Distribution System
Distribution System
They are only economical if one truly needs the giant size.
Utilization voltage:
66 kV -1100kV
Distribution:
33kV and below (some country up to 132 kV is
categorized as distribution.)
By Function:
Transmission:
Distribution:
includes utilization voltage and sources for these
including transformer & their source.
By Configuration:
Transmission:
Distribution:
FEED
ER
SERVI
CE
MAINS
SUBSTATIO
N
Generally from feeders no tapping is taken to the consumers, therefore
loading of current of theDISTRIBUT
feeders remains the same along its length.
Substation( Area Substation):
Primary Distribution System: It is the part of distribution system which operates at voltages
somewhat higher than general utilization
Handles large blocks of electrical energy than the average low voltage
consumers uses.
Criterion for primary voltage level??
The most commonly used primary distribution voltages are 33kv, 11
kv, 6.6 kv, and 3.3kv.
Due to economic consideration, normally primary distribution is carried
out by 3-phase 3-wire system ??
Secondary Distribution System: It is the part of distribution system at which the ultimate consumers
utilizes the electrical energy delivered to them.
Radial System
In this system, separate feeders radiate from a single substation and feed
the distributors at one end only.
The biggest advantage of the radial system configuration, in addition
to its lower cost, is the simplicity of analysis.
On debt side, radial feeder systems are less reliable than loop or
network systems because there is only one path between the
substation and the customer. Thus if any elements along the path fails,
a loss of power delivery results.
The end of the distributor nearest to the feeding point will be heavily
loaded.
The consumers at the distant end of a distributor would be subjected
to serious voltage fluctuations when the load on the distributor
changes.
Loop System
Loop system consists of a distribution design with two paths between the
sources (substations, service transformer) and customer.
The system is very reliable as each distributor is fed via two feeders.
This layout is often called European because this configuration is
preferred in Europe.
Equipment is sized and each loop is designed so that service can be
maintained regardless of where an open point is on the loop.
In terms of complexity, a loop feeder system is only slightly more
complicated than a radial system
A loop must be able to meet all power and voltage drop requirements
when fed from only one end, not both.
There are less voltage fluctuations at consumers terminals.
The major disadvantage of loop systems is capacity and cost.
Network system
The distribution network involves multiple paths between all points in
the network.
Power flow between any two points is usually split among several
paths, and if a failure occurs it instantly and automatically re-routes
itself.
Rarely does a distribution network involve primary voltage level
network design, in which all or most of the switches between feeders
are closed so that the feeder system is connected between
substations.
They are much more complicated, than other forms of distribution, and
thus more difficult to analyze.
It increases the service reliability.
Any area fed from one generating station during peak load hours can
be fed from the other generating stations. This reduces reserve
capacity and increases efficiency of the system.
Capacity limits design: Voltage drop & losses costs are seldom a
major concern
requiring large no. of feeders.
The load density is very high in urban. Thus the current flowing in
the conductor is very high. Before the criteria of voltage drop and
power loss violation, the current carrying capacity of the conductor
may be less than the current in the feeder. Thus, current carrying
capacity of conductor is the guiding factor for the load center
size. If the load center is chosen such that it doesnt exceed the
current carrying capacity of the conductor then it automatically doesnt
violate voltage regulation and power loss criterion.
For these reasons there are some common adaptations to work within
these design constraints as follows
For these reasons following there are some common adaptations to work
within these design constraints.