Installation & Setup VAV–SDA

Instructions
0001 Document ID: LTBT-VSDA-INST

Overview Power supply


The Alerton® BACtalk VAV-SDA™ is intended for use with variable air volume The VAV-SDA requires 24 VAC @ 65VA min. from a fused UL Listed Class 2
(VAV) boxes. It is a single-duct VAV controller with a differential pressure transformer (not provided). VAV-SDAs utilize a half-wave rectifier to convert the
transducer, five binary outputs, and one analog output. The five binary outputs AC power supply to onboard power. This enables multiple controllers with half-
are hot-switched 24 VAC @ 0.5A triac outputs. Analog output is DIP-switch wave power supplies to be powered from a single, grounded transformer. Refer
selectable between 0-10 volts and 0-20 mA. There are four 10-bit resolution to Figure 3, "VAV-SDA output wiring diagram," on p. 2 for details.
universal inputs.
Warning! Half-wave devices and full-wave devices can’t use the same
AC transformer. If a VAV-SDA shares power with another device, make
sure that the other device utilizes a half-wave rectifier and that polarity of
wiring is maintained.

Input wiring and configuration


Shielded, 18 AWG wire is required for all inputs and analog outputs to reduce
electrical interference (noise). A single-point grounding scheme that utilizes the
transformer or panel ground is recommended. Ground only one side of the
shield drain wire.
IN-0 supports an Alerton Microset™ or Microset II sensor. Other inputs do not
support the Microset or Microset II. IN-0 and IN-1 can be used for a Microtouch
sensor.
For more information, see "Input wiring and configuration tips" in the VLC
Fig. 1 VAV-SDA.
Installation and Wiring Guide (LTBT-TM-VLC).
Mounting
Warning! Do not ground shields to any terminal on the VAV-SDA
because any noise on the shield will be routed through the VAV-SDA circuit
Caution! Thoroughly read all instructions before mounting and wiring. board, potentially disrupting operation or damaging the VAV-SDA.
See the VLC Installation and Wiring Guide (LTBT-TM-VLC) for more
information. Always install equipment in accordance with the National
Electric Code, the instructions, and in a manner acceptable to the local
authority having jurisdiction.
Binary outputs (BOs)
See Figure 3, "VAV-SDA output wiring diagram," on p. 2 for details. For further
The VAV-SDA is suitable for indoor mounting only. If the unit must be installed in information on ideal wiring, see "Binary outputs (BOs)" in the VLC Installation
a location exposed to weather, use a water-tight, metallic, electrically-grounded, and Wiring Guide (LTBT-TM-VLC).
weatherproof enclosure. Make sure the location selected is dry and free from
electrical interference. Also ensure that technicians can access the unit. The Analog output (AO)
VAV-SDA can be mounted in any vertical or horizontal orientation.
See Figure 3, "VAV-SDA output wiring diagram," on p. 2 for details.

MS/TP LAN configuration


VAV-SDAs communicate on the site-wide BACnet system over a twisted-pair
MS/TP LAN, which uses the RS–485 signaling standard. VAV-SDAs are master
devices on the MS/TP LAN and can initiate communications with other devices.
Each VAV-SDA employs a high-quality RS–485 tranceiver and exerts ¼ unit load
on the MS/TP LAN. For details, refer to "MS/TP LAN configuration" in the VLC
Installation and Wiring Guide (LTBT-TM-VLC).

Fig. 2 Cover form dimensions for VAV-SDA.


VA V– S D A I ns t a ll at io n & S e t up I n s t ru c ti o ns

Transformer
24 VAC UL Listed Class 2 sized to include output loads.

Binary outputs (BOs)


Hot-switched, optically coupled triac outputs rated 24 VAC
@ 0.5A. Ground the BO return to the transformer or panel
ground. This reduces the chance of noise from contactors,
motors, VFDs, and other devices returning to the VAV-SDA.

Single-point common ground at


panel ground
When connecting power to the
VAV-SDA, ensure that one leg of
the transformer secondary
connects to a high-quality earth
ground and that the ground lug
(GND) directly above the 24 VAC
terminal on the VAV-SDA connects
to the same earth ground. Earth
ground can be a terminal (shown)
or bus-bar. Proper grounding is
essential for trouble-free
operation.

Warning! Do not ground


shields to any terminal on the
Analog output (AO) VAV-SDA because any noise or
The AO provides an electrical output signal in response to a transient voltages on the shield
will be routed through the VAV-
software control signal of 0–100. For the VAV-SDA, the AO is
SDA circuit board, potentially
configured with DIP switch 8 to provide either a current (0–
disrupting operation or
20mA) or voltage (0–10VDC) output. 18 AWG, shielded wire is damaging the VAV-SDA.
required for all AO connections. Ground one side of the shield
drain wire to the single grounding point.

Fig. 3 VAV-SDA output wiring diagram.

2 LTBT-VSDA-INST