Ashrae Journal On Reheat: Dan Int-Hout
Ashrae Journal On Reheat: Dan Int-Hout
Ashrae Journal On Reheat: Dan Int-Hout
Page: 1 of 7
Fig 1
Figure 1 illustrates a common miss-application. Air is discharged at around 100oF, and never reaches the
cold air stream falling down the window. Worse,
ventilation air short circuits back through the return
ceiling plenum, and never reaches the occupants.
The thermostat, meanwhile, may take as long as
an hour to respond to load changes.
The ASHRAE Fundamentals Handbook (2005,
Chapter 33) states that discharging air at a
temperature more than 15oF above the room
Krueger Corporate Headquarters
1401 N. Plano Rd. Richardson, TX 75081
Phone: (972) 680-9136 | Fax: (972) 497-0450 | E-Mail: kruegerinfo@krueger-hvac.com
www.krueger-hvac.com
(90oF in a 75oF room) will likely result in significant unwanted air temperature stratification (which will void
compliance with ASHRAE Standard 55). In addition, ASHRAE Standard 62.1 2004 (Indoor Air Quality) has
been modified to require increased outside air when heating from the ceiling if this rule is not followed
(Standard 62.1 2004):
This is because hot air tends to stay at the ceiling, and may 'short-circuit' directly back to the room exhaust
without mixing in the room. Indeed, using the ASHRAE 129 test procedure for Air Change Effectiveness,
mixing effectiveness values as low as 20% (or lower) has been observed, when the supply to room
differential exceeds 15oF. Calculations will show that in most cases, it only requires 85oF air to handle a
typical winter design perimeter load at 1 cfm/SqFt. air supply rate (the airflow rate we recommend for both
good ventilation mixing and comfort).
Fig 2
When properly operated, a discharge less than 15oF above room results in higher required airflows, longer
throws, and the room gets mixed. The thermostat responds in a few minutes to changes in loads.
The need to rapidly warm a space following a night setback has another set of requirements. Air needs to
be heated as rapidly as possible, with a maximum of mixing, without too much regard for occupant
comfort. This requires both a high delta-t and a high airflow. Note: The hotter the air temperature, the
longer it will take to heat the room, for a given heat delivery rate!
This is due to stratification of hot air at the ceiling. The engineer therefore needs to ensure that both
occupied heating and morning warm-up situations are covered in his design with proper staged or
proportional electric heat or proportional water coil valves.
Some Energy codes (currently in Florida and California), and ASHRAE 90.1, prohibit reheating cooled air
at more than 30% of design cooling flows. It is unlikely that meeting this requirement will result in
satisfactory diffuser mixing, occupant comfort or ventilation mixing. In temperate climates, this may be a
less than satisfactory, but an understood design compromise. In cold climates, this may not be acceptable.
Of course, the 90.1 prohibition only covers reheating previously cooled air. When the system is in
economizer mode, air is not being reheated. In fact, it may be argued that today, with better wall
insulation and glass, few systems should be in compressor cooling mode when perimeters require reheat.
The reheating of cold primary air seems, on the surface, to be a wasteful practice in terms of optimum
utilization of energy resources. There are many situations, however, where it is not only necessary, but
also beneficial to do so, and can save considerable energy. These include:
1.) Providing comfort with a great diversity of loads: When both heating and cooling is required from a
single air handler, due to climate and building design factors, reheat is often an economical solution.
As it is only used in a few locations, and only part of the time, the energy penalty for reheat is minimal.
2.) Supplementing baseboard perimeter heat: Baseboard heating systems can be the most effective
means of offsetting perimeter heating demand loads. At times, however, peak heating demand loads
may exceed the installed baseboard capacity and supplemental overhead heat can be supplied.
3.) Maintaining minimum ventilation rates: The benefit of an installed re-heat coil in non-perimeter
zones becomes apparent when a minimum ventilation rate exceeds the cooling demand. This happens
when the quantity of supply air to a space required to provide proper ventilation exceeds that required
to offset local heat sources, such as when the ratio of occupants to equipment (which requires little
ventilation air) shifts towards occupants, as in conference rooms. In these cases, the required quantity
of ventilation air may sub-cool the zone.
A slight amount of controlled reheat can prevent this sub cooling. The alternative, reducing supply air
temperature at the air handler, may result in other spaces that cannot be cooled at design maximum
airflows, and also tends to increases space relative humidity.
4.) Controlling Humidity: Humidity control can be enhanced using reheat coils, just as for ventilation
requirements. When the local humidity is too high, then drier cooler air can be added, and then slightly
reheated to avoid sub cooling.
