Instrumentation and Thermocouple Cables

Instrumentation Cables

Multipair/triad
Overall Screen
not armoured
PE/OS/PVC
XLPE/OS/LSZH

armoured
PE/OS/PE/SWA/PVC
XLPE/OS/LSZH/SWA/LSZH

Applications
Can be used in cable tray or conduit to connect electrical instrumentation
and communication circuits in industrial process controls, refineries, oil
and gas plants.

Cable construction
Conductors

Plain annealed electrolytic copper wire according to EN 60228 class 1(U)


solid, class 2 (R) stranded, class 5 (F) flexible.

Insulation

PVC, PE, XLPE or LSZH thermoplastic material.

Twisting

The insulated cores shall be twisted in pairs/ triads for a good reduction
of the electromagnetic noise.

Cabling

The pairs/triads are cabled with suitable non hygroscopic fillers (when
necessary) and wrapped with polyester tape if required.

Overall screen

Aluminium/polyester tape, coverage >100%, aluminium in contact with


tinned copper drain wire.

Inner sheath

PE, PVC or LSZH thermoplastic material.

Armour

armoured

Single layer of galvanized steel wires (SWA).

Outer sheath

PVC or LSZH thermoplastic material.

Operating temperature
-20 C to +80 C (for general use);
-40 C to +90 C (on request).

Minimum bending radius


Not armoured type:
12 times the outer diameter (for conductors class 1 and class 2);
10 times the outer diameter (for conductors class 5).
Armoured type:
15 times the outer diameter.

Applicable Standards
BS 5308 or EN 50288-7 Basic design
IEC 60332-1
Flame retardant
IEC 60332-3
Fire retardant (cat. C or A according to
requirements)
IEC 60754-1
Halogen free properties (only for LSZH cables)
IEC 61034-2
Low smoke emission (only for LSZH cables)

Available on request
Tinned conductors.
Moisture barrier.
Galvanized steel wire braid (GSWB) or galvanized steel tape armour
(GSTA).
Different insulation and sheath colours.
Sheath materials can be provided for excellent water, oil, hydrocarbons,
UV resistance or other special performance.

12

Instrumentation Cables
Multipair/triad Overall Screen

Multipair according to BS 5308 (300/500 V)


UNARMOURED
Cross section
(mm2)

0,5 mm2 solid


1x2x0,5
2x2x0,5 (quad cabled)

ARMOURED

Outer diameter

Weight

Diameter under
armour

(mm)

(kg/km)

(mm)

U-PE/OS/PVC
6.3

Outer diameter

Weight

Capacitance

L/R

(mm)

(kg/km)

(pF/m)

(H/Ohm)

U-PE/OS/PE/SWA/PVC
50

6.3

10.7

200

115

25

7.1

75

7.1

11.5

260

115

25

5x2x0,5

11.6

200

11.6

16.2

460

75

25

10x2x0,5

15.0

270

15.0

20.7

790

75

25

15x2x0,5

17.1

370

17.1

22.8

1100

75

25

20x2x0,5

19.4

440

19.4

26.0

1280

75

25

30x2x0,5

23.0

630

23.0

29.8

1520

75

25

50x2x0,5

28.9

980

28.9

36.1

2100

75

25

0,5 mm2 flexible

F-PE/OS/PVC

F-PE/OS/PE/SWA/PVC

1x2x0,5

7.0

60

7.0

11.4

250

115

25

2x2x0,5 (quad cabled)

7.9

80

7.9

12.3

300

115

25

5x2x0,5

13.1

210

13.1

17.9

560

75

25

10x2x0,5

17.2

340

17.2

22.9

970

75

25

15x2x0,5

19.8

440

19.8

26.4

1240

75

25

20x2x0,5

22.3

570

22.3

29.1

1640

75

25

30x2x0,5

26.9

780

26.9

33.9

1770

75

25

50x2x0,5

33.9

1130

33.9

42.1

2770

75

25

1 mm2 solid

U-PE/OS/PVC

U-PE/OS/PE/SWA/PVC

1x2x1

7.4

85

7.4

11.8

290

115

25

2x2x1 (quad cabled)

8.4

115

8.4

13.0

345

115

25

5x2x1

14.2

290

14.2

19.7

790

75

25

10x2x1

17.4

500

17.4

24.3

1310

75

25

15x2x1

21.3

670

21.3

28.1

1740

75

25

20x2x1

24.4

950

24.4

31.2

2040

75

25

30x2x1

29.0

1030

29.0

36.2

2180

75

25

50x2x1

37.3

1750

37.3

45.7

3500

75

25

1,5 mm2 stranded

R-PE/OS/PVC

R-PE/OS/PE/SWA/PVC

1x2x1,5

8.3

100

8.3

12.6

320

120

40

2x2x1,5 (quad cabled)

