MaxDNA Alarm Messages
MaxDNA Alarm Messages
MaxDNA Alarm Messages
Reference Guide
277558 Rev A1
Use this publication as a source for complete and accurate information that helps you better operate
or service Metso Automation MAX Controls equipment. Your comments and suggestions are
welcome.
Metso Automation MAX Controls
1180 Church Road
Lansdale, PA 19446
Attention: Manager, Technical Publications
Contents
Part I General Introduction
Preface ............................................................................................................................................ v
Chapter 1 ......................................................................................................................................... 1
Introduction .................................................................................................................................... 1
maxDNA System Alarm Classes .............................................................................................................. 1
Process Alarms ........................................................................................................................ 1
System Alarms ......................................................................................................................... 1
Alarm Configuration ................................................................................................................................. 2
Configuring Alarm Priorities ................................................................................................... 2
Viewing Alarm Messages ......................................................................................................................... 2
Alarm Summary Display........................................................................................................................... 3
Alarm Summary Menu Buttons ............................................................................................... 3
Alarm List Display................................................................................................................... 4
Printing Alarms Using Merged Events Program ....................................................................................... 5
Selecting Event Types ............................................................................................................. 6
Setting up EventMerge ............................................................................................................................. 7
Selecting EventMerge Settings ................................................................................................ 8
Printed Alarm Message Formats .............................................................................................. 9
Acknowledging and Silencing Alarms ...................................................................................................... 9
Using Keyboard Buttons ........................................................................................................................... 9
Acknowledge and Silence ........................................................................................................ 9
Defeat .................................................................................................................................... 10
Restore ................................................................................................................................... 10
Defeating and Restoring Alarms ............................................................................................................. 10
Using maxVUE Runtime Display Buttons ............................................................................................. 10
Chapter 2 ......................................................................................................................................... 1
How to Interpret ............................................................................................................................. 1
Process Alarms .............................................................................................................................. 1
Control Block Alarms ............................................................................................................................... 1
High Level Analog Input Alarms .............................................................................................................. 2
Data Block Alarms.................................................................................................................................... 3
Individual Alarm Cutouts ........................................................................................................ 4
Troubleshooting Process Problems ........................................................................................................... 4
Logged Process Alarm Format: ............................................................................................... 5
Chapter 3 ......................................................................................................................................... 1
How to Interpret ............................................................................................................................. 1
System Alarms ............................................................................................................................... 1
Part II ............................................................................................................................................... 1
Alarm Message ............................................................................................................................... 1
Reference Guide ............................................................................................................................. 1
Process Alarms ......................................................................................................................................... 1
Part III .............................................................................................................................................. 1
Alarm Message ............................................................................................................................... 1
Reference Guide ............................................................................................................................. 1
System Alarms ......................................................................................................................................... 1
Preface
The Alarm Reference Message Guide contains listings of all the process
and system related alarm messages you are likely to encounter in the
operation of a maxDNA system.
Part I of this publication introduces you to all the maxDNA alarm types,
alarm-related displays and alarm message formats appearing on displays
and on hard copy reports.
Part II provides a complete alphabetized listing of all the maxDNA
process alarm messages along with text explaining what they mean. Part
III provides a similar listing for system alarms.
This publication assumes you have installed the maxSTATION running
software Release 1.2.3 or later. This publication also assumes you are
familiar with the maxSTATION and the various display environments.
For more information about related topics, refer to the following
publications:
Book Title
maxSTATION Operator's Guide
Book Number
277557
Chapter 1
Introduction
maxDNA System Alarm Classes
maxDNA System lets you view two classes of alarms:
Process Alarms
System Alarms
Process Alarms
Process alarms consist of alarm messages associated with the process
itself. These consist of two types:
Process Limit Alarms
Process limit alarms are caused by values exceeding their
assigned limits. Alarm information consists of time, point
tagname and its long description, alarm text associated with the
alarm, current value of the point, alarm limit value, and the units
of measure for the point in alarm.
Process Status Alarms
Process status alarms are generated by points and programs at
DPUs. Alarm information consists of time, point tagname and its
long description, alarm type text and the alarm value.
