SLI50 Inverter Datasheet
SLI50 Inverter Datasheet
SLI50 Inverter Datasheet
FEATURES
Front panel LCD Display Unit to monitor and set main parameters
or LED Unit for visual indication available
Parallelable output
DESCRIPTION
The SLI 50 Series of Slim Line inverters provide an ideal solution for telecom,
IT and industrial applications. Due to innovative technology solutions like the
patent-pending Compact Coil", the SLI 50 Series inverters pack 5000 watts of
power into a compact package that is 19 rack mountable and only two rack
units high. Electrical performance of the SLI Series inverter products is at the
top of the market with efficiency that peaks at 93% and a patent-pending control
algorithm that compensates current harmonics on the DC side without using
bulky and expensive filters. The inverter includes an on-board powerful Digital
Signal Processor (DSP) that allows easy programmability of the main parameters on the front panel LCD display and keypad. The SLI Series inverters can be
interfaced with RS485.
BCD.00296_AA May-17-2013
APPLICATIONS
o
o
o
TELECOM
IT
INDUSTRIAL
FEATURES
www.power-one.com
DATA SHEET
TECHNICAL DATA:
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
40
48
60
150
VDC
ADC
5000
7000
240
30
63
93
5500
1
3
+0.5
0
0
W
VA
VAC
Arms
Hz
%
Wmin
<0.5
INPUT
Input Voltage
Input Current
Inrush Current
OUTPUT
Output Power
Output Voltage
Output Current
Frequency
Efficiency
Overload
Load Power Factor
Crest Factor
Load Regulation
Line regulation
Output Noise & Ripple
Total Harmonic Distortion
Adjustable
@ 40 VDC
Lagging or leading
200
230
47
50
0.33
-0.5
-6
-8,5
On Resistive Load
%
%
PROTECTION
Input Overcurrent Protection
Input Overvoltage Protection
Input Undervoltage Protection
Overvoltage Protection
Undervoltage Protection
Safety Overcurrent Protection
Short-Circuit Protection
Overcurrent Protection
Overtemperature Protection
Protection Restore Modes
@ 48 VDC
150
@ 48 VDC
65
@ 48 VDC
36
260 VAC 2%
195 VAC 2%
By safety fuse; 230 VAC Models: 30A
Yes; Ipk 95A 5% for 1 sec
30 A (factory default) to 15 A selectable with I2T curve (see spec.)
Tamb > 67 C and Tint > 110 C (Visual indication 5 C before shutdown)
The restore mode of each protection can be individually selected to "latch" or "auto-restart".
A
VDC
VDC
EMC
IEC 60950-1: 2001, 1st edition; EN 60950-1: 2001 + A11: 2004; UL 60950-1, 1st edition; CAN/CSA-C22.2
No.60950-1-03, 1st edition; CE according to Low Voltage Directive and EMC Directive; Kema; CB Report
Approval;
Primary-to-Secondary:
3000
Vrms
Primary-to-Ground:
500
VDC
Secondary-to-Ground:
1500
Vrms
Signal-to-Ground:
500
VDC
Emission: EN 61000-6-4: 2001; EN 55022: 1998 A1:2000 + A2:2003 (Class B)
Immunity: EN 61000-6-2: 1999; EN 61000-4-2: 1995 + A1:1998 + A2: 2001 (Crit. A); EN 61000-4-3: 2006
(Crit. A); EN 61000-4-4: 2004 (Crit. A); EN 61000-4-5: 2006 (Crit. A); EN 61000-4-6. 1996 + A1:2001 (Crit.
A); EN 61000-4-8: 1993 + A1:2001 (Crit. A); ETSI EN 300-132-2 (Crit. A)
ENVIRONMENTAL SPECIFICATIONS
Altitude
Operating Temperature
Storage Temperature
Humidity
Output Voltage Temp. Coefficient
Operating:
Non-Operating:
@ full load; Power derating: 150 W/ C; +55 C to +65 C
-25
-40
13000
40000
+55
+85
ft
C
C
0 90 %, non-condensing
0.02 % per C within rated load
MECHANICAL SPECIFICATIONS
Dimensions (W x H x D)
Weight
482 x 88 x 400 mm
14.5 kg
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems,