Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RP 32-6 Inspection and Testing of In-Service Instrumentation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

RP 32-6

INSPECTION AND TESTING OF


IN-SERVICE INSTRUMENTATION
July 1994

Copyright The British Petroleum Company p.l.c.

Copyright The British Petroleum Company p.l.c.


All rights reserved. The information contained in this document is subject to the terms
and conditions of the agreement or contract under which the document was supplied to
the recipient's organisation. None of the information contained in this document shall
be disclosed outside the recipient's own organisation without the prior written
permission of Manager, Standards, BP International Limited, unless the terms of such
agreement or contract expressly allow.

BP GROUP RECOMMENDED PRACTICES AND SPECIFICATIONS FOR ENGINEERING


Issue Date
Doc. No.

RP 32-6

July 1994

Latest Amendment Date

Document Title

INSPECTION AND TESTING OF


IN-SERVICE INSTRUMENTATION
APPLICABILITY
Regional Applicability:

International

SCOPE AND PURPOSE


This Recommended Practice gives general guidance for assessing the condition of
operating instrument systems by focusing on their inherent and functional integrity.
Its purpose is to give guidance on those requirements considered essential for assessing inservice instrumentation integrity, from which more specific requirements can be developed
by site engineers.

AMENDMENTS
Amd
Date
Page(s)
Description
___________________________________________________________________

CUSTODIAN (See Quarterly Status List for Contact)

Inspection
Issued by:-

Engineering Practices Group, BP International Limited, Research & Engineering Centre


Chertsey Road, Sunbury-on-Thames, Middlesex, TW16 7LN, UNITED KINGDOM
Tel: +44 1932 76 4067
Fax: +44 1932 76 4077
Telex: 296041

CONTENTS
Section

Page

FOREWORD ............................................................................................................... iii


1. INTRODUCTION................................................................................................... 1
2. SCOPE..................................................................................................................... 1
3. INSPECTION ORGANISATION .......................................................................... 2
3.1 Managements Responsibilities.............................................................................. 2
3.2 Inspection Authority Responsibilities ................................................................ 3
3.3 Operating Authority Responsibilities .................................................................... 3
3.4 Inspection Staff (Inspectors) ................................................................................ 4
3.5 External Inspection Authorities............................................................................ 4
3.6 Engineering Co-operation .................................................................................... 5
3.7 Competent Personnel........................................................................................... 5
3.8 Audit Function..................................................................................................... 5
4. GENERAL REQUIREMENTS .............................................................................. 5
4.1 Introduction......................................................................................................... 5
4.2 Identification/ Registration................................................................................... 5
4.3 Support Documentation....................................................................................... 6
4.4 Programmes and Procedures................................................................................ 6
4.5 Protective Systems Documentation ...................................................................... 7
4.6 Records ............................................................................................................... 7
4.7 Alteration of Trip and Alarm Settings .................................................................. 8
4.8 Disarming and Overriding Trips ........................................................................... 8
5. INSPECTION AND TEST PLAN .......................................................................... 8
5.1 Introduction......................................................................................................... 8
5.2 Procedures........................................................................................................... 9
5.2.1 Preparation .............................................................................................. 9
5.2.2 Approach ................................................................................................. 9
5.2.3
Approval................................................................................................ 11
5.2.4
Review................................................................................................... 11
5.2.5 Control ........................................................................................................... 11
5.3 Scheduling......................................................................................................... 11
5.3.1 Factors Affecting Test Frequency............................................................12
5.3.2 Review....................................................................................................13
5.3.3 Inspection and Test Deferrals ..................................................................13
5.4 Reporting .......................................................................................................... 14
5.4.1 Report Sheet ...........................................................................................14
5.4.2 Management Status Review ....................................................................15

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE i

6. REGIONAL ANNEX ............................................................................................ 16


6.1 United Kingdom ................................................................................................ 16
APPENDIX A.............................................................................................................. 17
DEFINITIONS AND ABBREVIATIONS .............................................................. 17
APPENDIX B.............................................................................................................. 21
LIST OF REFERENCED DOCUMENTS............................................................... 21

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE ii

FOREWORD
Introduction to BP Group Recommended Practices and Specifications for Engineering
The Introductory Volume contains a series of documents that provide an introduction to the
BP Group Recommended Practices and Specifications for Engineering (RPSEs). In
particular, the 'General Foreword' sets out the philosophy of the RPSEs. Other documents in
the Introductory Volume provide general guidance on using the RPSEs and background
information to Engineering Standards in BP. There are also recommendations for specific
definitions and requirements.
Value of this Recommended Practice
This document represents the accumulated practices of the BP Group Companies for ensuring
a high standard of integrity assessment of instrumentation systems on in-service plant, within
the constraints for cost effective engineering.
Application
Text in italics is Commentary. Commentary provides background information which supports
the requirements of the Recommended Practice, and may discuss alternative options. It also
gives guidance on the implementation of any 'Specification' or 'Approval' actions; specific
actions are indicated by an asterisk (*) preceding a paragraph number.
This document may refer to certain local, national or international regulations but the
responsibility to ensure compliance with legislation and any other statutory requirements lies
with the user. The user should adapt or supplement this document to ensure compliance for
the specific application.
The Regional Annexe of this document refers to national or international regulations.
However, the responsibility for ensuring compliance with legislation and any other statutory
requirements lies with the user. The user should adapt or supplement this document to ensure
compliance for the specific application. Also listed within the annexe are documents to which
reference may be made for more detailed information.
Principal Changes from Previous Edition
This Recommended Practice is a major revision of BP Engineering CP 52 - Inspection and
Testing of Plant in Service which was last revised in January 1991 and which has now been
split into four separate documents and updated to give more constructive guidance on the
requirements for assessing the integrity of in-service instrumentation.
Feedback and Further Information
Users are invited to feed back any comments and to detail experiences in the application of
BP RPSE's, to assist in the process of their continuous improvement.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE iii

For feedback and further information, please contact Standards Group, BP International or
the Custodian. See Quarterly Status List for contacts.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE iv

1.

INTRODUCTION
This document is one of a series of Recommended Practices, which provide guidance
on the essential requirements for ensuring the integrity of all equipment within the BP
group operating centres. In particular this document is aimed at the integrity
assessment of instrumentation systems on plants in service.
This Recommended Practice is written as a guide to those in the operating centres
with responsibility for ensuring plants are maintained in a safe and reliable condition.
Although primarily written for the maintenance engineer, design engineers also need to
be aware of the content in order that they may:(a)

provide the facilities necessary to perform these activities safely and


economically, and

(b)

take account of the practices during system reliability studies and communicate
recommended special requirements or departures from this code to the future
operating centre.

In developing this Recommended Practice, account has been taken of guidance given in
national/international codes and standards and established good industry (Petroleum/Chemical)
practices.

2.

SCOPE
This Recommended Practice gives general guidance for assessing the condition of
operating instrument systems by focusing on their :(a)

Inherent Integrity, including electrical protection, suitability for use in


hazardous areas and requirements for pressure containment.

(b)

Functional Integrity, for those instrument systems designed to give protection


against hazardous occurrences arising within process plants (i.e. trip and alarm
systems).

This Recommended Practice does not address the functional integrity of instrument
control systems, safety valves, bursting discs and mechanical machinery.
Factors considered include organisation responsibilities, equipment registration,
categorisation, procedures, frequency of inspection, reporting, recording and basic
inspection and test requirements.
Contained in the regional annex at the rear of the practice is guidance on particular
national legislation. Also contained in Appendix B is a listing of documents which
may be used for reference purposes to support the recommendations of this practice.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 1

It is of paramount importance that instrument systems installed for the protection of plant, personnel
or environment will operate correctly and reliably when a potentially hazardous condition is
approached. Instrument systems may remain static and not be called upon to operate for long
periods of time. Also component failure and deterioration may not be apparent to operators going
about normal duties. It is therefore necessary to carry out the regular programmes of inspection
and test contained within this document to ensure the protective instrumentation will function
correctly when called upon to do so.
Although not specifically covered by this document, it is also required that the inspection and test
programme for instrumentation should satisfy the plant requirements for availability and reliability.
Where the correct functioning of an instrument is critical to the operation of a plant, and plant
downtime incurs significant cost penalties, the inspection and test programme for the instrument will
be directed towards plant availability requirements, in addition to safety and integrity
considerations.

3.

INSPECTION ORGANISATION
3.1

Managements Responsibilities
It is the responsibility of management at each centre to:(a)

ensure that installed equipment is suited for its current service


and that it is in a safe condition to operate.

(b)

have confirmed that new equipment has been designed


constructed, installed and tested according to good engineering
practices, and that documentation to this effect is available.

(c)

ensure compliance with national statutory regulations applicable


to design, inspection, test and certification of equipment.

(d)

to have an organisation in place with responsibilities allocated


for ensuring that the integrity of the facility is maintained in
accordance with guidance given in this Recommended Practice
and relevant statutory regulations.