System Alarms
System Alarms consist of alarm messages associated with the system
hardware. These consist of two types:
Station Diagnostic Alarms
Station diagnostic alarms are caused by maxSTATION or
Remote Processing Unit (DPU, I/O boards) faults, such as weak
batteries, card failures, etc. Alarm information consists of time,
Alarm Configuration
You may set up alarms and events to be detected when you create
configurations using maxTOOLS. The system then automatically detects
the alarms and events, processes them, and identifies them for display
and acknowledgment, logging, analysis, and optional archiving.
Introduction
All
Process
diagnostic\control
Process\system
diagnostic
System diagnostic
Process diagnostic
Alarm Class
Alarm Types
Process
Diagnostic/Control
Process
Process/System
Diagnostic
System,
Process
System Diagnostic
System
Process Diagnostic
Process
Process Control
Process
All
Process,
System
Introduction
Process alarms
System alarms
Operator actions
Sequence of events
Program generated events
Edit actions
PA
SY
OA
SQ
PG
EA
Description
Start/Stop Print
Purge
Re-Print
Event Filters
Introduction
Setting up EventMerge
To set up the EventMerge program, you must edit the EventMerge INI
File to select configuration and connections for each EventMerge
instance. From this file, you may modify the default settings that appear
on the EventMerge dialog window. The Events.ini file contains
descriptions and default assignments for each command. See next
section.
If you are satisfied with the current settings, it may only be necessary to
change the service names.The Events.ini file must be updated to include
the appropriate event service names for the target system.
The service name is typically _RTG_EVENT_dbm_name. Substitute the
correct DBM name after _RTG_EVENT. (Check the RRS dialog
window for a list of registered service names.)
To configure the INI file:
1. Copy the file, which resides in \Custom\Sbp, to a new name and then
make the desired changes. The EventMerge program accepts one
input parameter: the name of its INI file.
2. Edit the new file as desired.
3. After you create the new event INI, go back to the startup INI file,
locate the file Events.ini and change it to match the new filename.
The following entry appears in the Startup.ini file (in
\custom\sbp\startup.ini):
3, c:\MCS\Sbp\EventMerge.exe,
Events.ini, /Events.ini
EventMerge
Note: INI filename appears twice on the EventMerge line. Change both
occurences.
4. Shutdown the Startup program that resides in each maxSTATION
(StopStation) and restart to pick up changes in the Startup.ini file.
The EventMerge INI file is only read during EventMerge
initialization.
Note: To create multiple instances of EventMerge make additional
EventMerge entries in the Startup.ini file. Each EventMerge instance
should have its own customized events INI file by including a different
INI filename in each entry in the Startup.ini file.
What It Means
Service
PrintState
FileEnable
Delay
EventType
Hid
SERVICE = _RTG_EVENT_DBM1
SERVICE = _RTG_EVENT_DBM2
SERVICE = _RTG_EVENT_DBM3
SERVICE = _lss
The print state specifies whether events are sent to
the printer. Valid ; command values are ON or OFF.
The print state can also be toggled from the
EventMerge dialog box.
The file enable specifies whether events are written
to a file in the Custom/History folder. This feature
can only be specified here (no dialog box
capability). Valid command values are ON or OFF.
If FileEnable is set to "ON" a file name for printed
events can be specified. The filename should not
contain an extension (.log is added by the program).
If a filename is not specifed, "events" is used. Note
that EventMerge will append day text to the file
name.
Delay specifies how long the events are held in the
event list before being moved to the dialog window
and print file. Some delay is necessary so that
events can be listed in time order. If DELAY is
commented out, a delay of 20 seconds is used. A
delay of less than 15 seconds is not recommended.
Event types preceded by a semicolon will not be
printed or written to the event file.
Event types can also be enabled/disabled from the
EventMerge dialog box. The spelling of the Event
type command values shown below should not be
changed.
Up to 10 HID specifiers can be included here. (Not
yet supported)
Introduction
Printed Alarm Message Formats
The format of printed alarm messages is different from the format used
on maxSTATION alarm displays. Logged messages appearing on
hardcopy reports tend to include more information because the printed
format, unlike the more restricted maxSTATION screen format, can
accommodate larger fields. Refer to Chapter 3, "How to Interpret System
Alarms," and Chapter 2, "How to Interpret Process Alarms," for a review
of Alarm Summary display alarm message formats and how they differ
from hardcopy formats.
