L-545 Servicemans Manual
L-545 Servicemans Manual
L-545 Servicemans Manual
Servicemans
Manual
The LP-Gas
Servicemans Manual
RegO, has prepared this LP-Gas Servicemans
Manual for use by installation servicemen and others
requiring a handy reference for field service work.
It deals with subjects that can be useful to field
servicemen striving for greater efficiency and safer
installations. For the more technical problems and
theories, the many texts and manuals concerning the
particular subject should be consulted.
This manual is not intended to conflict with federal,
state, or local ordinances and regulations. These
should be observed at all times.
This information is intended to be forwarded
throughout the product distribution chain. Additional
copies are available from RegO Products Master
Distributors.
Contents
Information About LP-Gas*.............................. 3
Vapor Pressures of LP-Gases*........................ 4
Installation Planning......................................... 5
Propane Storage Vessels................................. 5
Determining Total Load.................................... 6
100 LB. Cylinders............................................. 7
ASME Storage Containers............................... 8
Proper Purging of LP-Gas Containers............. 9
Proper Placement of Cylinders and Tanks..... 13
Pipe And Tubing Selection............................. 16
LP-Gas Regulators......................................... 27
Leak Testing the Installation........................... 36
Proper Use of Excess Flow Valves................ 40
Pressure Relief Valves................................... 41
Repair of the MultiBonnet............................ 43
Flow of LP-Gas Through Fixed Orifices......... 45
Line Sizing Chart for Liquid Propane............. 46
Representative Equivalent Lengths of Pipe
for Various Valves and Fittings....................... 47
Determining Age of RegO Products............. 48
Conversion Units............................................ 50
Propane Butane
Formula C H C H
Boiling Point, F
-44
15
Specific Gravity of Gas
(Air=1.00)
1.50 2.01
Specific Gravity of Liquid
(Water=1.00)
0.504 0.582
Lbs. per Gallon of Liquid at 60 F
4.20
4.81
BTU per Gallon of Liquid at 60 F
91502
102032
BTU per Lb. of Gas or Liquid
21548
21221
BTU per Cu. Ft. of Gas at 60 F
2488
3280
Cu. Ft. Vapor (at 60F and 14.7 PSIA)/Gal. Liq 36.38
31.26
Cu. Ft. Vapor (at 60F and 14.7 PSIA)/Lb. Liq 8.66
6.51
Cu. Ft. Vapor (at 60F and 14.7 PSIA) /Cu. Ft. of Liq 272
234
Latent Heat of Vaporization
at Boiling Point BTU/Gal.
773
808
Combustion Data:
Cu. Ft. Air Required to Burn
1 Cu. Ft. Gas
23.86
31.02
Flash Point, F
-156
N.A.
Ignition Temperature in Air, F
920-1120 900-1000
Maximum Flame
Temperature in Air, F
3595
3615
Limits of Flammability
Percentage of Gas in Air Mixture;
At Lower Limit %
2.15
1.55
At Upper Limit %
9.6
8.6
Octane Number
(ISO-Octane=100)
Over 100 92
3
10
(F)
(C) Propane
-40 -40
3.6
-30
-34
-20
-29
13.5
-10
-23
23.3
0 -18
28
10
-12
37
20
-7
47
30
-1
58
40
72 3.0
50
10
86 6.9
60
16
102 12
70
21
127 17
80
27
140 23
90
32
165 29
100
38
196 36
110
43
220 45
*Conversion Formula:
Degrees C = (F - 32) X 5/9
Degrees F = 9/5 X C + 32
Butane
Installation Planning
Propane Storage Vessels
The withdrawal of propane vapor from a vessel lowers the
contained pressure. This causes the liquid to boil in an
effort to restore the pressure by generating vapor to replace
that which was withdrawn. The required latent heat of
vaporization is surrendered by the liquid and causes the
temperature of the liquid to drop as a result of the heat so
expended.
The heat lost due to the vaporization of the liquid is replaced
by the heat in the air surrounding the container. This heat
is transferred from the air through the metal surface of
the vessel into the liquid. The area of the vessel in contact
with vapor is not considered because the heat absorbed
by the vapor is negligible. The surface area of the vessel
that is bathed in liquid is known as the wetted surface.
The greater this wetted surface, or in other words the
greater the amount of liquid in the vessel, the greater the
vaporization capacity of the system. A larger container
would have a larger wetted surface area and therefore would
have greater vaporizing capacity. If the liquid in the vessel
receives heat for vaporization from the outside air, the higher
the outside air temperature, the higher the vaporization rate
of the system. How all this affects the vaporization rate of
100-pound cylinders is shown on page 7. It will be noted
from this chart that the worst conditions for vaporization rate
are when the container has a small amount of liquid in it and
the outside air temperature is low.
With the principles stated above in mind, simple formulae
for determining the proper number of DOT cylinders and
proper size of ASME storage containers for various loads
where temperatures may reach 0F will be found on pages 7
and 8 respectively.
5
Approx. Input
(BTU per Hour)
65,000
25,000
40,000
30,000
38,000
50,000
142,800
285,000
428,400
3,000
35,000
2,500
30,000
Lbs. of
Propane
In Cyl.
100
90
80
70
60
50
40
30
20
10
This chart shows the vaporization rate of containers in terms of the temperature
of the liquid and the wet surface area of the container. When the temperature is
lower of if the container has less liquid in it, the vaporization rate of the container
is a lower value.
Where
D = Outside diameter in inches
L = Overall length in inches
K = Constant for percent volume
of liquid in container
Percentage of
Container Filled
60
50
40
30
20
10
K
*Propane Vaporization Capacity
Equals
at 0F (in BTU/hr.)
100
90
80
70
60
45
DXLX
DXLX
DXLX
DXLX
DXLX
DXLX
100
90
80
70
60
45
Air
Neutralizing Moisture
10
Emergency Unloading
Adapter
(RegO # 3119A, 3120
or 3121) on filler valve
Gauge Adapter
Assembly
1st Purging
2nd Purging
3rd Purging
4th Purging
5th Purging
6th Purging
12
% Air Remaining
50
25
12.5
6.25
3.13
1.56
% Propane Remaining
50
75
87.5
93.75
96.87
98.44
13
14
Reprinted with permission from NFPA 58-2004, Liquefied Petroleum Gas Code, Copyright 2004, National Fire Protection Association, Quincy, MA 02269.
This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
Notes:
1) 5-ft minimum from relief valve in any direction away from exterior source if ignition, openings into direct-vent gas appliances, or mechanical ventilation air intakes.
2) If the cylinder is filled on site from a bulk truck, the filling connection and vent valve must be at least 10 ft from any exterior source of ignition, openings into
directvent gas appliances, or mechanical ventilation air intakes.
3) Cylinders installed along side buildings the relief valve discharge must be:
(a) At least 3 ft horizontally away from any building openings that is below level of the relief valve discharge.
(b) For cylinders not filled on site the relief valve discharge must be at least 5 ft from any exterior source of ignition, openings into directvent gas appliances, or
mechanical ventilation air intakes.
Federal, state, and local ordinances and regulations should be observed at all times.
15
Reprinted with permission from NFPA 58-2004, Liquefied Petroleum Gas Code, Copyright 2004, National Fire Protection Association, Quincy, MA 02269.
This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
Location of
ASME Containers
16
17
Example 1.
Determine the sizes of piping or tubing required for the
twin-stage LP-Gas installation shown.
18
Total first stage piping length = 26 feet; first stage regulator setting is 10psig (use Table 1 or 2 @ 30 feet)
From aa to a, demand = 338,000 BTU/hr; use 1/2 pipe, 1/2 tubing, or 1/2 T plastic pipe.
Total second stage piping length = 58 feet (use Table 3 @ 60 feet)
From a to b, demand = 338,000 BTU/hr; use 1 pipe
From b to c, demand = 138,000 BTU/hr; use 3/4 pipe or 7/8 tubing
From c to d, demand = 100,000 BTU/hr; use 1/2 pipe or 3/4 tubing
From d to e, demand = 35,000 BTU/hr; use 1/2 pipe or 1/2 tubing
From b to f, demand = 200,000 BTU/hr; use 3/4 pipe or 7/8 tubing
From c to g, demand = 38,000 BTU/hr; use 1/2 pipe or 1/2 tubing
From d to h, demand = 65,000 BTU/hr; use 1/2 pipe or 5/8 tubing
19
Total first stage piping length = 26 feet; first stage regulator setting is 10psig (use Table 1 or 2 @ 30 feet)
Total 2 PSI Piping Length = 19 ft. (use Table 4 @ 20 ft. or Table
6 @ 20 ft.)