The senior manager at each centre should delegate the responsibility,


and the authority, for the correct application of this code and statutory
regulations to those persons having the necessary competencies. These
delegated responsibilities should be detailed in writing with recipients
formally declaring their understanding and acceptance.
Where for organisational reasons (devolved management) the responsibilities for
inspection are fragmented, and the accountability for inspection can be conflicting
with operational pressures , it is advisable to delegate a person or department a
monitoring and/or audit function. It is important that those given the monitoring
and/or audit role are technically capable of appreciating the significance of any
deficiencies and that they have direct access to senior management for the
resolution of any serious conflicting issues.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 2

3.2

Inspection Authority Responsibilities


The responsibilities of the instrument inspection authority are:-

3.3

(a)

to identify, categorise and register equipment requiring


inspection and test.

(b)

to prepare appropriate procedures and schedules for the


inspection and test of each item of equipment.

(c)

to ensure that appropriately detailed records of each item or


system subject to inspection and test are maintained.

(d)

to ensure the compilation and updating of a trip register for all


protective instruments.

(e)

to monitor the implementation of inspection and test


programmes and ensure management is advised of any
departures from the agreed inspection requirements for the
plant.

(f)

to ensure that the inspection procedures and schedules remain


appropriate following repairs, modifications, changes in
operating conditions or renewals of equipment.

(g)

to be assured of the competence of persons engaged in the


inspection of instrument systems.

(h)

to continually assess the effectiveness of the programmes and


adjust where optimisation can be affected or deficiencies need
to be addressed.

(i)

to ensure recurring deficiencies are highlighted for re-design or


upgrading considerations.

Operating Authority Responsibilities


(a)

to carry out the inspection of instrumentation systems in


accordance with the schedules and procedures defined by the
inspection authority and to provide complete and accurate
results and findings.

(b)

to provide details of any difficulties experienced in following the


procedures or in achieving the test programme.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 3

3.4

Inspection Staff (Inspectors)


For instrument systems the inspection function is normally undertaken
by instrument technicians (or equivalent). These can be company
employees, contractors or manufacturers employees. Which ever is
employed, it is important for them to be technically and practically
competent. In addition they should have high personal integrity to
ensure a professional approach to the function.
Where indirect employees such as contractors are employed to perform
the inspection function, it is important that contract documents clearly
define:-

3.5

(a)

the requirements in terms of competency and integrity for the


inspection personnel, with contract companies asked to
demonstrate the compliance of their staff to the BP contract
supervisor's satisfaction.

(b)

the demarcation of responsibilities with respect to who is


responsible for accepting the inspection findings,
recommendations, taking action and compiling reports.

(c)

Who is responsible for gaining occupation and achieving safe


isolation of the systems to be inspected.

External Inspection Authorities


In some countries statutory regulations require companies to use
independent inspection bodies. It is also possible for BP to elect to use
such organisations.
Where an external inspection body is used, the BP Inspection Authority
will normally be responsible for ensuring:(a)

that management is advised of all requirements for statutory


inspection

(b)

that all records of the examination are made available to BP.

(c)

that recommendations for repairs, renewals and refurbishment


etc. are adequately discussed and agreed with BP.

The statutory regulations express only the minimum necessary to satisfy


safety requirements. The documentation supplied by an external
inspection body following their examination is essentially a certificate
that states that the examination has been performed and that the
requirements of the legislation have been met. When the scope of the

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 4

inspection is not sufficient for BP purposes, and provided the statutory


authorities have no objection, the external inspection may be
supplemented by additional work, to be performed at the same time.
3.6

Engineering Co-operation
Every opportunity should be taken to optimise the use of resources and
plant outage times by integrating inter discipline inspections.
Therefore, organisations should be flexible to allow close links between
inspection organisations.

3.7

Competent Personnel
Personnel engaged on the testing and inspection of equipment must
have:(a)

practical and theoretical knowledge and actual experience of the


type of equipment, to enable them to carry it out effectively.

(b)

an understanding of the process implications of their actions and


the possible hazards involved in order that it can be done safely.

(c)

the ability to recognise when specialist advice or assistance is


needed to assess the importance of serious non-conformity.

It is possible that corporate or incorporate bodies e.g. Insurance


companies, manufacturers or contractors etc. may be appointed to
carry out inspection and test programmes. For such organisations the
above is equally applicable. Therefore, before such organisation are
appointed they must be able to assure BP that their personnel can meet
this level of competency. Where assurances cannot be given, training
(possibly joint) may be necessary to accommodate deficiencies.
3.8

Audit Function
To ensure the approach to system integrity is satisfactory, a department
with responsibility for assessment should commission independent
audits.

4.

GENERAL REQUIREMENTS
4.1

Introduction
This section outlines the general requirements for an inspection and test
system, including documentation and records. Because of the wide
diversity of operations, equipment and conditions, this practice cannot
provide the test and inspection requirements in detail for all the

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 5

instrument systems likely to be encountered. It does however, set out


the principles and procedures for establishing those requirements.
4.2

Identification/ Registration
A register should be compiled of equipment requiring regular
inspection and test. Each item should be uniquely identified (Tagged)
and registered before being taken into service.

4.3

Support Documentation
The support documentation listed below should be readily available to
those engineers preparing and implementing inspection and test
procedures. These are items of general plant documentation and
should be verified, modified when necessary and issued in accordance
with site authorisation procedures.
(a)

Instrument Data Sheets containing a detailed reference to every


item of equipment forming part of the system, including:(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)

Manufacturer
Type or Model
Serial numbers
Range and operating parameters
Reference to special materials of construction
Reference to special equipment requirements (e.g.
response time)
Date installed
Purchase order reference
Reference to hazardous area requirements

(b)

P&I drawings showing the basic arrangements of the plant


control and protection systems.

(c)

Functional description and schematic diagrams providing the


manner/sequence of events in which each instrument system is
designed to operate, with any test override or defeat facilities
highlighted.

(d)

Loop drawings showing the extent and interconnection of all


elements within the loop.

(e)

Wiring diagrams, where not fully detailed on the loop drawing.

(f)

Modifications register allowing the modification history of each


instrument system to be examined.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 6

(g)

4.4

Documentation showing software links to advanced control


schemes and software controls (pump autostart facilities).

Programmes and Procedures


Test programmes and procedures should be developed and maintained
in accordance with the site authorisation procedures. Guidance in the
preparation of test and inspection programmes and procedures is given
in section 5 of this Recommended Practice, but should include:-

4.5

(a)

Test Procedures to be applied to each loop or instrument within


the plant.

(b)

Test Programme which schedules the inspection and test


requirements for each instrument/system on the plant by
reference to the approved procedures.

Protective Systems Documentation


In particular for protective systems the following requirements apply:(a)

The test procedures for trips and alarms should include


functional loop checking together with the inherent integrity
checks.

(b)

A settings register should be compiled relating all current trip


and alarm settings by tag number. A tolerance should be
quoted for each setting, against which an instrument can be
calibrated and subsequently tested. A verified up-to-date copy
of the settings register should be readily available to the tester
to supplement the appropriate testing procedures.
Initial settings will have been assigned by the designer having paid due
regard to the plant design specifications and operating conditions. Once
allocated, trip and alarm settings should not be altered without
independent engineering analysis carried out by the relevant design
authority. The settings register should be controlled in accordance with
site authorisation procedures.

(c)

4.6

Cause and effect diagrams conveying the logic or functionality


of the protective instrumentation.

Records
A file or other suitable record should be established for all items of
equipment to be regularly tested/inspected. The record system should
contain a history of all inspection, testing, modification and
maintenance carried out on the system. For Category 1 and 2A
protective systems in particular, this history shall provide evidence,
RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 7

where necessary, to third parties or statutory bodies, that all reasonable


steps have been taken to ensure the integrity of the instrumentation.
The records must be kept in a safe place and be readily available to staff
responsible for operation, maintenance and inspection. Alteration and
updating should be carried out in accordance with the company's site
authorisation policy.
Records should be maintained in a manner that will allow subsequent
reliability and availability analysis to be performed on the system or its
component parts (refer to BP Group RP 50-2). This can be most
effectively carried out with the aid of a computerised Maintenance
Management System (MMS).
Where records are maintained on a computer based system, Category 1
and 2A documentation associated with the last test of systems or
devices shall be maintained as a hard copy record, signed and dated by
the competent person carrying out the Inspection and test.
As an aid to the management of the inspection and test programmes,
the MMS should provide summary reporting of overdue and future
inspection and test.
4.7

Alteration of Trip and Alarm Settings


Normally changes to trip and alarm settings will not form part of
routine test and inspection programmes. However, where testing
justifies a change, it should be subject to investigation and ratification
through the sites design change procedure.
To accommodate alterations to software driven trips a procedure
paying particular attention to the control and recording of such changes
must also be available.

4.8

Disarming and Overriding Trips


Where disarming or override facilities are installed for maintenance
purposes a procedure giving precise instructions for their use must be
available to inspectors. The implementation of these procedures must
be rigorously controlled to prevent inadvertent operation. For this
purpose their use should be logged in and out and controlled under a
permit system including check signatures.
The use of temporary disarming and override techniques (e.g.
'jumpers', 'frigs' etc.), is to be discouraged. When a temporary override
is essential, its use should be approved and controlled by the operating
authority, having consulted with the design authority as appropriate.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 8

Where an override facility is required for routine testing or inspection


then a correctly engineered solution should be provided.
The fitting of any trip override should be seen as a modification to the
trip system.
5.

