Chapter - 1
Chapter - 1
Chapter - 1
INTRODUCTION
1.1 INTRODUCTION
Electricity is dangerous. However electricity is very useful and has become essential
in modern life. Electricity is used in houses, farms, plants, factories, public places and
practically every working place. The main dangers from electricity are due to electric
faults resulting in arcing, explosions, burns, injury, deaths and fires. By proper
precautions, electricity can be used very safely.
Non-current carrying metallic parts which are not at high potential with respect to
earth and which are normally near earth potential may give shock to operation and
maintenance personnel or general public due to
Leakage current through poor insulation,
Induced current in metallic part due to vicinity with power circuit,
Dielectric charges in the capacitance associated with those metal parts.
Mostly 85% of electrical accidents are happened due to shocks. By providing proper
earthing we can avoid such accidents.
1.2 OBJECTIVES AND SCOPE OF EARTHING
1. Provide an alternative path for the fault current to flow so that it will not endanger the
user.
2. Ensure that all exposed conductive parts do not reach a dangerous potential.
3. Maintain the voltage at any part of an electrical system at a known value so as to
prevent over current or excessive voltage on the appliances or equipment.
The second chapter deals with the earthing standards and types of earthing.
The third chapter details deals with the major components of earthing.
The fourth chapter deals with the layout of earthing.
Discussion on maintenance of earthing is given in chapter five.
The sixth chapter deals with the conclusion.
CHAPTER -2
EARTHING
2.1 EARTHING AND GROUNDING
It is a universal practice to ground (earth) every non-current carrying metallic part
associated with electrical equipment, plant, installation to ensure safety.
Grounding is same as earthing. The term Grounding (or ground) is used in USA,
Canada, Japan and is defined in IEEE Standard Dictionary as Conducting connection to the
earth. The term Earthing (or earth) is used in India, UK, Europe and IEC standards.
Earth is a good conductor. It can absorb infinite charge without rise in voltage. Hence
earthed point is always at very low potential.
2.2 EARTHING STANDARDS
2.2.1 DOMESTIC, COMMERCIAL AND INDUSTRIAL PREMISES
(i.e. installations up to 1,000 V ac and 1,500 V dc - between phases, with some minor
exceptions).
2.2.1.1 Existing
BS 7671 1992, Amendment 1, 1994. Requirements for Electrical Installations. (This is
also known as the IEE Wiring Regulations, 16th Edition). Applies to all aspects of new
electrical installations and requires that older installations are re-appraised when they are
extended.
2.2.2
IS: 3043/1987
IS 1239 part
1/2004
IS 1239 part
IEEE-80
IEEE-837
No point is connected with earth (isolation), except perhaps via a high impedance.
The second letter indicates the connection between earth and the electrical device
being supplied:
T
the earth.
2.3.1 TN NETWORKS
In a TN earthing system, one of the points in the generator or transformer is
connected with earth, usually the star point in a three-phase system. The body of the electrical
device is connected with earth via this earth connection at the transformer.
The conductor that connects the exposed metallic parts of the consumer's electrical
installation is called protective earth. The conductor that connects to the star point in a
three-phase system, or that carries the return current in a single-phase system, is called
neutral (N). Three variants of TN systems are distinguished:
TNS
PE and N are separate conductors that are connected together only near the power
source. This arrangement is the current standard for most residential and industrial
electric systems in North America and Europe.
TNC
A combined PEN conductor fulfills the functions of both a PE and an N conductor.
Rarely used.
TNCS
Part of the system uses a combined PEN conductor, which is at some point split up
into separate PE and N lines. The combined PEN conductor typically occurs between
the substation and the entry point into the building, and separated in the service head.
In the UK, this system is also known as protective multiple earthing (PME), because
of the practice of connecting the combined neutral-and-earth conductor to real earth at
many locations, to reduce the risk of broken neutrals - with a similar system in
Australia being designated as multiple earthed neutral (MEN).
device.
distribution point.
power cords.
Fig.2.2 TN-S, TN-C, TN-C-S earthing system
It is possible to have both TN-S and TN-C-S supplies from the same transformer. For
example, the sheaths on some underground cables corrode and stop providing good earth
connections, and so homes where "bad earths" are found get converted to TN-C-S.
2.3.2 TT NETWORK
In a TT earthing system, the protective earth connection of the consumer is provided
by a local connection to earth, independent of any earth connection at the generator.
The big advantage of the TT earthing system is that it is clear of high and low
frequency noises that come through the neutral wire from connected equipment. TT has
always been preferable for special applications like telecommunication sites that benefit from
the interference-free earthing. Also, TT does not have the risk of a broken neutral.
