge method is useful every time new batteries are installed in the UPS. By increasing the voltage to 290 volts for a maximum of 24 hours, perfect equalisation of the battery charge is assured, thus guaranteeing a uniform discharge and wear of the battery monoblocks.

max 24h

The various recharge methods and the preset voltage values are defined using UPS tools. The presence of the external temperature sensor option will activate compensation of the voltage depending on the temperature with the battery backup voltage (272V for 20 battery blocks) 9

b) Battery test: during normal operation the battery is automatically tested at regular intervals. The battery test can also be manually activated. The test is performed to ensure a limited battery discharge and impact on overall life expectancy. If the test returns a negative result a warning is displayed on the UPS panel (or remote panel, if installed). c) Protection against deep discharge: for long runtimes and low load discharges, the end of discharge voltage is raised to approximately 1.8V/el as recommended by the battery manufacturers to avoid a deep discharge state. d) Ripple current: recharge ripple current (residual AC component) is one of the most important causes of poor battery reliability and reduced operating life. The UPS battery charger is a high-frequency design with a negligible level of ripple current, e) Battery recharge limit current: The battery recharge current is limited to a prefixed value of Cnom/8 (i.e. 12.5% Cnom) f) Cold-Start: This feature allows the Inverter to be switched on and the load to be powered by the battery, when the mains power supply is not present.

g) UPS without batteries: the UPS must always be operated with the batteries connected; if they are not connected alarms will be generated and the UPS will not be able to perform to specification.

10

> 6.3 INVERTER


The DC/AC Converter (Inverter) converts the direct current into a stabilised sinusoidal alternating current to power the load. When the UPS is in ON-LINE mode, the load is always powered by the Inverter. The Inverter is an IGBT (Isolated Gate Bipolar Transistor) based three-phase design; the IGBT is a transistor that allows high commutation frequencies (> 18kHz) and, as a result, the Inverter provides a high quality output voltage, with low noise levels and high operating efficiency. In addition, the DSP microprocessor controls, guarantee static and dynamic performance under any operating condition: Voltage adjustment The output voltage can be adjusted using the independent phase control and DSP microprocessor; this enables a better static and dynamic response. In detail: a) static condition: the Inverter output voltage remains within 1% for all variations of the input voltage within the accepted limits; b) dynamic condition: for load variations from 0 to 100%, the output voltage remains within 3%, (within the values defined by class 1 of the EN 62040-3 standard). Frequency adjustment The Inverter output frequency is generated autonomously by an internal oscillator, in synchronisation with the bypass supply. Frequency stability is operating condition dependent: a) Frequency stability With mains power present: the internal oscillator follows any frequency variations in the bypass supply and in relation to the preset value - normally 5% (configurable from 0.25% to 10%). With no supply present: the Inverter autonomously generates the frequency of the output voltage with a stability of 0.01%. b) Frequency variation speed The maximum Inverter output frequency variation (to lock to that of the bypass supply) is 1Hz/s (adjustable from 0.5 to 2Hz/s). Distortion of the output voltage Inverter output waveform distortion with a linear load is maintained within 1%. Within a non-linear load, as defined by the EN 62040-3 standard, output voltage distortion does not exceed 3% for 10 to 40kVA; 4% for 100 to 120kVA. Overload The inverter is sized to provide a power overload for a limited length of time (see the limits indicated in the Technical specifications table.) When the time period or power limits are exceeded, the load is transferred to the bypass supply. Short circuit capacity If a short circuit occurs whilst the UPS is operating from the batteries, the Inverter will carefully analyse the output voltage and current in order to distinguish if the short circuit is genuine or an overload. During battery operation (mains power supply failure) the Inverter can supply a current limited to 150% for 500ms. When the mains power supply is present, the Inverter will switch to bypass supplying a current limited to for 500ms.

11

The table below recommends the sizing of the various protection devices located downstream of the UPS in order to guarantee their selectivity even in the event of a power failure: Output protections (values recommended for selectivity) SR 10M to 20M SR 10T to 20T SR 60T to SR120T rapid fuses (GI) Magnetothermal switches (Curve C) Ultra-rapid fuses (GF) Output voltage symmetry Under all conditions, output voltage symmetry is maintained within 1%, for balanced loads and 2% for unbalanced loads of 100% (e.g. one phase with nominal load, the other two with no load). Phase shift angle The three-phase Inverter output voltages have a guaranteed phase separation angle of 120 1 for balanced loads and 100% for unbalanced loads. In (Nominal current)/7 In (Nominal current)/7 In (Nominal current)/2 SR 30T to 40T In (Nominal current)/7 In (Nominal current)/7 In (Nominal current)/3

Performance of a 3-phase Inverter with reactive loads

12

> 6.4 STATIC SWITCH (Automatic Bypass)


A static switch is an electronic device that can automatically transfer the loads connected to the UPS to the bypass supply in an emergency for example when: a) b) c) d) e) the Inverter is shut down manually; Inverter overload limits are exceeded; internal over temperature limits are exceeded; the Inverter fails; DC voltage goes outside the permitted range.