HOT WATER HEAT
Most manufacturers of VAV terminals offer a hot water coil selection program. This selection, however,
cannot defy the basic laws of physics, (regardless of what is specified). Unlike custom air handlers, the fin
spacing, circuiting, and tube spacing are usually fixed for VAV box coils. This means that there is only one
solution for a given gpm, # of rows and airflow rate, for a given coil size.
When selecting a coil, one can pick only one independent variable, with different parameters for increasing
the number of rows, gpm, etc. The selection of the best path almost always requires a discussion with the
engineer. It is necessary to know which item on the provided schedule is to be met. While this should
probably be the BTUH, it is often the gpm (which is apparently set in concrete due to prior pump selection),
etc. Both scheduled gpm and BTUH often cannot be met, (unless of course one will allow fractional rows)
As discussed earlier, the coil leaving air should be fixed so as to not exceed ASHRAEs recommended
15oF delta-t maximum (Chapter 32, Fundamentals Handbook) except in unoccupied morning warm-up, for
effective air distribution in the room. This often requires adjusting the heating CFM to achieve the desired
room BTUH at a discharge air temperature that will promote good room air distribution and ventilation
mixing. This action is apparently seldom performed, but should be.
WATER COIL ISSUES
For fan boxes, the mixed air temperature (the combination of primary and induced air temperatures) is
dependent on the coil location:
Series Fan boxes: As the coil is almost always on the discharge, the mixed air quantity (and the coil
entering air temperature) is based on the fan cfm. The coil entering air temperature is calculated based on
the minimum primary at one temperature and the induced airflow (which is the fan cfm less the minimum
primary) at another temperature. With series flow units, the coil leaving air temperature and the box leaving
air are the same.
Parallel fan boxes: With some parallel fan powered units, the coil location may be on the plenum inlet so
the coil entering air is always the plenum air temperature. There is mixing after the coil, however. The units
discharge air temperature is therefore a mix of primary air, typically at the minimum primary air flow rate,
and plenum air heated by the coil, at the fan air flow rate.
Most parallel units have the water coil on the discharge, in spite of the obvious pressure penalty seen by
the primary air handler. When on the plenum inlet, with a high minimum primary air setting (to meet
ventilation minimums) the required coil leaving temperature may exceed 120F, and there is a high
likelihood of cooking the fan motor, forcing the coil to be relocated to the unit discharge.
Leaving Water Temperature: Leaving water temperature should NOT be used in water coil selection.
Cooling coils are often selected on the basis of water coil delta-t, where the discharge temperature is
controlled. This technique, however, is not recommended for heating coils in VAV boxes, where the
discharge temperature is seldom controlled. It is recognized that non condensing boilers require a high
entering water (return water) temperature to avoid shocking the system. This should be accomplished
through three-way valves, secondary loops, or other means, not through coil selections. At part load, when
the water valve is throttled, coil leaving water temperatures will ALWAYS be less than recommended by
these boilers.
Fluid Type: Three hot fluids are commonly used: Water, Ethylene and Propylene Glycol. The use of Glycol
will significantly increase the minimum gpm allowed for turbulent flow. Most programs compute a Reynolds
number, which must be greater than 5000 for a valid selection, and which increases the minimum gpm as
the percentage of glycol increases.
Coil Load vs. Room Load: A water coil is often selected based on a given BTUH. There are, however, two
loads that can be used for this calculation. One is the coil load, which is based on the air flow rate and the
supply to discharge temperature differential. The other is the room load, which is the difference between
the room temperature and the discharge temperature, and may be calculated from skin losses less internal
loads. Often, it is not clear which is being specified. Most software assumes the BTUH load is the coil
load.
ELECTRIC HEAT
The electric heater provided with most single duct VAV boxes is essentially a rated duct heater installed in
an elongated single duct unit. This longer unit provides for developed flow, after the damper, and a
relatively uniform airflow across the coil elements. At low flows, however, there is both a minimum airflow
and a maximum kW consideration. The heater has a safety switch that prevents the heater from engaging
unless there is a minimum sensed pressure in the duct. Normally, this is a velocity pressure, although in
practice, it sometimes becomes a static pressure sensor.
At low airflows, there may be insufficient velocity, or static pressure, in the unit to make the contactor in
the flow switch. This may be due to probe location, damper position, low discharge static pressure or likely,
a combination of all. (Note: for fan powered terminals, the minimum fan setting is sufficient to operate the
electric heat) The kW selected at minimum flow must also avoid exceeding the maximum UL listed coil
temperature of 120F.