From aa to a, demand = 338,000 BTU
use 3/8 CSST or 1/2 copper tubing or 1/2 pipe
From Regulator a to each appliance:
From a to b, demand = 65,000 BTU; length = 25 ft. (Table 5),
use 1/2 CSST
From a to c, demand = 200,000 BTU; length = 30 ft. (Table 5)
use 3/4 CSST
From a to d, demand = 38,000 BTU; length = 21 ft.* (Table 5)
use 3/8 CSST
*use 25 ft. column
From a to e, demand = 35,000 BTU; length = 40 ft. (Table 5)
use 1/2 CSST
20
21
142
323
601
1018
852
1780
3354
6887
10318
19871
Copper
Tubing
(O.D.)
1
Pipe Size 1
1
2
130
293
546
923
772
1613
3039
6240
9349
18005
150
383
870
1622
2475
2295
4799
9040
18560
27809
53556
20
118
269
502
843
710
1484
2796
5741
8601
16564
175
309
700
1303
2205
1843
3854
7259
14904
22331
43008
30
235
531
988
1672
1398
2923
5507
11306
16939
32623
50
213
481
896
1515
1267
2649
4989
10244
15348
29559
60
104
235
438
740
619
1296
2441
5011
7508
14459
225
90
222
414
700
585
1224
2305
4733
7092
13658
250
275
196
443
824
1394
1165
2437
4590
9424
14120
27194
89
211
393
664
556
1162
2190
4495
6735
12971
111
251
467
790
660
1381
2601
5340
8002
15410
200
265
599
1115
1887
1577
3298
6213
12756
19113
36809
40
80
89
201
375
634
530
1109
2089
4289
6426
12375
300
182
412
767
1297
1084
2267
4270
8767
13136
25299
* Total length of piping from outlet of first stage regulator to inlet of second state regulator (or to inlet of second stage regulator furthest away).
Notes: 1) To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities from table.
2) For different first stage pressures, multiply total gas demand by the following factors, and use capacities from table.
Ex: 1,000,000 BTU load at 5 PSI: 1,000,000 (1.12) = 1,200,000 BTU then use chart bases on 1,200,000 BTU
First Stage Pressure PSIG
Multiply By
20
.844
15
.912
Data Calculated per NFPA #54 & 58
5
1.120
125
558
1387
2360
3993
3339
6982
13153
27004
40461
77924
10
Pipe Size
Copper
Tubing
(O.D.)
1
1
1
2
82
185
345
584
488
1020
1922
3945
5911
11385
350
171
386
719
1217
1017
2127
4007
8226
12325
23737
90
100
76
172
321
543
454
949
1788
3670
5499
10591
400
161
365
679
1149
961
2009
3785
7770
11642
22422
22
352
990
1983
2414
3578
6199
9361
16820
7.00
9.33
11.00
11.00
11.00
10.00
11.00
11.00
319
897
1797
2188
3242
5616
8482
15240
150
954
2681
5369
6536
9687
16781
45534
20
294
826
1653
2013
2983
5167
7803
14020
175
762
2143
4292
5225
7744
13416
20260
36402
30
273
778
1539
1872
2775
4807
7259
13043
200
653
1835
3673
4472
6628
11482
17340
31155
40
524
1473
2950
3591
5322
9220
13924
25019
256
721
1443
1757
2603
4510
6811
12238
242
681
1363
1659
2459
4260
6434
11560
578
1626
3256
3864
5874
10106
15368
27612
230
646
1294
1576
2336
4046
6111
10979
275
70
482
1355
2714
3304
4896
8433
12810
23017
219
617
1235
1503
2228
3860
5830
10474
300
80
448
1261
2525
3074
4555
7891
11918
21413
Multiply By
.844
.912
1.120
* Total length of piping from outlet of first stage regulator to inlet of second state regulator or to inlet of second stage regulator furthest away.