Restore
Restores all alarms on the currently selected block so that it can alarm
again. On the PC keyboard, the equivalent key is <Ctrl-F5>. See next
section.
Location
Description
Ack
Acknowledge Alarm
condition of the current point.
Ack Page
Alarm Summary
Introduction
Button
Location
Description
*Ack Point
Horizontal Toolbar
*Ack Top
Alarm Summary,
Alarm List
**Silence
Vertical Toolbar
* If an audible alarm is equipped, this action will silence the audible alarm.
** The Silence key only silences an audible alarm; the Acknowledge key both
silences and acknowledges the top most alarm on the list. maxSTATIONs not
equipped with sound boards and speakers may be configured to silence alarms
occurring at a maxSTATION playing the sound.
Chapter 2
How to Interpret
Process Alarms
A process alarm indicates that some portion of the process has gone
beyond its specified limits. When a point goes into alarm, the system
adds its tagname to the Alarm List and Alarm Summary displays, and
indicates the alarm condition on appropriate point-related pop-up
displays.
Each of the standard maxDNA functional blocks stored in the DPU
database has many alarm states and control conditions built into them,
which are set during the configuration process. This permits alarming
capability and an interlocking capability with other user-ready and userdefined blocks.
Setpoint LO
Process Variable LO
Deviation HI
Setpoint HI
Deviation LO
Alarm HI
Alarm (HI or LO)
Any limit exceeded
Link Failure (cannot communicate with I/O module)
Date
Tagname
Description
Message Text
Alarm Text
HH:MM:SS
MM:DD:YY
Up to 16
characters
Up to 32
characters
Alarm
Value
Limit
Date
Tagname
Description
Message Text
Alarm Text
HH:MM:SS
MM:DD:YY
Up to 16
characters
Up to 32
characters
Alarm
Value
Limit
Displayed process limit alarms and process status alarms are also
somewhat different from each other. Process limit alarms report:
Time the alarm occurred.
Tagname of associated point.
Name of point and alarm message text under the Description field.
Alarm type.
Current value of the point.
Alarm limit value.
Units of measure for the point.
The process status alarms format is similar to the process limit alarms
format as outlined above; however, because status alarms are associated
with digital type points, the Summary Display Limits field does not
apply and is not used.
Process alarm messages also appear in a hardcopy version that uses a
format somewhat different from the Alarm Summary Display format.
Because the printed format can accommodate 133 characters per line,
printed text may contain additional information. Refer to the following
figure to learn how to recognize logged process alarms:
severity
type
alm/clr
tagname
description
value
limit
long
title
18
16
16
38
32
Alm/clr
When an unacknowledged process alarm is logged, the characters alm
appear in this three-character wide field. If the alarm is acknowledged
or otherwise clears, the characters clr appear. If the line applies to an
edit action, the field is blank.
Description
Process Alarm message text, such as HiHi LoLo; Range High; and so
forth.
When this field applies to an edit action, the message text describes
an attribute that was edited.
Value Limit
When this field applies to a process alarm, it reports the current value
of the point and the alarm limit value.
When this field applies to an edit action, it reports that the limit was
changed; the new limit value along with the previous value limit
appear in this field.
Long Title
Long name of point.
To troubleshoot process alarms, you may access Point Data, Control, and
Detail pop-up displays to learn more about points in alarm and to make
quick adjustments to your process. When a process alarm occurs, the
alarm message will also appear on these displays.
Chapter 3
How to Interpret
System Alarms
System and Network Alarms
System diagnostic status alarms inform you of maxDNA system
hardware and software problems. Problems detected within a specific
module or station are classified as diagnostic failures. Problems with
communications are referred to as highway network alarms. DPU Bus
network alarms are further divided between DPU Bus network and
maxNET network communications problems. maxVUE Runtime System
Status displays show both alarm types.
System alarms appear along with process alarms on the Alarm Summary
Display and on the Alarm List. The format of displayed system alarms is
somewhat different from the format for process alarms; refer to the
previous chapter for a description of process alarm formats.
System alarms have the following format:
Time
Date
Tagname
HH:MM:SS
MM:DD:YY
Up to 16
characters
Text
Subsystem Name
Message Text
On the display, the subsystem reporting the fault and the message text
appear together under the Description field. The three fields to the right
of this field Type, Value, Limit apply to Process alarms.
