Electrical Interface

EUROMAP 71

between Injection Moulding Machine


and Mould Changing Device
Version 1.4, February 2015
(12 pages)

This recommendation was prepared by the Technical Commission of EUROMAP.

The diagram 'Signal sequence' in clause 3 was modified (v. 1.1).


A further supplier added (v. 1.2).
Supplier's data updated (Ver. 1.3).
A further supplier added (v. 1.4).

EUROMAP 71

Content

Version 1.4

Page

Scope and Application ........................................................................... 3

Description .............................................................................................. 6

2.1

Plug and socket outlet ................................................................................................. 6

2.2

Contact specification ................................................................................................... 7

2.2.1 Emergency stops, safety devices .............................................................................................7


2.2.2 Logical Signals .........................................................................................................................7
2.2.3 Reference potential (Table 1: ZA9, ZC9 and Table 2: A9, C9) ................................................7

2.3

Plug contact assignment............................................................................................. 7

2.3.1 Table 1: Plug on the IMM Signals from the IMM to the MCD...................................................8
2.3.2 Table 2: Plug on the IMM Signals from the MCD to the IMM.....................................................9

Signal sequence ................................................................................... 10

Sources of supply................................................................................. 11

EUROMAP 71

Page 2 of 12

EUROMAP 71

Version 1.4

1 Scope and Application


This EUROMAP recommendation defines the connection between the injection moulding machine (IMM) and
the mould changing device (MCD). This is intended to provide interchangeability.
In addition recommendations are given for signal voltage and current levels.
The following situations are covered:

TABLE A

IN/OUT

IMM and MCD with one table on the rear side of the IMM

Preheating
station
TABLE A
TABLE B

IN/OUT

IMM and MCD with two tables on the rear side of the IMM

EUROMAP 71

Page 3 of 12

EUROMAP 71

Version 1.4

TABLE A

IN

OUT
TABLE A

IN/OUT

IN/OUT
TABLE A

IMMs with MCDs on front and rear side of IMM

EUROMAP 71

Page 4 of 12

EUROMAP 71

Version 1.4

Preheating
station

IN/OUT
TABLE A
TABLE B

IN/OUT

Two IMMs and one MCD with two tables

EUROMAP 71

Page 5 of 12

EUROMAP 71

Version 1.4

2 Description
The signals in both the IMM and the MCD are given by contacts, e.g. contacts of relays or switches, semiconductors, etc. The contact making is either potential-free or related to a reference potential supplied to a contact
of the plug mounted on the IMM or the MCD (see Tables 1 and 2). All signals which are not optional shall be
supported by all IMMs and MCDs.

2.1 Plug and socket outlet


The connection between the IMM and the MCD is achieved by the plugs specified below. For the IMM (see
Figure 2) and the MCD (see Fig. 1) the plug contacts should be capable of taking a minimum of 250 V and 10 A.
Arrangements of pins and sockets viewed from the mating side (opposite the wiring side).

Figure 1 = Plug on the MCD

EUROMAP 71

Figure 2 = Plug on the IMM

Page 6 of 12

EUROMAP 71

Version 1.4

2.2 Contact specification


2.2.1

Emergency stops, safety devices

The voltages of the signals must not exceed 50 V DC

A current of at least 6 mA must be maintained during signalling.

The maximum current is 6 A.

2.2.2

Logical Signals

These signals shall be in accordance with clause 3.3.1 of EN 61131-2, Table 9, Type 2 or with clause 3.3.3
of EN 61131-2,Table 11, 0,1 A max.

2.2.3

Reference potential (Table 1: ZA9, ZC9 and Table 2: A9, C9)

Voltage

18 36 V DC

Overlayed ripple

max. 2,5 Vpp

Withstand against overvoltage

up to 60 V

Current

max. 2 A

min. 10 ms

2.3 Plug contact assignment


Notes on the tables below:

Unless otherwise noted, the switch contacts are switching the reference potential on plug contacts: Table1 /
No ZA9 (IMM signal) and Table 2 / No A9 (MCD signal).

All signals are continuous signals unless otherwise noted.

The signals are conducted from the signal source to the respective pin.

Apart from the MCD signal "Emergency stop " (Table 2; A1/C1) the signals can assume any status when
the MCD is switched off.

Apart from the IMM signals "Emergency stop " (Table 1; ZA1/ZC1) and Safety devices (Table 1; ZA3,ZC3)
the signals can assume any status when the MCD is switched off.