10
11
TT
IT
TN-S
TN-C
TN-C-S
High
Highest
Low
Low
Low
RCD preferred?
Yes
No
Yes
No
No
Need earth
Yes
Yes
No
No
No
Low
Low
Highest
Least
High
No
No
No
Highest
High
Safe
Less Safe
Safest
Least
Safe
electrode at site?
PE conductor cost
Risk of broken
neutral
Safety
Safe
Electromagnetic
Least
Least
Low
High
Low
High loop
Double fault,
Broken
Broken
Broken
impedance
overvoltage
PE
neutral
neutral
Safe and
Continuity of
Safest
Cost
Safety
reliable
operation, cost
interference
Safety risks
Advantages
and cost
12
System Earthing
Equipment Earthing
Reference Earthing
Discharge Earthing
Out of those systems earthing, Equipment earthing are most commonly made in industries.
Based on the usage earthing can be classified into
Conventional earthing.
Maintenance free earthing.
Ungrounded Systems
Solid Grounding
Resistance grounding
Resonant grounding
13
ground-to-ground are weak and easily distorted. Two principal advantages are attributed to
ungrounded systems.
Operational: The first ground fault on a system causes only a small ground current to
flow, so the system may be operated with ground fault present, improving system
continuity.
Economic: No expenditures are required for grounding equipment or grounded system
conductors.
14
16
17
The Conventional system of Earthing calls for digging of a large pit into which a GI
pipe or a copper plate is positioned amidst layers of charcoal and salt. It is cumbersome to
install only one or two pits in a day.
The Conventional system of GI pipe Earthing or copper plate Earthing requires
maintenance and pouring of water at regular interval.
2.4.4 MAINTENANCE FREE EARTHING
It is a new type of earthing system which is ready made, standardized and
scientifically developed.
2.4.4.1 Advantages of free earthing
1. Maintenance Free: No need to pour water at regular interval- except in sandy soil.
2. Consistency: Maintain stable and consistent earth resistance around the year.
3. More Surface Area: The conductive compound creates a conductive zone, which
provides the increased surface area for peak current dissipation. And also get stable
reference point.
4. Low earth resistance. Highly conductive. Carries high peak current repeatedly.
5. No corrosion. Eco Friendly.
6. Long Life.
7. Easy Installation.
18
CHAPTER -3
EARTHING COMPONENTS
3.1 COMPONENTS OF EARTHING SYSTEM
1.
2.
3.
4.
5.
19
20
R=
100
4l
log e
2l
d
ohms
21
...(3.1)
22
After laying the earth from the earth bus to the electrode through the PVC conduits at the pit
entry conduits should be sealed with bitumin compound.
3.1.1.1.2 Plates
There are several types of plate used for earthing purposes, but the only type which is
generally considered as an electrode would be solid and of substantial size. Lattice type
plates, as illustrated in Figure 4-1 are used for potential grading and would not be expected
topass significant amounts of fault current. They are normally made of copper or steel mesh.
23
R=
/ A
A
ohms
where
= resistivity of the soil ( assumed uniform) ( in ohm.m)
A = area of both sides of the plate (in m* ).
...(3.2)
1.
2.
3.
4.
For bare or PVC-covered cables, the cross section area of the cable could be either
The main incoming earthing cable connected to the earth bus is branched off from the
Connections between the marshalling earth buses and the equipments are carried out
by means of single wires or cables of appropriate size, which are referred to as earthing
wire, or earthing link. The connection between the earthing buses and the earthing grid is
also made by means of earthing cables.
Earthing wires and cables are used either bare or PVC-covered (preferably bare) and
are normally single core of the different cross section area, depending on the design
specification.
3.1.5 LIGHTNING ARRESTOR AND ACCESSORIES
To protect the installation against the damages which could happen in the event of a
lightning strike, special equipment of different installation set-up are used. The prime element
of these electrical safety equipment is the lightning arresters which are installed on the
highest point of an installation which are most liable to be struck by the lightning.
Lightning arresters are actually part of the earthing system of an installation and are,
therefore, appropriately connected to the main earthing grid by means of separate purpose
made earth wells.
28
found non-uniform, either a gradual variation or a two-layer model may be adopted for the
computation of earth resistivity.
The resistivity of earth varies over a wide range depending on its moisture content. It
is, therefore, advisable to conduct earth resistivity tests during the dry season in order to get
conservative results.
3.4.2 TEST LOCATIONS
In the evaluation of earth resistivity for substations and generating stations, at least
eight test directions shall be chosen from the centre of the station to cover the whole site. This
number shall be increased for very large station sites of it, the test results obtained at various
locations show a significant difference, indicating variations in soil formation.