9.7

150

9.7

14.3

420

120

40

5x2x1,5

16.4

360

16.4

22.1

940

85

40

10x2x1,5

21.6

690

21.6

28.4

1500

85

40

15x2 x1,5

25.2

880

25.2

32.2

1970

85

40

20x2x1,5

28.5

1230

28.5

36.5

2400

85

40

30x2x1,5

34.3

1560

34.3

42.5

3170

85

40

50x2x1,5

43.6

2400

43.6

53.4

5020

85

40
approximate values

Cavicel, Conducting Value

13

Instrumentation and Thermocouple Cables

Multipair according to EN 50288-7 (300 V)


UNARMOURED

ARMOURED

Outer diameter

Weight

Diameter under
armour

(mm2)

(mm)

(kg/km)

(mm)

0,5 mm2 stranded

R-XLPE/OS/LSZH

Cross section

Outer diameter

Weight

Capacitance

L/R

(mm)

(kg/km)

(pF/m)

(H/Ohm)

R-XLPE/OS/LSZH/SWA/LSZH

1x2x0,5

6.2

44

6.2

10.7

229

150

25

4x2x0,5

11.7

121

11.7

16.3

458

150

25

6x2x0,5

13.8

168

18.5

553

790

150

25

12x2x0,5

16.7

254

16.7

21.6

728

150

25

15x2x0,5

19.3

349

19.3

24.2

893

150

25

24x2x0,5

23.8

530

23.8

29.5

1380

150

25

0,75 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x2x0,75

6.4

48

6.4

10.9

241

150

25

4x2x0,75

12.2

136

16.9

483

460

150

25

6x2x0,75

14.5

191

14.5

19.2

594

150

25

12x2x0,75

18.2

338

18.2

23.1

845

150

25

15x2x0,75

20.4

412

20.4

25.3

986

150

25

24x2x0,75

25.2

626

25.2

30.9

1524

150

25

1 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x2x1

6.9

57

6.9

11.3

260

150

25

4x2x1

13.3

171

13.3

18.0

552

150

25

6x2x1

15.6

234

15.6

20.3

670

150

25

12x2x1

19.9

425

19.9

24.8

988

150

25

15x2x1

22.1

516

22.1

27.8

1308

150

25

24x2x1

27.3

789

27.3

33.2

1780

150

25

1,5 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x2x1,5

7.7

74

7.7

12.1

299

150

40

4x2x1,5

14.8

229

14.8

19.7

664

150

40

6x2x1,5

17.4

317

17.4

22.3

816

150

40

12x2x1,5

22.2

581

22.2

28.1

1389

150

40

15x2x1,5

24.8

718

24.8

30.7

1621

150

40

24x2x1,5

30.6

1102

30.6

36.7

2239

150

40
approximate values

14

Instrumentation Cables
Multipair/triad Overall Screen

Multitriad according to EN 50288-7 (300 V)


UNARMOURED

ARMOURED

Outer diameter

Weight

Diameter under
armour

(mm2)

(mm)

(kg/km)

(mm)

0,5 mm2 stranded

R-XLPE/OS/LSZH

Cross section

Outer diameter

Weight

Capacitance

L/R

(mm)

(kg/km)

(pF/m)

(H/Ohm)

R-XLPE/OS/LSZH/SWA/LSZH

1x3x0,5

6.5

54

6.2

10.7

229

150

25

2x3x0,5

10.9

101

11.7

16.3

458

150

25

6x3x0,5

15.7

226

18.5

553

790

150

25

12x3x0,5

20.2

402

16.7

21.6

728

150

25

15x3x0,5

22.4

497

19.3

24.2

893

150

25

24x3x0,5

27.9

760

23.8

29.5

1380

150

25

0,75 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x3x0,75

6.8

60

6.4

10.9

241

150

25

2x3x0,75

11.4

113

16.9

483

460

150

25

6x3x0,75

16.5

259

14.5

19.2

594

150

25

12x3x0,75

21.3

476

18.2

23.1

845

150

25

15x3x0,75

23.5

576

20.4

25.3

986

150

25

24x3x0,75

29.3

885

25.2

30.9

1524

150

25

1 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x3x1

7.4

74

6.9

11.3

260

150

25

2x3x1

12.4

142

13.3

18.0

552

150

25

6x3x1

18.0

330

15.6

20.3

670

150

25

12x3x1

23.1

598

19.9

24.8

988

150

25

15x3x1

25.7

739

22.1

27.8

1308

150

25

24x3x1

32.2

1154

27.3

33.2

1780

150

25

1,5 mm2 stranded

R-XLPE/OS/LSZH

R-XLPE/OS/LSZH/SWA/LSZH

1x3x1,5

8.1

94

7.7

12.1

299

150

40

2x3x1,5

13.7

180

14.8

19.7

664

150

40

6x3x1,5

20.1

450

17.4

22.3

816

150

40

12x3x1,5

25.9

836

22.2

28.1

1389

150

40

15x3x1,5

28.8

1033

24.8

30.7

1621

150

40

24x3x1,5

36.4

1612

30.6

36.7

2239

150

40
approximate values