If at the time of switchover, the inverter voltage is not synchronised with that of the bypass supply, the transfer will take place with a delay of around 20ms; in consideration of the various types of loads, this delay can be set with UPS Tools to 10ms or the switchover can be inhibited if there is no synchronism. Emergency Supply Voltage Transfer to the bypass supply only takes place if the voltage and the frequency are considered 'suitable' for the load and the limits for transfer can be set on-site by the UPS user. Voltage range: 10% (settable from -20% to +15%); Frequency range: 5% (settable from 0.25% to 10%) Overload The static switch has no over voltage protection devices to guarantee maximum continuity. Overload protection is provided by protective devices within the overall electrical network to ensure UPS compatibility. The UPS static switch is sized to support the following overload periods: 110% permanently 133% for 60 minutes 150% for 10 minutes >150% for 2 seconds Under short circuit conditions, the UPS will prevent transfer to bypass for 0.5 seconds; thyristors with IT = 11250 As for 10 to 40kVA; IT = 80000 As for 60-80kVA; IT = 125000 As for 100-120kVA; Redundant Auxiliary Power Supply for the Automatic Bypass The UPS is equipped with a redundant auxiliary power supply to allow the automatic bypass to function even if the main power supply has failed. If the UPS fails in addition to the main power supply, the load is powered through the automatic bypass. The multi processor card and control panel are not powered, and for this reason, all LEDs and the display are off.

13

7 - CONTROL PANEL
The control panel consists of a graphical display, 6 visual warning LEDs and 4 function keys.

F1 LED for mains operation LED for battery operation LED for load on bypass LED for stand-by/alarm

F2

F3

F4 LED for replace batteries LED for ECO mode Graphical Display

F1, F2, F3, F4=FUNCTION KEYS. The function of each key is illustrated in the lower part of the display and
varies according to the menu. Messages are available in the following languages: Italian, English, French, German, Spanish, Polish, Turkish, Chinese and Russian. At the centre of the control panel there is a wide-area graphical display providing a detailed real-time overview of the UPS operational state. From the control panel the user can switch the UPS on/off, read electrical measurements - mains, output, battery, etc, and set the main operational parameters.

14

The display is divided into four main areas, each with a specific function: 1 GENERAL INFORMATION An area permanently showing the date and time and according to the level of display, either the UPS model or the title of the menu active at that time. 2 DATA DISPLAY/NAVIGATION MENU The main area of the display showing key UPS measurements (constantly updated in real-time). The user can also select and view various menus using the appropriate function keys. After selecting the required menu, this part of the display shows one or more pages containing all the data relevant to that menu. 3 UPS STATE / ERRORS - FAILURES An area in which the UPS operating state is shown. The first line is always active and constantly displays the state of the UPS at any given time; the second line is active only if an error and/or failure of the UPS occurs and shows the type of error/failure found. Each line on the right shows the code corresponding to the current event. 4 EVENT LOG An area showing chronological events recorded (supply voltage out of range, high temperature, overload, etc.)and alarms. The log records 960 events in FIFO (First In First Out) mode and the string contains the following information: Event Code, Event Description, Date and Time. Data is displayed through the graphical display using the scroll keys; the log can be downloaded in TXT format using the UPSTools configuration software. 5 KEY FUNCTIONS An area divided into four sections, one for each of the function keys. According to the menu active at any time, the display will show the corresponding function key in the appropriate box. When an alarm appears an audible warning will sound.

Measurements
Input voltage and frequency By-pass voltage and frequency Output voltage, current and frequency Output power (VA, W and %) Output peak current Battery voltage Battery charge current Internal temperature (control logic, power modules, battery charger, internal batteries) External battery temperature Back-up time

15

8 - ISOLATING SWITCHES
The SR10-120 UPS is supplied with the following isolating switches located and accessible from behind the case front door: SWBATT (10 to 40kVA only) SWMB manual by pass SWIN input SWBYP bypass mains input (standard for 60 to 120kVA; optional for 10 40kVA) SWOUT output
SWMB Manual by pass SWOUT output SWIN input

SWBYP by pass

Isolating switches arrangement for 100 to 120kVA

9 - COMMUNICATION
COMMUNICATION PORTS The rear panel (see UPS rear view) provides access to the following communication ports: Serial port, available with RS232 connector and USB connector. NOTE: the use of one connector automatically excludes the other. Expansion slot for additional slot-in communications interface cards Behind the front terminal panel, a further expansion slot is available for a volt-free signal card (optional 250Vac, 3A, 4 programmable contacts).

RS232 AND USB CONNECTORS


RS232 Connector USB Connector

16

PIN #
1 2 3 4 5 6 7 8 9

NAME
TX RX GND

TYPE
IN OUT IN POWER OUT POWER OUT

SIGNAL
TX serial line RX serial line

PIN #
1 2 3 4

SIGNAL
VBUS DD+ GND

+15V WKATX

Isolated power supply 15V5% 80mA max ATX power supply wakeup

COMMUNICATION SLOTS The UPS has two panel expansion slots for slot-in interface accessories that can be used for a variety of communications options including: Second RS232 port Serial port duplicator Ethernet network agent with TCP/IP protocol, HTTP and SNMP RS232 + RS485 port with JBUS/22#MODBUS protocol For further accessory information please visit our website. Layout of Slots on the SR 10M to 20M SR 10T to 80T Layout of Slots on the SR 100T to 120T

Front side

Front side

17

AS400 PORT

PIN # 1 15 2 8

DESCRIPTION 15V GND REMOTE ON REMOTE OFF

TYPE POWER POWER INPUT #1 INPUT #2

FUNCTION Isolated auxiliary power supply +15V 5% 80mA max Ground for the isolated auxiliary power supply (15V) and remote controls (Remote ON, Remote BYPASS, Remote OFF) By connecting pin 2 with pin 15 for at least 3 seconds the UPS switches on By connecting pin 8 to pin 15 the UPS is shut down immediately By connecting pin 7 to pin 15 the load power supply switches from inverter to bypass. For as long as the connection is made, the UPS continues to operate on bypass even if the input mains supply fails. If the jumper is removed with the mains power supply present, the UPS will resume operation and the load will be powered by the inverter. If the jumper is removed with the mains power supply fails, the UPS will resume operation on battery power. Reports that the batteries are at the end of discharge when (1) contact 5/12 is closed Reports that the UPS is operating on battery power when contact 6/14 is closed When the contact is closed, reports that the UPS is blocked
(1)

REMOTE BYPASS

INPUT #3

4,5,12 6,13,14 9,10 3,11

BATTERY LOW BATTERY WORKING LOCK BYPASS

OUTPUT #1 OUTPUT #2 OUTPUT #3 OUTPUT #4

When the contact is closed, reports that the bypass supply is powering the load

NOTE: The diagram shows the contacts present inside the UPS that can provide a maximum current of 0.5A at 42Vdc. The position of the contacts in the diagram is shown without alarms or warnings.
(1)

The output can be programmed through the appropriate configuration software. The function shown is the default (configured by the manufacturer).

18

> 9.1 EMERGENCY SHUTDOWN (R.E.P.O.)


This isolated input is used to switch off the UPS in an emergency. The UPS is supplied with the "Remote Emergency Power Off" (R.E.P.O.) terminals short circuited. At installation, remove the short-circuit and connect to the normally closed contact of the shutdown device , using a double-insulating cable. When activated from a remote push-button or other device in an emergency, the R.E.P.O connection opens and the UPS switches to stand-by mode. The UPS no longer powers the load. The R.E.P.O circuit is supplied with SELV type circuits. No external supply voltage is required. When it is closed (normal condition), a maximum current of 15mA flows. After an emergency shutdown, the UPS will return to on-line operating mode only when it receives a startup command from the mimic panel (provided that the Remote Emergency Power Off device is not still active).

> 9.2 EXTERNAL SYNCHRONISATION


This non-isolated input can be used to synchronise inverter output with a suitable signal from an external source. It is essential when the SR10-120 is used in combination with Static Switch Transfer Systems. At installation, it is important to: use an isolation transformer with isolated single-phase output (SELV), 12-24ac and power = 0.5VA connect the transformer secondary to the "EXTERNAL SYNC" terminal through a double-insulation cable with cross-sectional area of 1 sq.mm. After installation, UPSTools can be used to configure and control this feature.

EXTERNAL SYNC

SYNCHRONY FROM UPS OR SYNCHRONY FROM GE OR SYNCHRONY FROM MAINS

UPS IN/OUT CONNECTION CARD

> 9.3 MONITORING AND CONTROL SOFTWARE


The UPS is supplied with UPS Network Monitoring UPS monitoring and control software to provide the following: Chronological event recording UPS operating status management E-mail, modem, SNMP agent support Sequential shutdown and load-shedding within a network environment

> 9.4 CONFIGURATION SOFTWARE


The UPSTools software package allows complete UPS configuration through an RS232 serial port, In the table overleaf: CP (Control Panel)=Shows that the configuration can be modified using UPSTools or the front control panel. SW (Software)=Shows that this configuration can be only modified through UPSTools.

19

FUNCTION
Output frequency

DESCRIPTION
Selection of the nominal frequency output

PRESET
Auto

POSSIBLE CONFIGURATIONS
50 Hz 60 Hz Auto: automatically selected from the input frequency 200V * 208V * 220V 230V 240V 220 to 240 in steps of 1V (only through software) ON LINE ECO SMART ACTIVE STAND-BY OFF FREQUENCY CONVERTER (only through sotware) Disabled 1 to 255 in steps of 1 second Enabled Disabled Min.: 1 second - Max.: 30 seconds

MOD. CP

Output voltage Phase Neutral

Selection of the nominal voltage

output

230V

CP

Modes of operation

Selection of one of the 4 different operating modes

ON LINE

CP

Switch-on delay

Delay time for automatic switching-on after the mains is restored Starts the ramp return mode from the mains Setting of the ramp duration when the mains is restored (only if Power Walk-In is enabled) Automatic shutdown of the UPS when battery-operated, if the load is lower than 5% Maximum time on batteryoperation Estimated remaining backup time before end of discharge pre-alarm Time range for automatic testing of batteries the the

5 seconds

CP

Power Walk In

Disabled

SW

Duration Power Walk In

10 seconds

SW

Shutdown due to minimum load Back-up time limit

Disabled

Enabled Disabled Disabled (batteries discharged) 1 to 65000 in steps of 1s 1 to 255 in steps of 1 minute totally

CP

Disabled

SW

End of discharge pre-alarm Battery Test

3 minutes

SW

40 hours

Disabled 1 to 1000 in steps of 1 hours Disabled 0 to 103 in steps of 1% Normal Limited:does not sound temporary bypass operation

SW

Alarm threshold for maximum load Buzzer

Selects the user limit for overload Selects the buzzer mode operation Selects the operating mode for the auxiliary socket

Disabled

SW

Limited

CP
for

Auxiliary Socket (power share)

Always connected

Always connected Disconnected after n seconds of battery operation Disconnected after n seconds from the end of discharge prealarm ... (see UPSTools manual)

SW

20

FUNCTION
Battery expansion

DESCRIPTION
Setting of the Ah installed (expansion of the external battery) It selects the display language

PRESET
0 Ah

POSSIBLE CONFIGURATIONS
Min.: 0 - Max.: 999 (in steps of 1 unit)

MOD.
CP

Language

English

English Italian German French

Spanish Polish Turkish Chinese

CP
Others languages available with different firmware version

Advanced Functions
Input frequency tolerance Selects the admitted input frequency range for the bypass transfer and output synchronization Selects the permissible voltage range for bypass transfer 5% 0.25% 0.5% 0.75% 1 to 10 in steps of 1% SW

Bypass voltage thresholds

Low:180V High:264V

Low: 180 to 200 in steps of 1V High: 250 to 264 in steps of 1V

SW

Bypass voltage thresholds for ECO

Selects the permissible voltage range for ECO operating mode

Low:200V High:253V

Low: 180 to 220 in steps of 1V High: 240 to 264 in steps of 1V

SW

Action sensitivity for ECO

Selects the operation sensitivity during ECO mode operation Load power supply on bypass with UPS off (stand-by state) Selects the operating mode of the bypass line

Normal

Low Normal High Disabled (not powered) Enabled (powered)

CP

Load power supply in stand-by

Disabled (load NOT powered)

SW

Bypass operation

Enabled / High sensitivity

Inverter synchronisation (External Sync) Inverter synchronisation speed at the bypass line External temperature probe (optional)

Selects the synchronisation source for the inverter output Selects the inverter synchronisation speed at the bypass line Enables reading of the external temperature probe

From line

bypass

Enabled / High sensitivity Enabled /Low sensitivity Disabled with input / synchronisation Disabled without input / synchronisation From bypass line From external input

SW output output SW

1 Hz/second

0.5 Hz/second 1 Hz/second 1.5 Hz/second 2 Hz/second Not enabled Enabled

SW

Not enabled

SW

* Setting these output voltage values will lead to the reduction of the output power of the UPS (see Reducing the load (at 200V and 208V) paragraph) ** Pressing the F1 and F4 keys at the same time for t > 2 sec will automatically reset English as the language.

21

10 - UPS CABINET
The cabinet is made of galvanised steel with an IP20 rating (degree of Ingress Protection), even with the front door open. Ventilation via the rear panel; air intake is front to rear. The main assemblies (including the power module and magnetics) are temperature monitored.

11 - OPTIONS
> 11.1 COMMUNICATION
PowerNETGuard is a centralised UPS management and control software package using the SNMP communications protocol. It is the ideal UPS management tool for IT/EDP managers running datacenters and medium-to-large-sized networks. The main features of the software include: Various display levels by geographical areas, building plans, maps. Multi-user accesses with various security levels. Compatible with RFC 1628 standard SNMP agents. Graphical representation and file backup of operating measurements Notification of alarms via email and SMS. Integrated Wap Server for display of alarms. Suitable for operation with Windows operating systems: (98, ME, NT, 2000, 2003, and Xp) Linux, Mac OS X, Solaris 8 and 9.

Hardware
Two slots are available in which to house one or two of the following options: a) NetMan 102 Plus: the NetMan Plus network agent allows UPS management across a LAN using any of the main network communication protocols - TCP/IP, HTTP and network interface (SNMP). NetMan Plus enabled UPS integrate easily into medium and large sized networks and provide reliable communications between the UPS and management systems employed. b) MultiCom 302: a Modbus/Jbus protocol converter through an RS232 or RS485 output for monitoring the UPS, for example, from a BMS (Building Management System). It also provides a second independent RS232 serial line that can be used by other devices such as a NetMan Plus or PC. c) MultiCom 352: it is a serial duplexer that allows two devices to be connected to a single serial port on a UPS.It can be used where numerous serial connections and multiple UPS polling are required, and is ideal for LAN networks with a firewall.. d) Multicom 382: it provides a set of relay contacts to provide UPS alarm and status indication. The contacts are connected through terminal connections. Signal contacts include Emergency Power Off (EPO), Remote Shut Down (RSD), On Battery, On Bypass, Alarm and Low battery. The contacts are change over or normally open.

22

e) Multicom 401: it is an external accessory with which you can connect a UPS to a Profibus DP network. With this device management and monitoring of the UPS can be integrated in a control system based on one of the field buses most widely used in industry for communication between control/automation systems and distributed I/O . f) Multi I/O Card: Multi I/O has configurable input and output signal contacts to allow UPS integration with control systems. It can be used to connect two devices to a single UPS serial communication port. It can also communicate using the MODBUS/JBUS protocol on RS485 lines.

g) Multicom 362: MultiCOM 362 provides a UPS with an additional RS232 serial interface or USB port. The USB port allows the UPS to communicate with Apple Macintosh computers as well as Windows and Linux operating systems. h) Multicom 372: MultiCOM 372 provides a UPS with an additional RS232 serial interface port. The card has Emergency Power Off (EPO) and Remote Shut Down (RSD) inputs with terminal connections. i) j) Usb Converter: the converter allows UPS without a USB port to connect to Macintosh, Windows and Linux PCs with this type of port. Kit for AS400 and i-Series: the IBM AS/400 has a single-level memory management feature that makes it compulsory for the system to be shutdown in a controlled and orderly manner. Without UPS protection an AS/400 is not protected from mains failures. A momentary loss of power can cause hardware damage, data corruption and a lengthy reboot period. The GTEC UPS AS/400 interface kit allows a UPS to be connected to the AS/400 to initiate an orderly system shutdown on mains failure.

k) Multi Panel: MultiPanel is a remote monitoring device that can provide a detailed UPS status overview in real time. It is compatible with all GTEC UPS and can display values for UPS specific input and output supplies, and battery set measurements. MultiPanel has a highdefinition graphical display and can report in 7 languages: English, Italian, German, French, Spanish, Russian and Chinese. It has 3 independent serial ports, one of which allows for UPS monitoring via the MODBUS/JBUS protocol (on either an RS485 or RS232 serial line). The 3 others can be used with devices such as the Netman 101 Plus or a PC running PowerShield software.

23

> 11.2 EXTERNAL BATTERY TEMPERATURE SENSOR


The UPS has a special entry point for measuring the temperature inside a remote Battery Box and indicating the temperature on the UPS display. The specific kit supplied by the manufacturer includes a bipolar double isolated cable measuring 6 meters. The use of a bipolar cable without isolation exposes the UPS and the user to risks resulting from a lack of isolation as the reading refers directly to the UPS neutral earthing. Once installed, the device is configured using the UPSTools software package supplied on the CD-ROM with the UPS.

> 11.3 EXTERNAL MAINTENANCE BYPASS


An external remote maintenance bypass can be installed with the UPS, to allow, for example, UPS replacement without disruption to the load. If this option is chosen, it is essential to connect the SERVICE BYPASS terminal located inside the UPS to the auxiliary Normally Open (NO) contact of the SERVICE BYPASS switch. Operation of the SERVICE BYPASS switch closes this auxiliary contact and informs the UPS. If such a connection is not made, operation of the remote maintenance bypass may disrupt the supply of power to the load and damage the UPS. Note: Always check that the remote maintenance bypass installation (if selected) is compatible with any transformer options selected for the UPS - see paragraph 11.6 Optional Transformer.

> 11.4 BATTERY CABINETS


This is an optional item. The battery cabinet can be used to extend an internal battery set runtime or provide an external battery set when the space within the UPS for an internal battery is populated with extended runtime chargers or transformer options. The number of batteries housed within the cabinet varies according to UPS rating. It is therefore necessary to carefully match that Battery Cabinet DC rating to that of the UPS. The Battery Cabinet configuration is shown below.

Some solutions that have been studied and are available in the catalogue for the 10-40kVA range are described below. Other solutions may be developed on site, bearing in mind that: -the structure of the battery enclosure must respect that described above. -the number of batteries must remain constant (20+20 12 volt monoblocks) -the battery capacity (expressed in AH) must fall within the range of 4 and 20 times the available recharging current (see the technical specifications table)

24

Battery Box SRT 10-40: (can be used on the entire range from 10 to 40 KVA)

BATTERY BOX MODELS

BB34009S2 BB34007S3 BB34009S3

BB4040S

BB4065S (replaced by BB40100B0)

BB40100B0

Dimensions (mm) H x WxD

Model Weight
Battery configuration

BB34009S2 300Kg (90 empty)


2 x 40 x 9Ah

BB34007S3 390Kg (90 empty)


3 x 40 x 7Ah

BB34009S3 400Kg (90 empty)


3 x 40 x 9Ah

BB4040S 730Kg (150 empty)


40 x 40Ah

BB4065S 1100Kg (200 empty)


40 x 65Ah

BB40100B0 200 empty

40 x 100Ah

> 11.5 ADDITIONAL BATTERY CHARGER


SR 10T 80T KVA model versions The SR10-120 UPS may be supplied with an additional battery charger in order to increase the battery recharge current. The additional battery charger is powered directly off mains power and therefore does not use any energy from the input stage or from the inverter. It is housed inside the SR030T and SR040T in the space normally dedicated to the batteries, therefore this option will be offered in alternative to the internal batteries and will not be available for installation at the client site. For 10 to 20kVA the batteries can be installed internally also with optional charger. The additional battery charger supplies 10 Amps per battery branch for 10 to 20kVA and 20A for 30 to 80kVA, it has a cable for communication with the UPS multiprocessor PCB which can manage the shutdown procedure.