INSPECTION AND TEST PLAN


5.1

Introduction
It is a fundamental requirement that all instrument systems are regularly
tested and/or inspected to ensure that their inherent integrity is
maintained. In addition, there is a requirement that protective
instruments are regularly tested to prove their functional integrity.
The need for inherent integrity assessment is justified on the basis that functional
testing alone does not normally confirm inherent integrity.

For each instrument/system there should be an Inspection and Test Plan


designed to establish the required integrity on a regular basis. The main
elements of the Inspection and Test Plan will be:(a) Procedures

Written descriptions of the test and/or


inspection work sequence necessary to
establish integrity.

(b)

Schedule

A programme for arranging the regular


implementation of procedures.

(c) Reporting

A reporting system
results/findings.

5.2

Procedures

5.2.1

Preparation

recording

the

Procedures for assessing the integrity of instrument systems must be


compiled by competent persons who are familiar with the system to be
assessed, its design intent, components, operating principles, process
implications,
environment and
all factors contributing to its
performance and reliability.
5.2.2

Approach
For protective instrumentation it is not necessary to include the two
aspects of integrity assessment within one procedure. It is common
practice to separate the trip/alarm functionality test from the inherent
integrity assessment. This is particularly applicable where the function

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 9

testing intervals are relatively short compared to intervals required for


assessing the inherent integrity.
Functional and inherent inspections should be combined where possible when the
test requirements coincide.
Functional test procedures should detail the requirements for assessing the
complete system (loop) from the initiating sensor to the final trip element. When
this is not practicable, or when the sensor and final trip element have differing test
intervals, then a number of procedures detailing the assessment on a sectional
basis can be developed. The coverage of the sectional tests should overlap such
that all 'loop' elements from sensor through to final trip element are tested with full
functionality assured.

Procedures should be designed to minimise the physical disturbance of


the system i.e. disconnection of impulse lines and cables etc.
The preparation of procedures should take account of:(a)

Manufacturers recommendations

(b)

Designer's recommendations.

(c)

Company, National or International standards or codes of


practice.

(d)

Known equipment failure modes.

(e)

Criticality of duty.

(f)

Environmental and process conditions.

(g)

Detection of covert failures, which cause loss of function on


demand.

(h)

Fault trees, where developed for Category 1 and 2A systems.

Guidance on the inherent integrity assessment of electrical systems can


be found in the relevant document in this series, BP Group RP 32-5.
Although primarily written for electrical systems the essential
requirements are equally applicable to instrumentation.
Procedures should be written in a standard format with information and
instructions clearly and concisely stated.
Each procedure shall be comprehensive, and require minimal reference
to other documents. Where reference to other data is unavoidable the
source shall be clearly identified.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 10

Procedures shall identify the need to obtain Operating Authority


sanction, normally controlled by a 'permit to work' system, before
commencing work. Each procedure shall identify and address safety
considerations, protective clothing, test equipment requirements,
isolation procedures, inhibits for on-line testing and precautions
necessary to carry out the test in a safe manner.
A brief summary of the system tests shall be included to ensure the
person conducting the test understands the scope of the work. Where a
system or test method is complex the procedure should contain step by
step instructions.
For Category 1 systems the procedures shall be established after a
systematic analysis to detect covert failures, which would cause failure
to act on demand (Fault trees, FMECA).
Calibration data necessary for the tests shall be included in the
procedure or the source of the data clearly identified.
A report sheet should be included with the procedure, see section 5.4.1
.
The steps necessary and responsibility for reinstating the trip or trip
system to normal operation should be identified in the procedure,
including de-isolation, removal of inhibits, handover to Area
Authority/Operating Authority and permit completion. The procedure
should indicate who must be informed if it becomes impossible to
reinstate the trip system within the expected time scale.
5.2.3

Approval
Prior to the issue and implementation of any procedure its:-

5.2.4

(a)

impact on operations in terms of possible interference or


resource commitment must be considered and agreed by the
relevant operating authority.

(b)

accuracy, practicality, purpose and fit must be checked and


approved by a technically competent person. In the case of new
system types where there may be no historical experience, the
endorsement may first require a ratifying first test.

Review
Periodically, procedures need to be reviewed and the ongoing fitness
for purpose established. Revisions should be approved as above and
registered with a revision number. It is important that the procedure

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 11

file or MMS data base is kept up to date with revisions. A recall


system for outdated procedures should be established.
5.2.5

Control
Each procedure should be allocated a unique identification number,
issue number and date. The number and location of copies should be
limited to the minimum required by the operating and
inspection/maintenance organisations. Unofficial copying should be
prohibited to prevent potential use of 'out of date' or inaccurate
procedures. This requirement is most easily achieved by the use of a
MMS.

