What Is A Surge Arrester
What Is A Surge Arrester
What Is A Surge Arrester
Surge arresters are devices that help prevent damage to apparatus due to high
voltages. The arrester provides a low-impedance path to ground for the current
from a lightning strike or transient voltage and then restores to a normal
operating conditions.
A surge arrester may be compared to a relief valve on a boiler or hot water
heater. It will release high pressure until a normal operating condition is reached.
When the pressure is returned to normal, the safety valve is ready for the next
operation.
When a high voltage (greater than the normal line voltage) exists on the line, the
arrester immediately furnishes a path to ground and thus limits and drains off the
excess voltage. The arrester must provide this relief and then prevent any further
flow of current to ground. The arrester has two functions; it must provide a point
in the circuit at which an over-voltage pulse can pass to ground and second, to
prevent any follow-up current from flowing to ground.
Top
Internal causes
Switching surge
The overvoltages produced on the power system due to switching are known as
switching surge.
Insulation failure
The most common case of insulation failure in a power system is the grounding
of conductors (i.e. insulation failure between line and earth) which may cause
overvoltage in the system.
Arcing ground
The phenomenon of intermittent arc taking place in line to ground fault of a
3phase system with consequent production of transients is known as arcing
ground.
Resonance
It occurs in an electrical system when inductive reactance of the circuit becomes
equal to capacitive reactance. under resonance , the impedance of the circuit is
equal to resistance of the circuit and the p.f is unity.
Top
The traveling waves produced due to lightning will shatter the insulators. If the
traveling waves hit the windings of a transformer or generator it may cause
considerable damage.
Top
1. Station Class
Station class arrestors are typically used in electrical power stations or
substations and other high voltage structures and areas.
These arrestors protect against both lightning and over-voltages, when
the electrical device has more current in the system than it is designed to
handle.
These arrestors are designed to protect equipment above the 20 mVA
range.
2. Intermediate Class
Like station class arrestors, intermediate class arrestors protect against
surges from lightning and over-voltages, but are designed to be used in
medium voltage equipment areas, such as electrical utility stations,
substations, transformers or other substation equipment.
These arrestors are designed for use on equipment in the range of 1 to
20 mVA.
3. Distribution Class
Distribution class arrestors are most commonly found on transformers,
both dry-type and liquid-filled.
These arrestors are found on equipment rated at 1000 kVA or less.
These arrestors are sometimes found on exposed lines that have direct
connections to rotating machines.
4. Secondary Class
Secondary class lightning arrestors are designed to protect most homes
and businesses from lightning strikes, and are required by most electrical
codes, according to, Inc., an electrical power protection company.
These arrestors cause high voltage overages to ground, though they do
not short all the over voltage from a surge. Secondary class arrestors
offer the least amount of protection to electrical systems, and typically do
not protect solid state technology, or anything that has a microprocessor.
Top
Top
diverted is a protective device, which conducts the high voltage surges on the
power system to the ground.
Fig below shows the basic form of a surge diverter.
It consists of a spark gap in series with a non-linear resistor. One end of the
diverter is connected to the terminal of the equipment to be protected and the
other end is effectively grounded. The length of the gap is so set that normal
voltage is not enough to cause an arc but a dangerously high voltage will break
down the air insulation and form an arc. The property of the non-linear resistance
is that its resistance increases as the voltage (or current) increases and viceversa.
This is clear from the volt/amp characteristic of the resistor shown in Figure
above.
The action of the lightning arrester or surge diverter is as under:
1. Under normal operation, the lightning arrester is off the line i.e. it
conducts no current to earth or the gap is non-conducting
2. On the occurrence of over voltage, the air insulation across the gap
breaks down and an arc is formed providing a low resistance path for the
surge to the ground. In this way, the excess charge on the line due to the
surge is harmlessly conducted through the arrester to the ground instead
of being sent back over the line.
3. It is worthwhile to mention the function of non-linear resistor in the
operation of arrester. As the gap sparks over due to over voltage, the arc
would be a short-circuit on the power system and may cause powerfollow current in the arrester. Since the characteristic of the resistor is to
offer low resistance to high voltage (or current), it gives the effect of
short-circuit. After the surge is over, the resistor offers high resistance to
make the gap non-conducting.
2. Intermediate Class
Like station class arrestors, intermediate class arrestors protect against
surges from lightning and over-voltages, but are designed to be used in
medium voltage equipment areas, such as electrical utility stations,
substations, transformers or other substation equipment.
These arrestors are designed for use on equipment in the range of 1 to
20 mVA.
3. Distribution Class
Distribution class arrestors are most commonly found on transformers,
both dry-type and liquid-filled.
These arrestors are found on equipment rated at 1000 kVA or less.
These arrestors are sometimes found on exposed lines that have direct
connections to rotating machines.
4. Secondary Class
Secondary class lightning arrestors are designed to protect most homes
and businesses from lightning strikes, and are required by most electrical
codes, according to, Inc., an electrical power protection company.
1.
Under normal operation, the lightning arrester is off the line i.e. it conducts no current to earth
or the gap is non-conducting
2. On the occurrence of over voltage, the air insulation across the gap breaks down and an arc is
formed providing a low resistance path for the surge to the ground. In this way, the excess
charge on the line due to the surge is harmlessly conducted through the arrester to the ground
instead of being sent back over the line.
3. It is worthwhile to mention the function of non-linear resistor in the operation of arrester. As the
gap sparks over due to over voltage, the arc would be a short-circuit on the power system and
may cause power-follow current in the arrester. Since the characteristic of the resistor is to offer
low resistance to high voltage (or current), it gives the effect of short-circuit. After the surge is
over, the resistor offers high resistance to make the gap non-conducting.
The string of insulators for an overhead line on the bushing of transformer has
frequently a rod gap across it. Fig 8 shows the rod gap across the bushing of a
transformer. Under normal operating conditions, the gap remains non-conducting.
On the occurrence of a high voltage surge on the line, the gap sparks over and
the surge current is conducted to earth. In this way excess charge on the line due
to the surge is harmlessly conducted to earth
Limitations
1. After the surge is over, the arc in the gap is maintained by the normal
supply voltage, leading to short-circuit on the system.
2. The rods may melt or get damaged due to excessive heat produced by
the arc.
3. The climatic conditions (e.g. rain, humidity, temperature etc.) affect the
performance of rod gap arrester.
4. The polarity of the f the surge also affects the performance of this
arrester.
Due to the above limitations, the rod gap arrester is only used as a back-up
protection in case of main arresters.
between them gradually increases towards the top as shown. The horns are
mounted on porcelain insulators. One end of horn is connected to the line
through a resistance and choke coil L while the other end is effectively grounded.
The resistance R helps in limiting the follow current to a small value. The choke
coil is so designed that it offers small reactance at normal power frequency but a
very high reactance at transient frequency. Thus the choke does not allow the
transients to enter the apparatus to be protected.
The gap between the horns is so adjusted that normal supply voltage is not
enough to cause an arc across the gap.
Under normal conditions, the gap is non-conducting i.e. normal supply voltage is
insufficient to initiate the arc between the gap. On the occurrence of an over
voltage, spark-over takes place across the small gap G. The heated air around
the arc and the magnetic effect of the arc cause the arc to travel up the gap. The
arc moves progressively into positions 1, 2 and 3.
At some position of the arc (position 3), the distance may be too great for the
voltage to maintain the arc; consequently, the arc is extinguished. The excess
charge on the line is thus conducted through the arrester to the ground.
limits the power arc. By the inclusion of series resistance, the degree of
protection against traveling waves is reduced.
In order to overcome this difficulty, some of the gaps (B to C in Fig) are shunted
by resistance. Under normal conditions, the point B is at earth potential and the
normal supply voltage is unable to break down the series gaps. On the
occurrence an over voltage, the breakdown of series gaps A to B occurs.
The heavy current after breakdown will choose the straight through path to
earth via the shunted gaps B and C, instead of the alternative path through the
shunt resistance.
Hence the surge is over, the arcs B to C go out and any power current following
the surge is limited by the two resistances (shunt resistance and series
resistance) which are now in series. The current is too small to maintain the arcs
in the gaps A to B and normal conditions are restored.
Such arresters can be employed where system voltage does not exceed 33kV.
upper electrode is connected to rod gap and the lower electrode to the earth.
One expulsion arrester is placed under each line conductor.
Fig shows the installation of expulsion arrester on an overhead line.
On the occurrence of an over voltage on the line, the series gap AA spanned and
an arc is stuck between the electrodes in the tube. The heat of the arc vaporizes
some of the fiber of tube walls resulting in the production of neutral gas. In an
extremely short time, the gas builds up high pressure and is expelled through the
lower electrode, which is hollow. As the gas leaves the tube violently it carries
away ionized air around the arc.
This deionizing effect is generally so strong that the arc goes out at a current zero
and will not be re-established.
Advantages
1. They are not very expensive.
2. They are improved form of rod gap arresters as they block the flow of
power frequency follow currents
3. They can be easily installed.
Limitations
1. An expulsion type arrester can perform only limited number of operations
as during each operation some of the fiber material is used up.
Under normal conditions, the normal system voltage is insufficient to cause the
break down of air gap assembly. On the occurrence of an over voltage, the
breakdown of the series spark gap takes place and the surge current is
conducted to earth via the non-linear resistors.
Since the magnitude of surge current is very large, the non-linear elements will
offer a very low resistance to the passage of surge. The result is that the surge
will rapidly go to earth instead of being sent back over the line. When the surge is
over, the non-linear resistors assume high resistance to stop the flow of current.
be taken on arresters that have failed but the over pressure relief valve did not
operate.
As shown in the following figure: High performance protections are not based
only on current but also on voltage
Protection
Convent
Adva
Adva
High
ional
nced
nced
Perform
Plus
ance
Short-circuit /
Instantaneous
overcurrent
Thermal
overload
Phase current
imbalance
Phase current
loss
Overcurrent(instant
aneous and
temporised)
Ground
current /
Instantaneous
earth fault
Long start
(stall) /
Incomplete
sequence
Jam (locked
rotor)
Under-current
Phase current
reversal
Motor
temperature
(by sensors)
Rapid cycle
lock-out /
Locking out
Load
shedding
Notching or
jogging /
Number of
starts
Phase voltage
imbalance
Phase voltage
loss
Phase voltage
reversal
Under-voltage
Over-voltage
Under-power
Over-power
Under power
factor
Over power
factor
Motor
reclosing