CTS
1 CTS
1
1
1
2
1387
3901
7811
9510
14094
24416
66251
125
7.00
9.33
11.00
11.00
11.00
10.00
11.00
11.00
CTS
1 CTS
1
1
1
2
10
202
567
1136
1383
2050
3551
5363
9636
350
90
421
1183
2369
2884
4274
7404
11182
20091
188
528
1057
1287
1907
3304
4989
8965
400
397
1117
2238
2724
4037
6994
10562
18978
100
23
12
28
52
89
137
74
155
292
600
899
1731
125
49
110
206
348
536
291
608
1146
2353
3525
6789
10
11
26
48
80
124
67
141
265
544
815
1569
150
34
76
141
239
368
200
418
788
1617
2423
4666
20
62
129
244
500
749
1443
175
27
61
114
192
296
161
336
632
1299
1946
3747
30
Copper Tubing
(O.D.)
Pipe Size
1
1
1
2
Copper Tubing
(O.D.)
Pipe Size
1
1
1
2
10
22
41
69
106
58
120
227
465
697
1343
54
113
213
437
654
1260
48
101
191
392
587
1130
8
18
33
55
85
46
97
182
374
560
1078
Data Calculated per NFPA #54 & 58
9
19
36
61
94
51
107
201
412
618
1190
300
80
19
42
78
132
203
110
231
435
892
1337
2575
16
36
67
113
174
94
198
372
764
1144
2204
20
46
86
146
224
122
255
480
985
1476
2842
23
52
97
164
253
137
287
541
1111
1665
3207
40
11 Inches Water Column Inlet with a 1/2 Inch Water Column Drop
Maximum capacity of pipe or tubing in thousands of BTU/hr of LP-Gas
7
16
30
51
78
43
89
167
344
515
992
350
33
62
105
161
87
185
349
717
1074
2068
90
7
15
28
47
73
40
83
156
320
479
923
400
14
32
59
100
154
84
175
330
677
1014
1954
100
426
558
927
1106
1735
2168
4097
4720
10
262
347
591
701
1120
1384
2560
2954
20
40
50
75
80
110
150
30
77
105
191
222
373
448
785
910
250
69
96
173
203
343
411
716
829
300
Table does not include effect of pressure drop across the line regulator. If regulator loss exceeds 1/2 psi(based on 13 in. water column outlet pressure), DONOT USETHISTABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator
may vary with flow rate.
CAUTION: Capacities shown in table may exceed maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for guidance.
*Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger number of bends and/or fittings shall be increased by
an equivalent length of tubing according to the following equation: L-1.3n where L is additional length (ft) of tubing and n is the number of additional
fittings and/or bends.
**EHD Equivalent Hydraulic Diameter A measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of
EHD, the greater the gas capacity of the tubing.
13
15
18
19
23
25
30
31
EHD** Flow
Size Designation
24
60
82
151
175
298
355
616
716
400
53
72
135
158
268
319
550
638
500
72
99
181
211
355
426
744
863
EHD** Flow
Designation
13
15
18
19
23
25
30
31
50
69
129
150
254
303
521
605
10
39
55
104
121
208
248
422
490
15
34
49
91
106
183
216
365
425
20
30
42
82
94
164
192
325
379
25
28
39
74
87
151
177
297
344
23
33
64
74
131
153
256
297
20
30
58
66
118
137
227
265
19 17 15 15 14 11
9
8
8
26 25 23 22 20 15 14 12 11
53 49 45 44 41 31 28 25 23
60 57 52 50 47 36 33 30 26
107 99 94 90 85 66 60 53 50
126 117 109 102 98 75 69 61 57
207 191 178 169 159 123 112 99 90
241 222 208 197 186 143 129 117 107
*Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger number of bends and/or fittings shall be increased by an equivalent
length of tubing according to the following equation: L = 1.3n where L is additional length (ft) of tubing and n is the number of additional fittings and/or bends.
**EHD Equivalent Hydraulic Diameter A measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the
greater the gas capacity of the tubing.