5.3

Scheduling
For all instrument systems and their components, assessment must be
carried out on a regular basis. For this purpose inspection procedures
above must be organised into schedules.
Schedules should identify the equipment to be tested by its discrete
identification number, tag or loop reference. Against each system or
component the schedule should include:(a)

required procedure reference number,

(b)

periodic frequency

(c)

due date

During the preparation of the inspection and test schedules the


Operating Authority should be consulted and the timings and their
resource implications agreed.
Although paper systems can be used for scheduling, in view of the large number of
systems and components together with their different inspection requirements and
intervals the scheduling should be applied to computerised MMS

5.3.1

Factors Affecting Test Frequency


In designating test frequencies account must be taken of the following:(a)

Consequences of instrument failure and level of economic or


safety risk.
In particular for protective devices, the
categorisation of the instrument.

(b)

Availability requirement of associated plant.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 12

(c)

Operational history

(d)

Nature of known failure modes, in particular, whether


predominate failure modes are revealed or unrevealed.

(e)

Process conditions e.g. corrosion, waxing, scale, fouling and


erosion.

(f)

Environmental conditions e.g. humidity, vibration, dust etc.

Although conditions between installations can vary widely, there is nevertheless


some similarity between the application and performance of the same
instrument/systems at different sites. This is especially true for Instruments of
conventional design, proven performance and similar process plants. In these
cases, previous recorded history and failure rate data for similar instrumentation
from existing operational installations can be used to assist in specifying inspection
and test periods for new systems.
Table 1 gives a guide to the range of typical test intervals currently used in
standard applications. They should be adjusted accordingly where any unusual
circumstances apply or where process/environmental conditions are onerous. They
should not be taken as a definitive guide but should be adjusted to take account of
any statutory requirements and the factors listed above.
Category 1 and certain Category 2A systems require that a reliability analysis is
carried out at the design stage of all new projects. The required frequency for
proof tests will be stated in the analysis. Where an analysis has been carried out,
the stated frequency must be adopted, and under no circumstances be extended
without a full re-analysis and design authority approval.
Table 1 - Typical Test Intervals

Function
Fire Detectors/Alarms
Gas Detectors/Alarms
Automatic Fire/Gas Protection Systems
Heat Off Systems
Emergency Shutdown Systems
Over-Speed Trips
Purge Failure Trips
Flame Failure Trips (Self Checking)
Flame Failure Trips (Not Self Checking)
Remote Shutoff or By-pass Valves
Thermal Runaway Protection
Flow, Level, Press, Temp. Trips
Slide Valve Trips
Machinery Trips
Other Alarms
Plant Instrumentation

Test Intervals
(Months)
3 - 12
3- 4
6 - 12
6 - 12
3 - 12
12 - 24
6 - 12
12 - 24
6 - 12
6 - 24
6 - 24
3 - 12
3 - 12
6 - 24
12 - 36
12 - 60

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 13

5.3.2

Review
To ensure that inspection and test intervals are appropriate the
effectiveness of the programmes must be continually assessed and
adjusted where optimisation can be affected or deficiencies need to be
addressed.
The reason and justification for a change in test frequency should be
formally approved by the design and operating authorities. This
enables the changes made over the lifetime of a particular installation to
be identified and traced.
Plant modifications and operating condition changes must be
communicated to the design authority in order that the impact on the
related instrument systems and inspection programmes can be assessed.
When reviewing test frequencies, account should be taken of
modifications, recorded test results and failures, comments from the
testers and changes to operating conditions. Test periods may only be
increased when an analysis based on a significant number of test results
can demonstrate that the deterioration or failure rate of the equipment
justifies the extension. The significant number of test results can take
account of numbers of identical equipment items operating on similar
duties, in similar environments.

5.3.3

Inspection and Test Deferrals


In the interest of safety and efficient maintenance the agreed schedules
should only be deferred for operational convenience in exceptional
circumstances. Should deferrals be a regular occurrence, it must be
brought to the attention of the Senior Operating Manager, who should
investigate and address the causes of non-conformance.
Category 1 and 2A trip testing must not be deferred or allowed to
lapse.

5.4

Reporting
Reports of all inspection and tests carried out must be recorded and
stored on file. In BP facilities with large inventories of instrumentation
the use of computerised systems are essential for this purpose.
To facilitate accurate reporting, report sheets should be structured for
assisting the recording of the information required as the test
progresses.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 14

5.4.1

Report Sheet
To provide the above information the report sheet should include:(a)

the plant name and/or plant code if applicable.

(b)

the tag number(s) of all instruments under test.

(c)

the date of the test and name/title of the tester.