In case of transmission lines, the measurements shall be taken along the direction of
the line throughout the length approximately once in every 4 kilometres.
3.4.3 PRINCIPLE OF TESTS
Wenner's four electrode method is recommended for these types of field
investigations. In this method, four electrodes are driven into the earth along a straight line at
equal intervals. A current is passed through the two outer electrodes and the earth as shown
in Fig. 3.6 and the voltage difference V, observed between the two inner electrodes. The
current I flowing into the earth produces an electric field proportional to its density and to the
resistivity of the soil. The voltage V measured between the inner electrodes is, therefore,
proportional to the field. Consequently, the resistivity will be proportional to the ratio of the
voltage to current. The following equation holds for:
29
4s V
I
=
1+
2s
2s
2
s + 4 e 4 s 2+ 4 e 2
...(3.3)
where
- Resistivity of soil in ohm-metre,
s - Distance between two successive electrodes in metres,
V - Voltage difference between the two inner electrodes in volts,
I - Current flowing through the two outer electrodes in amperes,
e - Depth of burial of electrode in metres.
If the depth of burial of the electrodes in the ground d is negligible compared to the
spacing between the electrodes, then
2 sV
I
...(3.4)
Earth testers normally used for these tests comprise the current source and meter in a
single instrument and directly read the resistance. The most frequently used earth tester is the
four-terminal megger shown in Fig. 33. When using such a megger, the resistivity may be
evaluated from the modified equation as given below:
=2 s R
...(3.5)
where
30
31
In cases where the resistance of the potential electrodes (the two inner electrodes) is
comparatively high, a correction of the test results would be necessary depending on its
value. For this purpose, the instrument is connected to the electrodes as shown in Fig. 34. The
readings are taken as before. The correction is then effected as follows.
Let the readings of the megger be Rp with the connections as shown in Fig. 3.7 and
'
and the
resistance of the voltage circuit of the instrument used to obtain R ( as indicated inside the
scale cover of the meter ) is Rv, the corrected value of the earth resistivity would be:
= ' (Rv + Rp) /Rv
...(3.6)
Fig.3.5 Test connection to measure the sum of the potential electrode resistances
32
33
S.NO
TYPES OF SOIL
RESISTIVITY IN OHM
METERS
Marsheel
1-5
Clay
3-150
10-1250
Chalk
60-500
Sand
90-1000
500-5000
Slate
100-500
Crystalline rock
500-10,000
34
CHAPTER -4
LAYOUT OF EARTHING
4.1 EARTHING IN SUBSTATION
In general, earthing installations will be required at power stations and substations
for:
The neutral points of each separate electricity system which has to be earthed at the
with each system, for example, transformer tanks, power cable sheaths;
Extraneous metalwork not associated with the powersystems, for example boundary
fences, sheaths of control or communication cables.
35
36
Top ring should be half the size of main vertical reinforcement rod.
Two extreme columns should be earthed like this in each substation.
This is applicable to RCG masts and equipment supports in OD switchyard.
Inserts other than earthing pads may or may not be welded to reinforcement.
37
The perimeter fence may need to be earthed separately from the main station earth
electrode system.
The tertiary winding of a power transformer should be connected to the transformer
tank by a connection of sufficient cross-sectional area to carry the primary short-circuit
current.
In the case of pole mounted transformers on overhead line systems, difficulties may
arise in areas of high soil resistivity. Here, if the pole carries also isolating switchgear with
low level operating handle, up to three separately earthed electrode systems may be required.
That for the neutral of the low voltage system is usually provided not nearer than one pole
span away on the low voltage line. That for the high voltage metalwork (transformer tank,
switch framework, support metal work), consists of one earth electrode at or near the pole.
Resistances of 5 to 50 are sometimes the minimum economically possible. In addition, an
earth mat should be provided, near the ground surface, in the position taken up by a person
operating the switch handle; this mat should be connected to the switch handle. The mat
should be electrically separated from the main electrode; this is considered to be achieved by
spacing the nearest element of that electrode at least 1 m from the periphery of the mat and
by placing the two earthing-wires on opposite sides of the pole. The tops of the main
electrodes should be at least 225 mm and preferably 750 mm below the ground, and the
earthing wire to the main electrode of outdoor type rubber or plastics-insulated cable up to a
point 2 m above ground level. This cable, between the bottom of the pole and the electrode
should be laid in a 50mm diameter earthenware duct filled solid with bitumen.