OVERHEAD HEAT AND THE DIFFUSER
Besides the minimum flow to activate the heater safety circuits, there is an issue of the diffuser
performance. All diffusers have a specific performance envelope in cooling mode, which can be
determined through ADPI analysis. (See D. Int-Hout, Best Practices for Diffuser selection, ASHRAE
Journal, June, 2004) With VAV systems, diffusers should be selected so that at full flow they are near the
Krueger Corporate Headquarters
1401 N. Plano Rd. Richardson, TX 75081
Phone: (972) 680-9136 | Fax: (972) 497-0450 | E-Mail: kruegerinfo@krueger-hvac.com
www.krueger-hvac.com
limit of objectionable sound, so as to allow for optimum performance at reduced flows. VAV boxes are also
selected at as high an inlet velocity as possible, for the same reason. When heated air is being discharged
from a ceiling diffuser, the outlet velocity needs to be as high as possible, to prevent stratification. Airflows
even close to the manufacturers electric heating minimum airflow unlikely to be satisfactory from an air
distribution standpoint, and short circuiting of ventilation air and excessive temperature stratification are
likely, regardless of the resultant discharge temperature.
It some cases, it may be desirable to decouple
the heating and cooling air supply to the room.
One option is to use down blow nozzles at the
window supplied from a heating only fan coil. A
parallel fanbox controller on the single duct VAV
terminal used for cooling can control this fan coil.
With fan boxes, the fans minimum flow rate is
sufficient to permit electric heater operation, so
there is no minimum setting or requirement.
Additionally, as there is minimum reheat, energy
codes are satisfied, and diffuser performance is
maintained. As a result, when restrictive energy
codes are in place, fan powered terminals may be
required for acceptable environments and
ventilation mixing, instead of shut off single duct
units.
As mentioned earlier, the ASHRAE Handbook recommends a maximum discharge temperature of 90oF
(in a 75oF room) with overhead heating to avoid excessive stratification (and ventilation short-circuiting).
Many times, simple logic can be applied to select suitable conditions of airflow and reheat which maintain
room air mixing, diffuser performance and air change effectiveness, within the factory airflow and kW
limitations for units with electric heaters. Setting one cfm/sqft as a heating flowrate in perimeter zones is
recommended to achieve optimum air distribution when heating.
HEAT CONTROL
The control of heat to a space is primarily the responsibility of the supplied controls. The controller
provides staged contacts for heat to an electric heater, and either a single contact for on-off, or two
contacts for three point floating outputs to a hot water valve. The control is most often open loop, in that
the controller relies on feedback from the room sensor to modify the heater control signal. If a room is
stratified (as when the discharge air temperature is greater than ASHRAEs recommended 15oF delta-t,)
the time response may be very slow, resulting in considerable room temperature swings (in addition to the
unacceptable room temperature stratification). The indicated temperature at the room sensor will, however,
indicate acceptable temperature.
New technologies permit proportional discharge temperature controlled heat for VAV boxes, at a very low
cost. The controller is connected either to a proportional hot water valve, or a single stage digital relay
electric heater. When tied with a discharge temperature sensor, will allow the controller to set the desired
discharge temperatures as a function of the DDC controllers demand. This technology allows for a better
control of space temperature than most other methods. It can be driven by a variety of application
sequences using proportional (0-10 VDC or 0-20 mA) output, pulsing or staged 24 VAC output. The use of
a three-point floating heater control option with either hot water or electric heat often reduces the cost
of the DDC controller by as much as $100 compared to a proportional output on the DDC controller. Some
DDC manufacturers do not have an analog output option available at all.
When the discharge temperature sensor is installed, one can control proportionally between the no-heat
duct temperature and a set maximum temperature.
SUMMARY
Overhead heating has been the primary method of offsetting perimeter winter loads with VAV systems for
30 years. Research was conducted on the rules to avoid excessive stratification and provide occupant
comfort back then, and included in the ASHRAE Handbooks ever since. In spite of this, however,
engineers continue to design systems delivering low velocity, high temperature air at the ceiling. These
designs are almost guaranteed to result in spaces which do not meet the minimum requirements of
ASHRAE Standard 55, and also fail to consider new ventilation requirements in ASHRAE Standard 62.1.
Electric and hot water reheat coils are provided on many types of VAV terminals. There are selection
criteria for each that should be considered both to ensure proper unit performance and to distribute the
heated air properly into the space. With all, however, the engineer should assure that the discharge
temperatures and air quantities will provide a comfortable space, and provide ventilation mixing as well. It
will often be necessary for the equipment supplier and control contractor to discuss these issues with the
design engineer before making a final selection to ensure that everyone is making the same assumptions
Meeting both ASHRAE Standard 62.1 and Standard 55, without violating 90.1, requires proper selection of
both heating control and heating equipment, as well as air delivery devices. As 62.1 is a prerequisite of the
current LEED requirements, and likely to be incorporated into the next version of the International
Mechanical Code, it is essential that these issues be understood by all parties. And code issues aside, if
the vertical temperature requirements of Standard 55 are not met, occupants will employ their own means
of providing space comfort (the dreaded 1500 watt heaters), or worse, move out.