(d)

the reason for carrying out the inspection and test. This can be
a scheduled test, a test initiated due to a suspected fault or a
test following an incident where the system failed to respond.

(e)

any limitations imposed on the test by the operational


conditions prevailing.

(f)

a reference to the procedure used to carry out the test.

(g)

the test equipment used, noting the Serial Number and the date
of its last calibration.

(h)

the test results as required by the procedure; expected and


observed results should be recorded. It is important that 'as
found' results are always recorded whether within specification
or requiring adjustment. Similarly, where adjustment has taken
place the precise 'as left' result should be recorded. Coded fault
reporting should be introduced to facilitate subsequent data
analysis.

(i)

the general condition of the equipment and comments on the


accuracy and practicality of the inspection and test procedures.

(j)

a description of abnormalities, discrepancies or faults that led to


an out of tolerance or incorrect result.

(k)

a description of remedial action taken to resolve abnormalities,


discrepancies or faults.

(l)

a list of all components replaced and the reason for their


replacement. The replacement component shall be identified by
number, type and serial number as appropriate.

(m)

re-testing after remedial action shall be subject to all the above


conditions.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 15

5.4.2

(n)

the tester shall report any further action necessary to maintain


the long term integrity of the system.

(o)

an estimate of the total time the system was not available


because of testing, including necessary remedial work and retest.

(p)

the number of manhours spent on inspection/testing activity.

Management Status Review


A management reporting programme should be implemented to provide
regular monitoring of the inspection/testing functions. These reports
should be produced on a regular basis, possibly at monthly intervals.
Reports should give the status of inspection and test programmes
against areas of responsibility.
Analysis of test results shall be carried out to establish that performance
is better than the required level of systematic failures. The results
should be compared with assumptions made during risk analysis of
Category 1 and 2A systems. If actual performance is less than that
indicated by assumptions in the analysis then functional integrity should
be assessed and modification may be necessary.
Effective inspection and testing programmes are the company's assurance against
equipment failures or malfunctions causing unsafe conditions, a requirement also
imposed by legislation. Regular reports will give management the status of the
programmes on which appropriate management actions can be taken. They may
also be used as an effective demonstration to any outside bodies ( e.g. Insurance
assessors or statutory body inspectors) of the company's commitment to the
assurance of plant/systems integrity.

6.

REGIONAL ANNEX
This section supplements the foregoing international requirements, to
assist with application in the particular region identified.
6.1

United Kingdom
The following standards are relevant to the inspection and testing of
plant instrument systems.
IP Model Code 14

Institute of Petroleum, Model Code of Practice


Part 14 August 1980 Inspection and Testing of
Protective Instrumentation Systems

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 16

PES

Health and Safety Executive Programmable


Electronic Systems in Safety Related
Applications (Parts 1 and 2).

SI 1029

Offshore Installations (Emergency


Valve) Regulations 1989

EEMUA 160

Safety Related Instrument Systems for the


Process Industries (including Programmable
Electronic Systems), Publication 160

SI 2169

The Pressure Systems and Transportable Gas


Containers Regulations 1989.

SI 289

The Offshore Installations (Construction and


Survey) Regulations 1974.

Pipeline

Associated guidance document issued by the Department of Energy


Offshore Installations Guidance
on
Design, Construction and Certification.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 17

APPENDIX A
DEFINITIONS AND ABBREVIATIONS
Definitions
Standardised definitions may be found in the BP Group RPSEs Introductory Volume.
alarm

a measuring instrument connected to an


annunciation system monitoring the plant
conditions and bringing to the operators
attention plant conditions outside pre-set
operating bands.

category 1 system

an application where to meet the risk


acceptability criteria it is necessary to use a
Protective Instrument System and where failure
of the system to act on demand is likely to lead
to risk of serious permanent injury or loss of life
to one or more persons and where exposure to
such risks is significant and cannot be avoided.

category 2A system

an application where risks are controlled by a


Protective Instrument System and where failure
of the system to act on demand is unlikely to
result in serious injury or loss of life. Failure
may well however, result in extensive or
prolonged damage to the environment, major
economic
risk
due
to
loss
of
plant/production/product or penalty due to
uncontrolled release and cannot be effectively
avoided by operator intervention.

category 2B system

an application where risks are controlled by a


Protective Instrument System and where failure
of the system to act on demand would not result
in risk as defined for Category 1 or 2A systems,
but could result in undesirable disruption to
operating or process conditions.

competent person

is someone having: adequate training,


appropriate experience, sufficient theoretical and
practical knowledge, maturity of judgement and
professionalism to enable them to detect defects
or weaknesses in the equipment under test or
examination, assess their importance in relation