Size
25
250
79
179
333
563
471
985
1855
3809
5707
10991
300
72
162
302
511
427
892
1681
3451
5171
9959
350
66
149
278
470
393
821
1546
3175
4757
9162
400
61
139
258
437
365
764
1439
2954
4426
8523
450
58
130
242
410
343
717
1350
2771
4152
7997
500
54
123
229
387
324
677
1275
2618
3922
7554
200
89
202
376
636
531
1111
2093
4298
6439
12401
Copper
Tubing
(O.D.)
1
Pipe Size
1
1
2
150
104
236
439
743
621
1298
2446
5021
7524
14490
80
146
331
617
1044
872
1824
3436
7055
10571
20359
451
310
249
213
189
171
157
1020
701
563
482
427
387
356
1900
1306
1049
898
795
721
663
Copper
3215
2210
1774
1519
1346
1219
1122
Tubing
2687
1847
1483
1269
1125
1019
938
(O.D.)
5619
3862
3101
2654
2352
2131
1961
Pipe
1
10585
7275
5842
5000
4431
4015
3694
Size
1
21731
14936
11994
10265
9098
8243
7584
1
32560
22378
17971
15381
13632
12351
11363
2
62708
43099
34610
29621
26253
23787
21884
26
600
49
111
207
351
293
613
1155
2372
3554
6844
90
137
311
579
979
819
1712
3224
6620
9918
19102
700
45
102
191
323
270
564
1063
2182
3270
6297
100
130
294
547
925
773
1617
3046
6253
9369
18043
LP-Gas Regulators
The regulator truly is the heart of an LP-Gas installation. It must
compensate for variations in tank pressure from as low as 8 psig
to 220 psig and still deliver a steady flow of LP-Gas at 11 w.c.
to consuming appliances. The regulator must deliver this pressure
despite a variable load from intermittent use of the appliances.
The use of a two-stage system offers the ultimate in pin-point
regulation. Two-stage regulation can result in a more profitable
LP-Gas operation for the dealer resulting from less maintenance
and fewer installation call-backs.
27
LP-Gas Regulators
28
The Problem:
A new, properly installed RegO regulator has a high lock-up, does
not lock up, or is creeping.
This is often caused by foreign material on the regulator seat disc.
Foreign material usually comes from system piping upstream of
the regulator. This material prevents the inlet nipple from properly
seating on the seat disc.
The Solution:
There is a simple procedure that can be completed in the field that
will resolve the problems in most cases. This procedure should be
LP-Gas Regulators
Step 1
Hold neck of
regulator securely
with this wrench
Step 2
Seat Disc
Step 3
Inlet Nipple
Hold neck of
regulator securely
with this wrench
29
LP-Gas Regulators
Pigtails
If you are replacing an old regulator, remember to replace the copper pigtail. The old pigtail may contain corrosion which can restrict
flow. In addition, corrosion may flake off and wedge between the
regulator orifice and seat discpreventing proper lock-up at zero
flow.
Regulator Vents/Installation
30
LP-Gas Regulators
3/4 Elbow
Vent Screen
with supressor
3/4 Pipe
From 1 stage
regulator
st
To appliances
3/4 Elbow
31
LP-Gas Regulators
Second Stage in a
Two Stage System
Maximum Load
1,500,000 (a)
LV3403TR
2,500,000 (b)
LV4403SR Series
LV4403TR Series
935,000 (c)
LV4403B Series
1,600,000 (c)
LV5503B4/B6
2,300,000 (c)
LV5503B8
9,800,000
LV6503B Series
450,000
Second Stage in a 2
PSIG System
Integral Twin Stage
Integral Twin Stage
2PSIG
Automatic
Changeover
Suggested
Regulator
1,000,000
LV3403B Series
LV4403Y Y4/Y46R
2,200,000
LV5503Y Y6/Y8
450,000 (d)
LV404B34/39 Series
525,000 (d)
LV404B4/B9 Series
800,000
LV404Y9
400,000 (d)
7525B34 Series
450,000 (d)
7525B4 Series
32
LP-Gas Regulators
Underground Installations
18
Refer to the capacity chart for the size and type regulator which fits
your particular application. Check the performance of this regulator with your actual load at the inlet pressure corresponding to your
lowest winter temperatures (as shown on Page 4).