25

> 11.6 OPTIONAL TRANSFORMERS


A transformer can be installed within the UPS battery compartment (removing the potential for an internal battery set). Transformer options include: supply neutral reference, Galvanic isolation and output voltage (stepup or down). ELECTRIC CONNECTIONS DIAGRAMS Note: An external transformer will modify the neutral arrangements of the installation. Therefore, if a "remote maintenance bypass is installed it must be sited downstream of the transformer (for an input-side transformer) or upstream (for an output-side transformer). UPS without variation of the neutral arrangements

UPS with Galvanic isolation on the input

UPS with Galvanic isolation on the output

26

Separate bypass supply input from a common mains or alternative power supply:
UPS without variation of the neutral arrangements and with a separate bypass supply input

Remove the jumpers present between the SWIN and SWBY isolating switches

UPS with Galvanic isolation on the input-side and separate bypass supply input

Remove the jumpers present between the SWIN and SWBY isolating switches

UPS with Galvanic isolation on the output-side and separate bypass supply input

Remove the jumpers present between the SWIN and SWBY isolating switches

27

Separate bypass on separated lines upstream:


If the separate bypass option is present, the protection devices will be installed both on the mains supply line and on the separate bypass line. Note: the neutral of the input line and that of the bypass are joined inside the equipment, therefore they will refer to the same potential. If the two mains supplies are different, it is necessary to use an isolation transformer on one of the inputs. UPS without variation of the neutral arrangement and with a separate bypass supply connected on the independent mains line

Remove the jumpers present between the SWIN and SWBY isolating switches

UPS with a separate bypass supply connected to an independent supply and with galvanic isolation on the input

Remove the jumpers present between the SWIN and SWBY isolating switches

UPS with a separate bypass supply connected to an independent mains supply and with galvanic isolation on the output

Remove the jumpers present between the SWIN and SWBY isolating switches

28

> 11.7 SEPARATE LINE INPUT


All the UPS versions in the range of 10-40 KVA models can be provided with input from the separate bypass line. This configuration can only be carried out in factory. For 60 120kVA model dual input connection but is connected with a jumper; simply remove the jumper link it can sepearte the bypass line from the Rectifier input line. This can be done at site.

12 - ENVIRONMENTAL CONDITIONS
Room ambient temperature Maximum temperature for 8 hours a day Average temperature over 24 hours Recommended working temperature for optimum battery performance Storage temperature 0 to 40 C 40 C 35 C 20 to 25 C - 25 up to +55 (UPS) C - 15 up to +40 (UPS with battery) C

13 - TECHNICAL DATA 10-120 KVA THREE-PHASE OUTPUT


UPS Power (kVA)
Mechanical Characteristics Dimensions (mm): L x D x H 440 x 850 x 1320 Weight (Kg) Ventilation Cabinet IP rating Cable input Colour 105 110 115 120 135 145

10

12

15

20

30

40

60

80

100

120

500 x 850 x 1600 190 200

750 x 855 x 1900 370 380

Forced through internal fans 20 From the bottom/On the rear RAL 7016

29

UPS Power (kVA) Electrical data INPUT


Nominal voltage
(1)

10

12

15

20

30

40

60

80

100

120

380-400-415 Vac Three-Phase plus neutral

Input Current

20

24

29

38

54

70

104

138

182

215

Voltage range (without switching to battery power) Nominal frequency Input frequency tolerance Total Harmonic distortion (THDi) and power factor with full load Rectifier progressive start-up (Power Walk-in duration) Delayed switching
(1)

320 to 480 V at 100% of the load 240 to 480 V at 50% of the load 50 or 60Hz 40 to 72Hz THDi 3% , 0.99 pF THDi 2,5% , 0.99 pF THDi 3% , 0.99 pF

Programmable from 5 to 125 seconds in steps of 1 second (this function is disabled by default) Programmable from 1 to 255 seconds in steps of 1second. (5 seconds by default)

The input current is stated for the following general conditions: - Output load at 0.9pF - Input voltage at 346 Volts - A 4A (10-20kVA); 7A (30-40kVA); 10A (60-80kVA); 25A (100-120kVA) battery charger UPS Power (kVA)

Electrical data
10 DC BUSBAR AND BATTERY SET
Number of battery cells Float voltage (2.27 V/el. adjustable) Boost voltage (2.4 V/el. adjustable) End of discharge voltage load dependent (1.6 V/el. adjustable) Recharge current max value (A) Full load 90% Load Additional Battery Charger (See note 11.5) 4A 6A 10 A 7A 10 A 20 A 10 A 10 A 20 A 25 A 25 A Consult us 120+120 274+274 Vdc 288+288 Vdc 192+192 Vdc

12

15

20

30

40

60

80

100

120

30

UPS Power (kVA)

Electrical data
10 INVERTER
Nominal power (kVA) Active power pF 0.9 (kW) Active power with load power factor from 0.9 inductive to 0.9 capacitive (kW). Nominal voltage Derating for output voltage (Phase Neutral) set to: 208 V 200 V Nominal frequency Static stability Dynamic stability Recovery Time within 1% Crest factor (Ipeak/Irms as per EN 62040-3) Voltage distortion with linear load (EN 62040-3) Frequency stability without Inverter and by-pass supply synchronisation Rtae of Frequency variation Voltage phase Dissymmetry with balanced and unbalanced loads Voltage phase shift with balanced and unbalanced loads Overload at 0.9pF at 0.8pF Short circuit current Efficiency on battery-operation
(1)