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 18

to the strength and functions of the particular


plant and seek such specialist advice and
assistance as will be required to enable them to
make the necessary judgement.
design authority

the person or persons appointed by the


Management to be responsible for the design
integrity of the facility.

functional integrity

the functional integrity of an instrument is its


ability to operate in the intended manner. As an
example, the intended function of a high pressure
switch might be to operate when the sensed
pressure reaches 50 2 barg.

hazard rate

the likelihood of a specified undesirable event


occurring within a specified time period. It may,
depending upon the circumstances, be expressed
either as a frequency (the number of events
occurring in unit time) or a probability in a given
time period.

inherent integrity

the inherent integrity of an instrument covers


those aspects of design and condition that allow
it to operate safely in a particular environment.
Examples of inherent integrity requirements are
electrical protection (MCB's), insulation,
earthing, hazardous area protection, pressure
containment capability and condition of the
equipment (physical damage, corrosion etc.).

inspection

a physical examination to determine the external


and/or internal condition of an item of
equipment.

inspectors

those persons appointed by the Management to


carry out the testing and inspection of
instrumentation in accordance with the approved
procedures.

inspection authority

the person or persons appointed by the


Management to ensure that the instrumentation
test and inspection programmes, and their
implementation, satisfy the design intent of the
facility and any applicable codes and standards.

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 19

management

the person or persons legally responsible for the


operating facility.

modification

any change made to the protective instrument


system or the plant which it is protecting.
Changes to hardware, software, settings or
operating conditions outside the original design
envelope would all be classed as modifications.

operating authority

the person or persons appointed by the


Management to be responsible for the operation
of the facility. The operation of the facility will
include the conduct of test and inspection
programmes.

override

device for deliberately rendering a trip system


inoperable for the purpose of on line testing and
maintenance, or for the controlled abnormal
operation of plant e.g.
the start up of
equipment. Such devices include defeat switches
and by-pass valves.

protective instrument systems

instrumentation provided to prevent losses of all


kinds, particularly in process upsets or
emergencies, as distinct from instrumentation
provided for normal process control. Included
in this definition are trip and alarm systems.

reliability

the probability that a system will respond


correctly if called upon to do so. Reliability is
often expressed as the system failure probability.

reliability analysis

an analysis carried out by recognised techniques


and generating a system failure probability.

software based system

(sometimes called Programmable Electronic


System (PES).
a system based on a computer* connected to
sensors and/or actuators on a plant for the
purpose of control, protection or monitoring.
* Computer, as used in this definition, includes
main frames, microprocessors and PLC's.

testing

the series of operations required to ensure that


any installed protective instrumentation acts in

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 20

accordance with its design intent and to reveal


any failures that may have occurred to the
protective instrumentation system.
trip

a measuring system operating protective devices


(actuators) and connected to an annunciation
device. The purpose of such a system is to sense
a hazardous condition, or a condition which may
become hazardous if no corrective action is
taken, and act to mitigate the effects of that
condition.

Abbreviations
FMECA
MMS

Failure Modes, Effects and Criticality Analysis


Maintenance Management System

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 21

APPENDIX B
LIST OF REFERENCED DOCUMENTS
A reference invokes the latest published issue or amendment unless stated otherwise.
Referenced standards may be replaced by equivalent standards that are internationally or
otherwise recognised provided that it can be shown to the satisfaction of the purchaser's
professional engineer that they meet or exceed the requirements of the referenced standards.
BP Group Documents
BP Group RP 32-5

Inspection and Testing of In-Service Electrical Plant


(replaces the relevant parts of BP CP 52)

BP Group RP 50-2

Guide to Reliability Analysis


(replaces BP CP 62)

Useful Documents not Referenced in this Recommended Practice


BP Group RP 30-5

Selection and Use of Equipment for Instrument Protection


Systems
(replaces BP CP 18)

BP Group RP 30-6

Process Design Guidance for Protective Instrument Systems


(replaces BP CP 48)

BP Group RP 32-3

Inspection and Testing of In-Service Civil and Mechanical Plant


- Management Principles
(replaces BP CP 52)

BP Group RP 32-4

Inspection and Testing of In-Service Civil and Mechanical Plant


- Technical Guidance
(replaces the relevant parts of BP CP 52)

BP Group RP 44-1

Over-Pressure Protection Systems


(replaces BP CP 14)

ISO 10418

Petroleum and Natural Gas Industries - Offshore Production


Platforms - Analysis, Design, Installation and Testing of Basic
Surface Safety Systems
(Based on API RP 14C)

IEC/SC 65A

Functional Safety Of Electrical/Electronic/Programmable


Electronic Systems. Generic Aspects

RP 32-6
INSPECTION AND TESTING OF
IN-SERVICE INSTRUMENTATION

PAGE 22

You might also like