System alarm messages also appear in a hardcopy version that uses a
format somewhat different from the Alarm Summary display format.
Because the printed format can accommodate 133 characters per line,
printed text may contain additional information.
Refer to the following figure to learn how to recognize logged system
alarms:
Size of field
date/time
severity
type
alm/clr
tagname
description
18
16
54
Part II
Alarm Message
Reference Guide
Process Alarms
Part II consists of an alphabetic listing of all maxDNA Process Alarm
messages. The following pages contain the actual message text
(appearing here in all upper case characters), the point or points which
can generate the alarm, and a description of what each process alarm
message means.
Process alarm message text for any given point appears in three versions:
16-character text used in alarm log
12-character text used in Alarm Summary displays
12-character text used in Detail pop-ups
All three versions are listed for each process alarm message entry.
Note: Points for which an alarm message is applicable include some
Control Blocks, which are no longer supported by maxDNA, but were
supported by the Models 582 and 585 Operator Stations. Those points
are identified using ** in the table.
ALM INRLOCK
ALARM INLK
ALM INTERLOC
ALM INTERLOC
this
alarm:
Binary
BACKED OVER
SEC ACTIVE
Backup
BACKUP
BACKUP
Point(s)
which
generate
**Receives (Control Blocks)
this
alarm:
Meaning:
This block is now receiving data
from the backup DPU of a backup pair,because
of a transfer of control in that pair.
BOTH LIMITS
BOTH LIMITS
BOTH LIMIT
Point(s)
which
generate
this
alarm:
Valve/Breaker Controller (Control Block)
Meaning:
CLOSED
CLOSED
in
Binary
Binary
Control
Process Alarms
COMM FAILED
COMM FAILED
Point(s)
which
generate
**Receives (Control Blocks)
Meaning:
CONF ERROR
COMM FAIL
this
alarm:
CONF ERROR
All Data
Meaning:
An illegal value has been entered
into one of the editable fields of a Data
Block.
DEV HIHI
DEV HIHI
DV HL
DEV LIMIT
Point(s) which
(Control Block)
generate
has
**Real
exceeded
the
alarm:
PID
DV
this
Meaning:
'Generic' alarm raised if the PID
algorithm has raised a deviation limit alarm
but the condition cleared before it was logged.
DEV LOLO
DEV LOLO
DV HL
DEVIATION
has
**Real
exceeded
the
DV
**Data
DEV HIGH
Point(s) which
(Control Block)
DV
generate
this
alarm:
PID
Meaning:
Deviation between process variable
and set point has exceeded the configured high
alarm limit.
DEVIATION LO
DEV LOW
Point(s) which
(Control Block)
DV
generate
this
alarm:
PID
DEV HIGH
DV
**Event
DEV LOW
DV
this
alarm:
**Event
Meaning:
Output minus the specified deviation
value has exceeded the configured deviation low
alarm limit.
DIGITAL ALRM
DIGITAL ALRM
ALARM
this
alarm:
All
ALARM
Digital
Meaning:
The output bit of the point has
become true and the algorithm is configured to
alarm.
Process Alarms
DISCREPANCY
DISCREPANCY
DISCREPANCY
Point(s)
which
generate
this
alarm:
Sequencer, Ramp Gen (Control Blocks)
Meaning: Either the first control block in a
'chain' of blocks (used to construct sequences
with more than 8 steps) is not the same type
as the others in the chain; or the control
block attempted to access a step which is
higher than allowed based on the number of
slots in the chain; or the control block was
trying to find the first 'off' step but either
could not find it or its number was greater
than 255.
DISCREP+TIM
DISCREP+TIME
DISC + TIME
Point(s)
which
generate
this
alarm:
Sequencer, Ramp Gen (Control Blocks)
Meaning:
A discrepancy alarm has occurred,
and the time in a particular step has exceeded
the allowed time.
DV HL
DV HL
DV
**Real
Meaning:
'Generic' alarm raised if the Real
Alarm algorithm has raised a deviation limit
alarm but the condition cleared before it was
logged.