12

15

20

30

40

60

80

100

120

10 9 9

12 10.8 10.8

15 13.5 13.5

20 18 18

30 27 27

40 36 36

60 54 54

80 72 72

100 90 90

120 108 108

380/400/415 Vac Three-Phase plus neutral

-5% - 10 % 50 / 60Hz 1% 0.5%

3% (1) (resistive load) EN62040-3 class performance 1 distorting load 20ms In compliance with standard EN 62040-3, class 1 3:1 1% with linear load 3% with distorting load 0,01% 1Hz/sec (adjustable from 0.5 to 2) 1% / 2% 120 1 2% with linear load 4% with distorting load

up to 110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds 115% infinite, 125% for 10 minutes, 150% for 1 minute, 168% for 5" 1.5 x In for t=500 ms 92,5% 93,5% 95,3% 95% 93%

@ Mains / battery / mains @ resistive load 0% / 100% / 0%

31

UPS Power (kVA)

Electrical data
10 12 15 20 30 40 60 80 100 120

BY-PASS
Nominal voltage 380-400-415 Vac Three-Phase plus neutral

Output nominal current (A)

15

17

22

29

43

58

87

116

145

174

Bypass voltage range

from 180V (adjustable 180-200) to 264 V (adjustable 250-264V)

Nominal frequency Bypass input frequency range Transfer time from By-pass to Inverter (UPS in "ECO mode") Transfer delay to Inverter from Bypass

50 to 60Hz 5% (adjustable from 0.25 to 10%) 2 ms typical 4 sec 110% infinite >110% 133% for 60 minutes >133% 150% for 10 minutes >150% for 2 seconds

By-pass overload capacity (kVA)

Max current in short-circuit for 20ms

1000 A

2000A

4000 A

4600 A

32

UPS Power (kVA)

Electrical data
10 12 15 20 30 40 60 80 100 120

SYSTEM
AC/AC Efficiency (On line) (%) 93,5 93,0 91,8 89,3 220 93,6 93,3 92,4 89,8 220 94,0 93,8 93,0 91,6 240 94,0 94,0 93,8 91,6 240 96,1 96,2 96,1 95,0 240 96,0 96,2 96,2 95,7 240 95,4 95,5 95,5 94,6 455 95,2 95,6 95,6 94,9 455 93.6 94,0 93.7 92.3 1160 93.5 94,0 93.8 92.5 1280

Full load 75% Load 50% Load 25% Load


Auto-consumption (W) Efficiency with UPS in STAND-BY mode Audible noise at 1mt (from 0 to full load) -(dBA) Operating temperature Max. relative humidity during operation

98 % 48 dB (A) 52 dB (A) 48 dB (A) 0 40 C 90% (without condensation)

99,1 % 56 dB (A)

98.6 % 70 dB (A)

Max. installation altitude

1000 m at nominal power (- 1% reduction in power for every 100m over 1000m) Max 4000m
0.63kW 540 kcal/h 2150 B.T.U./h 0.75 kW 645 kcal/h 2560 B.T.U./h 0.86 kW 740 kcal/h 2940 B.T.U./h 1.15 Kw 990 kcal/h 3930 B.T.U./h 1.10 kW 946 kcal/h 3755 B.T.U./h 1.50 kW 1290 kcal/h 5120 B.T.U./h 2,61kW 2245 kcal/h 8910 B.T.U./h 3,65kW 3140 kcal/h 12460 B.T.U./h 6,9 kW 5933 kcal/h 23550 B.T.U./h 7,2kW 6191 kcal/h 24578 B.T.U./ h

Power dissipated with resistive nominal load (pf=0.8) and backup battery* Fan capacity in installation room for dissipating heat ** Max current leaked to earth ***

340 m/h

400 m/h

460 m/h

615 m/h

587 m/h

800 m/h

2100 m/h

2100 m/h

2600 m/h

2600 m/h

5 mA

50 mA

100 mA

*3.97 B.T.U. = 1 kcal **To calculate air capacity the following formula can be used: Q [mc/h] = 3,1 x Pdiss [Kcal] / (ta - te) [ C] P diss is the power dissipated by the UPS (expressed in Kcal) within the installation environment. ta= room temperature, te= external temperature. 10% must be added to the derived figure to take into account system losses. In the above table an example is shown of capacity with (ta - te)=5 C and a resistive nominal load (pf=0.9). PS: This formula can be applicable if ta>te; otherwise, the installation will require air conditioning. ***The dispersion current of the load is added to that of the UPS on the ground protection conductor.

33

14 TECHNICAL DATA 10-20 KVA SINGLE-PHASE OUTPUT

UPS Power Modules (kVA)

Mechanical characteristics
10
Dimensions (mm): L x D x H 180Kg Weight with internal batteries (Kg) 305Kg version x

12

15

20

440 x 850 x 1320 182Kg 310Kg version x 190Kg 315Kg version x 195Kg 320Kg version x

Cooling Level of cabinet protection Cable entry Colour

Forced using internal fans IP20 Bottom, rear RAL 7016

UPS Power Modules (kVA)

Electrical Specifications INPUT


Nominal voltage 3-phase voltage input current ( ) 2 1-phase voltage input current ( ) Voltage range in the event the batteries do not take over Nominal frequency Input frequency tolerance Harmonic distortion (THDi) and power factor with full load Duration of Power Walk-in Delayed start up
2

10

12

15

20

380-400-415 Vac 3-phase with neutral or 220-230-240 Vac 1-phase 18 55 21 64 26 77 33 99

320 - 480 @ 100% load 240 - 480 V @ 50% load (3Ph) 184 - 276 @ 100% load 140276 V @ 50% load(1Ph) 50 or 60Hz from 40 to 72Hz THDi 3% , 0.99 Pf Programmable from 5 to 30 sec. in 1 second steps (standard value: the function is deactivated) Programmable from 1 to 255 sec. in 1 second steps (standard value is 5 seconds)

(1) The input current is referred to the following overall conditions: - Output load with 0.8 PF -Input voltage equal to 346 / 200volt -Battery charger current equal to 4 Amps

34

UPS Power Modules (kVA)

Electrical Specifications
10 12 15 20

DC INTERMEDIATE CIRCUIT
Number of iron elements Maintenance voltage (2.27 V/el., adjustable) Load voltage (2.4 V/el., adjustable) End of discharge voltage dependent on the load (1.6 V/el., adjustable) Max. recharge current value (A)) Full load 90% load 4A 6A 6A 120+120 274+274 Vdc 288+288 Vdc 192+192 Vdc

Additional battery charger (See note 11.5)

35

UPS Power Modules (kVA)

Electrical Specifications
10 12 15 20

INVERTER
Nominal power (kVA) Active Power, Pf 0.8 (kW) Active power with load power factor ranging from 0.8 inductive to 0.8 capacitive (kW) Nominal voltage Power derating with output voltage (Phase Neutral) set at: 208 V 200 V Nominal frequency Static variation
(1)

10 8 8

12 9.6 9.6

15 12 12

20 16 16

220/230/240 Vac single-phase with neutral

-5% - 10 % 50 / 60Hz 1% 3% (resistive load) EN62040-3 performance class 1 on distorting load 20ms Compliant with EN 62040-3, class 1 standards 3:1 1% with linear load 3% with non-linear load 0.01% 1Hz/sec (adjustable from 0.5 to 2)

Dynamic variation Restore time within 1% Current crest factor (Ipeak/Irms compliant with EN 62040-3) Voltage distortion with linear and non/linear loads (EN 62040-3) Frequency stability with unsynchronised inverter and bypass power supply Frequency variation speed Overload capability on output power at P.f. 0.8

110% for 10 minutes, 133% for 1 minute, 50% for 5 seconds 1.5 x In for t500 ms 92,5% 93,5%

Short circuit current Efficiency in battery mode (%)

(1)

@ Mains power/ battery / mains power @ 0% / 100% / 0% resistive load

36

UPS Power Modules (kVA)

Electrical Specifications
10 12 15 20

BY-PASS
Nominal voltage Nominal output current (A) Voltage range for switchover to bypass Nominal frequency Tolerance of the bypass input frequency Switchover from bypass to inverter in ECO mode Delay in transferring to inverter following the switchover to bypass mode Overload capability on bypass line power (kVA) P.f. 0.8 43 220-230-240 Vac 1-phase 52 65 87

from 180V (180-200 adjustable) to 264 V (250-264V adjustable) 50 - 60Hz 5% (adjustable from 0.25 to 10% ) Typically 2 ms 4 sec

110% infinite 133% for 60 minutes 150% for 10 minutes >150% for 2 seconds

37

UPS Power Modules (kVA)

Electrical Specifications
10 12 15 20

SYSTEM
AC/AC (On line) efficiency (%) Full load 75% load 50% load 25% load Auto-consumption (W) Efficiency with UPS in STAND BY mode Audible noise at 1mt (from 0 to full load) (dBA) Operating temperature Max. relative humidity during operation 48 dB (A) 0 40 C 90% (non condensing) 1000 m at nominal power ( - 1% power for every 100m above 1000m ) Max 4000m 0.58 kW 500 kcal/h 1980 B.T.U./h 0.69 kW 594 kcal/h 2355 B.T.U./h 0.79 kW 680 kcal/h 2700 B.T.U./h 1.02 kW 880 kcal/h 3495 B.T.U./h 93,3 92,7 91,7 87,6 220 93,5 92,9 92,2 90,2 220 98 % 52 dB (A) 93,8 93,2 92,6 89,8 240 94,0 93,3 92,8 91,0 240

Max. installation altitude

Power dissipated with resistive nominal load (pf=0.8) and backup battery*

Power dissipated with distorting nominal load (pf=0.7) and charged battery * Fan capacity in installation room for dissipating heat ** Max current leaked to earth ***

0.50 kW 430 kcal/h 1710 B.T.U./h 340 mc/h

0.58 kW 500 kcal/h 1980 B.T.U./h 400 mc/h

0.69 kW 594 kcal/h 2355 B.T.U./h 460 mc/h

0.90 kW 775 kcal/h 3070 B.T.U./h 615 mc/h

6 mA

*3.97 B.T.U. = 1 kcal **To calculate air capacity the following formula can be used: Q [mc/h] = 3,1 x Pdiss [Kcal] / (ta - te) [ C] P diss is the power dissipated by the UPS (expressed in Kcal) within the installation environment. ta= room temperature, te= external temperature. 10% must be added to the derived figure to take into account system losses. In the above table an example is shown of capacity with (ta - te)=5 C and a resistive nominal load (pf=0.9). PS: This formula can be applicable if ta>te; otherwise, the installation will require air conditioning. ***The dispersion current of the load is added to that of the UPS on the ground protection conductor.

38

www.gtec-power.eu www.gtec-power.com

39

You might also like