EUROMAP 71

Page 7 of 12

EUROMAP 71

2.3.1

Version 1.4

Table 1: Plug on the IMM


Signals from the IMM to the MCD

Contact
No (male),
see fig. 2
ZA1
ZC1

Signal designation

Description

Emergency stop of IMM

The switch contact must be open when the IMM emergency stop device is being actuated.
Opening the switch contact causes emergency stop of the MCD.

ZA2
ZC2

Reserved for future use of EUROMAP

ZA3
ZC3

The switch contact is closed when safety devices on the IMM are operative (e.g. guard of the
mould area opposite the mould change side is closed and/or sensitive floor in the mould area
is not actuated) so that dangerous movements of the MCD are possible. The signal is active
in any operation mode.

Safety devices of IMM

ZA4
ZC4

Reserved for future use of EUROMAP

ZA5

Request: Operation by IMM

HIGH signal when there is a request to operate the MCD by the IMM.

ZA6

Operation by IMM

HIGH signal when the operation of the MCD by the IMM is active. (The IMM is either in the
automatic mould change mode or the movements of the MCD are controlled by actuators on
the IMM.)

ZA7

Enable table movement


IN/OUT

HIGH signal when the IMM is ready for the table to move into or out of the IMM (mould in
position and unclamped, ejector not connected, guard of the mould area at the mould side
open). This signal shall not be used to start the movement.

ZA8
ZA9

Reserved for future use of EUROMAP


Supply from MCD

24 V DC (Reference potential)

ZB2

Move mould OUT

HIGH signal when the IMM is ready to move the mould out of the IMM (e.g. mould
unclamped, guard of the mould area at the mould change side open, MCD in change
position). This signal is used to start the movement. The movement shall continue as long as
the signal is HIGH.

ZB3

Move mould IN

HIGH signal when the IMM is ready to move the mould into the IMM (e.g. no mould in IMM,
guard of the mould area at the mould change side open, correct mould height). This signal is
used to start the movement. The movement shall continue as long as the signal is HIGH.

ZB4

Move table A in position

To move table A in position in front of the guard of the mould area. The signal shall remain
HIGH until B4 changes to HIGH.

ZB5

Move table B in position

To move table B in position in front of the guard of the mould area. The signal shall remain
HIGH until B5 changes to HIGH.

ZB6

Reserved for future use of EUROMAP

ZB7

Reserved for future use of EUROMAP

ZB8

Reserved for future use of EUROMAP

ZC5

Reserved for future use of EUROMAP

ZC6

Reserved for future use of EUROMAP

ZC7

Reserved for future use of EUROMAP

ZC8
Optional

Mould preparation

HIGH signal for preheating the mould

ZC9

Supply from MCD

0 V (Reference potential)

EUROMAP 71

Page 8 of 12

EUROMAP 71
2.3.2

Version 1.4

Table 2: Plug on the IMM


Signals from the MCD to the IMM

Contact
No (female),
see fig. 2
A1
C1

Signal designation

Description

Emergency stop of MCD

The switch contact must be open when the MCD emergency stop is being actuated. The
switch contact opening causes emergency stop of the IMM. The switch contact must be
operative if the MCD is switched off.

A2
C2

Reserved for future use of EUROMAP

A3

Request: Operation by
MCD

HIGH signal when there is a request to operate the mould changing by the MCD.

A4

Operation by MCD

HIGH signal when the operation of the mould change by the MCD is active. (The MCD is either
in its manual mould change mode or the movements of the MCD are controlled by another
IMM.) An automatic mould change cannot be started.

A5

MCD failure status

HIGH signal when the MCD has no failures e.g. guards of the MCD are closed.

A6

Reserved for future use of EUROMAP

A7

Mould is OUT

HIGH signal when the mould has been moved out of the IMM.

A8

Mould is IN

HIGH signal when the mould has been moved into the IMM and is centred. (The mould is now
ready for clamping; the closing movement of the platen is enabled.)

A9

Supply from IMM

24V DC (Reference potential)

B2

Mould detection A

HIGH signal when a mould is on table A .

B3

Mould detection B

HIGH signal when a mould is on table B .

B4

Table A in position

HIGH signal when table A is in position in front of the guard of the mould area.

B5

Table B in position

HIGH signal when table B is in position in front of the guard of the mould area.

B6

Table is OUT

HIGH signal when the table is in a position to enable the closing movement of the guard of the
mould area of the IMM on mould change side .

B7
Optional

MCD failure 0

HIGH signal when the MCD has a failure code bit 0.

B8
Optional

MCD failure 1

HIGH signal when the MCD has a failure code bit 1.

C3
Optional

MCD failure 2

HIGH signal when the MCD has a failure code bit 2.

C4
Optional

MCD failure 3

HIGH signal when the MCD has a failure code bit 3.

C5
Optional

MCD failure 4

HIGH signal when the MCD has a failure code bit 4.

C6

Reserved for future use by EUROMAP

C7

Reserved for future use by EUROMAP

C8
Optional

C9

Enable mould preparation HIGH signal when MCD is ready for preheating the mould.

Supply from IMM

EUROMAP 71

0 V (Reference potential)

Page 9 of 12

EUROMAP 71

Version 1.4

3 Signal sequence
Example:

In the example this signal sequence of a MCD with two tables on the rear side of IMM is shown:
The mould being clamped in the IMM is unclamped and moved out to table A, then the mould
being already available on table B is moved into the mould area of the IMM to be clamped.

ZA5
Request: Operation by IMM
A4
Operation by MCD

ZA6
Operation by IMM
B2
Mould detection A
ZB4
Move Table A in position
B4
Table A in position

ZB2
Move mould OUT
A7
Mould is OUT

ZB5
Move table B in position

B5
Table B in position

B3
Mould detection B

ZB3
Move mould IN
A8
Mould is In

B6
Table is OUT
ZA7
Enable table movement IN/OUT
NOTE:

With the switching on the signal ZA5 to HIGH, the signal A5 shall be monitored.

EUROMAP 71

Page 10 of 12

EUROMAP 71

Version 1.4

4 Sources of supply
Pin insert
Pin insert Z

Supplier

Plug type

Amphenol

Heavymate C146 10A025 500 2


D50
C146 10A025 505 2

HARTING

Han 50 D

ILME

CD 50

LAPP

EPIC
H-D 50

PHOENIX

HC-D 50

Tyco / HTS

HD 50

WAIN

HD-050

Weidmller

HD 50

Westec

S-D 50

WIELAND

revos HD

Socket insert
Socket insert Z
C146 10B025 500 2
C146 10B025 505 2

09 21 025 3001

09 21 025 3101

09 21 025 3011

09 21 025 3111

CDM 25

CDF 25

CDM 25 Z

CDF 25 Z

11283300

11282300

11283400

11283500

1584932

1584402

1411478

1411481

2-1103108-3

2-1103109-3

0-1103108-1

0-1103109-1

HD-025-MC

HD-025-FC

HD-025-MC Z

HD-025-FC Z

165081 0000

165082 0000

102304 0000

102305 0000

7125.4112.0

7125.4012.0

7125.4112.3

7125.4012.3

73.700.2553.0

73.710.2553.0

73.700.2553.3

73.710.2553.3

Address
Amphenol Tuchel Electronics GmbH
August Husser Str.10, 74080 Heilbronn,
Germany
HARTING Electric GmbH & Co.KG
Wilhelm-Harting-Str. 1, 32339 Espelkamp,
Germany
ILME S.p.A.
Via Marco Antonio Colonna 9, 20149 Milano, Italy
U. I. Lapp GmbH
Schulze-Delitzsch Str. 25, 70565 Stuttgart,
Germany
Phoenix Contact GmbH & Co. KG
Flachsmarktstr. 8, 32825 Blomberg, Germany
Tyco Electronics AMP GmbH, HTS Div.
Ohlenhohnstr. 17, 53819 Neunkirchen, Germany
WAIN Electric GmbH
Mergenthalerallee 23/25, 65760 Eschborn,
Germany
Weidmller Interface GmbH & Co. KG
Klingenbergstr. 16, 32758 Detmold, Germany
Westec S.r.L.
Via Fiume Lambro 1, 20097 San Donato
Milanese, Italy
Wieland Electric GmbH
Brennerstr. 10-14, 96052 Bamberg, Germany

The plugs from these suppliers are interchangeable.


Note: Further suppliers are invited to be listed.

EUROMAP 71

Page 11 of 12

EUROMAP 71

Version 1.4

EUROMAP
Europisches Komitee
Gummimaschinen

der

Hersteller

von

Kunststoff-

und

European Committee of Machinery Manufacturers for the Plastics


and Rubber Industries

Comit Europen des Constructeurs de Machines pour Plastiques


et Caoutchouc

Comitato Europeo Costruttori Macchine per Materie Plastiche e


Gomma

See you again


http://www.euromap.org

Copyright by EUROMAP