Subject: WellPad Clash Reporting Procedures
1.2. Once your new session file is created select Run Report from the Tools pulldown menu
Rev. 0
Page 2 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
1.3. From the Catalog Reports tab expand Types of Reports folder and pick Clash folder then
select Clash Detection by Volume (Full Object Path & PG) - SLOW report. Click Run.
Rev. 0
Page 3 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
Ensure that the folder structure begins with a plant number as seen in the following screenshot.
Selecting a volume from any other folder structure may not include all clashes for the selected
module.
Note: If the volume corresponding to the area to be clashed does not exist, the volume must be
created, naming it appropriately. Ensure that the volume is saved to the proper folder location.
Rev. 0
Page 4 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
1.6. The default Volume name will appear as IFC Reports Filter. Rename this to be the Module
Volume that was previously selected
1.7. Final step is to save the report. From the File pulldown select SaveAs. The folder is
.....\CADD\Piping\Clash Reports and the filename will be the same name as Volume name
(e.g. 170-PR-1101.xls).
Rev. 0
Page 5 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
2. Reviewing/Approving Clashes
2.1. Open SmartPlant and use the appropriate template from the PADS tab to create a new session
file.
2.2. Define workspace with the area/module you wish to check clashes on.
2.3. Select Check Interference from the Tools pulldown if it is not already selected.
2.4. When Check Interference is active the following toolbar will be active.
Rev. 0
Page 6 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
The following section deals with this toolbar and is for information purposes only.
2.4.1. The first button,
, is Settings. Deselecting anything on this page will filter the clash
list. Do not deselect more than None under Required Action, this will not display any
false clash.
Page 7 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
2.5. Review all clashes where Required Action is UNDEFINED, if the clash selected is a valid
clash, set Required Action to EDIT-must resolve. . and fix clashing by revising the model.
Once model is fixed, clash will not be shown in the list again. If the clash is a false clash ( e.g.
Insulation of 2 pipe runs at a tee) change the Required Action to be NONE and add the
appropriate comment in the Notes column. To review all clashes with required action set to
NONE, select (check) the None box in step 1.4.1.
Review all clashes where Required Action is EDIT must resolve. ., if the clash selected is
a valid clash, investigate why model clash is not yet fixed. Coordinate with other disciplines to fix
clash. Once model is fixed, clash will not be shown in the list again. If the clash is a false clash
( e.g. Insulation of 2 pipe runs at a tee) change the Required Action to be NONE and add the
appropriate comment in the Notes column. To review all clashes with required action set to
NONE, select (check) the None box in step 1.4.1.
NOTE: Required Action can ONLY be set to NONE or EDIT.
Rev. 0
Page 8 of 9
3/23/2015
SmartPlant SP3D
Subject: WellPad Clash Reporting Procedures
2.6. Checker MUST review all clashes with Required Action set to NONE status prior to any
IFC issue.
Rev. 0
Page 9 of 9
3/23/2015