LP-Gas Regulators
LP-Gas Regulators
35
36
38
After this, shut off all appliance valves to determine if the regulator has a worn seat or if it has been set too high to compensate for
line losses due to undersize piping. A slight rise in pressure will
occur under these conditions. This is called the lock-up pressure.
The lock-up pressure should not exceed 130% of the regulator set
delivery pressure. A quick rise in pressure above this point will
indicate undersize piping.
Continue this same test for 5 minutes or more. If a creeping rise is
noticed in the pressure, the regulator seat is not closing off properly. Inspect regulator inlet nozzle for dirt, scratches, or dents, and
seat disc for signs of wear. Replace where necessary.
For more information, refer to NFPA 54, Section on Inspection,
Testing and Purging, NPGA Propane Safety and Technical Support
Manual Bulletin 403, Pressure testing and leak checking LP Gas
piping systems. For more information on setting single stage regulators, request RegO Products Technical Guide 107.
39
40
Surface
Area
Sq. Ft.
20 or less
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
160
165
Flow
Rate
CFM
Air
626
751
872
990
1100
1220
1330
1430
1540
1640
1750
1850
1950
2050
2150
2240
2340
2440
2530
2630
2720
2810
2900
2990
3080
3170
3260
3350
3440
3530
Surface
Area
Sq. Ft.
170
175
180
185
190
195
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
450
500
550
Flow
Rate
CFM
Air
3620
3700
3790
3880
3960
4050
4130
4300
4470
4630
4800
4960
5130
5290
5450
5610
5760
5920
6080
6230
6390
6540
6690
6840
7000
7150
7300
8040
8760
9470
Surface
Area
Sq. Ft.
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
2000
Flow
Rate
CFM
Air
10170
10860
11550
12220
12880
13540
14190
14830
15470
16100
16720
17350
17960
18570
19180
19780
20380
20980
21570
22160
22740
23320
23900
24470
25050
25620
26180
26750
27310
41
42
100
125
150
175
200
See RegO Products Safety Warning in the L-500 and L-102 Catalogs for
important warning information.
43
Propane
519
656
812
981
1,169
1,480
1,708
2,080
2,629
3,249
3,581
4,119
4,678
5,081
5,495
6,375
6,934
7,813
8,320
8,848
9,955
10,535
11,125
11,735
12,367
13,008
13,660
14,333
15,026
17,572
21,939
24,630
28,769
32,805
Butane
589
744
921
1,112
1,326
1,678
1,936
2,358
2,980
3,684
4,059
4,669
5,303
5,760
6,230
7,227
7,860
8,858
9,433
10,031
11,286
11,943
12,612
13,304
14,020
14,747
15,486
16,249
17,035
19,921
24,872
27,922
32,615
37,190
Orifice or
Drill Size
51
50
49
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
Propane
36,531
39,842
43,361
46,983
50,088
53,296
54,641
60,229
64,369
71,095
74,924
78,,029
80,513
83,721
87,860
92,207
98,312
100,175
103,797
109,385
117,043
134,119
150,366
160,301
168,580
175,617
181,619
187,828
192,796
200,350
205,525
210,699
233,945
233,466
Butane
41,414
45,168
49,157
53,263
56,783
60,420
61,944
68,280
72,973
80,599
84,940
88,459
91,215
94,912
99,605
104,532
111,454
113,566
117,672
124,007
132,689
152,046
170,466
181,728
191,144
199,092
205,896
212,935
218,567
227,131
232,997
238,863
253,880
264,673
Reprinted with permission from NFPA 54, National Fuel Gas Code,
Copyright1999, National Fire Protection Association, Quincy, MA 02269. This
reprinted material is not the complete and official position of the NFPA on the
referenced subject which is represented only by the standard in its entirety.
