PROVIDES CONNECTIVITY TO MAXNET THRODUAL ETHERNET PORTS & RESIDES AS A STATION ON THE MAXNET ALONG WITH THE I/O MODULES.
ON THE MAXNET EACH DPU/DPU PAIR IS IDENTIFIED WITH A UNIQUE ETHERNET IP ADDRESS.
OPTIONALLY CONTAINS A RS232 PORT ON THE FRONT PANEL FOR INTERFACING TO EXTERNAL PLCS.
DISTRIBUTED PROCESSING UNIT FUNCTIONS. EXECUTION OF CONTROL ALGORITHMS (CONFIGURATION/DATABASE) FOR PROCESS CONTROL & DATA ACQUISITION.
- UPTO 8500 FUNCTION BLOCKS CAN BE EXECUTED IN THREE DIFFERENT TIME CLASSES. (10ms to 1/2s)
CONTINUOUS SCANNING OF I/O MODULES. LOGGING OF SOE AT 1 ms RESOLUTION. ACQUISITION OF TREND INFORMATION. CALCULATIONS & ALARMING. SCANS AND PROCESSES INFORMATION FOR USE BY OTHER DEVICES IN THE maxDNA SYSTEM.
Switch A Switch B
D P U D P U I O
I O I O I O
I O I O I O
I O I O I O
I / O S I G N A L S
DPU 4F -- SPECIFICATIONS
COMPACT FLASH
ON BOARD
REGULATORS
NET A CONTR
ETHERNET
CONTROLLER
BIOS FLASH
5V/3.3V/2.1V
24V IN
I/O BACKPLANE
SHARED RAM
BACK UP CONTR
ETHERNET CONTROLL ER
IOM PROCESSOR
(CP)
IRIG/ RS232 FRONT END (OPTIONAL)
MEMORY BUS
(IOM)
IOM FPGA SDRAM
I/O BUS
POSITI ON 0 1
OPERATIONAL STATE
ON LINE OPERATION / BUT LOCKED. OFF-LINE OPERATION . O/Ps ARE FROZEN AND WILL NOT CHANGE. THE STATE LED WILL BE RED. RESERVED / DIAGNOSTICS -- NOT FOR CUSTOMER USE. IF THIS MODE IS SET DURING RE-BOOT OF DPU,THE DPU WILL CLEAR THE DATABASE FROM COMPACT FLASH & GO ONLINE AS IN MODE F NETWORK FLASH MODE. USED FOR CONFIGURING THE DPU FOR THE FIRST TIME/CHANGE OF ADDRESS.DPU SOFTWARE CAN ALSO BE DOWNLOADED. FACTORY DEBUG MODE NETWORK FLASH MODE.USED FOR DOWNLOADING THE DPU SOFTWARE . NORMAL OPERATING MODE. WILL USE THE DATABASE STORED IN FLASH IF AVAILABLE.
2-A
D E
SOLID GREEN
NETWORK IS OPERATIONAL DPU HAS DETECTED A STATION WHICH DOES NOT HEAR FROM IT NETWORK FAILURE. DPU DOES NOT HEAR FROM ANY STATION.
SOLID YELLOW
BLINKING YELLOW
BACKUP PORT A 100 MBPS ETHERNET INTERFACE USED TO PASS DATABASE INFORMATION TO A HOT STAND BY DPU.
BACKUP LED. INDICATES THE REDUNDANCY STATUS OF THE DPUs CONFIGURED AS A BACKUP PAIR.
SOLID GREEN BACKUP NETWORK IS OPERATIONAL SOME BACKUP NETWORK ERRORS
SOLID YELLOW
SOLID RED
SOLID RED
ALL CONFIGURED I/O CARDS ARE WORKING CORRECTLY SOLID GREEN SOME CONFIGURED CARDS ARE WORKING CORRECTLY. SOME ARE NOT.
SOLID YELLOW
SOLID RED
HEALTHY HEARTBEAT
SOLID YELLOW
STANDALONE DPUs
BACKUP WARMING UP
SOLID GREEN
SOLID YELLOW
INDETERMINATE
OFFLINE
RED RED
SERIAL PORT
RESET BUTTON PRESSING THIS BUTTON WILL CAUSE THE DPU TO STOP CONTROLLING & GO THRO A RESET CYCLE. TAKEOVER BUTTON PRESSING THIS BUTTON WILL CAUSE A PREVIOUSLY INACTIVE DPU TO GO ACTIVE. SERIAL PORT(OPTIONAL) OPTIONAL RS232 SERIAL PORT WITH RJ45 CONNECTOR FOR INTERFACING TO EXTERNAL PLC TYPE DEVICES. IRIG-B PORT(OPTIONAL) BNC CONNECTOR WHICH SUPPORTS AN INTERFACE TO A GPS RECIEVER.THIS OPTION ALLOWS TIME SYNCHRONISATION TO GLOBAL TIME.
IRIG PORT
INFORMATION BETWEEN THE BACKUP PAIR IS EXCHANGED BY MEANS OF A 100MBPS ETHERNET INTERFACE.
A CAT5e ETHERNET CABLE IS USED TO CONNECT THE TWO DPUS TOGETHER.
PROCESS CONTROL CAN BE TRANSFERRED AUTOMATICALLY(FAILOVER) OR MANUALLY BETWEEN PRIMARY & SECONDARY. AUTOMATIC FAILOVER CAN OCCUR FROM EITHER THE PRIMARY DPU TO THE SECONDARY DPU OR VICEVERSA & THIS OCCURS BASED ON THE HEALTH OF BOTH DPUS. MANUAL TAKEOVER CAN BE ACHIEVED BY PRESSING THE TAKEOVER BUTTON ON THE FRONT PANEL OF THE MODULE.