DV RATE
DV RATE
DV R
**Real
FAIL
FAIL
in
Binary
Binary
Control
FAILED
FAILED
Backup
FALLING
FALLING
Analog
Meaning:
The output of the Data Block is
decreasing
at
a
rate
faster
than
the
configured Rate-of-Change limit.
HIGH ALARM
HIGH ALARM
ALARM HIGH
Analog
HIHI ALARM
HIHI ALARM
Analog
INP 1
INP
Analog
INP 2
INP
Analog
Process Alarms
INP 3
INP 3
INP
Analog
INP 4
INP
Analog
INP 5
INP
Analog
INP 6
INP
Analog
INP 7
INP
Analog
INP 8
INP
Analog
INPUT ALARM
INP
Analog
Meaning:
'Generic' alarm raised if the
control block has raised an input alarm but
the condition cleared before it was logged.
I1 LIMIT
I1 LIMIT
INP
Select
I2 LIMIT
INP
Select
INSTR HIGH
INST HIGH
Analog
INSTR LOW
INST LOW
Analog
Meaning:
Hardware failure alarm indicating
that the input is less than 0.5V on a 1V-5V
input.
Process Alarms
LEFT LIMIT
LEFT LIMIT
LEFT LIMIT
Point(s)
which
generate
Positioner (Control Block)
this
alarm:
Point(s)
Blocks
LINK FAILED
which
generate
LINK FAIL
this
alarm:
Data
Point(s)
Blocks
LOLO ALARM
which
generate
LOLO ALARM
this
alarm:
Data
LOW ALARM
ALARM LOW
Analog
NO MIN SPEED
NO MIN SPEED
in
NO MF/MR
Binary
Control
NO MF/MR
Binary
in
Binary
Binary
Control
NON CNG
INPT
in
NORMAL
Binary
Control
NORMAL
Point(s)
Blocks
which
Meaning:
normal.
NOT CLOSED
generate
Binary
this
NOT CLOSED
alarm:
Data
NOT CLOSED
Point(s)
which
generate
this
alarm:
Valve/Breaker Controller (Control Block)
Meaning: The 'closed' feedback input has not
gone true within the specified time limit.
Point(s) which generate this alarm:
Control (Control Block)
Meaning:
User-defined
Module ExCEL.
NOT OPEN
in
NOT OPEN
Binary
Binary
Control
NOT OPEN
Point(s)
which
generate
this
alarm:
Valve/Breaker Controller (Control Block)
Meaning:
The 'open' feedback input has not
gone true within the specified time limit.
NOT OFF
NOT OFF
NOT OFF
Reversing
Meaning:
Within 2 seconds of the start/stop
input going false the motor forward (or motor
reverse) input has not gone false; or the run
feedback input has not gone false within the
configured
time
limit
during
the
stop
sequence.
Process Alarms
Point(s) which generate this alarm:
Control (Control Block)
Meaning:
User-defined
Module ExCEL.
NOT OPEN/CLOSED
in
NOT OP/CL
Binary
Binary
Control
NOT OP/CL
in
NO OP+CLOSED
Binary
Binary
Control
NOT OP + CL
Point(s)
which
generate
this
alarm:
Valve/Breaker Controller (Control Block)
Meaning:
Both 'open' and 'closed' feedback
inputs are false.
NOT READY
NOT READY
NOT READY
Reversing
Meaning:
The 'motor ready' input goes false
while the motor is running, or during startup.
Point(s) which generate this alarm:
Control (Control Block)
Meaning:
User-defined
Module ExCEL.
NOT START
in
NOT START
Binary
OPEN T/C
OPEN T/C
Control
NOT START
Binary
in
Binary
Binary
Control
OPEN TC
Analog
DV
**Demand
Meaning:
Generic alarm indicating that the
point has generated either an output > input
alarm or an output < input alarm, but the
condition cleared before it was logged.
OUTPUT<INPUT
DV
**Demand
DV
**Demand
POS'N TMOUT
Point(s)
which
generate
Positioner (Control Block)
POS TIME
this
alarm:
Meaning:
The motor has been started and the
maximum positioning time has been exceeded.
POS+BOTH LIM
POS+BOTH LMS
Point(s)
which
generate
Positioner (Control Block)
POS BOTH
this
Meaning:
Maximum position time
exceeded and both limits are true.
POS+L LIMIT
POS+LEFT LM
Point(s)
which
generate
Positioner (Control Block)
alarm:
has
POS LEFT
this
alarm:
Meaning:
Maximum position time has
exceeded and the left limit is true.
been
been
Process Alarms
POS+R LIMIT
POS+RIGHT LM
Point(s)
which
generate
Positioner (Control Block)
POS RIGHT
this
alarm:
Meaning:
Maximum position time has
exceeded and the right limit is true.
PV HIGH HIGH
PV HIHI
been
PV HL
**Real
PV LOLO
PV HL
**Real
PV HIGH
PV
Analog
PV HL
PV
**Real
Meaning:
Generic alarm indicating that the
point has generated a PV high or low alarm,
but the condition cleared before it was
logged.
PV LOW
PV LOW
PV
Analog
PV RATE
PV
**Real
Meaning:
The process input value rate
change has exceeded the configured limit.
PV I1 HIGH
PV I1 HIGH
of
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I1 is greater than the
configured HI alarm value.
PV I1 LOW
PV I1 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I1 is less than the
configured LO alarm value.
PV I2 HIGH
PV I2 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I2 is greater than the
configured HI alarm value.
PV I2 LOW
PV I2 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I2 is less than the
configured LO alarm value.
PV I3 HIGH
PV I3 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I3 is greater than the
configured HI alarm value.
PV I3 LOW
PV I3 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Process Alarms
Meaning:
Analog input I3 is less than the
configured LO alarm value.
PV I4 HIGH
PV I4 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I4 is greater than the
configured HI alarm value.
PV I4 LOW
PV I4 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I4 is less than the
configured LO alarm value.
PV I5 HIGH
PV I5 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I5 is greater than the
configured HI alarm value.
PV I5 LOW
PV I5 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I5 is less than the
configured LO alarm value.
PV I6 HIGH
PV I6 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I6 is greater than the
configured HI alarm value.
PV I6 LOW
PV I6 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I6 is less than the
configured LO alarm value.
PV I7 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I7 is greater than the
configured HI alarm value.
PV I7 LOW
PV I7 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I7 is less than the
configured LO alarm value.
PV I8 HIGH
PV I8 HIGH
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning: Analog input I8 is greater than the
configured HI alarm value.
PV I8 LOW
PV I8 LOW
PV
Point(s)
which
generate
this
alarm:
Overrides, 8 Pos Switch (Control Blocks)
Meaning:
Analog input I8 is less than the
configured LO alarm value.
PV LIMIT
PV LIMIT
PV
Analog
RANGE HIGH
OVERRANGE
alarm:
Data
Meaning:
The input to the data block is
greater than the configured range high limit.
RANGE LOW
RANGE LOW
UNDERRANGE
alarm:
Data
Process Alarms
Meaning: The input to the data block is less
than the configured range low limit.
RIGHT LIMIT
RIGHT LIMIT
RIGHT LIMIT
Point(s)
which
generate
Positioner (Control Block)
this
alarm:
Meaning:
The right limit input has become
true while the motor is running in the reverse
direction.
RISING
RISING
RISING
Analog
Meaning:
The output of the data block is
increasing
at
a
rate
faster
than
the
configured Rate-of-Change limit.
RUNBACK
RUNBACK
DV
this
alarm:
Hard
Meaning:
The logic input calling for a
runback has become true and the output of the
block is being decreased; or the limit
associated with the logic input calling for
the runback has been exceeded.
RUNDOWN
RUNDOWN
DV
Demand
Meaning:
The logic input calling for a
rundown has become true and the output of the
block
is
being
decreased
to
the
limit
associated with the logic input calling for
the rundown.
RUN'G NO F/R
RUN NO MF/MR
RUN NO FF
Reversing
RUNN NO RF
RUN NO RF
Reversing
RUNUP
DV
Demand
SEC FAIL
Point(s)
which
generate
**Receives (Control Blocks)
SEC FAIL
this
alarm:
Meaning:
No data being received from the
other station; the last value that was
received came from the secondary DPU of a
backup pair.
SEC'Y NO RDY
NOT READY
Backup
Meaning:
There is a problem with the
secondary DPU of a backup pair, or the backup
link is not working; the secondary will not be
able to assume control.