45
Liquid
Iron Pipe (Feet)
Propane
1/4 3/8 1/2 3/4 1 1-1/4 1-1/2 2
Flow Schedule Schedule Schedule Schedule Schedule Schedule Schedule Schedule
GPH 40 80 40 80 40 80 40 80 40 80 40 80 40 80 40 80
10 729 416
15 324 185
60 20 11 92 58 331 224
80 11
100
120 23 15 83 56
326
238
140 15
160 13
350
38
28
130
99
578
459
400
30
22
99
75
433
344
980
794
500
19
14
64
49
283
225
627
508
600
44
33
197
156
435
352
700
32
24
144
114
320
259
800
25
19
110
87
245
198
965
795
900
1000
16
12
71
56
157
127
618
509
1500
31
25
70
57
275
227
2000
18
14
39
32
154
127
3000 8
6
17
14
69
57
4000
10
8
39
32
5000
25
21
10000
6
5
46
To Use Chart
1. Having determined the required flow at point of use, locate this flow in the left
hand column. If this falls between two figures, use the larger of the two.
2. Determine total length of piping required from source to point of use.
3. Read across chart from left (required flow) to right to find the total length
which is equal to or exceeds the distance from source to use.
4. From this point read up to find the correct size of pipe required.
Fitting
47
48
7 July
2 February
8 August
3 March
9 September
4 April
10 October
5 May
11 November
6 June
12 December
91 1991
98 1998
92 1992
99 1999
93 1993
00 2000
94 1994
01 2001
95 1995
etcetera . . .
96 1996
97 1997
Example: 6A92 = First week of June, 1992
Air
Butane
Natural Gas
Propane
By
0.707 Butane
1.290
Natural Gas
0.816 Propane
1.414 Air
1.826
Natural Gas
1.154 Propane
0.775 Air
0.547
Butane
0.632 Propane
1.225 Air
0.866 Butane
1.580
Natural Gas
49
Conversion Units
Multiply
By To Obtain
Pressure
Atmospheres
1.0332 kilograms per sq. centimeter
Atmospheres
14.70 pounds per square inch
Atmospheres
407.14 inches water
Grams per sq. centimeter 0.0142 pounds per square inch
Inches of mercury
.4912 pounds per square inch
Inches of mercury
1.133 feet of water
Inches of water
0.0361 pounds per square inch
Inches of water
0.0735 inches of mercury
Inches of water
0.5781 ounces per square inch
Inches of water
5.204 pounds per square foot
bar
100 kPa
Kilograms per sq. centimeter 14.22 pounds per square inch
Kilograms per square meter 0.2048 pounds per square foot
Pounds per square inch 0.0680 atmospheres
Pounds per square inch 0.07031 kilograms per sq. centimeter
Pounds per square inch* 6.89 kPa
Pounds per square inch 2.036 inches of mercury
Pounds per square inch 2.307 feet of water
Pounds per square inch .06897 bar
Pounds per square inch 27.67 inches of water
kPa
.145 PSI
Length
Centimeters
0.3937 inches
Feet
0.3048 meters
Feet
30.48 centimeters
Feet
304.8 millimeters
Inches
2.540 centimeters
Inches
25.40 millimeters
Kilometer
0.6214 miles
Meters
1.094 yards
Meters
3.281 Feet
Meters
39.37 inches
Miles (nautical)
1,853.0 meters
Miles (statute)
1,609.0 meters
Yards
0.9144 meters
Yards
91.44 centimeters
*Ex. 5 pounds per square inch X (6.89) = 34.45 kPa
50
Conversion Units
Multiply
Volume
Cubic centimeter
Cubic feet
Cubic feet
Cubic feet
Cubic feet
Cubic feet
Gallons (Imperial)
Gallons (US)*
Gallons (US)
Gallons (US)
Gallons (US)
Liters
Liters
Liters
Liters
Pints (US)
Miscellaneous
BTU
Calories
Ton (US)
Kilogram
Kilowatt Hour
Ounces
Pounds
Pounds
Ton (US)
Therm
API Bbls
By
0.06103
7.48
28.316
1728
.03704
.02832
1.201
0.1337
0.8326
3.785
231
0.0353
0.2642
1.057
2.113
0.4732
To Obtain
cubic inch
gallons (US)
liters
cubic inches
cubic yards
cubic meters
gallons (US)
cubic feet
gallons (Imperial)
liters
cubic inches
cubic feet
gallons (US)
quarts (US)
pints (US)
liters
252 calories
3.968 BTU
2000 pounds
2.205 pounds
3412 BTU
28.35 grams
0.4536 kilograms
453.5924 grams
.908 tonne
100,000 BTU
42 gallons (US)
51
52
53
54