DATA SHEET

SLI 50 INVERTER SERIES, 5000 W

FEATURES

Compact design: 2U height, 19" rack mountable

Front panel LCD Display Unit to monitor and set main parameters
or LED Unit for visual indication available

High efficiency: up to 93%

True sine wave output

RS485 serial link

Input reflected ripple current <150 mArms @ maximum load

Advanced cooling system to optimize fan life and minimize noise

Parallelable output

2-position subrack availability

DESCRIPTION
The SLI 50 Series of Slim Line inverters provide an ideal solution for telecom,
IT and industrial applications. Due to innovative technology solutions like the
patent-pending Compact Coil", the SLI 50 Series inverters pack 5000 watts of
power into a compact package that is 19 rack mountable and only two rack
units high. Electrical performance of the SLI Series inverter products is at the
top of the market with efficiency that peaks at 93% and a patent-pending control
algorithm that compensates current harmonics on the DC side without using
bulky and expensive filters. The inverter includes an on-board powerful Digital
Signal Processor (DSP) that allows easy programmability of the main parameters on the front panel LCD display and keypad. The SLI Series inverters can be
interfaced with RS485.
BCD.00296_AA May-17-2013

APPLICATIONS
o
o
o

TELECOM
IT
INDUSTRIAL

FEATURES

www.power-one.com

DATA SHEET

TECHNICAL DATA:
PARAMETER

DESCRIPTION / CONDITION

MIN

NOM

MAX

UNIT

40

48

60
150

VDC
ADC

5000
7000
240
30
63
93
5500
1
3
+0.5
0
0

W
VA
VAC
Arms
Hz
%
Wmin

<0.5

INPUT
Input Voltage
Input Current
Inrush Current

ETSI EN 300 132-2; Ver, 2.12, Clause 4.7

OUTPUT
Output Power
Output Voltage
Output Current
Frequency
Efficiency
Overload
Load Power Factor
Crest Factor
Load Regulation
Line regulation
Output Noise & Ripple
Total Harmonic Distortion

Adjustable
@ 40 VDC
Lagging or leading

200

230

47

50

0.33
-0.5
-6
-8,5

On Resistive Load

%
%

PROTECTION
Input Overcurrent Protection
Input Overvoltage Protection
Input Undervoltage Protection
Overvoltage Protection
Undervoltage Protection
Safety Overcurrent Protection
Short-Circuit Protection
Overcurrent Protection
Overtemperature Protection
Protection Restore Modes

@ 48 VDC
150
@ 48 VDC
65
@ 48 VDC
36
260 VAC 2%
195 VAC 2%
By safety fuse; 230 VAC Models: 30A
Yes; Ipk 95A 5% for 1 sec
30 A (factory default) to 15 A selectable with I2T curve (see spec.)
Tamb > 67 C and Tint > 110 C (Visual indication 5 C before shutdown)
The restore mode of each protection can be individually selected to "latch" or "auto-restart".

A
VDC
VDC

INTERFACE & CONTROL SIGNALS


LCD Display Unit
LED Unit

128 x 128 pixel graphic with keypad used for monitoring


and setting the main parameters.
Standard for visual indication of the main parameters

General Alarm Signal

By a form C signal relay

LED Indicators for both units:


GREEN - Power ON
YELLOW - Fan Failure, Addresses
RED
- Overtemperature, Faulty Condition

SAFETY, REGULATORY AND EMC SPECIFICATIONS


Agency Approvals
Insulation

EMC

IEC 60950-1: 2001, 1st edition; EN 60950-1: 2001 + A11: 2004; UL 60950-1, 1st edition; CAN/CSA-C22.2
No.60950-1-03, 1st edition; CE according to Low Voltage Directive and EMC Directive; Kema; CB Report
Approval;
Primary-to-Secondary:
3000
Vrms
Primary-to-Ground:
500
VDC
Secondary-to-Ground:
1500
Vrms
Signal-to-Ground:
500
VDC
Emission: EN 61000-6-4: 2001; EN 55022: 1998 A1:2000 + A2:2003 (Class B)
Immunity: EN 61000-6-2: 1999; EN 61000-4-2: 1995 + A1:1998 + A2: 2001 (Crit. A); EN 61000-4-3: 2006
(Crit. A); EN 61000-4-4: 2004 (Crit. A); EN 61000-4-5: 2006 (Crit. A); EN 61000-4-6. 1996 + A1:2001 (Crit.
A); EN 61000-4-8: 1993 + A1:2001 (Crit. A); ETSI EN 300-132-2 (Crit. A)

ENVIRONMENTAL SPECIFICATIONS
Altitude
Operating Temperature
Storage Temperature
Humidity
Output Voltage Temp. Coefficient

Operating:
Non-Operating:
@ full load; Power derating: 150 W/ C; +55 C to +65 C

-25
-40

13000
40000
+55
+85

ft
C
C

0 90 %, non-condensing
0.02 % per C within rated load

MECHANICAL SPECIFICATIONS
Dimensions (W x H x D)
Weight

482 x 88 x 400 mm
14.5 kg

NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems,
equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.

SLI 50 Inverter Series

www.power-one.com