SEQ INT'LOCK
SEQ INRLOCK
SEQ INLK
Reversing
Meaning:
One
of
the
Interlock
inputs
configured as a Sequence Interlock has become
true. The motor will be turned off only if it
is not already in the Running Forward or
Running Reverse states. This alarm may cause
the algorithm to go to the stopping state.
Process Alarms
SEQUENC INTERLOC
SEQ INTERLOC
SEQ INTERLOC
SETPT CLAMP
Point(s) which
Control Block
generate
in
Binary
Binary
Control
SP
this
alarm:
PID
SETPT HI
Point(s) which
Control Block
generate
SP
this
alarm:
PID
Meaning:
The setpoint is greater than the
value configured in K5.
SETPT LO
SETPT LO
Point(s) which
Control Block
generate
SP
this
alarm:
PID
START
START
this
alarm:
Binary
START NO RF
START NO RF
ST NO MF/MR
START NO FF
Reversing
TIME EXCEED
TIME XCD
Point(s)
which
generate
this
Sequencer, Ramp Gen (Control Block)
alarm:
Meaning:
The configured time to move to the
next step of the ramp or sequence has been
exceeded.
TRIP
TRIP
TRIP
in
UA FIELD DEV UA
Binary
in
Control
FIELD DEV
Binary
Binary
Binary
Control
Part III
Alarm Message
Reference Guide
System Alarms
Part III consists of an alphabetic listing of all maxDNA System Alarm
messages. The following pages contain the actual message text (appearing
here in all upper case characters), how the alarm impacts the DPU, the
reporting device and a description of what each system alarm message
means.
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
YES
NO
43
DHW
HWYn
Highway
Comm
HWYn
(name)
YES
NO
39
IOP
RTP
maxSTATION
maxSTATION
RTP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
AP CANNOT COMMUNICATE ON
NETWORK A
APPL
APPL
AP CANNOT COMMUNICATE ON
NETWORK B
APPL
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
NO
NO
11
QUE
NO
NO
13
QUE
NO
NO
04
QUE
BATTERY #1 WEAK
NO
NO
02
IOP
BATTERY #2 WEAK
NO
NO
03
IOP
BUFFER OVERFLOW
BUFFER OVERFLOW
DHWn
YES
NO
37
DHW
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
GP
GP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
RTP
RTP
YES
NO
46
DHW
RTP
CONFIGURATION ROLLBACK
RTP
RTP
Description
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
NO
NO
09
IOP,SLOT,
PFI
RTP
RTP
DHWn
YES
NO
48
DHW
APPL GP
RTP
YES
YES
18
IOP
YES
NO
25
IOP
DHWn
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
YES
NO
F0
DHW
RTP
NO
NO
07
SLOT
RTP
RTP
YES
YES
FE
SLOT
YES
YES
FF
SLOT
DPU IS OFFLINE
NO
NO
07
IOP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
NO
NO
04
SLOT
YES
YES
FD
SLOT
YES
NO
46
DHW
DHWn
NO
NO
11
DHW
RTP
RTP
YES
NO
E2
QUE
QUE
APPL
APPL
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
NO
NO
04
Reporting
Device
Description
APPL
Same as above, but Event History data has now been lost
and cannot be recovered.
As of the execution of a check command, the ExCEL
processor's stack was not empty (the check command tests
the state of the stack to permit debug of an ExCEL
program which is causing the alarm "User Stack no empty
at Restart" to be reported by PFI).
There is a fault in the SCSI bus of this WorkStation. This
can be caused by either hardware, software, or a processor
which is temporarily too busy.
An IGAP (Initialize Go-Ahead Pointers) was completed on
this highway.
The Real-Time Processor annunciates that the attached
Graphics Processor has become active.
The Graphics Processor has either lost Control Room
Network communications with its current Real-Time
Processor or has determined that a different Real-Time
Processor in the same domain has a better data highway
status. This is a one shot alarm and does not persist.
An HDI card has failed during normal operation. This may
be a temporary condition due to this station's being IGAP'd
out; if not, then the Real-Time Processor will have to be
reset.
This highway processor is reporting that the periodic check
of its highway address is failing.
This highway processor is reporting that the periodic check
of its highway address is failing.
PFI
RTP
Highway
Comm
HWYn
GP BECAME ACTIVE
RTP
APPL
RTP
NO
NO
04
DHW
DHWn
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
RTP
YES
NO
B0
PFI
YES
NO
40
SLOT
YES
NO
30
DHW
DHWn
YES
NO
17
PFI
YES
YES
E8
QUE
RTP
Reporting
Device
Description
RTP
maxSTATION
maxSTATION
maxSTATION
maxSTATION
DHW
Type
System Alarms
Causes
DPU
Failover
YES
Activates
DPU
Offline
Contact
NO
DPU
Alarm
Severity
31
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
NO CLEAR-TO-SEND AFTER
REQUEST-TO-SEND
NO CLEAR-TO-SEND AFTER
REQUEST-TO-SEND
NO TIME CONF DATA FOR CURRENT
YEAR
NO
NO
12
Reporting
Device
Description
DHWn
DHW
DHWn
RTP
Highway
Comm
HWYn
APPL
APPL
RTP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
YES
CONFIG.
DEP.
B0
IOP
RTP
APPL
APPL
APPL
APPL
YES
NO
44
DHW
YES
NO
45
DHW
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
YES
NO
35
DHW
NO
Type
System Alarms
ST
DB
DHWn
NO
10
IOP,SLOT,
DHW,PFI
DHWn
YES
NO
28
IOP
YES
NO
27
DHW
DHWn
RESET
RTP CANNOT COMMUNICATE ON
NETWORK A
(any)
RTP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
RTP
RTP
RTP
RTP
RTP
RTP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
NO
NO
08
Reporting
Device
Description
RTP
DHW
DHWn
YES
NO
NO
NO
50
12
13
IOP
PFI
YES
NO
D1
B1-BF
C1-D0
SLOT
YES
NO
E0
IOP
YES
NO
38
DHW
Type
System Alarms
Reporting
Device
Description
Highway
Comm
HWYn
(name)
Highway
Comm
HWYn
(name)
APPL GP
Highway
Comm
HWYn
Highway
Comm
HWYn
(name)
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
RTP
Highway
Comm
HWYn
Highway
Comm
HWYn
(name)
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
Highway
Comm
HWYn
(name)
Highway
Comm
HWYn
(name)
Highway
Comm
HWYn
This station has the token, and therefore is the master at the
present moment. This station then detects that another
station is attempting to transmit (illegally).
A station appeared to have missed the token pass, maybe
because this station had a receiver problem and did not
hear the token being passed.
During an IGAP procedure, a station was searching for
stations with addresses greater than its own; during that
search, that station appeared to have skipped a station.
Task overrun counters are non-zero: the CP couldnt keep
up with scheduled periodic tasks (control blocks, data
blocks, and analog input buffers).
When this station had the token, it attempted to pass it on,
but it got no response; so, it dropped the token to force a
stallout, thus permitting a system monitor to restart token
passing.
When this station had the token, it attempted to pass it on,
but it got no response; so, it dropped the token to force a
stallout, thus permitting a system monitor to restart token
passing.
The time configuration file which describes timezone,
standard or daylight savings, etc. was read correctly, but
when the file was to be used by this Real-Time Processor,
there was an error in the file. This Real-Time Processor
will 'roll back' to its previous configuration. See the Install
log file which is built by the Configuration Builder.
The time configuration file which describes time zone,
standard or daylight savings, etc. was not read correctly by
this Real-Time Processor. This Real-Time Processor will
roll back to its previous configuration. See the Install log
file which is built by the Configuration Builder.
TASK OVERRUN
YES
NO
27
IOP
NO
NO
13
DHW
DHWn
RTP
RTP
Type
System Alarms
Causes
DPU
Failover
Activates
DPU
Offline
Contact
DPU
Alarm
Severity
Reporting
Device
Description
YES
NO
29
IOP
RTP
Highway
Comm
HWYn
YES
NO
49
Highway
Comm
IOP,DHW
HWYn
YES
NO
E1
QUE
RTP
Type
System Alarms
Causes
DPU
Failover
Reporting
Device
Description
RTP
RTP
YES
NO
Activates
DPU
Offline
Contact
NO
DPU
Alarm
Severity
32
DHW
DHWn
DHWn
NO
07
PFI