CHAPTER -5
MAINTENANCE OF EARTHING SYSTEMS
38
5.1 INTRODUCTION
Where an electricity supplier provides an earth terminal at premises, maintenance of
the earthing and bonding system is confined to maintenance of the conductors and
connections which form part of that system. At special locations, e.g. on an IT or TT system,
the occupant/owner is required to provide an independent earth electrode, and any
maintenance procedure must include this electrode.
For electricity suppliers, or other owners of distribution networks, maintenance of
their earthing and bonding systems involves work on both the bonding conductors above
ground and the buried electrode. For the electrode, testing from above ground has been the
accepted method of verifying its condition. Corrosion can take place on some electrode
components or joints. A test of the earthing system impedance will not necessarily detect this
corrosion and is not, on its own, sufficient to indicate that the earthing system is adequate.
For electrode systems associated with the higher voltage networks, selected excavation and
inspection of electrode systems is now recommended.
5.2 PHILOSOPHY OF MAINTENANCE
Maintenance of earthing systems normally forms part of the maintenance of the
overall electrical system. The quality and frequency of the maintenance should be sufficient
to prevent danger, so far as is reasonably practicable. Recommendations on the type of
maintenance required and the frequency for various types of installation can be found in the
following documents:
39
For factories, the HSE. has issued a Memorandum of Guidance on the Electricity at
Work Regulations 1989. In Appendix 2, a list is given of the various documents
made, accessible.
Examination which includes a more thorough inspection than that possible by
inspection, possibly including testing.
5.3 INSPECTION
Inspection of the earthing system at an installation normally takes place in association with
visits for other maintenance work. It consists of a visual inspection only of those parts of the
system which can be seen, particularly looking for evidence of decay, corrosion, vandalism or
theft.
5.4 EXAMINATION
40
An earth loop impedance test. Commercial testers are available for this purpose.
A function test on all RCDs in the installation. This test has to be independent of the
built-in push button on the RCD.
In factories examination is required regularly according to the type of installation. A
detailed record should be kept at each examination. The examiner will check that the existing
earthing system complies with current Regulations.
The following tests are required on the earthing system:
41
carried out using a low resistance measuring (micro) Ohmmeter and the test is
required between the customers earth terminal and all extraneous non-conductive
metalwork.
5.4.1.1 Installations with lightning protection
Examination is recommended to meet the requirement of BS 6651. As well as a very
thorough inspection, to ensure that the installation complies with the current Regulations, the
following testing is required.
5.4.1.2 Earth electrode value
The value of the electrode should be measured. Previously this meant isolating the
electrode from the main lightning protection conductors. This could not be carried out during
any lightning activity and precautions were required when breaking the link between the
electrode and the lightning conductors, since it was possible for an excessive voltage to
appear across the open link, should there be a fault to earth on the electricity supply network.
lip on type impedance measuring instruments are now available for this and do not require
the electrode to be disconnected.
Once measured, the value of the earth electrode should be compared with the design
value, or that obtained during the previous test.
42
Examination is carried out less frequently - typically once every 5 or 6 years. A very
thorough inspection is recommended, removing covers etc. where appropriate. The examiner
is particularly required to check that the bonding of all normally accessible metalwork,
transformer switchgear tanks, steel doors, steel fencing etc. meets the requirement of
Technical Standard 41 - 24.
The following testing is typically carried out, with the equipment normally in
commission. A special procedure has to be used to guard against possible excessive voltage
occurring during the testing.
1. Bonding tests between the earth electrode and normally accessible metalwork.
2. Tracing of buried electrode and examination of this at some locations to ensure
corrosion has not taken place.
3. The high-voltage earth electrode value is measured and compared with previous or
design values.
4. Checking the pH value of the soil.
5. A separation test to ensure that the HV electrode and LV electrodes are electrically
separate. This test is not required if the design conditions permit the two electrode
systems to be bonded together installed.
CHAPTER -6
CONCLUSION
43
From this thesis we know about the importance of earthing in industrial practices. The
various types have been discussed in the thesis. The maintenance of earthing shows that
giving proper connection is not only the sufficient to ensure safety, maintenance is very
important. Thus by giving proper earth connections to equipments, we can avoid man
accidents and ensure maximum safety.
44
REFERENCES
[1] L.W. Manning, Industrial Power System grounding practices presented at the
Industrial and Commercial power systems technical conference, Philadelphia. PA.
October 1964.
[2] IEEE Transactions on Industry Applications, Vol. 35 No. 4 July/August 1999.
[3] IEEE Standard for generating station grounding. The instiue of electrical and
electronic engineering, inc. March 18,1996.
[4] W. Keith Switzer, Practical Guide To Electrical Grounding, An ERICO Publication
First Printing, First Edition, August 1999.
[5] Trevor Charlton, Earthing Practice, CDA Publication 119, February 1997.
45